AERIAL
manufacture.
The extensive range of Olex bare overhead conductors includes
Contents
Introduction
Type AAC
Type AAAC/1120
Type ACSR/GZ
Type ACSR/AC
10
12
13
14
Covered Conductors
16
Type CCT
17
18
21
22
23
24
ialist
are manufactured to Australian Standards and specific customer
by economic considerations.
of 160185MPa.
Aluminium alloy 1120 Olex alloy 1120 has a conductivity of 59% IACS
International Standards.
Properties of Materials
Unit
Aluminium
Aluminium
alloy 1120
Copper
Galvanised
steel
Aluminium-clad
steel
Density at 20C
8890
7800
6590
Conductivity at 20C
% IACS 61
59
97
10.1
20.3
Resistivity at 20C
.m 0.0283
0.0293
0.01777
0.17
0.085
Constant-mass temperature coefficient of resistance
per C 0.00403
0.00390
0.00381
0.0044
0.0036
Ultimate tensile stress
MPa
160185
230250
405460
13101390
12701340
Modulus of elasticity
GPa
68
68
124
193
162
Coefficient of linear expansion
per C 23.0 x 10 6
23.0 x 10 6
17 x 10 6
11.5 x 10 6
12.9 x 10 6
kg/m 3
2700
2700
air movement
continuous current
carrying capacity
ambient temperature
absorption coefficients
solar radiation
Electrical characteristics
AC resistance
ctors
inductive reactance
thermal elongation
everyday tension
creep
stress-strain characteristics
cladding with a radial thickness not less than 5% of the overall wire
Construction
Packing
equipment.
Bare Conductors
Type AAC
Aluminium conductors manufactured to AS/NZS 1531.
Physical and Mechanical Performance Data
Conductor
codename
Stranding
and wire
diameter
no/mm
Nominal
overall
diameter
mm
Crosssectional
area
mm 2
Approximate
mass
Breaking
load
kg/km
kN
Leo
Leonids
Libra
Mars
Mercury
Moon
Neptune
Orion
Pluto
Saturn
Sirius
Taurus
Triton
Uranus
Ursula
Venus
7/2.50
7/2.75
7/3.00
7/3.75
7/4.50
7/4.75
19/3.25
19/3.50
19/3.75
37/3.00
37/3.25
19/4.75
37/3.75
61/3.25
61/3.50
61/3.75
7.50
8.25
9.00
11.3
13.5
14.3
16.3
17.5
18.8
21.0
22.8
23.8
26.3
29.3
31.5
33.8
34.4
41.6
49.5
77.3
111
124
158
183
210
262
307
337
409
506
587
673
94.3
113
135
211
304
339
433
503
576
721
845
924
1120
1400
1620
1860
5.71
6.72
7.98
11.8
16.9
18.9
24.7
28.7
31.9
42.2
48.2
51.3
62.2
75.2
87.3
97.2
Modulus
of elasticity
Product
code
GPa
Coefficient
of linear
expansion
x 10 6/C
65
65
65
65
65
65
65
65
65
64
64
65
64
64
64
64
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
Leo
Leonids
Libra
Mars
Mercury
Moon
Neptune
Orion
Pluto
Saturn
Sirius
Taurus
Triton
Uranus
Ursula
Venus
Leo
Leonids
Libra
Mars
Mercury
Moon
Neptune
Orion
Pluto
Saturn
Sirius
Taurus
Triton
Uranus
Ursula
Venus
DC
resist.
at 20C
Inductive
Continuous
reactance
Rural weathered
to 0.3m
Winter night
at 50Hz
Still
1m/s
2m/s
/km
air
wind
wind
/km
AC
resist.
at 50Hz
75C
/km
0.833
0.689
0.579
0.370
0.258
0.232
0.183
0.157
0.137
0.110
0.0940
0.0857
0.0706
0.0572
0.0493
0.0429
1.02
0.842
0.707
0.452
0.315
0.284
0.224
0.192
0.168
0.135
0.116
0.105
0.0872
0.0710
0.0616
0.0539
0.295
0.289
0.284
0.270
0.259
0.255
0.244
0.240
0.235
0.227
0.222
0.220
0.213
0.206
0.201
0.197
95
107
119
157
196
209
243
269
295
341
379
402
457
525
578
631
123
140
157
211
269
289
343
381
420
490
547
583
668
773
856
941
211
237
265
350
440
470
548
603
657
755
834
883
997
1137
1246
1356
245
276
308
408
511
546
636
699
762
875
975
1039
1190
1377
1524
1674
Summer noon
Still
1m/s
air
wind
190
213
237
311
388
413
479
525
570
651
716
756
849
962
1049
1137
2m/s
wind
225
253
281
369
461
492
570
625
679
776
854
902
1028
1188
1314
1442
Industrial weathered
Winter night
Still
1m/s
2m/s
air
wind
wind
Summer noon
Still
1m/s
air
wind
2m/s
wind
132
150
169
228
292
314
373
416
458
536
599
639
733
850
942
1036
88
99
110
143
176
188
216
238
260
299
331
350
396
52
495
539
222
249
277
364
453
483
559
612
665
759
834
880
1002
1158
1280
1405
216
243
272
361
454
486
568
626
683
786
869
921
1042
1191
1307
1424
250
282
314
417
524
560
653
719
784
901
1006
1071
1228
1422
1574
1730
186
209
232
304
378
403
465
510
553
630
692
730
818
925
1006
1089
Bare Conductors
Type AAAC/1120
Aluminium alloy 1120 conductors manufactured to AS/NZS 1531.
Physical and Mechanical Performance Data
Conductor
codename
Stranding
and wire
diameter
no/mm
Nominal
overall
diameter
mm
Crosssectional
area
mm 2
Approximate
mass
Breaking
load
Modulus
of elasticity
Product code
GPa
Coefficient
of linear
expansion
x 10 6/C
kg/km
kN
Chlorine
Chromium
Fluorine
Helium
Hydrogen
Iodine
Krypton
Lutetium
Neon
Nitrogen
Nobelium
Oxygen
Phosphorus
Selenium
Silicon
Sulfur
7/2.50
7/2.75
7/3.00
7/3.75
7/4.50
7/4.75
19/3.25
19/3.50
19/3.75
37/3.00
37/3.25
19/4.75
37/3.75
61/3.25
61/3.50
61/3.75
7.50
8.25
9.00
11.3
13.5
14.3
16.3
17.5
18.8
21.0
22.8
23.8
26.3
29.3
31.5
33.8
34.4
41.6
49.5
77.3
111
124
158
183
210
262
307
337
409
506
587
673
94.3
113
135
211
304
339
433
503
576
721
845
924
1120
1400
1620
1860
8.18
9.91
11.8
17.6
24.3
27.1
37.4
41.7
47.8
62.2
72.8
73.6
93.1
114
127
145
65
65
65
65
65
65
65
65
65
64
64
65
64
64
64
64
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
Chlorine
Chromium
Fluorine
Helium
Hydrogen
Iodine
Krypton
Lutetium
Neon
Nitrogen
Nobelium
Oxygen
Phosphorus
Selenium
Silicon
Sulfur
DC
resist.
at 20C
/km
Chlorine 0.864
Chromium 0.713
Fluorine 0.599
Helium
0.383
Hydrogen 0.266
Iodine
0.239
Krypton 0.189
Lutetium 0.163
Neon
0.142
Nitrogen 0.114
Nobelium 0.0973
Oxygen
0.0884
Phosphorus0.0731
Selenium 0.0592
Silicon
0.0511
Sulfur
0.0444
AC
resist.
at 50Hz
75C
/km
Inductive
Continuous
reactance
Rural weathered
to 0.3m
Winter night
at 50Hz
Still
1m/s
2m/s
/km
air
wind
wind
2m/s
wind
Industrial weathered
Winter night
Still
1m/s
2m/s
air
wind
wind
Summer noon
Still
1m/s
air
wind
2m/s
wind
1.05
0.866
0.728
0.465
0.323
0.291
0.230
0.198
0.173
0.139
0.119
0.108
0.0897
0.0730
0.0634
0.0554
0.295
0.289
0.284
0.270
0.259
0.255
0.244
0.240
0.235
0.227
0.222
0.220
0.213
0.206
0.201
0.197
94
106
118
155
194
207
240
265
290
336
373
397
451
518
569
623
221
249
277
364
455
486
562
615
669
765
842
891
1013
1172
1295
1423
130
148
166
225
288
310
368
409
451
528
590
630
722
838
928
1021
87
98
108
141
74
185
213
234
256
295
326
346
391
446
488
532
219
246
273
358
447
477
551
603
655
748
822
870
988
1142
1262
1386
121
137
154
208
265
285
338
375
413
482
539
575
658
762
843
927
207
234
261
345
434
464
540
593
647
743
821
871
982
1120
1227
1336
241
272
303
401
504
539
627
688
750
861
961
1025
1172
1357
1501
1650
187
210
234
307
383
409
473
517
562
642
706
747
837
949
1034
1122
212
240
268
356
448
480
560
615
672
774
856
908
1026
1173
1287
1403
246
277
309
410
517
553
644
707
771
887
990
1057
1209
1401
1550
1705
183
206
229
300
373
398
459
502
545
621
682
721
807
912
992
1074
Bare Conductors
Hard Drawn Copper
Hard drawn copper conductors manufactured to AS/NZS 1746.
Physical and Mechanical Performance Data
Stranding
and wire
Crosssectional
area
mm 2
Approximate
mass
Breaking
load
Modulus
of elasticity
no/mm
Nominal
overall
diameter
mm
Product
code
GPa
Coefficient
of linear
expansion
x 10 6/C
kg/km
kN
7/1.00
7/1.25
7/1.75
7/2.00
7/2.75
19/1.75
19/2.00
7/3.50
7/3.75
37/1.75
19/2.75
19/3.00
37/2.50
37/2.75
37/3.00
61/2.75
3.00
3.75
5.25
6.00
8.25
8.75
10.0
10.5
11.3
12.3
13.8
15.0
17.5
19.3
21.0
24.8
5.50
8.59
16.8
22.0
41.6
45.7
59.7
67.4
77.3
89.0
113
134
182
220
262
362
49.3
76.9
151
197
375
413
538
607
696
806
1020
1210
1640
1990
2370
3290
2.32
3.59
6.89
8.89
16.2
18.3
23.6
25.4
28.8
35.6
43.1
50.8
70.3
83.9
98.9
138
120
120
120
120
120
118
118
120
120
117
118
118
117
117
117
117
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
ACUT35AA001
ACUT36AA001
ACUT37AA001
ACUT38AA001
ACUT39AA001
ACUT40AA001
ACUT41AA001
ACUT42AA001
ACUT63AA001
ACUT43AA001
ACUT44AA001
ACUT45AA001
ACUT46AA001
ACUT47AA001
ACUT48AA001
ACUT49AA001
DC
resist.
at 20C
no/mm
/km
AC
resist.
at 50Hz
75C
/km
7/1.00
7/1.25
7/1.75
7/2.00
7/2.75
19/1.75
19/2.00
7/3.50
7/3.75
37/1.75
19/2.75
19/3.00
37/2.50
37/2.75
37/3.00
61/2.75
3.25
2.09
1.06
0.815
0.433
0.395
0.303
0.268
0.233
0.203
0.160
0.134
0.0996
0.0823
0.0691
0.0500
3.93
2.53
1.28
0.986
0.524
0.478
0.367
0.324
0.282
0.246
0.194
0.163
0.121
0.100
0.0846
0.0618
Inductive
Continuous
reactance
Rural weathered
to 0.3m
Winter night
at 50Hz
Still
1m/s
2m/s
/km
air
wind
wind
2m/s
wind
Industrial weathered
Winter night
Still
1m/s
2m/s
air
wind
wind
Summer noon
Still
1m/s
air
wind
2m/s
wind
0.353
0.339
0.318
0.310
0.289
0.283
0.275
0.274
0.270
0.261
0.255
0.249
0.239
0.233
0.227
0.217
39
51
78
92
136
144
170
183
199
217
251
280
339
384
431
533
93
122
185
217
320
340
400
430
468
511
590
657
787
883
981
1193
49
66
104
124
190
203
242
262
288
318
374
423
523
598
676
847
37
48
73
86
126
133
156
167
181
197
226
250
300
339
378
463
92
121
183
215
316
335
394
423
460
502
579
645
771
864
959
1164
47
62
97
116
176
188
225
243
267
294
344
388
479
547
618
772
85
112
171
202
300
319
377
406
443
485
563
629
758
854
952
1162
99
131
200
235
350
371
438
472
515
564
653
730
879
989
1102
1376
79
103
156
183
270
286
337
362
394
430
496
552
661
742
823
996
86
114
175
206
308
327
388
418
456
500
581
650
786
887
991
1213
101
133
203
239
356
379
448
482
526
577
670
748
903
1018
1136
1419
78
102
154
180
265
281
330
354
385
420
484
538
642
719
796
961
Bare Conductors
Type ACSR/GZ
Aluminium conductors, galvanised steel reinforced manufactured to AS/NZS 3607.
Physical and Mechanical Performance Data
Conductor
codename
Almond
Apricot
Apple
Banana
Cherry
Grape
Lemon
Lychee
Lime
Mango
Orange
Olive
Pawpaw
Quince
Raisin
Sultana
Walnut
Aluminium
Steel
Nominal
overall
diameter
mm
6/2.50
6/2.75
6/3.00
6/3.75
6/4.75
30/2.50
30/3.00
30/3.25
30/3.50
54/3.00
54/3.25
54/3.50
54/3.75
3/1.75
3/2.50
4/3.00
4/3.75
1/2.50
1/2.75
1/3.00
1/3.75
7/1.60
7/2.50
7/3.00
7/3.25
7/3.50
7/3.00
7/3.25
7/3.50
19/2.25
4/1.75
4/2.50
3/3.00
3/3.75
7.5
8.3
9.0
11.3
14.3
17.5
21.0
22.8
24.5
27.0
29.3
31.5
33.8
5.3
7.5
9.0
11.3
Crosssectional
area
mm 2
Approximate
mass
Breaking
load
Modulus
of elasticity
Product
code
GPa
Coefficient
of linear
expansion
x 10 6/C
kg/km
kN
34.4
41.6
49.5
77.3
120
182
262
307
356
431
506
587
672
16.8
34.4
49.5
77.3
119
144
171
268
402
677
973
1140
1320
1440
1690
1960
2240
95
195
243
380
10.5
12.6
14.9
22.7
33.4
63.5
90.4
105
122
119
137
159
178
12.7
24.4
28.3
43.9
83
83
83
83
80
88
88
88
88
78
78
78
77
136
136
119
119
19.3
19.3
19.3
19.3
19.9
18.4
18.4
18.4
18.4
19.9
19.9
19.9
20.0
13.9
13.9
15.2
15.2
Almond
Apricot
Apple
Banana
Cherry
Grape
Lemon
Lychee
Lime
Mango
Orange
Olive
Pawpaw
Quince
Raisin
Sultana
Walnut
Almond
Apricot
Apple
Banana
Cherry
Grape
Lemon
Lychee
Lime
Mango
Orange
Olive
Pawpaw
Quince
Raisin
Sultana
Walnut
DC
resist.
at 20C
/km
AC
resist.
at 50Hz
75C
/km
Inductive
reactance
to 0.3m
at 50Hz
/km
Winter night
Still
1m/s
air
wind
0.975
0.805
0.677
0.433
0.271
0.196
0.136
0.116
0.100
0.0758
0.0646
0.0557
0.0485
3.25
1.59
0.897
0.573
1.31
1.08
0.910
0.582
0.367
0.263
0.167
0.142
0.123
0.0955
0.0816
0.0705
0.0615
4.37
2.14
1.21
0.770
0.296
0.290
0.285
0.271
0.256
0.240
0.228
0.223
0.219
0.212
0.207
0.202
0.198
0.346
0.324
0.302
0.288
108
123
138
187
259
330
441
493
548
648
724
804
885
53
85
120
161
186
209
233
309
416
513
680
752
826
960
1061
1165
1270
93
145
203
269
216
244
272
359
483
598
787
879
976
1147
1282
1421
1563
108
169
236
312
84
95
107
141
191
238
307
341
377
443
492
543
595
42
66
91
121
167
188
209
274
364
449
586
645
706
816
898
981
1065
85
131
181
238
2m/s
wind
Industrial weathered
Winter night
Still
1m/s
2m/s
air
wind
wind
Summer noon
Still
1m/s
air
wind
2m/s
wind
198
223
248
326
434
531
698
769
843
991
1106
1225
1347
100
155
215
283
116
131
148
201
280
361
482
540
601
711
796
884
974
56
91
129
175
79
89
98
129
171
211
269
298
328
383
424
466
508
40
61
84
111
196
220
244
321
426
520
682
751
823
966
1078
1194
1312
99
153
212
279
190
215
240
318
430
532
707
783
862
1003
1110
1220
1333
95
149
208
277
220
248
277
367
495
614
811
906
1007
1183
1323
1466
1614
110
172
241
319
164
184
205
268
354
436
567
623
681
786
863
941
1020
83
129
178
233
Bare Conductors
Type ACSR/AC
Aluminium conductors, aluminium-clad steel reinforced manufactured to AS/NZS 3607.
Physical and Mechanical Performance Data
Conductor
codename
Stranding and
wire diameter
no/mm
Aluminium
Steel
Nominal
overall
diameter
mm
Crosssectional
area
mm 2
Approximate
mass
Breaking
load
Modulus
of elasticity
kg/km
kN
Angling
Aquatics
Archery
Baseball
Bowls
Cricket
Darts
Dice
Diving
Golf
Gymnastics
Hurdles
Lacrosse
Skating
Soccer
Swimming
Tennis
6/2.50
6/2.75
6/3.00
6/3.75
6/4.75
30/2.50
30/3.00
30/3.25
30/3.50
54/3.00
54/3.25
54/3.50
54/3.75
3/1.75
3/2.50
4/3.00
4/3.75
7.5
8.3
9.0
11.3
14.3
17.5
21.0
22.8
24.5
27.0
29.3
31.5
33.8
5.3
7.5
9.0
11.3
34.4
41.6
49.5
77.3
120
182
262
307
356
431
506
587
672
16.8
34.4
49.5
77.3
113
137
163
254
385
636
913
1070
1240
1380
1620
1880
2150
83
171
218
340
10.6
12.7
15.1
22.3
32.7
64.4
91.6
106
122
120
139
159
180
12.3
24.9
28.9
42.6
1/2.50
1/2.75
1/3.00
1/3.75
7/1.60
7/2.50
7/3.00
7/3.25
7/3.50
7/3.00
7/3.25
7/3.50
19/2.25
4/1.75
4/2.50
3/3.00
3/3.75
Product
code
GPa
Coefficient
of linear
expansion
x 10 6/C
79
79
79
79
76
82
82
82
82
75
75
75
74
119
119
106
106
20.1
20.1
20.1
20.1
20.6
19.4
19.4
19.4
19.4
20.6
20.6
20.6
20.7
15.3
15.3
16.5
16.5
Angling
Aquatics
Archery
Baseball
Bowls
Cricket
Darts
Dice
Diving
Golf
Gymnastics
Hurdles
Lacrosse
Skating
Soccer
Swimming
Tennis
DC
resist.
at 20C
/km
Angling
0.923
Aquatics 0.763
Archery
0.641
Baseball 0.410
Bowls
0.259
Cricket
0.182
Darts
0.126
Dice
0.108
Diving
0.0928
Golf
0.0726
Gymnastics0.0619
Hurdles
0.0533
Lacrosse 0.0465
Skating
2.75
Soccer
1.34
Swimming 0.807
Tennis
0.517
AC
resist.
at 50Hz
75C
/km
Inductive
reactance
to 0.3m
at 50Hz
/km
Continuous
Rural weathered
Winter night
Still
1m/s
2m/s
air
wind
wind
1.24
1.03
0.861
0.551
0.352
0.245
0.155
0.133
0.114
0.0915
0.0782
0.0675
0.0590
3.70
1.80
1.08
0.695
0.296
0.290
0.285
0.271
0.256
0.240
0.228
0.223
0.219
0.212
0.207
0.202
0.198
0.346
0.324
0.302
0.288
111
126
141
192
265
342
458
511
569
662
740
821
904
57
92
127
170
87
98
109
145
195
246
319
354
391
452
503
555
607
46
72
96
127
191
215
240
318
425
532
706
779
857
980
1084
1190
1297
101
158
214
283
222
250
279
369
494
620
817
911
1013
1172
1309
1452
1596
118
184
249
329
172
193
215
282
372
465
609
668
732
834
917
1003
1088
92
143
191
251
2m/s
wind
Industrial weathered
Winter night
Still
1m/s
2m/s
air
wind
wind
Summer noon
Still
1m/s
air
wind
2m/s
wind
204
229
255
335
444
554
725
797
875
1012
1130
1252
1375
109
169
227
298
119
136
152
207
286
374
501
560
624
726
813
903
995
61
99
136
184
81
91
100
133
175
219
280
309
340
392
433
476
519
43
67
89
116
201
226
251
329
436
540
709
779
854
987
1101
1220
1339
108
167
224
293
195
221
246
327
440
555
735
812
895
1024
1134
1247
1361
103
162
219
291
226
255
285
378
506
637
842
939
1045
1208
1351
1499
1648
120
188
254
336
169
189
210
276
362
452
589
646
707
803
882
962
1042
91
140
187
245
Bare Conductors
Type SC/GZ & SC/AC
Galvanised steel conductors manufactured to AS 1222.1
and aluminium-clad steel conductors manufactured to AS/NZS 1222.2
SC/GZ
Stranding
and wire
diameter
Nominal
overall
diameter
CrossApprox.
sectional mass
area
Breaking
load
Modulus Coeff.
of
of linear
elasticity expan.
GPa
DC
resistance
/km
At
At
x 10 6/C 20C
75C
no/mm
mm
mm 2
kg/km
kN
3/2.00
3/2.75
7/2.00
7/2.75
7/3.25
7/3.75
19/2.00
19/2.75
19/3.25
4.3
5.9
6.0
8.3
9.8
11.3
10.0
13.8
16.3
9.43
17.8
22.0
41.6
58.1
77.3
59.7
113
158
74
140
173
328
458
609
473
894
1250
Winter night
Still
1m/s
air
wind
Summer noon
2m/s
Still
wind
air
1m/s
wind
2m/s
wind
11.7
22.2
26.0
49.0
68.7
91.3
70.5
133
186
189
189
187
187
187
187
184
184
184
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
21
31
35
54
67
81
69
105
133
43
63
71
106
131
156
134
199
247
34
49
55
82
100
119
102
150
186
40
58
66
97
119
141
121
179
221
Stranding
and wire
diameter
Nominal
overall
diameter
CrossApprox.
sectional mass
area
Breaking
load
Modulus Coeff.
of
of linear
elasticity expan.
no/mm
mm
mm 2
kg/km
kN
GPa
3/2.75
3/3.00
3/3.25
3/3.75
7/2.75
7/3.00
7/3.25
7/3.75
7/4.25
19/2.75
19/3.00
19/3.25
19/3.75
19/4.25
5.9
6.5
7.0
8.1
8.3
9.0
9.8
11.3
12.8
13.8
15.0
16.3
18.8
21.3
17.82
21.21
24.89
33.12
41.58
49.48
58.07
77.28
99.33
112.9
134.3
157.6
209.8
269.6
118
141
165
220
277
330
387
515
662
755
899
1060
1410
1800
22.7
27.0
31.6
39.3
50.1
59.7
69.9
86.9
105
136
162
189
236
286
159
159
159
159
157
157
157
157
157
155
155
155
155
155
20
11
8.7
4.6
3.3
2.5
3.2
1.7
1.2
25
14
11
5.7
4.1
3.1
4.0
2.1
1.5
37
54
61
91
113
134
115
171
213
17
25
28
41
51
60
52
76
94
Product
code
GALSTEEL
GALSTEEL
GALSTEEL
GALSTEEL
GALSTEEL
GALSTEEL
GALSTEEL
GALSTEEL
GALSTEEL
3/2.00
3/2.75
7/2.00
7/2.75
7/3.25
7/3.75
19/2.00
19/2.7
19/3.25
SC/AC
x 10 6/C
DC
resistance
/km
At
At
20C
75C
Winter night
Still
1m/s
air
wind
2m/s
wind
Summer noon
Still
1m/s
air
wind
2m/s
wind
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
4.80
4.02
3.42
2.58
2.06
1.73
1.47
1.11
0.864
0.764
0.642
0.545
0.411
0.320
48
54
60
72
81
91
102
123
145
158
178
200
244
291
97
108
120
143
161
179
198
237
277
300
335
371
443
519
38
42
47
56
63
70
77
92
107
116
129
142
172
203
90
100
110
131
148
164
181
215
251
272
302
334
397
462
5.75
4.82
4.10
3.09
2.47
2.07
1.76
1.33
1.04
0.915
0.769
0.653
0.492
0.383
83
93
103
123
138
154
170
204
238
259
288
320
382
448
Product code
76
84
93
111
124
138
153
181
211
228
54
280
333
387
ALCLAD3/2.75
ALCLAD3/3.00
ALCLAD3/3.25
ALCLAD3/3.75
ALCLAD7/2.75
ALCLAD7/3.00
ALCLAD7/3.25
ALCLAD7/3.75
ALCLAD7/4.25
ALCLAD19/2.75
ALCLAD19/3.00
ALCLAD19/3.25
ALCLAD19/3.75
ALCLAD19/4.25
Note The electrical performance characteristics shown above do not take magnetic effects
into consideration and are therefore only approximate. Current ratings are based on the
following conditions:
Conductor temperature rise above ambient of 40C
Ambient air temp. of 35C for summer noon or 10C for winter night
Direct solar radiation intensity of 1000W/m 2 for summer noon or zero for winter night
Diffuse solar radiation intensity of 100W/m 2 for summer noon or zero for winter night
Ground reflectance of 0.2
Emissivity and solar absorption coefficient of the conductor surface, 0.5
Cross sections not to scale
Conductor
All four conductors are manufactured from high conductivity high
Insulation
The insulation consists of X-90UV, a cross-linked polyethylene with
service performance.
10
led Cables
The cores
Each phase core is marked with numerals 1, 2 or 3 and with one rib,
two ribs or three ribs to denote the three phases. The neutral core
Both insulation types are tested at 80C with a special adhesion test
carries equally spaced ribs right round the circumference. These ribs
of 120C, and are also subjected to a heat radiation test that simulates
passes the criteria test at 105C which provides our customer with
one metre intervals. Drum lengths start at any number with the lowest
The cores are laid up in a bundle with a left hand lay. Rating of LV ABC
11
2 Core
16
25
35
50
95
3 Core
25
35
50
4 Core
16
25
35
50
70
95
120
150
Nominal conductor
diameter
mm
Average insulation
thickness
mm
Nominal diameter
over insulation
mm
Nominal diameter
over laid-up cores
mm
Approximate
mass
kg/km
Product code
4.7
5.9
6.9
8.1
11.4
1.3
1.3
1.3
1.5
1.7
7.4
8.6
9.6
11.2
14.9
14.8
17.2
19.3
22.3
29.8
130
190
250
340
640
XDAB15AA002
XDAB17AA002
XDAB18AA002
XDAB19AA002
XDAB22AA002
5.9
6.9
8.1
1.3
1.3
1.5
8.6
9.6
11.2
18.5
20.8
24.1
290
370
510
XDAB17AA003
XDAB18AA003
XDAB19AA003
4.7
5.9
6.9
8.1
9.7
11.4
12.8
14.2
1.3
1.3
1.3
1.5
1.5
1.7
1.7
1.7
7.4
8.6
9.6
11.2
12.8
14.9
16.3
17.7
17.8
20.8
23.2
27.0
30.8
36.0
39.3
42.8
270
390
500
670
930
1280
1570
1890
XDAB15AA004
XDAB17AA004
XDAB18AA004
XDAB19AA004
XDAB20AA004
XDAB22AA004
XDAB23AA004
XDAB24AA004
Performance Data
Nominal DC
conductor resist.
area
at 20C
mm 2
2 Core
16
25
35
50
95
3 Core
25
35
50
4 Core
16
25
35
50
70
95
120
150
/km
AC
resist.
at 50Hz
80C
/km
Inductive Voltage
reactance drop
at 50Hz
at 50Hz
80C
/km
mV/A.m
1m/s
wind
2m/s
wind
Fault
current
rating
kA for
1s
1.91
1.20
0.868
0.641
0.320
2.37
1.49
1.08
0.796
0.398
0.094
0.089
0.086
0.086
0.080
4.75
2.99
2.16
1.60
0.812
49
64
78
94
140
78
105
125
150
230
91
120
145
180
275
1.20
0.868
0.641
1.49
1.08
0.796
0.089
0.086
0.086
2.99
2.16
1.60
59
72
88
97
120
140
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
2.37
1.49
1.08
0.796
0.551
0.398
0.315
0.257
0.10
0.097
0.094
0.093
0.088
0.087
0.085
0.084
4.11
2.59
1.87
1.39
0.966
0.706
0.566
0.468
44
59
72
88
110
135
155
180
74
97
120
140
175
215
250
280
Minimum
bending radius
(installed) mm
Rec. tension
Highest
Max
everyday working
tension
tension
kN
kN
Core
Cable
Min.
breaking
load of
cable
kN
Modulus
of
elasticity
Coeff.
of linear
expansion
GPa
x10 6/C
1.4
2.2
3.1
4.1
8.3
30
35
60
65
90
90
100
120
130
270
4.4
7.0
9.8
14.0
26.6
0.79
1.26
1.76
2.52
4.79
1.23
1.96
2.74
3.92
7.45
59
59
59
59
56
23.0
23.0
23.0
23.0
23.0
115
135
165
2.2
3.1
4.1
35
60
65
110
120
140
10.5
14.7
21.0
1.89
2.65
3.78
2.94
4.12
5.88
59
59
59
23.0
23.0
23.0
86
115
135
165
205
255
300
345
1.4
2.2
3.1
4.1
6.0
8.3
10.5
12.9
30
35
60
65
75
90
100
110
110
120
140
160
280
320
350
390
8.8
14.0
19.6
28.0
39.2
53.2
67.2
84.0
1.58
2.52
3.53
5.04
7.06
9.58
12.1
15.1
2.46
3.92
5.49
7.84
11.0
14.9
18.8
23.5
59
59
59
59
56
56
56
56
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
Note Voltage drops are single-phase for 2 & 3 core cables and three-phase for 4 core
cables. Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 80C and solar radiation intensity of 1000W/m 2. Ratings for 2 & 3
core cables are based on all cores fully loaded. Ratings for 4 core cables are based on
a lightly loaded neutral. Fault current ratings are based on initial and final conductor
temperatures of 80C and 210C respectively.
An improved performance grade of XLPE (X-FP-90) designed to provide improved circuit
integrity when subjected to the heat radiation effects of a bush fire or overload conditions
is available as an option.
12
2 Core
6
10
16
3 Core
6
10
16
4 Core
6
10
16
Number and
nominal
diameter
of wires
no/mm
Nominal
conductor
diameter
Average
insulation
thickness
Nominal
diameter
over laid-up
cores
mm
Approximate
mass
mm
Nominal
diameter
over
insulation
mm
mm
7/1.04
7/1.35
7/1.70
Product code
3.1
4.1
5.1
1.3
1.3
1.3
5.8
6.8
7.8
11.7
13.5
15.6
150
230
350
XDAT11AA002
XDAT13AA002
XDAT15AA002
7/1.04
7/1.35
7/1.70
3.1
4.1
5.1
1.3
1.3
1.3
5.8
6.8
7.8
12.6
14.6
16.9
220
340
520
XDAT11AA003
XDAT13AA003
XDAT15AA003
7/1.04
7/1.35
7/1.70
3.1
4.1
5.1
1.3
1.3
1.3
5.8
6.8
7.8
14.1
16.3
18.9
290
460
690
XDAT11AA004
XDAT13AA004
XDAT15AA004
kg/km
Performance Data
Nominal DC
conductor resist.
area
at 20C
mm 2
2 Core
6
10
16
3 Core
6
10
16
4 Core
6
10
16
/km
AC
resist.
at 50Hz
80C
/km
Inductive Voltage
reactance drop
at 50Hz
at 50Hz
80C
/km
mV/A.m
Minimum
bending radius
(installed) mm
2m/s
wind
Fault
current
rating
kA for
1s
Still
air
1m/s
wind
3.17
1.88
1.18
3.89
2.31
1.45
0.11
0.098
0.092
7.79
4.62
2.91
36
48
64
3.17
1.88
1.18
3.89
2.31
1.45
0.11
0.098
0.092
7.79
4.62
2.91
3.17
1.88
1.18
3.89
2.31
1.45
0.11
0.11
0.10
6.75
4.00
2.52
Min.
breaking
load of
cable
kN
Rec. tension
Highest
Max
everyday working
tension
tension
kN
kN
Modulus
of
elasticity
Coeff.
of linear
expansion
GPa
x10 6/C
56
77
100
66
90
120
0.8
1.4
2.2
25
25
30
70
80
95
4.6
7.8
11.8
0.84
1.41
2.13
1.30
2.20
3.32
112
112
112
17.0
17.0
17.0
32
44
58
54
73
96
62
84
110
0.8
1.4
2.2
25
25
30
75
90
100
7.0
11.8
17.8
1.25
2.12
3.20
1.95
3.29
4.97
112
112
112
17.0
17.0
17.0
32
44
58
54
73
96
62
84
110
0.8
1.4
2.2
25
25
30
85
100
110
9.3
15.7
23.7
1.67
2.82
4.26
2.60
4.39
6.63
112
112
112
17.0
17.0
17.0
Core
Cable
Note Voltage drops are single-phase for 2 & 3 core cables and three-phase for 4 core
cables. Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 80C and solar radiation intensity of 1000W/m 2. Ratings for 2 & 3
core cables are based on all cores fully loaded. Ratings for 4 core cables are based on
a lightly loaded neutral. Fault current ratings are based on initial and final conductor
temperatures of 80C and 220C respectively.
13
Single Core
6
10
16
25
35
50
70
2 Core
6
10
16
25
3 Core
6
10
16
Number and
nominal
diameter
of wires
no/mm
Nominal
conductor
diameter
Average
insulation
thickness
Nominal
diameter
over insulation
Approximate
mass
mm
mm
mm
kg/km
7/1.04
7/1.35
7/1.70
19/1.35
19/1.53
19/1.78
19/2.14
3.1
4.1
5.1
6.8
7.7
8.9
10.7
1.0
1.0
1.0
1.2
1.2
1.4
1.4
5.3
6.2
7.2
9.3
10.2
11.9
13.7
80
120
180
300
370
510
710
BAAT11AA001
BAAT13AA001
BAAT15AA001
BAAT17AA001
BAAT18AA001
BAAT19AA001
BAAT20AA001
7/1.04
7/1.35
7/1.70
19/1.35
3.1
4.1
5.1
6.8
1.0
1.0
1.0
1.2
5.3
6.2
7.2
9.3
11.1
13.0
15.1
19.2
150
240
360
600
DAAT11AA002
DAAT13AA002
DAAT15AA002
DAAT17AA002
7/1.04
7/1.35
7/1.70
3.1
4.1
5.1
1.0
1.0
1.0
5.3 x 17.0
6.2 x 19.8
7.2 x 22.9
230
360
540
FAAT11AA003
FAAT13AA003
FAAT15AA003
x
x
x
x
Product
code
Performance Data
Nominal
DC
conductor resist.
area
at 20C
mm 2
/km
Single Core
6
3.17
10
1.88
16
1.18
25
0.749
35
0.540
50
0.399
70
0.276
2 Core
6
3.17
10
1.88
16
1.18
25
0.749
3 Core
6
3.17
10
1.88
16
1.18
AC
resist.
at 50Hz
75C
/km
Inductive Voltage
reactance drop
at 50Hz
at 50Hz
75C
/km
mV/A.m
1m/s
wind
2m/s
wind
Fault
current
rating
kA for
1s
3.83
2.27
1.43
0.906
0.653
0.483
0.334
0.38
0.37
0.35
0.33
0.32
0.31
0.30
6.67
3.99
2.55
1.67
1.26
0.998
0.781
35
48
65
88
105
130
165
70
96
125
165
205
240
305
79
110
145
190
230
275
345
0.6
1.0
1.7
2.8
3.6
4.9
7.1
3.83
2.27
1.43
0.906
0.10
0.096
0.091
0.085
7.67
4.55
2.86
1.82
30
40
52
68
50
68
90
120
59
80
105
140
0.6
1.0
1.7
2.8
3.83
2.27
1.43
0.12
0.11
0.11
7.67
4.55
2.86
30
40
52
50
68
90
59
80
105
0.6
1.0
1.7
Min.
breaking
load of
cable
kN
Rec. tension
Highest
Max
everyday working
tension
tension
kN
kN
Modulus
of
elasticity
Coeff.
of linear
expansion
GPa
x10 6/C
2.3
3.9
5.9
10.4
12.7
17.3
25.0
0.42
0.71
1.07
1.87
2.29
3.11
4.50
112
112
112
110
110
110
110
17.0
17.0
17.0
17.0
17.0
17.0
17.0
30
35
45
55
4.6
7.8
11.8
20.8
0.84
1.41
2.13
3.74
1.30
2.20
3.32
5.82
112
112
112
110
17.0
17.0
17.0
17.0
30
35
45
7.0
11.8
17.8
1.25
2.12
3.20
1.95
3.29
4.97
112
112
112
17.0
17.0
17.0
Minimum
bending
radius
(installed)
mm
20
25
30
35
60
70
80
0.65
1.10
1.66
2.91
3.56
4.84
7.00
Note Reactance and voltage drop are based on three cables laid in flat formation spaced
0.46m apart. The values can also be applied to single-phase circuits or 3-phase circuits with
cables in trefoil formation. For single-phase circuits the voltage drop values should be multiplied
by 1.155. Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 75C and solar radiation intensity of 1000 W/m 2. Fault current
ratings are based on initial and final conductor temperatures of 75C and 150C respectively.
14
2 Core
6
10
16
25
3 Core
6
10
16
25
4 Core
6
10
16
25
Number and
nominal
diameter
of wires
no/mm
Nominal
conductor
diameter
Average
insulation
thickness
Nominal
diameter
over insulation
mm
mm
mm
Nominal
diameter
over laid-up
cores
mm
Approximate
mass
Product
code
7/1.04
7/1.35
7/1.70
19/1.35
3.1
4.1
5.1
6.8
1.0
1.0
1.0
1.2
5.3
6.2
7.2
9.3
10.5
12.4
14.5
18.6
160
240
370
610
DAFT11AA002
DAFT13AA002
DAFT15AA002
DAFT17AA002
7/1.04
7/1.35
7/1.70
19/1.35
3.1
4.1
5.1
6.8
1.0
1.0
1.0
1.2
5.3
6.2
7.2
9.3
11.3
13.3
15.6
20.1
240
360
550
910
FAFT11AA003
FAFT13AA003
FAFT15AA003
FAFT17AA003
7/1.04
7/1.35
7/1.70
19/1.35
3.1
4.1
5.1
6.8
1.0
1.0
1.0
1.2
5.3
6.2
7.2
9.3
12.7
14.9
17.5
22.5
310
480
730
1210
HAFT11AA004
HAFT13AA004
HAFT15AA004
HAFT17AA004
kg/km
Performance Data
Nominal DC
conductor resist.
area
at 20C
mm 2
2 Core
6
10
16
25
3 Core
6
10
16
25
4 Core
6
10
16
25
/km
AC
resist.
at 50Hz
75C
/km
Inductive Voltage
reactance drop
at 50Hz
at 50Hz
75C
/km
mV/A.m
1 m/s
wind
3.17
1.88
1.18
0.749
3.83
2.27
1.43
0.906
0.098
0.092
0.087
0.083
7.67
4.55
2.86
1.82
30
40
52
68
3.17
1.88
1.18
0.749
3.83
2.27
1.43
0.906
0.098
0.092
0.087
0.083
7.67
4.55
2.86
1.82
3.17
1.88
1.18
0.749
3.83
2.27
1.43
0.906
0.11
0.10
0.095
0.090
6.64
3.94
2.48
1.58
Cable
Minimum
breaking
load of
cable
kN
Recomm.
Highest
everyday
tension
kN
20
25
30
35
65
75
85
110
4.6
7.8
11.8
20.8
0.84
1.41
2.13
3.74
0.6
1.0
1.7
2.8
20
25
30
35
70
80
95
120
7.0
11.8
17.8
31.2
0.6
1.0
1.7
2.8
20
25
30
35
75
90
100
140
9.3
15.7
23.7
41.6
Minimum bending
radius (installed)
mm
2 m/s
wind
Fault
current
rating
kA for
1s
Core
50
68
90
120
59
80
105
140
0.6
1.0
1.7
2.8
26
36
47
63
48
65
85
115
56
76
100
135
26
36
47
63
48
65
85
115
56
76
100
135
tension
Max.
working
tension
kN
Modulus
of
elasticity
Coeff.
of linear
expansion
GPa
x 10 6/C
1.30
2.20
3.32
5.82
112
112
112
110
17.0
17.0
17.0
17.0
1.25
2.12
3.20
5.62
1.95
3.29
4.97
8.74
112
112
112
110
17.0
17.0
17.0
17.0
1.67
2.82
4.26
7.49
2.60
4.39
6.63
11.6
112
112
112
110
17.0
17.0
17.0
17.0
Note Voltage drops are single-phase for 2 & 3 core cables and three-phase for 4 core
cables. Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 75C and solar radiation intensity of 1000 W/m 2. Ratings for 2
and 3 core cables are based on all cores fully loaded. Ratings for 4 core cables are based
on a lightly loaded neutral. Fault current ratings are based on initial and final conductor
temperatures of 75C and 150C respectively.
15
Covered Conductors
Covered conductors are conductors covered with insulation material
Operating temperatures
are available: CC and CCT. Olex technical staff can provide detailed
Covered Conductors
properties and in Australia and Sweden has taken the place of other
types of aluminium alloys.
Water blocking Olex pioneered the development of water blocking
for covered conductors in Australia. Extensive research in material
processing and techniques has enabled the manufacturing of covered
conductors that are water blocked with a special material meeting all
the test requirements of AS/NZS 3675.
1.0mm. CCT are marked on the external surface with CCT, Olex,
16
6.35/11kV
40
80
120
180
240
12.7/22kV
80
120
180
19/33kV
80
120
180
Nominal and
nominal
diameter
of wires
no/mm
Nominal
conductor
diameter
Average
insulation
thickness
Nominal
diameter
over insulation
Approximate
mass
Product
code
mm
mm
mm
kg/km
7/2.75
7/3.75
7/4.75
19/3.50
19/4.01
8.3
11.3
14.3
17.5
20.1
3.4
3.4
3.4
3.4
3.4
15.6
18.6
21.6
24.9
27.4
250
400
570
780
1060
UJAJ12AA001
UJAJ87AA001
UJAJ90AA001
UJAJ73AA001
UJAJ83AA001
7/3.75
7/4.75
19/3.50
11.3
14.3
17.5
5.5
5.5
5.5
22.9
25.9
29.2
530
720
950
ULAJ87AA001
ULAJ90AA001
ULAJ73AA001
7/3.75
7/4.75
19/3.50
11.3
14.3
17.5
8.0
8.0
8.0
28.2
31.2
34.4
720
940
1190
UNAJ87AA001
UNAJ90AA001
UNAJ73AA001
Performance Data
Nominal
DC
conductor resist.
area
at 20C
mm 2
/km
6.35/11kV
40
0.713
80
0.383
120
0.239
180
0.163
240
0.124
12.7/22kV
80
0.383
120
0.239
180
0.163
19/33kV
80
0.383
120
0.239
180
0.163
AC
resist.
at 50Hz
80C
/km
Fault
current
rating
kA for
1s
Minimum
bending
radius
(installed)
mm
Min.
breaking
load of
cable
kN
Rec. tension
Highest
Max
everyday working
tension
tension
kN
kN
Modulus
of
elasticity
Coeff.
of linear
expansion
GPa
x10 6/C
0.880
0.473
0.295
0.202
0.154
0.331
0.311
0.296
0.281
0.272
1.63
0.980
0.724
0.598
0.541
115
170
230
295
350
190
280
370
470
550
215
310
420
530
630
3.7
6.8
11.0
16.2
21.2
230
280
320
370
410
9.9
17.6
27.1
41.7
52.3
1.49
2.64
4.07
6.26
7.85
4.96
8.80
13.6
20.9
26.2
65
65
65
65
65
23.0
23.0
23.0
23.0
23.0
0.473
0.295
0.202
0.311
0.296
0.281
0.980
0.724
0.598
170
230
295
265
355
450
295
395
500
6.8
11.0
16.2
340
390
440
17.6
27.1
41.7
2.64
4.07
6.26
8.80
13.6
20.9
65
65
65
23.0
23.0
23.0
0.473
0.295
0.202
0.311
0.296
0.281
0.980
0.724
0.598
175
230
295
255
340
430
280
375
475
6.8
11.0
16.2
420
470
520
17.6
27.1
41.7
2.64
4.07
6.26
8.80
13.6
20.9
65
65
65
23.0
23.0
23.0
Note Reactance and voltage drop are based on three cables laid in flat formation spaced
0.46m apart. The values can also be applied to three-phase circuits with cables in trefoil
formation. Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 80C and solar radiation intensity of 1000W/m 2. Fault current
ratings are based on initial and final conductor temperatures of 80C and 210C respectively.
17
18
led Cables
be noted that the screens of individual cores are not in direct contact
with each other and therefore the fault current level is limited.
on the cores, the sheaths of each phase cable are marked with phase
the bundled cable comprises embossing of the words Olex, the year
on request.
of manufacture, and the voltage on the sheath or the use of printed tapes
19
The three single core cables are bundled around the galvanised steel
Operating temperature
In addition the words Olex, the year of manufacture, and the voltage
Olex has developed a special NMS HV ABC with far greater resistance
to damage from abrasion during installation or due to brushing
with trees. This special cable has a semiconductive HDPE layer over
Conductors
20
Nominal
conductor
diameter
Average
insulation
thickness
mm 2
mm
6.35/11kV
35
50
70
95
120
150
185
12.7/22kV
35
50
70
95
120
150
185
Average
insulation
screen
thickness
mm
Nominal
diameter
over core
AAAC/1120
support conductor
Size
Diameter
Nominal
overall
diameter
Approximate
mass
mm
Nominal
diameter
over
insulation
mm
Product
code
mm
no/mm
mm
mm
kg/km
6.9
8.1
9.7
11.4
12.8
14.2
15.7
3.4
3.4
3.4
3.4
3.4
3.4
3.4
15.1
16.2
17.8
19.5
20.9
22.3
23.8
1.2
1.2
1.2
1.2
1.2
1.2
1.2
17.7
18.8
20.4
22.1
23.5
24.9
26.4
7/4.75
7/4.75
7/4.75
7/4.75
19/3.50
19/3.50
19/3.50
14.3
14.3
14.3
14.3
17.5
17.5
17.5
49.6
51.9
55.1
58.5
64.5
67.4
70.4
1250
1410
1650
1950
2380
2680
3010
UJCA18AA003
UJCA19AA003
UJCA20AA003
UJCA22AA003
UJCA23AA003
UJCA24AA003
UJCA25AA003
6.9
8.1
9.7
11.4
12.8
14.2
15.7
5.5
5.5
5.5
5.5
5.5
5.5
5.5
19.4
20.5
22.1
23.8
25.2
26.6
28.1
1.2
1.2
1.2
1.2
1.2
1.4
1.4
22.0
23.1
24.7
26.4
27.8
29.7
31.2
7/4.75
7/4.75
7/4.75
7/4.75
19/3.50
19/3.50
19/3.50
14.3
14.3
14.3
14.3
17.5
17.5
17.5
58.3
60.5
63.7
67.2
73.2
77.0
80.0
1630
1810
2090
2420
2880
3280
3640
ULCA18AA003
ULCA19AA003
ULCA20AA003
ULCA22AA003
ULCA23AA003
ULCA24AA003
ULCA25AA003
Minimum bending
radius (installed)
mm
Core
Cable
Projected
diameter
for wind
loading
mm
Performance Data
Nominal
conductor
area
DC
resistance
at 20C
mm 2
6.35/11kV
35
50
70
95
120
150
185
12.7/22kV
35
50
70
95
120
150
185
/km
AC
resistance
at 50Hz
90C
/km
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.868
0.641
0.443
0.320
0.253
0.206
0.164
Inductive
reactance
at 50Hz
Conductor
to screen
capacitance
/km
Three-phase
voltage
drop at
50Hz 90C
mV/A.m
F/km
Still
air
1m/s
wind
2m/s
wind
Earth fault
current
rating
for 1s
kA
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.154
0.146
0.135
0.127
0.128
0.123
0.119
1.95
1.45
1.01
0.745
0.604
0.506
0.419
0.206
0.228
0.258
0.290
0.317
0.343
0.371
110
130
160
195
230
260
295
155
185
235
285
335
380
440
185
225
285
350
410
465
540
3.3
4.7
6.6
9.0
11.3
14.2
17.5
270
280
310
330
350
370
400
500
520
550
590
650
670
700
42.5
44.8
48.0
51.4
55.8
58.6
61.6
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.154
0.142
0.135
0.134
0.130
0.126
1.95
1.45
1.01
0.748
0.609
0.511
0.425
0.147
0.161
0.180
0.200
0.216
0.233
0.250
110
130
160
195
225
255
295
155
185
235
285
330
375
435
185
220
275
340
395
450
520
3.3
4.7
6.6
9.0
11.3
14.2
17.5
330
350
370
400
420
450
470
580
610
640
670
730
770
800
51.2
53.4
56.6
60.0
64.4
68.2
71.2
Nominal overall
diameter
mm
Cross-sectional
area
mm 2
DC resistance
at 20C
/km
Minimum
breaking load
kN
Recommended tension
Highest everyday Max. working
kN
kN
Modulus of
elasticity
GPa
Coeff. of linear
expansion
x 10 6/C
7/4.75
19/3.50
14.3
17.5
124.0
182.8
0.239
0.163
27.1
41.7
4.1
6.3
59
56
23.0
23.0
13.6
20.9
Note Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 90C and solar radiation intensity of 1000W/m 2. Fault current
ratings are based on an initial conductor temperature of 90C and final conductor
temperature of 250C.
21
Nominal
conductor
diameter
Average
insulation
thickness
mm 2
mm
6.35/11kV
35
50
70
95
120
150
185
12.7/22kV
35
50
70
95
120
150
185
Average
insulation
screen
thickness
mm
Nominal
diameter
over core
AAAC/1120
support conductor
Size
Diameter
Nominal
overall
diameter
Approximate
mass
mm
Nominal
diameter
over
insulation
mm
Product
code
mm
no/mm
mm
mm
kg/km
6.9
8.1
9.7
11.4
12.8
14.2
15.7
3.4
3.4
3.4
3.4
3.4
3.4
3.4
15.1
16.2
17.8
19.5
20.9
22.3
23.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
19.0
20.2
21.8
23.5
24.9
26.3
27.8
7/4.75
7/4.75
7/4.75
7/4.75
19/3.50
19/3.50
19/3.50
14.3
14.3
14.3
14.3
17.5
17.5
17.5
52.4
54.6
57.8
61.3
67.3
70.1
73.1
1370
1530
1790
2100
2540
2840
3190
UJDA18AA003
UJDA19AA003
UJDA20AA003
UJDA22AA003
UJDA23AA003
UJDA24AA003
UJDA25AA003
6.9
8.1
9.7
11.4
12.8
14.2
15.7
5.5
5.5
5.5
5.5
5.5
5.5
5.5
19.4
20.5
22.1
23.8
25.2
26.6
28.1
1.8
1.8
1.8
1.8
1.8
1.8
1.8
23.3
24.5
26.1
27.8
29.2
30.6
32.1
7/4.75
7/4.75
7/4.75
7/4.75
19/3.50
19/3.50
19/3.50
14.3
14.3
14.3
14.3
17.5
17.5
17.5
61.0
63.3
66.5
69.9
75.9
78.7
81.7
1780
1970
2260
2600
3070
3390
3760
ULDA18AA003
ULDA19AA003
ULDA20AA003
ULDA22AA003
ULDA23AA003
ULDA24AA003
ULDA25AA003
Performance Data
Nominal
conductor
area
DC
resistance
at 20C
mm 2
6.35/11kV
35
50
70
95
120
150
185
12.7/22kV
35
50
70
95
120
150
185
Inductive
reactance
at 50Hz
/km
AC
resistance
at 50Hz
90C
W/km
Conductor
to screen
capacitance
/km
Three-phase
voltage
drop at
50Hz 90C
mV/A.m
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.868
0.641
0.443
0.320
0.253
0.206
0.164
Minimum bending
radius (installed)
mm
2m/s
wind
Earth fault
current
rating
for 1s
kA
Core
Cable
Projected
diameter
for wind
loading
mm
F/km
Still
air
1m/s
wind
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.156
0.149
0.137
0.130
0.130
0.125
0.121
1.95
1.45
1.01
0.746
0.606
0.507
0.421
0.206
0.228
0.258
0.290
0.317
0.343
0.371
110
130
160
195
230
255
295
155
185
235
285
335
380
440
185
225
280
345
405
460
530
3.3
4.7
6.6
9.0
11.3
14.2
17.5
290
300
330
350
370
390
420
520
550
580
610
670
700
730
45.2
47.6
50.8
54.2
58.6
61.4
64.4
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.164
0.156
0.145
0.137
0.136
0.131
0.127
1.95
1.45
1.02
0.750
0.610
0.512
0.426
0.147
0.161
0.180
0.200
0.216
0.233
0.250
110
130
160
195
225
255
290
155
185
230
285
330
375
435
180
220
275
335
395
450
520
3.3
4.7
6.6
9.0
11.3
14.2
17.5
350
370
390
420
440
460
480
610
630
670
700
760
790
820
53.8
56.2
59.4
62.8
67.2
70.0
73.0
Nominal overall
diameter
mm
Cross-sectional
area
mm 2
DC resistance
at 20C
/km
Minimum
breaking load
kN
Recommended tension
Highest everyday Max. working
kN
kN
Modulus of
elasticity
GPa
Coeff. of linear
expansion
x 10 6/C
7/4.75
19/3.50
14.3
17.5
124.0
182.8
0.239
0.163
27.1
41.7
4.1
6.3
59
56
23.0
23.0
13.6
20.9
Note Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 90C and solar radiation intensity of 1000W/m 2. Fault current
ratings are based on an initial conductor temperature of 90C and final conductor
temperature of 250C.
22
Nominal
conductor
diameter
Average
insulation
thickness
mm 2
mm
Average
insulation
screen
thickness
mm
Copper
wire
screen
stranding
no/mm
Nominal
diameter
over
screen
mm
Average
sheath
thickness
mm
Nominal
diameter
over
insulation
mm
Galvanised
steel
catenary
stranding
no/mm
Nominal
overall
diameter
Approx.
mass
mm
Nominal
diameter
over
sheath
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
15.1
15.1
16.2
17.8
19.5
20.9
22.3
23.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
15.1
15.1
16.2
17.8
19.5
20.9
22.3
23.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
40/0.85
40/0.85
23/1.35
32/1.35
39/1.35
39/1.35
39/1.35
39/1.35
Product
code
mm
kg/km
19.8
19.8
20.9
22.5
24.2
25.6
27.0
28.5
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
24.0
24.0
25.2
26.8
28.5
29.9
31.5
33.0
7/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
54.1
58.1
60.4
63.6
67.0
69.8
73.0
76.0
1820
2130
2300
2570
2900
3190
3530
3890
UJLA18DZ003
UJLA18AA003
UJLA19AA003
UJLA20AA003
UJLA22AA003
UJLA23AA003
UJLA24AA003
UJLA25AA003
19.8
19.8
21.9
23.5
25.2
26.6
28.0
29.5
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
24.0
24.0
26.2
27.8
29.5
30.9
32.5
34.0
7/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
54.1
58.1
62.4
65.6
69.0
71.8
75.0
78.0
2050
2360
2820
3440
4030
4320
4670
5020
UJHA18DZ003
UJHA18AA003
UJHA19AA003
UJHA20AA003
UJHA22AA003
UJHA23AA003
UJHA24AA003
UJHA25AA003
Performance Data
Nominal
conductor
area
DC
resistance
at 20C
mm 2
/km
AC
resistance
at 50Hz
90C
/km
Inductive
reactance
at 50Hz
Conductor
to screen
capacitance
/km
Three-phase
voltage
drop at
50Hz 90C
mV/A.m
Minimum bending
radius (installed)
mm
2m/s
wind
Earth fault
current
rating
for 1s
kA
Core
Cable
Projected
diameter
for wind
loading
mm
F/km
Still
air
1m/s
wind
1.11
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.150
0.158
0.150
0.139
0.131
0.126
0.122
0.118
1.95
1.95
1.45
1.01
0.747
0.603
0.505
0.418
0.206
0.206
0.228
0.258
0.290
0.317
0.343
0.371
99
100
120
150
180
205
235
265
140
145
170
215
260
300
340
390
165
165
200
250
305
355
400
460
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
360
360
380
400
430
450
470
500
540
580
600
640
670
700
730
760
51.0
53.0
55.4
58.6
62.0
64.8
68.0
71.0
1.11
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.150
0.158
0.152
0.140
0.133
0.128
0.123
0.119
1.95
1.95
1.45
1.01
0.747
0.604
0.506
0.420
0.206
0.206
0.228
0.258
0.290
0.317
0.343
0.371
99
100
120
150
180
205
230
265
140
145
175
215
260
300
340
390
165
165
200
250
305
355
400
460
3.3
3.3
4.8
6.7
8.1
8.1
8.1
8.1
360
360
390
420
440
460
490
510
540
580
620
660
690
720
750
780
51.0
53.0
57.4
60.6
64.0
66.8
70.0
73.0
Nominal overall
diameter
mm
Cross-sectional
area
mm 2
DC resistance
at 20C
/km
Minimum
breaking load
kN
Recommended tension
Highest everyday
Max. working
kN
kN
Modulus of
elasticity
GPa
Coeff. of linear
expansion
x 10 6/C
7/2.00
19/2.00
6.0
10.0
22.0
59.7
8.7
3.2
26.0
70.5
6.5
17.6
170
166
11.5
11.5
13.0
35.3
Note Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 90C and solar radiation intensity of 1000W/m 2 with screens
solidly bonded at both ends. Fault current ratings are based on an initial screen temperature
of 85C and final screen temperature of 250C.
23
Nominal
conductor
diameter
Average
insulation
thickness
mm 2
mm
Average
insulation
screen
thickness
mm
Copper
wire
screen
stranding
no/mm
Nominal
diameter
over
screen
mm
Average
sheath
thickness
mm
Nominal
diameter
over
insulation
mm
Galvanised
steel
catenary
stranding
no/mm
Nominal
overall
diameter
Approx.
mass
mm
Nominal
diameter
over
sheath
mm
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
19.4
19.4
20.5
22.1
23.8
25.2
26.6
28.1
0.8
0.8
0.8
0.8
0.8
0.8
1.0
1.0
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
25/0.85
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
19.4
19.4
20.5
22.1
23.8
25.2
26.6
28.1
0.8
0.8
0.8
0.8
0.8
0.8
1.0
1.0
40/0.85
40/0.85
23/1.35
32/1.35
39/1.35
39/1.35
39/1.35
39/1.35
Product
code
mm
kg/km
24.1
24.1
25.2
26.8
28.5
29.9
31.7
33.2
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
28.4
28.4
29.5
31.3
33.0
34.6
36.4
38.1
7/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
62.7
66.7
69.0
72.6
76.0
79.2
82.8
86.2
2280
2580
2780
3110
3460
3810
4230
4650
ULLA18DZ003
ULLA18AA003
ULLA19AA003
ULLA20AA003
ULLA22AA003
ULLA23AA003
ULLA24AA003
ULLA25AA003
24.1
24.1
26.2
27.8
29.5
30.9
32.7
34.2
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
28.4
28.4
30.5
32.3
34.0
35.6
37.4
39.1
7/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
62.7
66.7
71.0
74.6
78.0
81.2
84.8
88.2
2510
2810
3300
3970
4600
4950
5360
5790
ULHA18DZ003
ULHA18AA003
ULHA19AA003
ULHA20AA003
ULHA22AA003
ULHA23AA003
ULHA24AA003
ULHA25AA003
Performance Data
Nominal
conductor
area
DC
resistance
at 20C
mm 2
/km
AC
resistance
at 50Hz
90C
/km
Inductive
reactance
at 50Hz
/km
Three-phase
voltage
drop at
50Hz 90C
mV/A.m
Conductor
Continuous current rating, A
to screen
capacitance
Still
1m/s
2m/s
F/km
air
wind
wind
Earth fault
current
rating
for 1s
kA
Minimum bending
radius (installed)
mm
Core
Cable
Projected
diameter
for wind
loading
mm
1.11
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.158
0.166
0.158
0.146
0.138
0.133
0.129
0.125
1.95
1.95
1.45
1.02
0.750
0.608
0.510
0.424
0.147
0.147
0.161
0.180
0.200
0.216
0.233
0.250
100
105
125
150
180
205
230
265
140
145
170
215
260
300
340
390
165
165
200
250
300
350
395
450
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
430
430
440
470
500
520
550
570
630
670
690
730
760
790
830
860
59.8
61.8
64.0
67.6
71.0
74.2
77.8
81.2
1.11
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.158
0.166
0.159
0.148
0.140
0.134
0.130
0.126
1.95
1.95
1.45
1.02
0.751
0.609
0.511
0.426
0.147
0.147
0.161
0.180
0.200
0.216
0.233
0.250
100
105
125
155
180
205
230
265
140
145
175
215
260
300
340
390
165
165
200
250
305
350
395
450
3.3
3.3
4.8
6.7
8.1
8.1
8.1
8.1
430
430
460
480
510
530
560
590
630
670
710
750
780
810
850
880
59.8
61.8
66.0
69.6
73.0
76.2
79.8
83.2
Nominal overall
diameter
mm
Cross-sectional
area
mm 2
DC resistance
at 20C
/km
Minimum
breaking load
kN
Recommended tension
Highest everyday
Max. working
kN
kN
Modulus of
elasticity
GPa
Coeff. of linear
expansion
x 10 6/C
7/2.00
19/2.00
6.0
10.0
22.0
59.7
8.7
3.2
26.0
70.5
6.5
17.6
170
166
11.5
11.5
13.0
35.3
Note Continuous current ratings are based on an ambient temperature of 40C, maximum
conductor temperature of 90C and solar radiation intensity of 1000W/m2 with screens solidly
bonded at both ends. Fault current ratings are based on an initial screen temperature of 85C
and final screen temperature of 250C.
24
The future is
our favourite place
At Olex, the future always looks incredibly bright. Thats because we
spend most of our time there. Over the decades, Olex has consistently
led the cable market in technological innovation. For more than 60 years
Olex has stood for the highest quality and the most innovative
Fire Rated Cables, Low Voltage Building Wires, Airport Lighting Cables
www.olex.com.au
Olex reserves the right to change or vary the construction of any of their products without notice.
Every care has been taken in the printing of this publication but Olex accepts no liability of any
kind resulting from the information provided herein.
Olex Australia Pty Limited A.B.N. 61 087 542 863 Printed in Australia 9/2003 Disegno OLC5345
25
www.olex.co.nz
South East Asia 396C River Valley Road
Singapore 248290 Phone 65 688 70200
China Room 57119 Building 7# Xiyuan Hotel
Beijing China 100044 Phone 86 10 6831 8549
For more information see
www.olex.com.au
LOW VOLTAGE
INDUSTRIAL
HIGH VOLTAGE
FIRE RATED
DATA / COMMS
MINING