TECHNICAL DATA

BULLETIN 140U/UE
Molded Case Circuit Breakers
CATALOG NUMBERS 140U/UE

Bulletin 140U/UE

Molded Case Circuit Breakers


Electrical Specifications
Standards Interrupting Ratings Rated Insulation Voltage Rated Impulse Withstand Voltage Rated Operational Voltage Permissible Ambient Temperature DC-Rated Short Circuit Breaking Capacity Utilization Category Power Loss 4 4 4 4 4 4 4 5 5

Auxiliary Circuit Specifications


Internal Control Module Terminations Auxiliary and Alarm Contacts Undervoltage Release Shunt Trips 5 5 6 6

Mechanical Specifications
Weight Dimensions Mounting Hardware Terminals, Lugs, and End Caps 7 7 7 7

Termination Specifications
G- & H-Frames J- & K-Frames L- & M-Frames N-Frame 8 10 12 14

Dimension Drawings
G-Frame H-Frame J-Frame K-Frame L-Frame M-Frame N-Frame 18 20 23 24 25 27 28

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves
G-Frame 100 A Thermal-Magnetic MCCBs H-Frame 125 A Thermal-Magnetic MCCBs J-Frame 250 A Thermal-Magnetic MCCBs J-Frame 250 A Electronic LS MCCBs J-Frame 250 A Electronic LSI MCCBs J-Frame 250 A Electronic LSG & LSIG MCCBs K-Frame 400 A Thermal-Magnetic MCCBs 35, 65 kA (-K3, -K6) 100 kA (-K0) K-Frame 400 A Electronic LS,LSG MCCBs 35, 65 kA (-K3, -K6) 100 kA (-K0) K-Frame 400 A Electronic LSI,LSIG MCCBs 35, 65 kA (-K3, -K6) 100 kA (-K0) K-Frame 400 A Electronic MCCBs with Ground Fault Protection L-Frame 600 UL (630 IEC) A Thermal-Magnetic MCCBs Q-Frame 600 A Thermal-Magnetic MCCBs 35, 65 kA (-Q3, -Q6) M-Frame 800 A Thermal-Magnetic MCCBs (300600 A) 50, 65 A (-M5, -M6) M-Frame 800 A Thermal-Magnetic MCCBs (700 & 800 A) 50, 65 A (-M5, -M6) M-Frame Electronic LS, LSG MCCBs 50, 65 A (-M5, -M6) M-Frame Electronic LSI, LSIG MCCBs 50, 65 A (-M5, -M6) M-Frame 800A Electronic MCCBs with Ground Fault Protection N-Frame Electronic LS MCCBs N-Frame Electronic LSI MCCBs N-Frame Electronic LSG, LSIG MCCBs with Ground Fault Protection 27 28 29 35 36 37 40 40 41 42 40 41 40 40 41 44 48 52 52 52 53 52 54 55 55 55 56 57 58 59 60

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Electrical Specifications
Frame Size Interrupting Ratings Max Rated Current In Frame Ratings [A] [A] G 100 100 2, 3 2-3P 415 690 H 125 125 1, 2, 3 750 690 H (UE) 160 160 3, 4 750 690 J 250 250 3 750 690 K 400 400 3 750 690 L 600 600 3 750 690 L (UE) 630 630 3, 4 750 690 M 800 800 3 750 690 N 1200 800/1200 3 750 690

No. of Poles Main Poles Auxiliary Circuit Main Conductors Auxiliary Circuits IEC (50 Hz) [V] [V]

Rated Insulation Voltage (U) According to IEC 60947-2

Rated Impulse Withstand Voltage (Uimp) [kV] [kV] 2-3P 6 4 6 4 6 4 8 4 8 4 8 4 8 4 8 4 8 4

Rated Operational Voltage (Ue) - AC [V] 440 480 690 600/347 690 600/347 690 600 690 600 690 600 690 600 690 600 690 600 UL/NEMA (60 [V] Hz) UL 489 CSA 22.2 No. 5 IEC 60947-2

Standards Compliance Ambient Operating Temperature Range +16140F (8.960C) Permissible Ambient Temperature, Low Setting/High Setting Derating Factor (%) Molded Case Circuit Breaker At 40 C At 50 C At 55 C At 60 C At 70 C At 40 C At 50 C At 55 C At 60 C At 70 C 100 96 93 91 86 100 /100 96/92 93/87 91/83 86/73 100 100 96 81 86 100 /100 96/92 93/87 91/83 86/73 100 100 96 81 86 100/100 96/94 94/90 92/87 88/80 Isolation Switch 100 100 96 88 82 100 100 96 90 85 100 100 95 90 84 100 100 95 90 84 100 100 95 90 84 100 91 85 81 100/100 96/92 93/87 90/84 85/75 100/100 96/91 93/86 90/82 84/70 100/100 96/91 93/86 90/82 84/70 100/100 96/91 93/86 90/82 84/70 100 91 85 81

DC - Rated Short Circuit Breaking Capacity (kA) Time Constant < 8ms, non-inductive loads 1 Pole 2 Poles in Series 3 Poles in Series 250V 440V 660V 10 (2p) 10 20 20 10 20 20 10 20 20 10 20 20 10 20 20 10 20 30 10

Thermal set at max. on Fixed Thermal. Bulletin 140UE versions of the H-, J-, L-, M-, and N-Frame only comply with IEC 60947-2.

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Electrical Specifications, Continued
Frame Size G Utlization Category Maximum Switching Ops/hour Frequency At maximum rated current (In), 3-Phase Symmetrical Load Molded Case Circuit Breaker Molded Case Switch [W] 50 50 75 175 250 87 87/210 H A 300 300 H (UE) A 300 J A 240 Power Loss K A 240 L A 240 L (UE) A 240 M A 60 N A 60

[W]

40

40

75

107

160

87

87/210

Auxiliary Circuit Specifications


Frame Size G with Terminal Connections - Cable Size Wire size range Lead Length Wire size range Tightening Torque AWG mm2 H H (UE) J K L L (UE) M N Internal Control Module Terminations

with Supplied Leads in. (cm) AWG mm2 Lb-in Nm 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4

Auxiliary & Alarm Contacts Rated Thermal Current - Ith Rated Making Capacities Rated Operational Current (AC15) 230V 400V 480V 690V Rated Operational Current (DC13) 24V 125V 240V [A] [A] [A] 5 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 [A] [A] [A] [A] 6 (240V) 0.25 (600V) 0.25 (600V) 0.25 0.25 0.25 0.25 0.25 0.25 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 [A] 6 6 6 6 6 6 6 6 6

[A]

10

20

20

20

20

20

20

20

20

Back-up Protection (max rating) Fuses Miniature Circuit Breakers [A] [A] 6 6 6/4/4 6/4 6/4/4 6/4/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Auxiliary Circuit Specifications, Continued
Frame Size G Response Voltage Drop-out (CB trip) Pick-up (CB switch on) AC (50/60 Hz) 12V 24V 4860V 110127V 208240V 380500V 525600V DC 12V 24V 4860V 110125V 220250V Max. Operating Time Response Voltage Pick-up (CB Trip) AC (50/60 Hz) 24V 4860V 110240V 380440V 480600V DC 12V 24V 4860V 110125V 220250V Max. Operating Time [W] [W] [W] [W] [W] [ms] 50 29 120 475720 99121 50 29 120 475720 99121 50 164 631 8301580 112150 50 164 631 8301580 112150 4058 50 79 1000 1831 112150 50 79 1000 1831 112150 50 35 170 7101105 110140 4154 50 46 405 5894 7498 3849 62 [VA] [VA] [VA] [VA] [VA] 135500 10 139210 83360 4181080 10 139210 83360 4181080 87405 7101105 66432 127188 3460 87405 7101105 66432 127188 3460 87405 7101105 66432 127188 3460 87405 7101105 66432 127188 3460 200 8301280 100550 95136 4070 86631 4871 81505 4368 4169 [Us] 70110% 70110% 70110% 70110% 70110% 70110% 70110% 70110% 70110% [W] [W] [W] [W] [W] [ms] 50 0.88 0.7 1.121.76 0.941.21 1.451.86 50 0.88 0.7 1.121.76 0.941.21 1.451.86 50 1.6 3.1 2.03.1 1.62.2 3.14 50 Shunt Trips 1.6 3.1 2.03.1 1.62.2 3.14 50 1.6 3.1 2.03.1 1.62.2 3.14 50 1.6 3.1 2.03.1 1.62.2 3.14 50 1.6 3.1 2.03.1 1.62.2 3.14 50 2.6 3.6 3.55.5 2.93.6 4.86.3 80 [VA] [VA] [VA] [VA] [VA] [VA] [VA] 5.3 1.5 1.8 1.4 4.8 0.95 0.72 1.15 1.78 0..961.25 1.281.68 2.23.9 0.95 0.72 1.15 1.78 0..961.25 1.281.68 2.23.9 1.9 3.9 2.53.8 1.82.4 2.73.8 3.45.8 1.9 3.9 2.53.8 1.82.4 2.73.8 3.45.8 1.9 3.9 2.53.8 1.82.4 2.73.8 3.45.8 3.44.3 1.9 3.9 2.53.8 1.82.4 2.73.8 3.45.8 3.44.3 1.9 3.9 2.53.8 1.82.4 2.73.8 3.45.8 3.45.4 1.9 2.4 2.34.1 3.44.2 4.86.5 6.812.0 [Us] [Us] 3570% 85110% 3570% 85110% 3570% 85110% 3570% 85110% 3570% 85110% 3570% 85110% 3570% 85110% 3570% 85110% 3570% 85110% H H (UE) J K L L (UE) M N Undervoltage Releases

Power Consumption

Power Consumption

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Mechanical Specifications
Frame Size G [lb.] [kg] [lb.] [kg] [lb.] [kg] [lb.] [kg] Height 1-Pole Width Depth Height 2-Pole Width Depth Height 3-Pole Width Depth Height 4-Pole Width Depth Endurance Operating Cycles 1.5 0.7 2.2 1 4.88 (124.0) 2 (50.8) 2.81 (71.4) 4.88 (124.0) 3 (76.2) 2.81 (71.4) 10000 H 1.0 0.45 2.0 0.91 3.0 1.36 4.0 1.81 5.5 (139.7) 1 (25.4) 3 (76.2) 5.5 (139.7) 2 (50.8) 3 (76.2) 5.5 (139.7) 3 (76.2) 3 (76.2) 5.5 (139.7) 4 (101.6) 3 (76.2) 10000 H (UE) 1.0 0.45 2.0 0.91 3.0 1.36 0.0 5.5 (139.7) 1 (25.4) 3 (76.2) 5.5 (139.7) 2 (50.8) 3 (76.2) 5.5 (139.7) 3 (76.2) 3 (76.2) 5.5 (139.7) 4 (101.6) 3 (76.2) 10000 J Weight (approx.) 1-Pole 2-Pole 3-Pole 4-Pole 11.4 5.2 11.4 5.2 15.4 7 7 (177.8) 4.13 (105) 4.05 (103) 7 (177.8) 4.13 (105) 4.05 (103) 7 (177.8) 4.13 (105) 4.05 (103) 7 (177.8) 5.51 (140) 4.05 (103) 10000 Mounting Hardware Imperial (in.) Cat. No. Metric Cat. No. Quantity Style Tightening Torque Lb-in Nm 0.138-32 x 2.63 0.138-32 x 3.00 0.250-20 x 1.75 0.3125-18 x 3.9 0.3125-18 x 3.9 0.3125-18 x 1.25 140U-MMHS 0.3125-18 x 1.25 140U-N-MHS 13.4 6.1 16.1 7.3 10.16 (258) 5.51 (140) 4.09 (104) 10.16 (258) 7.2 (183) 4.09 (104) 10000 13.4 6.1 16.1 7.3 10.16 (258) 5.51 (140) 4.09 (104) 10.16 (258) 7.2 (183) 4.09 (104) 8000 13.4 6.1 16.1 7.3 10.16 (258) 5.51 (140) 4.09 (104) 10.16 (258) 7.2 (183) 4.09 (104) 8000 43.9 19.9 16 (406) 8.25 (210) 4.05 (103) 3000 46.9 21.3 62.3 28.3 15.98 (406) 8.27 (210) 4.09 (104) 15.98 (406) 11.02 (280) 4.09 (104) 3000 K L L (UE) M N

Dimensions in Inches (mm)

140U-G-MHS 140U-H-MHS

140U-K-MHS 140U-L-MHS 140U-L-MHS

M4 x 0.7 x 75 M4 0.7 x 75 M4 x 0.7 x 75 M4 x 0.7 x 90 M6 x 1.0 x 45 M5 x 0.8 x M5 x 0.8 x M8 x 1.0 x 35 M8 x 1.0 x 35 mm mm mm mm mm 100 mm 100 mm mm mm 140U-G140U-H140U-H140U-K140U-M140U-N140U-J-MHM 140U-L-MHM 140U-L-MHM MHM MHM MHM MHM MHM MHM 4 Pan Head 15 1.69 4 Pan Head 15 1.69 4 Pan Head 15 1.69 4 Pan Head 10 1.13 4 Pan Head 2025 23 4 Pan Head 25 3 4 Pan Head 25 3 4 Pan Head 28 3 4 Pan Head 28 3

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Terminal and Lugs Specifications
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Terminals Specification Material A Dim. B C Fastener Torque Lb-in Nm 1/2 (12.7) 3/8 (9.53) 1/8 (3.175) Specification Std/Optional Cat. No. Material Terminal Fastener Hardware Lb-in Nm Box Lugs Standard Steel Flathead 10 0.2 Cu Only 60/75C 1 1/2 12.7 #143 2.526 Slotted #8 40 lb-in. 10 mm 4.5 Nm #63 45 lb-in. 1626 mm 5.1 Nm Optional 140U-H-MTL3A Aluminum Lugs Multitap Optional 140U-H-MTL6A Aluminum

Frame Size

End Cap Optional 140UH-ECM Molded Housing

Slip on Terminal box lug Fastene r Torque

Cable Type Cable Temperature Rating Cable Quantity

Wire Strip Length Wire Range

in. mm AWG mm2

Terminal Type
B

Lb-in #1410 36 lb-in. Wire Torque Nm 2.56 mm 3.9 Nm

Material A B C D Fastener Lb-in Torque Nm 1/2 (12.7) 7/16 (10.99) 1/4 (6.35) 1/5 (5.0)

Std/Optional Cat. No. Material Terminal Fastener Hardware Lb-in Nm

Standard Steel

Dim.

Flathead

#10-32 Slotted Screw

#10-32 Slotted Screw

Flathea Terminal d Fastene 3550 r Torque 4.05. 6

10 0.2 Cu Only 60/75C (1) 1/2

45 lb-in 5 Nm Cu/Al 60/75C (3)

45 lb-in 5 Nm Cu/Al 60/75C (6)

Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length in.

(A) (B) (C) 1(A) (B) (C) 13/81/ 3/47/ 1/41- 3/81/ 3/47/ 1/412 in. 8 in. 3/8 in. 2 in. 8 in. 3/8 in. (A) 913 mm #3 3/0 3595 (B) 1922 mm #14#2 2.535 Allen - 5/32 in. (4 mm) 50 5.6 70 lb-in 7.9 Nm (C) 3235 mm (A) 913 mm (B) 1922 mm #14#6 2.510 Allen - 3/32 in. (3 mm) 25 lb-in 2.8 Nm (C) 3235 mm

mm
D C

12.7 #141 0 #8 10 #64 1625

Allen - 4 mm 3438 Lb-in 3.84.3 Nm

Wire Range
B

AWG

mm2 2.56

Terminal Type Lb-in Nm 35 4.0

Slotted 40 4.5 45 5.1

Wire Torque

10

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Terminal and Lugs Specifications, Continued
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Terminals Frame Size Specification Material A Dim. B C D Fastener Torque Lb-in Nm J
A

Lugs Specification Std/Optional 3/4(19.05) 5/8(15.88) Cat. No. Material Box Lugs Optional 140U-JTLS1 Steel Phillips Head 10 0.2 Cu Only 60/75C (1) 0.75 19.05 4350 MCM Allen 180 20 Optional 140U-KTLC1 Copper Optional 140U-JTLA1 Alumium Phillips head 10 0.2 Cu/Al 60/75C (1) 0.75 19.05 4350 MCM 25185 Allen 250 28 Optional 140U-KTLA1 Optional 140U-KTLA1A Optional 140U-KTLC2 Copper Mechanical Lugs Optional 140U-KTLA2 Alumium Optional 140U-KTLC1A Copper Optional 140U-KTLA2A Optional 140U-KTLA1B Optional 140U-KTLC1B Copper

5/16(7.94) Terminal Fastener Hardware 5/16(8.0) Hex 180/250 20/28 Terminal Fastener Torque Lb-in Nm

Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length in. mm AWG

D C

Wire Range
B

mm2 25185 Lb-in Nm

Terminal Type Wire Torque

Material A Dim. B C D Fastener Torque Lb-in Nm 1(25.4) 3/4(19.05) 3/8(9.53) Hex 275/375 3/42

Std/Optional Cat. No. Material

Alumium Alumium

Alumium Alumium

Terminal Fastener Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hardware 11/32(8.9) Terminal Fastener Torque Lb-in Nm 96 10.8 Cu Only 60/75C (1) 1 25.4 96 10.8 Cu/Al 60/75C (1) 1 25.4 96 10.8 Cu/Al 60/75C (1) 1 25.4 96 10.8 Cu Only 60/75C (2) 1 25.4 96 10.8 Cu/Al 60/75C (2) 1 25.4 96 10.8 Cu Only 60/75C (1) 1 25.4 96 10.8 Cu/Al 60/75C (2) 1 25.4 96 10.8 Cu/Al 60/75C (1) 1 25.4 96 10.8 Cu Only 60/75C (1) 1 25.4

Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length in. mm

K
A

AWG
D C

250 500

250 500

#3350 3/0250 3/0250

3350

Wire Range
B

2/0250 MCM (2) 50075 or 0 2/0500 (1) 70120 (2) or 70240 (1) 27537 5 31 or 42 30040 0 (1)

50075 0

mm2

120 240

120 240

30185

95120

95120

30185

Terminal Type Wire Torque Lb-in Nm

Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 375 42 375 42 275 31 275 31 275 31 275 31 550 62 550 62

Visit our website: www.ab.com/catalogs

11

Bulletin 140U/UE

Molded Case Circuit Breakers

Lugs Frame Size Specification Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Lb-in Nm Optional 140U-J-MTL3A Aluminum 1/420 screw 50 lb-in 5.6 Nm Cu/Al 60/75C (3) (A) 3/81/2 in. (A) 913 mm (B) 3/47/8 in. (B) 1922 mm #14#2 2.525 Allen - 5/32 in. (4 mm) 70 lb-in 7.9 Nm Optional 140U-K-MTL3A Aluminum .375 x 25 screw 72 -96 lb-in 8.610.8 Nm Cu/Al 60/75C (3) (A) 9/16.3/4 (B) 1-3/16.1in. 1/2 in. (A) 1419 mm (B) 3038 mm #122/0 470 Allen - 3/16 in. (5 mm) 120 lb-in 13.5 Nm (C) 1-7/821/4 in. (C) 4857 mm (C) 1-1/413/8 in. (C) 3235 mm (6) (A) 3/81/2 in. (A) 913 mm (B) 3/47/8 in. (B) 1922 mm #14#6 2.510 Allen - 3/32 in. 25 lb-in 2.8 Nm Optional 140U-K-MTL6A Aluminum .375 x 25 screw 72 -96 lb-in 8.610.8 Nm Cu/Al 60/75C (6) (A) 9/16.3/4 (B) 1-3/16.1in. 1/2 in. (A) 1419 mm (B) 3038 mm #142 AWG 2.570 Allen - 1/8 in. (3 mm) 25 lb-in 2.8 Nm (C) 1-7/821/4 in. (C) 4857 mm (C) 1-1/413/8 in. (C) 3235 mm Multitap Optional 140U-J-MTL6A Aluminum 1/420 screw 50 lb-in 5.6 Nm Cu/Al 60/75C End Cap Optional 140U-J-ECM Molded Housing Allen - 4 mm 120144 Lbin 1416 Nm Optional 140U-K-ECM Molded Housing Allen - 8 mm 275 Lb-in 31 -m

Cable Type Cable Temperature Rating J Cable Quantity Wire Strip Length in. mm Wire Range AWG mm2

Terminal Type Wire Torque Lb-in Nm Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Lb-in Nm

Cable Type Cable Temperature Rating K Cable Quantity Wire Strip Length in. mm AWG mm2 Lb-in Nm

Wire Range

Terminal Type Wire Torque

12

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Terminal and Lugs Specifications, Continued
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Frame Size Terminals Specification Material A B C D Fastener Torque L Lb-in Nm 1.0 (25.4) 15/16 (23.81) 1/2 (12.7) 33/64 (13.0) Slotted 42 3 Specification Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Lb-in Nm Box Lugs 140U-LTL6A1 Aluminum 140U-LTL6C1 Copper 140U-LTL6A2 Aluminum 140U-LTL6C2 Copper 140U-LTL4A1 Aluminum 140U-LTL4C1 Copper Lugs Mechanical Lugs

Dim.

Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) 200 22 Cu/Al 60/75C (1) 1-1/8 29 500750 240380 550 62 Optional 140U-MTLC3 Copper Bolt (19 mm) 3035 200 22 Cu only 60/75C (1) 1-1/8 29 500750 240380 500 57 Optional 140U-MTLA2 Aluminum Bolt (19 mm) 3035 200 22 Cu/Al 60/75C (2) 1-1/8 29 2500 35240 375 42 Optional 140U-MTLC2 Copper Bolt (19 mm) 3035 200 22 Cu only 60/75C (2) 1-1/8 29 2500 35240 375 42 Optional 140U-MTLA3 Aluminum Bolt (19 mm) 3035 200 22 Cu/Al 60/75C (1) 1-1/8 29 2500 35240 375 42 Optional 140U-MTLA2A Aluminum Bolt (19 mm) 3035 200 22 Cu only 60/75C (1) 1-1/8 29 2500 35240 375 42 Optional

Cable Type Cable Temperature Rating

Cable Quantity Wire Strip Length in. mm AWG mm2 Lb-in Nm

D C

Wire Range

Terminal Type
B

Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm)

Wire Torque 1-1/16 (26.99) 17/8 (45) 1/2 (12.7) 1/2 (12.7) Socket 275/400 31.1/45.2

Material A Dim. B C D Fastener Torque M


A

Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length
D

ft-lb Nm

Lb-in Nm

40.547.5 40.547.5 40.547.5 40.547.5 40.547.5 Cu only 60/75C (3) 1-1/16 27 3/0300 95185 275 31 Cu/Al 60/75C (2) 1-1/16 27 1500 50240 375 42 Cu only 60/75C (2) 1-1/16 27 2/0500 70240 300 34 Cu/Al 60/75C (3) 1-1/16 27 3/0400 95185 375 42 Cu/Al 60/75C (2) 1-1/16 27 500750 95185 500 56

in. mm

Wire Range
B

AWG mm2 Lb-in Nm

Terminal Type Wire Torque

Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm)

Visit our website: www.ab.com/catalogs

13

Bulletin 140U/UE

Molded Case Circuit Breakers

Lugs Frame Size Specification Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Lb-in Nm Optional (B) 3038 mm #122/0 470 Lb-in Nm (C) 1-7/821/4 in. (C) 4857 mm Multitap Optional (6) (A) 9/16.3/4 (B) 1-3/16.1in. 1/2 in. (A) 1419 mm (B) 3038 mm (C) 1-7/821/4 in. (C) 4857 mm End Cap Optional 140U-L-ECM Molded Housing Allen - 8 mm 200 Lb-in 22 Nm

Cable Type Cable Temperature Rating L Cable Quantity Wire Strip Length in. mm AWG mm2 Lb-in Nm

Wire Range

Terminal Type Wire Torque

Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque

Cable Type Cable Temperature Rating M Cable Quantity Wire Strip Length in. mm Wire Range AWG mm2 Lb-in Nm

Terminal Type Wire Torque

14

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Terminal and Lugs Specifications, Continued
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Terminals Frame Size Specification Material A B Dim. C D Fastener Torque N Lb-in Nm 1-3/8 in. (35 mm) 1-1/2 in. (38 mm) 1/2 in. (12.7 mm) (2) 0.5x13 (12.7x1.75) Specification Std/Optional Cat. No. Material Optional 140U-NTLA3 Aluminum Optional 140U-NTLA2 Aluminum Lugs Mechanical Lugs Optional 140U-NTLC2 Copper Optional 140U-NTLA4 Aluminum Optional 140U-NTLC3 Copper Optional 140U-NTLC4 Copper

Terminal Fastener Hardware Terminal Fastener Torque Cable Type Cable Temperature Rating ft-lb

Bolt (19 mm) 3545

Bolt (19 mm) 3545 40.547.5 Cu/Al 60/75C (2) 1 25.4 #1500 MCM 50240 Hex (8 mm) 375 42

Bolt (19 mm) 3545 40.547.5 Cu Only 60/75C (2) 1 25.4 2/0500 MCM 70240 Hex (8 mm) 300 34

Bolt (19 mm) 3545 40.547.5 Cu/Al 60/75C (4) 1 25.4 4/0500 MCM 120240 Hex (8 mm) 375 34

Bolt (19 mm) 3545 40.547.5 Cu Only 60/75C (3) 1 25.4 3/0500 MCM 95240 Hex (8 mm) 300 34

Bolt (19 mm) 3545 40.547.5 Cu Only 60/75C (4) 1 25.4 3/0400 MCM 95185 Hex (8 mm) 275 31

Nm 40.547.5 Cu/Al 60/75C (3) in. mm AWG mm2 1 25.4 3/0400 MCM 95185 Hex (8 mm) 375 42

Cable Quantity Wire Strip Length

D C D

Wire Range

Terminal Type
B

Wire Torque

Lb-in Nm

Visit our website: www.ab.com/catalogs

15

Bulletin 140U/UE

Molded Case Circuit Breakers

Dimensions
G Frame

15-20 AMP, CLAMP AND BINDING SCREW TERMINALS


.84 [ 21,4 ] .16 [ 4,1 ]

25-100 AMP, PRESSURE COLLAR TERMINALS


.84 [ 21,4 ]

.49 [ 12,5 ]

2.00 [ 50,8 ] 1.00 [ 25,4 ] .97 [ 24,6 ]

.14 [ 3,6 ]

2.42 [ 61,5 ]

3.22 [ 81,8 ]

1.00 [ 25,4 ]

3.21 [ 81,5 ] .49 [ 12,4 ]

.16 [ 4]

1.22 [ 30,9 ]

1.22 [ 30,9 ]

16

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

Dimensions, Continued
.84 [ 21,3 ] .36 [ 9,1 ] .45 [ 11,4 ]

3.00 [ 76,2 ] 1.00 [ 25,4 ]

.16 [ 4,1 ]

3.21 [ 81,4 ]

4.88 [ 123,8 ]

140U G FRAME

3.22 [ 81,7 ]

1.00 [ 25,4 ]

1.00 [ 25,4 ]

2.41 [ 61,2 ]

.45 [ 11,4 ]

.36 [ 9,1 ] 2.83 [ 71,8 ]

1.22 [ 31 ]

140U G-FRAME

Visit our website: www.ab.com/catalogs

17

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued


H Frame

0.8524 (21.6509)

0.4179 (10.6146)

3.4141 (86.7181) 1.9730 (50.1142)

0.1680 (4.2672)

3.8120 (96.8248)

1.0070 (25.5778)

2.9725 (75.5015)

BUL 140U/UE J FRAME 2-POLE

18

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

.47 [ 11,9 ]

.88 [ 22,2 ]

.54 [ 13,6 ]

3.00 [ 76,2 ] 1.00 [ 25,4 ]

2.47 [ 62,7 ] .97 [ 24,6 ]

5.50 [ 139,7 ]

3.81 [ 96,9 ]

3.44 [ 87,4 ]

1.00 [ 25,4 ]

1.00 [ 25,4 ]

2.93 [ 74,3 ] .88 [ 22,4 ]

BUL 140U/UE H FRAME 3-POLE

Visit our website: www.ab.com/catalogs

19

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued


4.00 2.00 1.00 1.00 1.00 3.00

.97

.97

5.50

3.81

3.81

5.50

4-POLE

3-POLE BUL 140U/UE H FRAME

20

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued


J Frame
4.13 [ 104,8] 1.38 [ 34,9] .20 [ 5] 4.43 [ 112,4] 3.19 [ 81,1]

7.00 [ 177,8]

5.50 [ 139,7]

1.38 [ 34,9]

1.38 [ 34,9]

2.84 [ 72,2]

3-POLE 140U/UE J FRAME


.19 [ 4,8 ] 3.44 [ 87,3] .81 [ 20,6]

4.13 5.50 1.38

.78

7.00 7.00 5.50

4-POLE

3-POLE BUL 140U/UE J FRAME

Visit our website: www.ab.com/catalogs

21

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued


K Frame
.95 [ 24,2 ]

1.48 [ 37,7 ]

5.49 [ 139,4 ] .63 [ 15,9 ] 1.72 [ 43,7 ]

.28 [ 7,1 ]

.84 [ 21,4 ]

1.19 [ 30,2 ]

10.13 [ 257,2 ]

8.88 [ 225,4 ] 8.44 [ 214,3 ]

1.72 [ 43,7 ]

1.72 [ 43,7 ] 4.86 [ 123,3 ]

4.06 [ 103,2 ]

1.43 [ 36,2 ]

1.06 [ 27]

1.01 [ 25,7 ]

140U K FRAME

22

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued


L Frame
5.48 [ 139,2] 1.72 [ 43,6 ] .22 [ 5,5 ] 3.36 [ 85,3 ]

10.13 [ 257,2]

8.44 [ 214,4]

1.72 [ 43,7 ]

1.72 [ 43,7 ]

5.43 [ 137,9 ]

.25 [ 6,4 ] .97 [ 24,6] 1.34 [ 34,1]

140U/UE L FRAME 3-POLE

Visit our website: www.ab.com/catalogs

23

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued

7.22 1.72 1.72

5.48

1.72

.84

.84

10.13

8.44

8.44

10.13

BUL 140U/UE L FRAME 4 POLE

24

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued


M Frame
8.25 [ 209,6] 2.75 [ 69,9]

.38 [ 9,5 ]

.63 [ 15,9]

.74 [ 18,7]

16.00 [ 406,4]

14.75 [ 374,7]

.84 [ 21,4] 1.03 [ 26,2] 5.50 [ 139,6]

.84 [ 21,4]

1.87 [ 47,6]

1.03 [ 26,2]

BUL 140U/UE M FRAME

Visit our website: www.ab.com/catalogs

25

Bulletin 140U/UE

Molded Case Circuit Breakers Dimensions, Continued


N Frame
8.25 [ 209,6] 2.75 [ 69,9]

2.75 [ 69,9]

.34 [ 8,7]

.63 [ 15,9]

5.19 [ 131,8]

16.00 [ 406,4]

14.75 [ 374,7]

5.50 [ 139,7] 7.18 [ 182,5]

5.50 [ 139,7]

3.84 [ 97,6] .97 [ 24,6] 1.09 [ 27,8]

140U/UE N FRAME

2.00 [ 50,8]

11.00 2.75 2.75 .63

8.25 2.75 .63

14.75 16.00 14.75 16.00

BUL 140U/UE N FRAME 4-POLE

26

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Discrimination Short-circuit level to which discrimination is achieved.
Upstream (max. settings) "T" represents max. discrimination to kA rating level of the downstream device. Bulletin 140UE H-Frame 16 Breaker Rating (A) 16 20 32 Bulletin 140UE H-Frame MCCB 18 kA & 25 kA versions 40 50 63 80 100 125 160 16 20 32 Bulletin 140UE H-Frame MCCB 45 kA & 70 kA versions 40 50 63 80 100 125 50 63 Bulletin 140UE J-Frame MCCB 45 kA & 70 kA versions 80 100 125 160 200 250 Bulletin 140UE L-Frame MCCB 50 kA & 70 kA versions Bulletin 140UE N-Frame MCCB 50 kA & 70 kA versions 250 320 400 500 630 800 1250 1600 0.32 kA 0.2 kA 0.32 kA 0.2 kA 20 32 40 0.4 kA 0.4 kA 0.1 kA 0.4 kA 0.4 kA 0.1 kA 50 0.5 kA 0.5 kA 0.5 kA 0.8 kA 0.5 kA 0.5 kA 0.5 kA 0.8 kA 63 0.63 kA 0.63 kA 0.63 kA 0.63 kA 0.63 kA 0.63 kA 0.63 kA 0.63 kA 0.63 kA 0.63 kA 80 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 0.8 kA 100 125 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1 kA 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1.3 kA 1 kA 160 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 50 80 18, 25, 40, or 70 kA version 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA 1 kA Bulletin 140UE J-Frame 100 125 160 200 250 45 or 70 kA version T T T T T T T T T T T T T T T T

10 kA 10 kA 10 kA 10 kA

10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 3 kA 3 kA 3 kA

40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 1 kA 1.25 kA 1.25 kA 1.25 kA 10 kA 10 kA 10 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 3 kA 2 kA 2 kA 2 kA 2 kA 2 kA 3 kA 3 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA

Downstream

Visit our website: www.ab.com/catalogs

27

Bulletin 140U/UE

Molded Case Circuit Breakers


Discrimination, Continued
Upstream (max. settings) "T" represents max. discrimination to kA rating level of the downstream device. Bulletin 140UE L-Frame 250 Breaker Rating (A) 16 20 Bulletin 140UE H-Frame MCCB 18 kA & 25 kA versions 32 40 50 63 80 100 125 160 16 20 Bulletin 140UE H-Frame MCCB 45 kA & 70 kA versions 32 40 50 63 80 100 125 50 63 Bulletin 140UE J-Frame MCCB 45 kA & 70 kA versions 80 100 125 160 200 250 Bulletin 140UE L-Frame MCCB 50 kA & 70 kA versions Bulletin 140UE N-Frame MCCB 50 kA & 70 kA versions 250 320 400 500 630 800 1250 1600 T T T T T T T T T T 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 26 kA T T T T T T T T T T 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 26 kA 320 400 50 or 70 kA versions T T T T T T T T T T 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 26 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA T T T T T T T T T T 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 26 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA T T T T T T T T T T 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 26 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA T T T T T T T T T T 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 22 kA 500 630 800 Bulletin 140UE N-Frame 1250 T T T T T T T T T T 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 22 kA 1600 T T T T T T T T T T 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 22 kA 50, 70, or 100 kA versions

28

Downstream

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves

Bul.140U
Time-Current Curves for Bulletin 140U-G Thermal-Magnetic Molded Case Circuit Breakers
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING
40 00 6000 70 00 8000 9000 10,000 6 00 700 8 00 900 1 000 2000 3000 5000 70 80 90 100 2 00 300 400 5 00 60,000 70,000 80,000 90,000 100,000 20,000 30,000 40,000 50,000 50 60

10,000

10,000

2 HOURS

2 HOURS

5,000

5,000

1 HOUR

1 HOUR

Circuit Breaker Time/Current Curves


3,000

For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60/75C) per terminal. Tested in open air with current in all poles except for instantaneous trip, see below. Maximum Volts Breaker Type 140U-G Ac Volts 60 Hz 480

3,000

2,000

2,000

1,000

1,000

Breaker Rating Continuous Amperes 15-60 70-100 Interrupting Rating (UL Listed) Breaker Type 140U-G Instantaneous Trip, Amperes Single Pole 2 Poles in Series 500-1300 400-1100 1300-1800 700-1300 Symmetrical RMS Amperes 240 Volts 480 Volts 22,000 65,000

500

500

300

300

200

200

100

100

1 MINUTE

1 MINUTE

50

50

30

30

20

20

10

10

Maximum
5

Minimum

TIME IN SECONDS

TIME IN SECONDS

.5

.5

.3

.3

.2

.2

.1

.1

.05

.05

.03

.03

Instantaneous Trip (See Tabulation Above)


.02 .02

Maximum Interrupting Time Interrupting Rating (See Tabulation Above)


.01 .01

.005

.005

.003

.003

.002

.002

.001
60 70 80 90 100 50 60,000 70,000 80,000 90,000 100,000 6000 7000 8 000 9000 10,000 20,000 30,000 40,000 50,000 600 700 800 900 1000 3000 4000 5 000 2000 400 300 500 200

.001

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

40752-600 (1) SC-6030-95 Effective October 1997


Visit our website: www.ab.com/catalogs

29

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Bulletin 140U/UE - H-, J-, L-Frames Current Limiting Characteristics (Ip) 210415V AC, 50/60 Hz

200 kA 100 80

0.2

cos = 0.25
60

CUT-OFF CURRENT ID

40

0.3
20

J
10 8 6

2 5 7 10 20 30 50 kA 100

SHORT CIRCUIT CURRENT ISrms

40752-610 (1) Effective April 2004

30

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Time-Current Curves for Bulletin 140U-H Thermal-Magnetic Molded Case Circuit Breakers

Thermal/Magnetic Trip Rated Operating Voltage :

600Y / 347V AC 480V AC 415 V AC

Number of Poles: 3, 4 o Ambient 40 C Interrupting Ratings - 50/60 Hz RMS Symmetrical Amperes (kA), Icu Two Series Poles Inst. MagneticTrip Shown. Individual Pole Inst. Magnetic Trip +30%. DC Inst. Magnetic Trip +30% Higher Than AC. Notes: (a) (b) Fixed Inverse-Time Overcurrent Release. Fixed Electromagnetic Release. Total Operation Time. Interrupting Rating determines end of Curve.

(c)

1 minute
(d)

1 minute

40752-601 (1) SC-XXX Effective March 2004

Visit our website: www.ab.com/catalogs

31

Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves, Continued

Bul.140U/UE
Bulletin 140U/UE - H-, J-, L-Frames Current Limiting Characteristics (Ip) 210415V AC, 50/60 Hz

200 kA 100 80

0.2

cos = 0.25
60

CUT-OFF CURRENT ID

40

0.3
20

J
10 8 6

2 5 7 10 20 30 50 kA 100

SHORT CIRCUIT CURRENT ISrms

40752-610 (1) Effective April 2004

32

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-H IEC-Rated Thermal-Magnetic Molded Case Circuit Breakers
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0

1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0

7.0

10.0

20.0

50.0

80.0

Circuit Breaker Time/Current Curves 1. 140U/UE-H Circuit Break.Earth Leakage Mod., 3 and 4 Poles, 110 - 480V 60Hz. 2. For application and coordination purposes only. -20 C to 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.

1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0

200.0

200.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

20.0

20.0

.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

.1

.3

10

Available I n Settings
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

2.0

2.0

1S
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3

TIME IN SECONDS

500ms

300ms

.2

150ms

.2

.1 .09 .08 .07 .06 .05 .04 .03

60ms

.1 .09 .08 .07 .06 .05 .04 .03

Inst.
.02 .02

.01 .009 .008 .007 .006 .005 .004 .003

.01 .009 .008 .007 .006 .005 .004 .003

.002

.002

.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

.001

40752-602 (1) Curve No. TC01212003E Effective September 2005

Ig (Amperes)

Visit our website: www.ab.com/catalogs

33

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-H UL-Rated Thermal-Magnetic Molded Case Circuit Breakers
1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

Circuit Breaker Time/Current Curves 1. 140U/UE-H Cir. Break. Earth Leakage Mod., 3 and 4 Poles, 110 - 480V 60Hz. 2. For application and coordination purposes only. -20 C to 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation

1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0

200.0

200.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

20.0

20.0

10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

.03

.1

.3

10

Available Ig (A) Settings

10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

2.0

2.0

1S
TIME IN SECONDS
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3

500ms

300ms

150ms
.2 .2

.1 .09 .08 .07 .06 .05 .04 .03

60ms

.1 .09 .08 .07 .06 .05 .04

Inst.

.03

.02

.02

.01 .009 .008 .007 .006 .005 .004 .003

.01 .009 .008 .007 .006 .005 .004 .003

.002

.002

.001

.01

.02

.03

.04 .05

.07

.1

.2

.3

.4

.5

.7

1.0

2.0

3.0

4.0 5.0

7.0

10.0

20.0

50.0

80.0

.001

Ig (A)
40752-603 (1) Curve No. TC01212004E Effective September 2005

34

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Thermal-Magnetic Molded Case Circuit Breakers

Allen-Bradley 63250 A

40752-620 (1) SC-XXX Effective March 2004

Visit our website: www.ab.com/catalogs

35

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Electronic LS Molded Case Circuit Breakers
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30

Long Delay Response & Short Delay with I T Response Curve

2 HOURS

10000 9000 8000 7000 6000 5000

1 HOUR

1.15

4000 3000

Circuit Breaker Time/Current Curve


Long Delay (LD) & Short Delay (SD) with I T Response (LS)
2

2000

Ir Available Sensors (In):


1000 900 800 700 600 500 400 300

In

50 A 20A 20A 25A 30A 32A 40A 45A 50A

100 A 40A 45A 50A 63A 70A 80A 90A 100A

160 63A 80A 90A 100A 110A 125A 150A 160A

250 A 100A 125A 150A 160A 175A 200A 225A 250A

50A 100A 160A 250A Maximum Total Clearing Time

A B C D E F G H

Notes: 1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +88 C cause an over temperature protection trip. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. 2. Application frequency is 50/60 Hertz.

200

1 MINUTE

100 90 80 70 60 50 40 30

Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%

3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 5. The left portion of the curve is shown as a multiple of the Long Delay Setting (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%.

20

24

TIME IN SECONDS

. . .
7

6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has 9 settings/positions: 2 - 8 & 10, 14. 8. Short Delay I T band has a tolerance of 15%. 9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I T curve. 10. For high fault current levels an additional fixed instantaneous hardware override is provided at 14x (In). 11. For LD Response & SD with Flat Response curve, see:
2 2 2

10 9 8 7 6 5 4 3

Minimum Total Clearing Time

15

.
4 3

40752-622

12. For LD Response & SD with I T Response (this curve): 40752-621 13. For Ground Fault Delay Response curve, see: 40752-623

.
2 4

2
1 .9 .8 .7 .6 .5 .4 .3

1 .9 .8 .7 .6 .5
7

.4 .3
8 14

.2

I T Short Delay (See Note 8)


.1 .09 .08 .07 .06 .05 .04 .03

Instantaneous Override (See Note 10)

.2

10

.
67ms

Application Determines End of Curve

.1 .09 .08 .07 .06 .05 .04 .03

See Note 9
.02

14x
.02

.01

.5

.7

10

20

30

40

50

70

100

10

20

30

40

50

70

.01 100

Current in Multiples of (Ir) I T


2

Current in Multiples of ( I n )

Trip Style

40752-621 (1) TC-01201002E Effective September 2003

36

Visit our website: www.ab.com/catalogs

TIME IN SECONDS

Available Short Delay Pick Up Settings 2 - 8,10, 14 x Ir 5% (See Note 7)

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Electronic LSI Molded Case Circuit Breakers
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30

Long Delay Response & Short Delay with Flat Response Curve

2 HOURS

10000 9000 8000 7000 6000 5000

1 HOUR

1.15

4000 3000

Circuit Breaker Time/Current Curves


Long Delay (LD) & Short Delay (SD) with Flat Response (LSI)

2000

Ir Available Sensors (In):


1000 900 800 700 600 500 400 300

In

50A 20A 20A 25A 30A 32A 40A 45A 50A

100A 40A 45A 50A 63A 70A 80A 90A 100A

160A 63A 80A 90A 100A 110A 125A 150A 160A

250A 100A 125A 150A 160A 175A 200A 225A 250A

50A 100A 160A 250A Maximum Total Clearing Time

A B C D E F G H

Notes:
200

1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +88 C cause an overtemperature protection trip. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation.
100 90 80 70 60 50 40 30

1 MINUTE

Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%

2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.

20

24

TIME IN SECONDS

. . .
7

5. The left portion of the curve is shown as a multiple of the Long Delay Setting. (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%. 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has 9 settings/positions, 2 - 8 & 10, 14. 8. For high fault current levels an additional fixed instantaneous hardware override is provided at 14x (In). 9. For LD Response & SD with Flat Response (this curve): 10. For LD Response & SD with I T Response curve, see: 11. For Ground Fault Delay Response curve, see:
2

10 9 8 7 6 5 4 3

Minimum Total Clearing Time

15

40752-622 40752-621 40752-623

.
4

.
2 2 4 14 3 5 6 8

.6

.5 .4 .3

Instantaneous Override (See Note 8) 300ms (P,Q,R)

.5 .4 .3

.2

.2
7

.1 .09 .08 .07 .06 .05 .04 .03

120ms (M,N,O)

Application Determines End of Curve


.1 .09 .08 .07 .06 .05 .04 .03

10

Inst. (J,K,L)

.02

.02

14x

.01

.5

.7

10

20

30

40

50

70

100

10

20

30

40

50

70

.01 100

Current in Multiples of (Ir)

Current in Multiples of (In)

40752-622 (1) TC01201001E Effective September 2003

Adjustable Flat Trip Style

TIME IN SECONDS

1 .9 .8 .7 .6

Available Short Delay Pick Up Settings 2 - 8,10, 14 x Ir 5% (See Note 7)

1 .9 .8 .7

Visit our website: www.ab.com/catalogs

37

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Electronic LSG & LSIG Molded Case Circuit Breakers
.1
10000 9000 8000 7000 6000 5000 4000

.2

.3

.4

.5

.7

1.0

2.0

Circuit Breaker Time/Current Curves


Ground Fault Delay Response (LSG, LSIG)

3000

2000

1000 900 800 700 600 500 400 300

Switch Setting J K L M N O P Q R

tSD Inst. Inst. Inst. 120 120 120 300 300 300

tGF Inst. 120 300 Inst. 120 300 Inst. 120 300

200

1 MINUTE

100 90 80 70 60 50 40 30

TIME IN SECONDS

20

Cat. No. 140U-JTI3-D25

10 9 8 7 6 5 4 3

Ground Fault Pickup Settings (Tolerance 10%)

Cat. No. 140U-JTG3-D25

0.4X 0.2X 0.6X 0.3X 1X

1 .9 .8 .7 .6 .5 .4 .3

0.8X

NOTE: Labels shown are for 250A style.

300ms (L,O,R)

.2

Notes:
.1 .09 .08 .07 .06 .05 .04 .03

120ms (K,N,Q)

1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +88 C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. 2.Application frequency is 50/60 Hertz.

Inst. (J,M,P)

3. Trip units are suitable for functional field testing with test kit style # 70C1056G52. 4. For LD Response & SD with Flat Response curve, see: 5. For LD Response & SD with I T Response curve, see: 6. For Ground Fault Delay Response (this curve):
2

40752-622 40752-621 40752-623

.02

.01

.1

.2

.3

.4

.5

.7

1.0

2.0

Ground Current in Multiple of (In)

40752-623 (1) TC01203004E Effective September 2003

38

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-J IEC-Rated Thermal-Magnetic Molded Case Circuit Breakers
1000 900.0 800.0 700.0 600.0 500.0 400.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

1000 900.0 800.0 700.0 600.0

Circuit Breaker Time/Current Curves

1. 140U/UE-J Circuit Breaker Earth Leakage Module, 3 and 4 Poles, 110 - 480V 50/60Hz. 2. For application and coordination purposes only. -20C to 55C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.

500.0 400.0

300.0

300.0

200.0

200.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0

30.0

30.0

20.0

20.0

.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0

.1

.3

10

Available I n settings
10.0 9.0 8.0 7.0 6.0 5.0 4.0

3.0

3.0

2.0

2.0

TIME IN SECONDS

TIME IN SECONDS

1S
1.0 .9 .8 .7 .6 .5 .4

1.0 .9

500ms

.8 .7 .6 .5

300ms

.4

.3

.3

150ms
.2 .2

.1 .09 .08 .07 .06 .05 .04

60ms

.1 .09 .08 .07 .06 .05 .04

.03

.03

Inst
.02 .02

.01 .009 .008 .007 .006 .005 .004

.01 .009 .008 .007 .006 .005 .004

.003

.003

.002

.002

.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

.001

40752-624 (1) Curve No. TC01205001E Effective September 2005

I n

(Amperes)

Visit our website: www.ab.com/catalogs

39

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-J UL-Rated Thermal-Magnetic Molded Case Circuit Breakers
1000 900.0 800.0 700.0 600.0 500.0 400.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

Circuit Breaker Time/Current Curves

1000 900.0 800.0 700.0 600.0

1. 140U/UE-J Circuit Breaker Earth Leakage Module, 3and 4 Poles, 110 - 480V 50/60Hz. 2. For application and coordination purposes only. -20C to 55C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation. F

500.0 400.0

300.0

300.0

200.0

200.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0

30.0

30.0

20.0

20.0

.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0

.1

.3

10

Available Ig(A) Settings.


10.0 9.0 8.0 7.0 6.0 5.0 4.0

3.0

3.0

2.0

2.0

TIME IN SECONDS

TIME IN SECONDS

1S
1.0 .9 .8 .7 .6 .5 .4

1.0 .9

500ms

.8 .7 .6 .5

300ms

.4

.3

.3

150ms
.2 .2

.1 .09 .08 .07 .06 .05 .04

60ms

.1 .09 .08 .07 .06 .05 .04

.03

.03

Inst
.02 .02

.01 .009 .008 .007 .006 .005 .004

.01 .009 .008 .007 .006 .005 .004

.003

.003

.002

.002

.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

.001

Ig(A)
40752-625 (1) Curve No. TC01204004E Effective September 2005

40

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K3/K6 Thermal-Magnetic Molded Case Circuit Breakers
600 700 800 900 1000 60 70 80 90 100 6000 7000 8000 9000 10,000 4000 2000 3000 300 200 400 500 5000 60,000 70,000 80,000 90,000 100,000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)


20,000 30,000 40,000 50 50,000

10,000

10,000

2 HOURS

2 HOURS

5,000

5,000

1 HOUR

1 HOUR

Circuit Breaker Time/Current Curves


3,000

2,000

For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60C up to 125 A. 75 C above 125 A) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600V., AC (60 Hz) 250 V., DC

3,000

2,000

1,000

1,000

500

(250-400A)

300

(125-225A)

200

Maximum Single Pole Trip Times at 25 C

Breaker Rating Rated Amperes (In) Instantaneous Trip Amperes 100, 125, 150, 500 to 1000% of trip unit rating 175, 200, 225, (See Figure Below) 250, 300, 350, (Dc values are approximately 40% higher) 400 Interrupting Rating (UL/CSA) RMS Sym Amperes Amperes Breaker Type @ 240 V., AC @ 480 V., AC @ 600 V., AC @ 250 V., DC
140U-K3 140U-K6

500

300

65,000 100,000

35,000 65,000

25,000 35,000

10,000 22,000

200

(100A)
100

Single pole data at 25C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.

100

1 MINUTE

1 MINUTE

Minimum
50

Maximum
50

30

30

20
7.5

20
7.5

10

Typical Trip Unit Nameplate

C Thermal Magnetic Trip Unit


10
5

Push to Trip

7.5

10

5 Amps (In)

10

10

Magnetic Multiples Of In

40C

Cat. No.

Individual Pole Adjustments


3 3

Adjustable Magnetic Trip


2 2

TIME IN SECONDS

TIME IN SECONDS

.3

10X

.5

5X

20%

10%

.5

.3

.2

.2

.1

.1

.05

.05

.03

.03

.02

.02

Maximum Interrupting Time

.01

.01

.005

.005

.003

Interrupting Rating Determines End of Curve

.003

.002

.002

.001
30,000 20,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 60 70 80 90 100 50 6000 7000 8000 9000 10,000 500 600 700 800 900 1000 200 300 400 2000 4000 3000 5000

.001

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

40752-630 (1) SC-4118-87B Effective October 1997

Visit our website: www.ab.com/catalogs

41

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K0 Thermal-Magnetic Molded Case Circuit Breakers
60 00 7000 8000 9000 10,000 2000 4000 600 700 800 900 1 000 300 200 4 00 500 70 80 90 100 5000 3000 50 60 60,000 70,000 80,000 90,000 100,000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)


20,000 30,000 40,000 50,000

10,000

10,000

2 HOURS

2 HOURS

5,000

1 HOUR

Circuit Breaker Time/Current Curves


For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60C up to 125 A. 75 C above 125 amps) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600V., AC (60 Hz) 250 V., DC

5,000

1 HOUR

3,000

3,000

2,000

2,000

1,000

Breaker Rating Rated Amperes (In) 100, 125, 150, 175, 200, 225, 250, 300, 350, 400

1,000

Instantaneous Trip Amperes 500 to 1000% of trip unit rating (See Figure Below) (DC values are approximately 40% higher)
500

500

(250-400A)

300

200

(125-225A) Maximum Single Pole Trip Times at 25C

Interrupting Rating (UL/CSA) RMS Sym Amperes Breaker Type @ 240 V., AC @ 480 V., AC 140U-K0 200,000
100,000

Amperes
@ 600 V., AC 50,000 @ 250 V., DC 22,000
200 300

Single pole test data at 25C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.

(100A)
100 100

1 MINUTE

1 MINUTE

Minimum
50

Maximum
50

30

30

20
7.5 7.5

20

10

Typical Trip Unit Nameplate

C Thermal Magnetic Trip Unit


10 5 10 5 Amps (In)

Push to Trip

7.5

10

10

Magnetic Multiples Of In

40C

Cat. No.

Individual Pole Adjustments


3 3

Adjustable Magnetic Trip


2 2

TIME IN SECONDS

TIME IN SECONDS

.3

10X

.5

5X

20%

10%

.5

.3

.2

.2

.1

.1

.05

.05

.03

.03

.02

.02

Maximum Interrupting Time 600 V., Ac


.01 .01

480 V., Ac
.005 .005

240 V., Ac
.003 .003

.002

Interrupting Rating Determines End of Curve

.002

.001
30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 6000 7000 8000 9000 10,000 20,000 50 60 70 80 90 100 500 600 700 800 900 1000 200 300 400 2000 3000 4000 5000

.001

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

40752-631 (1) SC-4119-87B Effective October 1997

42

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LS, LSG Trip Units and Bulletin 140U-K3, -K6 Molded Case Circuit Breakers
10,000 .5 .7

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)


.9 .186 2 3 4 5

6 7 8 9 10

20

2 HOURS

5,000

Circuit Breaker Time/Current Curves (Phase Current)

1 HOUR

Technical Data Covers, Bul. No. 140U-KTH3, -KTG3 Electronic Trip Units for use with Circuit Breaker Types 140U-K3X3 and -K6X3, 400 A Max.
3,000

Fixed Short Delay Time


2,000
Rating Plug Short Delay Pickup xIr 4 Engaged 2 Trip Unit 40 oC 5 6 3 7 8 Cat. In Push to Trip

Typical Trip Unit Nameplate

Standard Fixed Rating Plug


1,000

TEST

Remove

Available Rating Plugs


500

Ampere Rating (In) 400 350 300 250 225 200

Type

Catalog Number 140U-KRP3-D40 140U-KRP3-D35 140U-KRP3-D30 140U-KRP3-D25 140U-KRP3-D22 140U-KRP3-D20

300

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

Fixed Fixed Fixed Fixed Fixed Fixed

Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600

100

1 MINUTE

50

Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K3 140U-K6 Breaker Type

Hz UL/CSA 240V 65 100 IEC 947-2 480V 35 65 600V 25 35

240V 65 100

380V 40 65

415V 40 65

30

140U-K3 140U-K6

20

2X

Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 4000 A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.

10

3X

Short Delay Pick Up Settings (Tolerance 10%)

4X 5X 6X

TIME IN SECONDS

.5

.2

7X

.3

8X

.1

.1

.05

.05 .04

Fixed Instantaneous Override

.03

.03

.02

.02

SECONDS

Interrupting Rating Determines End of Curve

.01

.01

.005

.003

.002

.001

.001
1000 2000 3000 4000 5000 10,000 20,000 30,000 40,000 50,000

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS

40752-632 (1) SC-5638-93 Effective October 1997


Visit our website: www.ab.com/catalogs

100,000

.5

.6 .7 .8 .9 1

3 4 5

6 7 8 9 10

20

43

Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LSI, LSIG Trip Units and Bulletin 140U-K3, -K6 Molded Case Circuit Breakers
.5 .7

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)


.8 . .9 16 2 3 4 5

10,000

6 7 8 9 10

20

2 HOURS

5,000

Circuit Breaker Time/Current Curves (Phase Current)

1 HOUR

Technical Data Covers, Cat. Nos. 140U-KTL3, -KTI3 Electronic Trip Units for use with Circuit Breaker Types 140U-K3, -K6, 400A. max.
3,000

Adjustable Short Delay Time


Rating Plug Short Delay Push to Trip Pickup xIr 5 4 6 3 7 2 Trip Unit o 40 C 8 Time ms 200 100 INST 300 Cat. In Engaged

Typical Trip Unit Nameplate

2,000

Standard Fixed Rating Plug


1,000

TEST

Remove

500

Available Rating Plugs Ampere Rating (In) 400 350 300 250 225 200

Type

Catalog Number 140U-KRP3-D40 140U-KRP3-D35 140U-KRP3-D30 140U-KRP3-D25 140U-KRP3-D22 140U-KRP3-D20

300

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

Fixed Fixed Fixed Fixed Fixed Fixed

Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600

100

1 MINUTE

Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K3 140U-K6 Breaker Type

Hz UL/CSA 240V 65 100 IEC 947-2 480V 35 65 600V 25 35

50

240V 65 100

380V 40 65

415V 40 65

30

140U-K3 140U-K6

20

Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991.

2X

10

Short Delay Pick Up Settings (Tolerance 10%)

There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20C to +55C ambient. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 4000A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.

4X
2

6X 7X 8X

TIME IN SECONDS

.5

.5

3X

5X

300 ms
.3

.4 .3

200 ms
.2 .2

100 ms
.1 .1

.05

I
.05 .04

Fixed Instantaneous Override

.03

.03

.02

.02

SECONDS

Interrupting Rating Determines End of Curve

.01

.01

.005

.003

.002

1000

3000

4000

2000

5000

.001

.001 10,000 20,000 30,000 40,000 50,000

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS

40752-633 (1) SC-5639-93 Effective October 1997

44

Visit our website: www.ab.com/catalogs

100,000

.5

.6 .7 .8 .9 1

3 4 5

6 7 8 9 10

20

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LS, LSG Trip Units and 140U-K0 Molded Case Circuit Breakers
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.. 8 .9 16 2 3 4 5

10,000

.5

.7

6 7 8 9 10

20

2 HOURS

Circuit Breaker Time/Current Curves (Phase Current)

5,000

1 HOUR

3,000

Technical Data Covers, Cat. No. 140U-KTH3, -KTG3 Electronic Trip Units for use with Circuit Breaker Type 140U-K0, 400A. max. Fixed Short Delay Time Typical Trip Unit Nameplate
Short Delay Push to Trip Pickup xIr 4 Engaged 2 Trip Unit o 40 C 5 6 3 7 8

2,000

Standard Fixed Rating Plug


1,000

Rating Plug Cat. In

TEST

Remove
500

Available Rating Plugs


300

Ampere Rating (In)

Type

Catalog Number 140U-KRP3-D40 140U-KRP3-D35 140U-KRP3-D30 140U-KRP3-D25 140U-KRP3-D22 140U-KRP3-D20

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

100

400 350 300 250 225 200

Fixed Fixed Fixed Fixed Fixed Fixed

Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600

1 MINUTE

50

30

Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K0

Hz UL/CSA 240V 200 480V 100 600V 50

20

3X

10

Breaker Type 140U-K0

2X

IEC 947-2 240V 200 380V 100 415V 100

Short Delay Pick Up Settings (Tolerance 10%)

4X

Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20 C to +55 C ambient. For possible continuous amp derating for ambient above 40 C, consult Rockwell Automation For high fault current levels a fixed instantaneous override is provided at 4000A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.

5X 6X

TIME IN SECONDS

.5

.2

7X

.3

8X

.1

.1

.05

.05 .04

Fixed Instantaneous Override Maximum Interrupting Time

.03

.03

.02

.02

SECONDS

600 VAC
.01

.01

480 VAC 240 VAC

.005

.003

.002

.001

.001
2000 3000 4000 5000

Interrupting Rating Determines End of Curve


100,000 200,000 10,000 30,000 40,000 20,000 50,000

.5

.6 .7 .8 .9 1

3 4 5

6 7 8 9 10

20

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS

40752-634 (1) SC-5644-93 Effective October 1997

Visit our website: www.ab.com/catalogs

45

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LSI, LSIG Trip Units and 140U-K0 Molded Case Circuit Breakers
10,000 .5 .7

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)


.9 1 5

6 7 8 9 10

20

2 HOURS

5,000

Circuit Breaker Time/Current Curves (Phase Current)

1 HOUR

Technical Data Covers, Cat. Nos. 140U-KTL3, -KTI3 Electronic Trip Units for use with Circuit Breaker Cat. No 140U-K0, 400A. max.
3,000

Adjustable Short Delay Time


2,000
Rating Plug Short Delay Push to Trip Pickup xIr 4 Engaged 2 Trip Unit o 40 C 5 6 3 7 8 Time ms 200 100 INST 300

Typical Trip Unit Nameplate

Standard Fixed Rating Plug


1,000

Cat. In

TEST

Remove

Available Rating Plugs


500

Ampere Rating (In) 400 350 300 250 225 200

Type

Catalog Number 140U-KRP3-D40 140U-KRP3-D35 140U-KRP3-D30 140U-KRP3-D25 140U-KRP3-D22 140U-KRP3-D20

Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600

300

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

Fixed Fixed Fixed Fixed Fixed Fixed

100

1 MINUTE

Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K0

Hz UL/CSA 240V 200 IEC 947-2 480V 100 600V 50

50

Breaker Type
30

240V 200

380V 100

415V 100

140U-K0

20

Notes electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991.

2X

10

Short Delay Pick Up Settings (Tolerance 10%)

There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20C to +55 C ambient. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 4000A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.

4X
2

6X 7X 8X

TIME IN SECONDS

.5

3X

5X

300 ms
.3

200 ms
.2

100 ms
.1 .1

I
.05 .05 .04 .03 .03

Fixed Instantaneous Override Maximum Interrupting Time 600 VAC

Interrupting Rating Determines End of Curve

.02

.02

SECONDS

.01

.01

480 VAC 240 VAC

.005

.003

.002

.001

2000

3000

4000

5000

10,000

30,000

40,000

20,000

50,000

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS

40752-635 (1) SC-5645-93 Effective October 1997

46

Visit our website: www.ab.com/catalogs

100,000

200,000

.5

.6 .7 .8 .9 1

6 7 8 9 10

.001 20

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic Trip Units with Ground Fault Protection

480

10,000

2 HOURS

5,000

560 640 720 800

160

240

320

80

400

8000

GROUND CURRENT-AMPERES

1 HOUR

Circuit Breaker Time/Current Curves (Ground Current)


Electronic Trip Units for use with Bulletin 140U-K3, -K6, and K0 Molded Case Circuit Breakers For use with Trip Unit Catalog Numbers 140U-KTG3-D40 140U-KTI3-D40
Rating Plug Cat. In Push to Trip Short Delay Pickup xIr 5 4 6 3 7 2 Trip Unit o 40 C Short Delay Push to Trip Pickup xIr 4 Engaged 2 Trip Unit 40 oC 5 6 3 7 8 Time ms 200 100 INST 300 8 Ground Fault Pickup xIg 4 3 5 2 1 Ig = 80A Ground Fault Pickup xIg
3 2 1 Ig = 80A 4 5

3,000

2,000

Time ms 300 150 INST 500 TEST

1,000
Engaged

Remove

500

Rating Plug Cat. In

Time ms
300 150 INST 500

300

TEST

200

Remove

Notes Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation.
100

1 MINUTE

Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991.
50

For phase time/current curves see 40752-632, -633, -634, or 40752-635.

30

20

10

1xIG

3xIG

4xIG

TIME IN SECONDS

Ground Fault Pickup Settings (Tolerance 10% Except 20% on 1xIG Setting)

2xIG

5xIG

500 ms
.5

300 ms
.3

.2

150 ms

.1

.05

.03

.02

.01

.005

.003

.002

.001

7 8 9 10

100

GROUND CURRENT-IN MULTIPLES OF Ig = 80A

40752-636 (1) SC-5650-93 Effective October 1997

Visit our website: www.ab.com/catalogs

47

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-K0 Thermal-Magnetic Molded Case Circuit Breakers
600 700 800 900 1 000 4 00 60 00 7000 8000 9000 10,000 2000 4000 30 0 200 70 80 90 100 500 5000 3000 50 60 60,000 70,000 80,000 90,000 100,000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)


20,000 30,000 50,000 40,000

10,000

10,000

2 HOURS

2 HOURS

5,000

1 HOUR

Circuit Breaker Time/Current Curves


For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60C up to 125 A. 75 C above 125 amps) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600V., AC (60 Hz) 250 V., DC

5,000

1 HOUR

3,000

3,000

2,000

2,000

1,000

Breaker Rating Rated Amperes (In) 100, 125, 150, 175, 200, 225, 250, 300, 350, 400

1,000

Instantaneous Trip Amperes 500 to 1000% of trip unit rating (See Figure Below) (Dc values are approximately 40% higher)
500

500

(250-400A)

300

200

(125-225A) Maximum Single Pole Trip Times at 25 C

Interrupting Rating (UL/CSA) RMS Sym Amperes Breaker Type @ 240 V., AC @ 480 V., AC 140U-K0 200,000
100,000

Amperes
@ 600 V., AC 50,000 @ 250 V., DC 22,000 0
200 300

Single pole test data at 25 C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.

(100A)
100 100

1 MINUTE

1 MINUTE

Minimum
50

Maximum
50

30

30

20
7.5 7.5

20

10

Typical Trip Unit Nameplate

C Thermal Magnetic Trip Unit


10 5 10 5 Amps (In)

Push to Trip

7.5

10

10

Magnetic Multiples Of In

40C

Cat. No.

Individual Pole Adjustments


3 3

Adjustable Magnetic Trip


2 2

TIME IN SECONDS

TIME IN SECONDS

.3

10X

.5

5X

20%

10%

.5

.3

.2

.2

.1

.1

.05

.05

.03

.03

.02

.02

Maximum Interrupting Time 600 V., Ac


.01 .01

480 V., Ac
.005 .005

240 V., Ac
.003 .003

.002

Interrupting Rating Determines End of Curve

.002

.001
30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 6000 7000 8000 9000 10,000 20,000 50 60 70 80 90 100 500 600 700 800 900 1000 200 300 400 2000 3000 4000 5000

.001

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

40752-651 (1) SC-4119-87B Effective October 1997

48

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Time-Current Curves for Bulletin 140U-L Thermal-Magnetic Molded Case Circuit Breakers
Circuit Breaker Time/Current Curves
For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (75C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600V., AC (50/60 Hz) 250 V., DC Breaker Rating Rated Amperes (In) 250, 300, 320, 350 Poles 3 and 4

1 Hour

1 Hour

Instantaneous Trip Amperes (see below) 500 to 1000% of trip unit rating (DC values are approximately 40% higher)

Interrupting Rating (UL/CSA) Breaker RMS Sym Amperes Type @ 240 V., AC @ 480 V., AC 140U-L3 140U-L6 65 100 35 65

Amperes @ 600 V., AC 18 35 @ 250 V., DC 22 42

Interrupting Rating (IEC 60947-2) Breaker RMS Sym kA, 50/60 Hz, AC Type @ 240 V. (Ue) @ 480 V (Ue) Icu 140U-L3 140U-L6 65 Ics 65 Icu 35 70 Ics 35 70

kA, DC @600V. (Ue) Icu 12 25 Ics 6 13 @ 250 V.(Ue) Icu 22 42 Ics 22 42

100 100

1 MINUTE

1 MINUTE

Maximum Interruption Time

Interruption Rating determines end of curve

Current in Multiples of Rating (In)

40752-650 (1) TC-XXXXX Effective June 2003

Visit our website: www.ab.com/catalogs

49

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-L Thermal-Magnetic Molded Case Circuit Breakers
1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

Circuit Breaker Time/Current Curves 1. 140U/UE-L Cir. Break. Earth Leakage Mod., 3 and 4 Poles, 110 480V 60Hz. 2. For application and coordination purposes only. -20 C 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.

1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0

200.0

200.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

20.0

20.0

10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

Available Ig (A) Settings

.03

.1

.5

30
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

2.0

2.0

1S
TIME IN SECONDS
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3

500ms

300ms

.2

150ms

.2

.1 .09 .08 .07 .06 .05 .04 .03

60ms

.1 .09 .08 .07 .06 .05 .04 .03

.02

Inst.
.02

.01 .009 .008 .007 .006 .005 .004 .003

.01 .009 .008 .007 .006 .005 .004 .003

.002

.002

.001

.01

.02

.03

.04 .05

.07

.1

.2

.3

.4

.5

.7

1.0

2.0

3.0

4.0 5.0

7.0

10.0

20.0

50.0

80.0

.001

40752-651 (1) Curve No. TC01212009E Effective September 2005

Ig (A)

50

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-L Thermal-Magnetic Molded Case Circuit Breakers
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0

Circuit Breaker Time/Current Curves 1. 140U/UE-L Cir. Break. Earth Leak. Mod., 3 and 4 Poles, 110 480V 60Hz. 2. For application and coordination purposes only. -20 C 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.

1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0

200.0

200.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0

20.0

20.0

.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

.1

.3

10

Available I n Settings
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0

2.0

2.0

1S
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3

TIME IN SECONDS

500ms

300ms

.2

150ms

.2

.1 .09 .08 .07 .06 .05 .04 .03

60ms

.1 .09 .08 .07 .06 .05 .04 .03

Inst.
.02 .02

.01 .009 .008 .007 .006 .005 .004 .003

.01 .009 .008 .007 .006 .005 .004 .003

.002

.002

.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

.001

40752-652 (1) Curve No. TC01212008E Effective September 2005

I n (Amperes)

Visit our website: www.ab.com/catalogs

51

Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves, Continued

Bul.140U/UE
Long Delay Response & Short Delay with Flat Response Curve, Bulletin 140U/UE-L
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30

2 HOURS

10000 9000 8000 7000 6000 5000

Circuit Breaker Time/Current Curves (Phase Current)


1.15

1 HOUR

Bulletin 140U/UE L-Frame 3- and 4-Pole Molded Case Circuit Breakers


Long Delay (LD) & Short Delay (SD) with Flat Response Available Sensors (In): 250A 400A 600A 630A Ir A B C D E F G H
In

4000 3000

2000

250A 100A 125A 150A 160A 175A 200A 225A 250A

400A 160A 200A 225A 250A 300A 315A 350A 400A

600A 250A 300A 315A 350A 400A 450A 500A 600A

630A 250A 300A 315A 350A 400A 500A 600A 630A

1000 900 800 700 600 500 400 300

Maximum Total Clearing Time Notes:

1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +85 C cause an overtemperature protection trip. For possible continuous ampere derating for ambient above 40C, refer to Rockwell Automation. 2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 5. The left portion of the curve is shown as a multiple of the Long Delay Setting. (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%. 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has 8 settings/positions, 2 - 8 & 10. 8. For high fault current levels an additional fixed instantaneous hardware override is provided (corresponding to SDPU position 9) at 14x (In) and designated as 14I i. Instantaneous tolerance is 20%. 9. For LD Response & SD with Flat Response (this curve): 10. For LD Response & SD with I T Response curve, see: 11. For Ground Fault Delay Response curve, see:
2

200

1 MINUTE

100 90 80 70 60 50 40 30

Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%

20

24

TIME IN SECONDS

. . .
7

10 9 8 7 6 5 4 3

Minimum Total Clearing Time

15

TC01207004E TC01207005E TC01207006E

.
4

.
2

8 5

.6 .5 .4

.5 .4 .3

300ms (P,Q,R) Instantaneous Override (See Note 8)


7

.3

.2

.2

.1 .09 .08 .07 .06 .05 .04 .03

120ms (M,N,O)

Application Determines End of Curve


.1 .09 .08 .07 .06 .05 .04 .03

10

Inst. (J,K,L)

.02

.02

14 Ii
.01

.5

.7

10

20

30

40

50

70

100

10

20

30

40

50

70

.01 100

Current in Multiples of (Ir)

Current in Multiples of (In)

Adjustable Flat Trip Style

40752-653 (1) TC01207004E Effective March 2006

52

Visit our website: www.ab.com/catalogs

TIME IN SECONDS

1 .9 .8 .7 .6

Available Short Delay Pick Up Settings 2 - 8,10 x Ir 5% (See Note 7)

1 .9 .8 .7

Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves, Continued

Bul.140U/UE
Long-Delay Response & Short-Delay with I2T Response Curve, Bulletin 140U/UE-L
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30

Long Delay Response & Short Delay with I T Response Curve

2 HOURS

10000 9000 8000 7000 6000 5000

Circuit Breaker Time/Current Curves (Phase Current)


1.15

1 HOUR

Bulletin 140U/UE L-Frame 3- and 4-Pole Molded Case Circuit Breakers


2

4000 3000

Long Delay (LD) & Short Delay (SD) with I T Response


2000

Available Sensors (In):


1000 900 800 700 600 500 400 300

Ir A B C D E F G H

In

250A 100A 125A 150A 160A 175A 200A 225A 250A

400A 160A 200A 225A 250A 300A 315A 350A 400A

600A 250A 300A 315A 350A 400A 450A 500A 600A

630A 250A 300A 315A 350A 400A 500A 600A 630A

250A 400A 600A 630A Maximum Total Clearing Time

Notes: 1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +85 C cause an over temperature protection trip. For possible continuous ampere derating for ambient above 40C, refer to Rockwell Automation. 2. Application frequency is 50/60 Hertz.

200

1 MINUTE

100 90 80 70 60 50 40 30

Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%

3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 5. The left portion of the curve is shown as a multiple of the Long Delay Setting (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%.

20

24

TIME IN SECONDS

. . .
7

6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has eight settings/positions: 2 - 8 & 10. 8. Short Delay I T band has a tolerance of 15%. 9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I T curve. 10. For high fault current levels an additional fixed instantaneous hardware override is provided (corresponding to SDPU position 9) at 14x (In) and designated as 14I i . Instantaneous tolerance is 20% 11. For LD Response & SD with Flat Response curve, see:
2 2 2

10 9 8 7 6 5 4 3

Minimum Total Clearing Time

15

.
4 3

40752-653

12. For LD Response & SD with I T Response (this curve): 40752-654

.
2 4

13. For Ground Fault Delay Response curve, see:

40752-655

2
1 .9 .8 .7 .6 .5 .4 .3

1 .9 .8 .7 .6 .5
7

.4 .3
8

.2

.2

I T Short Delay (See Note 8)


.1 .09 .08 .07 .06 .05 .04 .03

10

.
67ms

Application Determines End of Curve

.1 .09 .08 .07 .06 .05 .04 .03

See Note 9
.02

14 Ii

.02

.01

.5

.7

10

20

30

40

50

70

100

10

20

30

40

50

70

.01 100

Current in Multiples of (Ir) I T


2

Current in Multiples of (In)

40752-654 (1) TC01207005E Effective March 2006

Trip Style

TIME IN SECONDS

Available Short Delay Pick Up Settings 2 - 8 & 10 x Ir 5% (See Notes 7 and 10)

Instantaneous Override (See Note 10)

Visit our website: www.ab.com/catalogs

53

Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves, Continued

Bul.140U/UE
Ground Fault Delay Response Curve, Bulletin 140U/UE-L
.1
10000 9000 8000 7000 6000 5000 4000 3000

.2

.3

.4

.5

.7

1.0

2.0

Circuit Breaker Time/Current Curves (Ground Current)


bulletin 140U/UE L-Frame 3- and 4-Pole Molded Case Circuit Breakers

Ground Fault Delay Response Notes: 1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +85 C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40C, refer to Rockwell Automation. 2.Application frequency is 50/60 Hertz.

2000

1000 900 800 700 600 500 400 300

3. Trip units are suitable for functional field testing with test kit style # 70C1056G52. 4. For LD Response & SD with Flat Response curve, see: 5. For LD Response & SD with I T Response curve, see: 6. For Ground Fault Delay Response (this curve):
2

40752-653 40752-654 40752-655

200

1 MINUTE

100 90 80 70 60 50 40 30

TIME IN SECONDS

20

10 9 8 7 6 5 4 3

Ground Fault Pickup Settings (Tolerance 10%) NOTE: Refer to table below for variations.

Available Sensors (In): 250A 400A 600A 630A


.4X .2X .6X .3X 1X

Ir A B C D E F G H

In

250A 100A 125A 150A 160A 175A 200A 225A 250A

400A 160A 200A 225A 250A 300A 315A 350A 400A

600A 250A 300A 315A 350A 400A 450A 500A 600A

630A 250A 300A 315A 350A 400A 500A 600A 630A

1 .9 .8 .7 .6 .5 .4 .3

.8X

300ms (L,O,R)

.2

.1 .09 .08 .07 .06 .05 .04 .03

120ms (K,N,Q)

Inst. (J,M,P)

.02

.01

.1

.2

.3

.4

.5

.7

1.0

2.0

40752-655 (1) TC01207006E Effective March 2006

Ground Current in Multiple of (In)

54

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers


Time-Current Curves, Continued

Bul.140U
Time-Current Curves for Bulletin 140U-Q3/Q6 Thermal-Magnetic Molded Case Circuit Breakers

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)


600 70 0 80 0 900 1000 6000 7000 8000 9000 10,000 2000 3000 4000 5000 300 400 50 0 70 80 90 100 200 60,000 70,000 80,000 90,000 100,000 20,000 30,000 40,000 50,000

50

60

10,000

10,000

2 HOURS

2 HOURS

5,000

5,000

1 HOUR

1 HOUR

Circuit Breaker Time/Current Curves


3,000

2,000

For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (75C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600 V., AC (50/60 Hz.) 250 V., DC

3,000

2,000

1,000

Breaker Rating Rated Amperes (In) 300, 350, 400, 500, 600

1,000

Instantaneous Trip Amperes (See Figure Below) 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
500

500

300

Maximum Single Pole Trip Times at 25 1 C

Interrupting Rating Breaker UL/CSA Type RMS Sym. kA, 50/60 Hz. 240 V. 140U-Q3 140U-Q6 480 V. 600 V. 25 35

kA, Dc 250 V. 10 20 kA, Dc 415 V., (U ) e Icu Ics 40 65 10 17 250 V., (U) e Icu Ics 10 20 3 5

300

200

Minimum
100

Maximum

65 35 100 65 IEC 947-2 RMS Sym. kA, 50/60 Hz. 240 V., (U ) e Icu Ics 380 V., (U) e Icu Ics 40 65 10 17

200

100

1 MINUTE

1 MINUTE

50

140U-Q3 65 140U-Q6 100

17 25

Utilization Category A U IMP = 8 kV Note: For additional information on the trip unit, see IL 29C606. Single pole data at 25 C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.

50

30

30

20

20

7.5

7.5

10

Typical Trip Unit Nameplate

C Thermal Magnetic Trip Unit


10 5 10 5 Amps (In)

Push to Trip

7.5

10
10 5

Magnetic Multiples Of In

40C

Cat. No.

Individual Pole Adjustments

TIME IN SECONDS

TIME IN SECONDS

10X

5X

20%

10%
1

.5

.5

Adjustable Magnetic Trip


.3 .3

.2

.2

.1

.1

.05

.05

.03

Maximum Interrupting Time

.03

.02

.02

.01

.01

.005

Interrupting Rating Determines End of Curve

.005

.003

.003

.002

.002

.001
60,000 70,000 80,000 90,000 100,000 30,000 6000 7000 8000 9000 10,000 20,000 50,000 40,000 60 70 80 90 100 50 500 600 700 800 9 00 1000 30 0 40 0 200 2000 3000 4000 5000

.001

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

40752-670 (1) SC-4547-89B Effective October 1997

Time-Current Curves, Continued

Visit our website: www.ab.com/catalogs

55

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-M5, -M6 Thermal-Magnetic (300600 A) Molded Case Circuit Breakers
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
6000 7000 8000 9000 10,000 600 700 800 900 1000 3000 4000 2000 60 70 80 90 100 200 5000 500 300 400 60,000 70,000 80,000 90,000 100,000 20,000 30,000 40,000 50,000

50

10,000

10,000

2 HOURS

5,000

1 HOUR

Circuit Breaker Time/Current Curves


For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (75 C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600 V AC (50/60 Hz.) 250 V DC

5,000

3,000

3,000

2,000

2,000

1,000

Breaker Rating Rated Amperes (I n 300, 350, 400, 500, 600

1,000

Instantaneous Trip Amperes (See Figure Below) 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
500

500

300

Maximum Single Pole Trip Times at 25 1 ?C

Interrupting Rating Breaker UL/CSA Type RMS Sym. kA, 50/60 Hz. 140U-M5 140U-M6 Breaker Type 240V 65 100 IEC 947-2 RMS Sym. kA, 50/60 Hz. ) 240V (Ue Icu Ics 140U-M5 140U-M6 65 100 65 100 380/415V (Ue ) 690V (Ue) Icu Ics Ics Icu 50 70 50 50 20 25 10 13 480V 50 65 600V 25 35

kA, DC 250V 22 25 kA, DC 250V (Ue) Ics Icu 20 20 10 10

300

200

200

Minimum
100

Maximum

100

1 MINUTE

50

Utilization Category A U IMP = 8 kV Note: For additional information on the trip unit, see IL 29C607.

50

30

Single pole data at 25 C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.

30

20
7.5 7.5 Push to Trip 7.5

20

10

Typical Trip Unit Nameplate

10

10

5 Amps (In)

10

10

Magnetic Multiples Of In

40 C

Cat. No.

Individual Pole Adjustments


3 3

TIME IN SECONDS

10X

5X

? 20%

? 10%
1

.5

.5

Adjustable Magnetic Trip


.3 .3

.2

.2

.1

.1

.05

.05

.03

Maximum Interrupting Time

.03

.02

.02

.01

.01

.005

Interrupting Rating Determines End of Curve

.005

.003

.003

.002

.002

.001 30,000 40,000 60,000 70,000 80,000 90,000 100,000 20,000 6000 7000 8000 9000 10,000 50,000 60 70 80 90 100 50 500 600 700 800 900 1000 200 300 400 2000 3000 4000 5000

.001

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

40752-674 (1) SC-6911-98 Effective February 1999


Time-Current Curves, Continued

56

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-M5, -M6 Thermal-Magnetic (700 & 800 A) Molded Case Circuit Breakers
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
2000 3000 6000 7000 8 0 00 9000 10,000 600 700 800 900 1000 4000 5000 200 300 400 70 80 90 100 500 60,000 70,000 80,000 90,000 100,000 30,000 40,000 20,000 50,000 50 60

10,000

10,000

2 HOURS

2 HOURS

5,000

5,000

1 HOUR

1 HOUR

Circuit Breaker Time/Current Curves


3,000

2,000

For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (75 C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600 V AC (50/60 Hz.) 250 V DC

3,000

2,000

1,000

Breaker Rating Rated Amperes (I 700, 800

1,000
n)

Instantaneous Trip Amperes (See Figure Below) 400 to 800% of Trip Unit rating (DC values are approximately 40% higher)
500

500

300

Maximum Single Pole Trip Times at 25 1 ?C

Interrupting Rating Breaker UL/CSA Type RMS Sym. kA, 50/60 Hz. 140U-M5 140U-M6 Breaker Type 240V 65 100 IEC 947-2 RMS Sym. kA, 50/60 Hz. 240V (U ) e Ics Icu 140U-M5 140U-M6 65 100 65 100 380/415V (U e) Ics Icu 50 70 50 50 690V (U) e Ics Icu 20 25 10 13 480V 50 65 600V 25 35

kA, DC 250V 22 25 kA, DC 250V (U) e Ics Icu 20 20 10 10

300

200

200

Minimum
100

Maximum

100

1 MINUTE

1 MINUTE

50

Utilization Category A U IMP = 8 kV

50

30

Single pole data at 25C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.
6 6 Thermal Magnetic Trip Unit 8 4 8 4 Amps (In) C Cat. No. Push to Trip 8 4 6

30

20

20

10

Typical Trip Unit Nameplate

10

Magnetic Multiples Of In

Individual Pole Adjustments


3 3

TIME IN SECONDS

TIME IN SECONDS

4X

8X

? 20%

? 10%
1

.5

.5

Adjustable Magnetic Trip


.3 .3

.2

.2

.1

.1

.05

.05

.03

Maximum Interrupting Time

.03

.02

.02

.01

.01

.005

Interrupting Rating Determines End of Curve

.005

.003

.003

.002

.002

.001 20,000 30,000 60,000 70,000 80,000 90,000 100,000 40,000 6000 7000 8000 9000 10,000 50,000 50 60 70 80 90 100 500 600 70 0 800 900 1000 200 300 400 4000 2000 3000 5000

.001

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

40752-675 (1) SC-6912-98 Effective February 1999


Time-Current Curves, Continued

Visit our website: www.ab.com/catalogs

57

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-M Electronic LS, LSG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers
10,000 .5
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .7 .9 16 .8 . 2 3 4 5 6 7 8 9 10

20

2 HO U R S

Circuit Breaker Time/Current Curves (Phase Current)


5,000
Technical Data Covers, Cat. Nos. 140U-MTL3, -MTG3 Electronic Trip Unit for use with Circuit Breaker Types 140U-M5, -M6, 800 A max.

1 HO U R

3,000

2,000

Fixed Short Delay Time

Typical Trip Unit Nameplate


Test

Standard Fixed Rating Plug


1,000

Rating Plug Cat. In Engaged Push to Trip

Short Delay Pickup x I n 5 4 6 3 7 2 8

Trip Unit 40o C Ambient

Remove

500

Available Rating Plugs Ampere Rating (I n ) 800 700 600 500 450 400 Interrupting Rating

Type

300

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

Fixed Fixed Fixed Fixed Fixed Fixed

Rating Plug Catalog Number 140U-MRP3-D80 140U-MRP3-D70 140U-MRP3-D60 140U-MRP3-D50 140U-MRP3-D45 140U-MRP3-D40

Short Delay Pickup Range Amperes 1600-6400 1400-5600 1200-4800 1000-4000 900-3600 800-3200

100

Breaker Type 140U-M5 140U-M6 Breaker Type

UL/CSA RMS Sym. kA, 50/60 Hz 240V 65 100 480V 50 65 600V 25 35

1 MIN U T E

50

30
140U-M5 140U-M6

IEC 947-2 RMS Sym. kA, 50/60 Hz 380/415V (U 240V (U e) Ics Icu Ics Icu 65 100 Utilization Category A U imp = 8kV 65 100 50 70 50 50

e)

Icu 20 25

690V (U e) Ics 10 13

20

10

2X

3X

Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA AB4-1991 publications.

3 2

Short Delay Pick Up Settings (Tolerance 10%)

Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick-up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory.

4X 5X

TIME IN SECONDS

Curve accuracy applies from 20 C to +55C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation.

8X

For high fault current levels a fixed instantaneous override is provided at 5500A.
1
(Tolerance 15%).

6X

The end of the curve is determined by the interrupting rating of the circuit breaker.
See above tabulation.

.5

For ground fault time/current curves see 40752-678.

.2

7X

.3

.1

.1

.05

.05 .04

Fixed Instantaneous Override

.03

.03

.02

.02

.01

SECONDS

Interrupting Rating Determines End of Curve

.01

.005

.003

.002

30,000

40,000

10,000

20,000

50,000

CURRENT IN AMPS

40752-676 (1) SC-7204-99 Effective February 1999


Time-Current Curves, Continued

58

Visit our website: www.ab.com/catalogs

100,000

.001 2 3 4 5 6 7 8 9 10 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

1000

2000

4000

3000

5000

20

.001

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-M Electronic LSI, LSIG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers
10,000 2 HO U R S .5

.7

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .9 16 .8 . 2 3 4 5 6 7 8 9 10

20

Circuit Breaker Time/Current Curves (Phase Current)


5,000

1 HO U R

Technical Data Covers, Cat. nos. 140U-MTH3, -MTI3 Electronic Trip Units for use with Circuit Breaker Types 140U-M5, -M6, 800 A max.
3,000

Adjustable Short Delay Time


2,000

Typical Trip Unit Nameplate


Time MIsec 200 100 I 300 Trip Unit o 40 C Ambient Test

Standard Fixed Rating Plug


1,000

Rating Plug Cat. In Engaged Push to Trip

Short Delay Pickup x In 5 4 6 3 7 2 8

Remove

Available Rating Plugs Ampere Rating (In)


500

Type

300

800 700 600 500 450 400

Fixed Fixed Fixed Fixed Fixed Fixed

Rating Plug Catalog Number 140U-MRP3-D80 140U-MRP3-D70 140U-MRP3-D60 140U-MRP3-D50 140U-MRP3-D45 140U-MRP3-D40

Short Delay Pickup Range Amperes 1600-6400 1400-5600 1200-4800 1000-4000 900-3600 800-3200

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

Interrupting Rating Breaker Type 140U-M5 140U-M6 Breaker Type UL/CSA RMS Sym. kA, 50/60 Hz 240V 65 100 IEC 947-2 RMS Sym. kA, 50/60 Hz 240V (Ue) Icu Ics 140U-M5 140U-M6 65 100 Utilization Category A U imp = 8kV 65 100 380/415V (U e ) Icu Ics 50 70 50 50 690V (U e) Icu Ics 20 25 10 13 480V 50 65 600V 25 35

100

1 MIN U T E

50

30

20

2X

10

Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA AB4-1991 publications. Calibration response in short delay pickup range is same for 1, 2 or 3 poles in series.

4X

Short Delay Pickup Settings (Tolerance ? 10%)

6X

There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 5500A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curves see 40752-678.

TIME IN SECONDS

.5

3X

5X

7X

8X

300 ms
.3

200 ms
.2

100 ms
.1 .1

I
.05 .05 .04 .03 .03

Fixed Instantaneous Override

.02

.02

.01

SECONDS

Interrupting Rating Determines End of Curve

.01

.005

.003

.002

1000

4000

2000

3000

5000

.001

.001 10,000 40,000 30,000 50,000 20,000 100,000 .5 2 3 4 5 6 7 8 9 10 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 20

CURRENT IN AMPS

40752-677 (1) SC-6913-98 Effective February 1999


Time-Current Curves, Continued

Visit our website: www.ab.com/catalogs

59

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-M Electronic Trip Units with Ground Fault Protection
Ground Fault Protection
320 160 10,000 1120 1280 1440 1600 800 480 640 960 16000

GROUND CURRENT-AMPERES

2 HOURS
5,000

1 HOUR

Circuit Breaker Time/Current Curves (Ground Current)


Technical Data Covers, Electronic Trip Units for use with Circuit Breaker Types 140U-M5, -M6, 800 A max. Fixed Short Delay Time
Rating Plug

3,000

Typical Trip Unit Nameplate


Short Delay Pickup x In Ground Fault Pickup x Ig 3 2 1 4 5 Time MIsec 500 Trip Unit 40 o C Ambient Test 5

2,000

Cat. In Engaged Push to Trip

4 2

6 3 7 8

300 150 I Ig = 160A

Remove

1,000

Adjustable Short Delay Time


Rating Plug Cat. In Push to Trip 4 Engaged 2 Short Delay Pickup x In 5 6 3 7 8 Time MIsec 200 100 I 300 Ground Fault Pickup x Ig 3 2 1 4 5 Time MIsec 500

Typical Trip Unit Nameplate


Test

500

300 150 I Ig = 160A

Trip Unit 40 oC Ambient

Remove

300

Notes Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation. Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication (AB4-1991). For phase time/current curves see: 40752-674 40752-675 40752-676 40752-677

200

100

1 MINUTE

50

30

20

10

1xIG

3xIG
5 3

4xIG

TIME IN SECONDS

Ground Fault Pickup Settings (Tolerance 10% Except 20% on 1xIG Setting)

2xIG

5xIG

500 ms
.5

300 ms
.3

.2

150 ms

.1

.05

.03

.02

.01

.005

.003

.002

.001

7 8 910

100

40752-678 (1) SC-6914-98 Effective February 1999

GROUND CURRENT-IN MULTIPLES OF Ig = 160A

Time-Current Curves, Continued

60

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-N Electronic LS Trip Units
10,000
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10

20

2 HO U R S

Circuit Breaker
5,000

Time/Current Curves (Phase Current)

1 HO U R

Electronic Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types 140U-N5, -N6, and -N0. I2t Ramp Short Time Delay
Rating Plug

3,000

Typical Trip Unit Nameplate

2,000

Standard Fixed Rating Plug


1,000

Push to Trip

Cat. /n Y

Short Delay Pickup x In 5 4 6 3 2 7 8

TEST

Trip Unit 40 C Ambient

Engaged

Remov e

500

Frame Rating Amperes (Max.) 1200

A vailable Rating Plugs Ampere Rating (I n) 1200 1000 800 700 600 600, 800, 1000, 1200

Type

Catalog Number 140U-NRP3-E12 140U-NRP3-E10 140U-NRP3-D80 140U-NRP3-D70 140U-NRP3-D60 140U-NRPA-E12

Short Delay Pickup Range Amperes 2400-9600 2000-8000 1600-6400 1400-5600 1200-4800 1200-9600

300

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

Fixed Fixed Fixed Fixed Fixed Adj.

100

50

Interrupting Ratings 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 ND, CND 100 65 HND, CHND 200 100 NDC, CNDC

1 MIN U T E

600V 25 35 50

IEC 947-2 220-240V 65 100 200

380-415V 50 65 100

30

20

ICS = .25 ICU ICW = 15 kA @ .5S U imp = 8kV

3X

2X

Notes
Curve accuracy applies from -20 C to +55 ambient above 40 C, consult Rockwell Automation Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. For ground fault time-current curves see 40752-692.

10

3 2

Short Delay Pick Up Settings (Tolerance 10%)

There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overloads will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance 15%).

4X 5X

8X

TIME IN SECONDS

The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. Not UL/CSA Listed.

.5

.2

7X

.3

6X

.1

.1

.05

.05

Fixed Instantaneous Overide

.03

.03 .02

.02

SECONDS

.01

.01

Interrupting Rating Determines End of Curve

.005

.005

.003

.003 .002

.002

60,000 70,000 80,000 90,000 100,000

CURRENT IN AMPS

40752-690 (1) SC-5375-92A Effective October 1997


Time-Current Curves, Continued

200,000

40,000

10,000

20,000

30,000

50,000

.001 2 3 4 5 6 7 8 9 10 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

20

.001

Visit our website: www.ab.com/catalogs

61

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-N LSI Electronic Trip Unit
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10

10,000

20

2 HO U R S

Circuit Breaker

Time/Current Curves (Phase Current)

1 HO U R

5,000

Electronic Trip Units are AC only devices that employ microprocessor-based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. For use with Circuit Breaker Types 140U-N5, -N6, and -N0. Adjustable Short Time Delay
Rating Plug
Push to Trip Cat. /n Y Short Delay Pickup x In 5 4 6 3 2 7 8

3,000

Typical Trip Unit Nameplate

2,000

Standard Fixed Rating Plug

TEST

Trip Unit 40 Ambient C

Engaged

Remov e

1,000
Frame Rating Amperes (Max.) 1200 A vailable Rating Plugs Ampere Type Rating (I n) 1200 1000 800 700 600 600, 800, 1000, 1200 Fixed Fixed Fixed Fixed Fixed Adj. Catalog Number 140U-NRP3-E12 140U-NRP3-E10 140U-NRP3-D80 140U-NRP3-D70 140U-NRP3-D60 140U-NRPA-E12 Short Delay Pickup Range Amperes 2400-9600 2000-8000 1600-6400 1400-5600 1200-4800 1200-9600

500

300

200

Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time

100

1 MIN U T E

Interrupting Ratings 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 140U-N5 100 65 140U-N6 200 100 140U-N0

600V 25 35 50

IEC 947-2 220-240V 65 100 200

380-415V 50 65 100

50
Notes

ICS = .25 ICU ICW = 15 kA @ .5S U imp = 8kV


Curve accuracy applies from -20 C to +55 C ambient. For possible ampere derating for ambient above 40 C, consult Rockwell Automation Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991.

30

20

2X

For ground fault time-current curves see 40752-692. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overloads will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory

10

4X

3 2

Short Delay Pick Up Settings (Tolerance 10%)

For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. Not UL/CSA Listed.

6X 3X 5X 7X 8X

TIME IN SECONDS

.5

300 MS
.3

200 MS
.2

100MS
.1 .1

I
.05 .05

Fixed Instantaneous Overide

.03

.03 .02

.02

.01

SECONDS

.01

Interrupting Rating Determines End of Curve

.005

.005

.003

.003 .002

.002

CURRENT IN AMPS

40752-691 (1) SC-5376-92A Effective October 1997


Time-Current Curves, Continued

62

Visit our website: www.ab.com/catalogs

60,000 70,000 80,000 90,000 100,000

200,000

40,000

50,000

20,000

10,000

30,000

.001 2 3 4 5 6 7 8 9 10 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

20

.001

Bulletin 140U/UE

Molded Case Circuit Breakers

Bul.140U/UE
Time-Current Curves for Bulletin 140U-N Electronic LSG, LSIG Trip Units with Ground Fault Protection
CURRENT IN AMPERES
2000 3000 600 700 800 900 1000 4000 .50 .60 .70 .80 .90 100 5000

200

300

400

10,000
2 HO U R S

500

Circuit Breaker

Time/Current Curves (Ground Current)

1 HO U R

5,000

Electronic Trip Units are AC only devices that employ microprocessor-based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types 140U-N5, -N6, and N0.

3,000 Typical Trip Unit Nameplate

2,000
Rating Plug
Push to Trip Cat. /n Y

Short Delay Pickup x In 5 4 6 3 2 7 8

Ground Fault Pickup x IG 4 3 5 2 1 6

Time 500 300 150 1 TEST

1,000
Engaged Remov e

Trip Unit 40 Ambient C


Millisec

IG=200A

500 Notes 300 200


Curve accuracy applies from 20 C to + 55C ambient. Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. For phase time-current curves see 40752-690, and -691.

100
1 MIN U T E

50

30

20

200 A .

600 A .

10

1000 A .

3 2

Ground Fault Pick Up Settings (Tolerance 10% Except 20% on 200 A. Setting)
400 A . 1200 A .

1
TIME IN SECONDS

800 A .

.5

.5 SEC

.3

.3 SEC

.2

.15 SEC

.1

.05

.03

.02

.01

.005

.003

.002

.50 .60 .70 .80 .90 100

.001

500

600 700 800 900 1000

2000

4000

CURRENT IN AMPERES

40752-692 (1) SC-5377-92A Effective October 1997

3000

5000

200

300

400

Visit our website: www.ab.com/catalogs

63

Publication 140U-TD001B-EN-P November 2006 Copyright 2006 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.