ROSEDALE HOTEL MANAGEMENT LIMITED HOTEL DESIGN GUIDE Section: Mechanical Requirements Sub-Section: Guest Rooms

Guest Rooms Guest Room heating and cooling units shall be fan coil type. Self-contained terminal air conditioning units or heat pumps may be used subject to the prior approval from Rosedale Hotel Management Limited. If horizontal concealed fan coil units are used, they shall be located over the foyer ceiling, with filter access doors as return grills. If vertical-stacked fan coil units are used, air outlets shall be located so as not to cause drafts and to minimize sound levels at the bed location. The fan coil units shall be sized to maintain desired room temperature at no higher than medium speed. Individual Guest Room thermostats shall be provided. The thermostat shall be a combination heating-cooling type with colour coded graduated temperature adjustment, on-off switch and multiple speed fan control. Thermostat shall be adjustable through 5K by the guest. Control valves shall be twoway type. The thermostat shall throttle the control valve only; fan control is not acceptable. An automatic aquastat changeover controller shall be provided for 2-pipe systems. Isolation of the fan (off position0 will disable the thermostat and drive control valves closed. A minimum of fifty (50) cfm must be exhausted from each bathroom. Door grills in bathroom doors are not acceptable. Undercut door to achieve free air space for toilet exhaust air. Room ambient design conditions: Heating: 22C, dry bulb Cooling: 24C, dry bulb, 55 percent R.H. Fresh air make-up shall be introduced to the Guest Room fan coil units ducted directly
Filename: 80040704.doc Page 1 of 2 Prepared by: Edward Ng Date: December 1, 2006

ROSEDALE HOTEL MANAGEMENT LIMITED HOTEL DESIGN GUIDE Section: Mechanical Requirements Sub-Section: Guest Rooms
into the Guest Room. Ducts shall be fitted with fire dampers where they penetrate walls, or otherwise suitably designed to prevent smoke ingression in the event of fire provided that it is able to meet the local fire codes. All fan coil units shall have (min.) 25mm or one inch filters (disposable or washable type) on the intake side of the coil(s). Ensure that condensate pipes are correctly graded to fall and are fully lagged. Fan coil unit is to accessible through a hinged access panel secured by budget locks. Opening to give unobstructed access to isolation valves, drains and controls. Supply and return grills shall be aluminum and finished as required by the Architect or Interior Designer. Supply grills are to be double deflection type. Return air grills to be hinged with filter fixed in slide rail for maintenance.

Filename: 80040704.doc

Page 2 of 2

Prepared by: Edward Ng Date: December 1, 2006

Вам также может понравиться