Cerberus AlgoRex

Fire detection system


Interactive / AnalogPLUS / Collective Modular, microprocessor-controlled fire detection system Processes the signals from fire detectors from widely varying detection systems such as: interactive fire detectors, series DS1150 AnalogPLUS fire detectors, series DS1130 collective fire detectors, series DS1100 addressable fire detectors, series MS7i/MS9i Highest system availability through decentralized signal evaluation in control unit and detectors Parametrisation as required by the application Emergency power operating period 12 to 24 hours, optionally up to 72 hours Integrated emergency operation electronics Control console can be connected separately or builtin into the control unit housing Several control consoles can be operated with each control unit Designed for optimum installation efficiency and commissioning

CS1140

VENTEVILLE bv

Fire & Security Products

System overview
Control console CT1142 Optional text display and control terminals B3Q580 / B3Q590 External interface to drive LEDs (for mimic display panels) or relays

C Bus

LON Bus

Interactive detector bus for series DS1150 fire detectors Fire detection system control unit CI1142/CC1142/CC1143 Alarm devices

CPU
T-tap

Alarm reception centre (Fire department)

AnalogPLUS detector bus for series DS1130 fire detectors

I Bus

Fire control installations Control module

Line module

Autonomous extinguishing area VdS periphery: Fire department control panel Fire department key cabinet Main fire alarm box Pager system (protocol ESPA 4.4.4)

T-tap

Collective detection line for series DS1100 fire detectors

FBF FSK HM

Mains

Printer Maintenance PC

Interactive and AnalogPLUS comparison Interactive G G G G G G G G G AnalogPLUS G G G G G G

Algorithms can be selected for each detector Response behaviour can be selected for each detector Detector operation monitored Automatic self test The detector transmits any variation from the quiescent value (drift) Application error warning by the detector Free allocation of logical addresses Automatic measured value compensation Multi detector linking

Signal registration Detector bus / Detection line The control unit registers signals from automatic fire detectors, manual call points and input modules via detector bus or detection line and carries out decentralized control functions via output modules. All three detector systems can be connected to the CS1140 system. Series DS1150 Interactive fire detectors have a unique evaluating and decision logic based on algo rithms. They provide the highest level of detection reliability and differentiate clearly between genuine fire and deceptive phenomena. AnalogPLUS is an addressable detector system in which detector sensitivity can be selected centrally. Intelligent signal evaluation (alarm verification, comparison and evaluation of signals from several detectors). Collective fire detectors with traditional technology for communication and signal eval uation (one address per detection line, only alarm signal). The detectors have the same first class sensor system as the other DS11 detectors. Furthermore, it is possible to integrate existing parts of systems with detectors from series MS6, MS7, MS9 and MS24. These addressable detection lines can be integrated as parts of existing systems.

Series DS1130

Series DS1100

MS7i, MS9i

Evaluation Alarm Operation Control Parameterization The modification of control unit organization to changed customers requirements is no problem. Freely programmable control outputs are available for fire control installations. Driver and/or relay outputs as required. Automatic summer/winter switchover by means of an integrated real time clock. With its own emergency power supply. Up to 1000 events can be arranged, stored and recalled chronologically and accord ing to message category. Emergency operation functions are integrated in the important function modules. As a result, the system can continue to signal fire even if a component malfunctions. An extinguishing section can be activated via the Extinguishing" control module. Several extinguishing sections can be activated from one control unit. The structure of the C Bus network permits the connection of several control units and control consoles. These stations can be mounted in the same housing or in separate housings. The location is chosen according to where it is easiest for operation or installation. However, the fire detection system can be extended even further. Several C Bus net works can be combined to a danger management system by means of the data link Cerloop/Cerban".

Control outputs

Real time clock

Event memory

Emergency operation

Extinguishing activation

System flexibility

Expansion up to a complex fire detection system

Control console CT1142

CPU

Control unit CC1142/CC1143

C Bus

Maximum 16 stations can be connected to the C Bus (length of C Bus max. 1800m): up to 4 CPUs (CI1142/CC1143) up to 12 control consoles (CT1142) 1 Gateway (CK1142)

Control unit CI1142 CPU

Gateway

Gateway CK1142

Cerloop/Cerban

Gateway (further C Bus network)

Danger management system

Types of control units (CPU)


Number of detectors Number of line and control modules Control console Metal housing, type Dimensions WxHxD [mm]
4

CI1142 up to 800 up to 16

CC1142 up to 1000 up to 16

CC1143 up to 2000 up to 16

permanently built in and additionally mounted in separate housing

built in and/or mounted in separate housing

H38G200

H38G300

H47...

H67...

H98...

515x602x100

515x602x155

434x735x300

434x1130x300

600x2012x300

Operation

Cerberus CT11

1 2

ALARM

FIRE BRIGADE called 01 AUTOM. FIRE DETECTOR building 10 1st floor room 105 05 MANUAL CALL POINT building 10 1st floor staircaise F1: function F2: detail

Total:05

C: end

Acknowledge

3
Reset

Information Premises manned Alarm delay off Detector test mode

Isolation Alarm device off Remote alarm off Control function off

Alarms Alarm device active Remote alarm active System on

Faults Alarm device fault Remote transmission fault System fault

7 4 1

8 5 2 0

9 6 3 C

F1 F2 ok

Illuminated keys enable clear, guided operation even in an emergency. Function and recall commands which cannot be carried out by means of separate keys, can be selected using menus accessed via plain text display. Operating access is via password or key. Illuminated alarm panel (1) When an alarm event is received the red text ALARM" lights up. Plain language display (2) Automatic plain text information on events, event location, counter measures as well as operating mode and operator infos is displayed on the large liquid crystal display (LCD). The LCD background lights up red for alarm and yellow for fault and operating functions. The display mode complies with EN54: 2 alarm events can be displayed simulta neously on the LCD. A user text is displayed for each event to provide precise location information. User texts are prepared for each specific system. Standard texts are available for type of signal, infos on operation etc. Even special language symbols can be indicated on LCD without difficulty. An individual counter measures text can be allocated to each zone. When an event occurs, the texts are displayed upon command. In each control unit (CPU), up to 16 freely programmable counter measures texts are available. (3) If several events are signalled, the information can be recalled one by one. (4) 4 categories of messages: Information, Isolation, Alarms and Faults. Emergency operation is a permanent component of the control console. This ensures operation, which complies with standards, even if the processor in the control console is malfunctioning.

Messages

Countermeasures text

Alarm scroll key Indicator fields Emergency operation

Interfaces The control console has interfaces for: parallel indicators and/or mimic display panels logging printer and/or pager system external key switch

Line length up to 1000m / max. 8 addresses Control console

Parallel indicators Printer Pager system Mimic display panel(s)

Control consoles available

B3Q460 International

B3Q480 Nordic

B3Q560 Asian

Auxiliary equipment
Information module H23B040 Fire department control panel B3Q321 Operating unit Extinguishing B3Q440 Parallel indicators (24 x 2 LEDs) B3R051

Cover H23B010

Options
Plexiglass door Control consoles in H26G... / H28G... housings which are particularly exposed can be fitted with a lockable Plexi glass door to prevent tam pering. Inscriptions sets Inscriptions for dis play and operating elements are pro vided separately on strips for insertion. These are available in more than 20 lan guages.

Mounting possibilities of control consoles Metal housing H28G200


520

300

Auxiliary equipment
70

Auxiliary equipment

Control console Metal housing H28G200 with door H28T110

Door H28T130 with fire plan compartment Mounted in metal housing H28G200 with door. Installation possibility for auxiliary equipment.

Plastic housing H23G230, H26G220

125

H23G230
366

Standard application in the attractive plastic housing. Installation of auxiliary equipment in a separate plastic housing.

H26G220

219

Auxiliary equipment Control console


76

Control unit housings

Housing H47G...

Door H47T... Built into the door of the control unit. Possibility of installing auxiliary equipment. Installation of the control console and auxiliary equipment with adapter plate in any 19" housing.

Technical data Control unit Control console CI1142/CC1142/CC1143 CT1142 Key module B3Q460 B3Q480 Protection category (EN60529 / IEC529) in housing H38/H47/H67/H98 in housing H26G220 in housing H28G200 Colour housing H38/H47/H67/H98 housing H26G220 housing H28G200 door H28T... front surface keys/display panel Operating temperature Storage temperature Humidity KABA 8 #100 (option) Nordic fire department lock built in

IP40 RAL7035 light grey 0...+50C 20...+60C max. 95%, no condensation (IEC721 3 3, class 3K5) EN54 2, EN54 4

IP52 IP40 Pantone 421 grey RAL7035 light grey 1E110 dark grey Pantone 421 grey Pantone 424, 427 grey 0...+50C 20...+60C max. 95%, no condensation (IEC721 3 3, class 3K5) EN54 2

Standards

Bus / Detection line Number of addresses Number of wires Network structure Loop line Short circuit proof T tap

Interactive DS1150 up to 128 2 Master/Slave yes yes yes

AnalogPLUS DS1130 up to 128 2 Master/Slave yes yes yes

Collective DS1100 1 2 no no no