380CS/HS
880102-0001
BadgerMeter, Inc.
REV. 1 8-09
INTRODUCTION
The Badger Series 380 Btu Systems provide a low cost system for metering cold or hot systems. The 380CS/HS can accurately measure flow and temperature differential to compute energy. Utilizing BACnet or Modbus RS-485 communications protocols or a scaled pulse output, the Btu System can interface with many existing control systems. The rugged design incorporates an impeller flow sensor and two temperature probes. One temperature probe is conveniently mounted directly in the flow sensor tee. The second temperature probe is placed on either the supply or the return line depending on ease of installation for the application. These minimal connections help simplify installation and save time. The main advantage of the Series 380 Btu System is the cost savings over other systems offered on the market today. The integration of flow and temperature sensors, along with metering components provide a single solution for metering. With this system it will be possible to meter energy where it hasn't been cost effective before. Commissioning of this meter can be completed in the field via a computer connection or setup at the factory with the customers requirements. Setup includes energy measurement units, measurement method, communications protocol, pulse output control, fluid density, and specific heat parameters.
2)
Series 380
The 380 combines a PEEK electronics package inserted in a 3/4", 1", 1 1/4", 1 1/2", and 2" proprietary cast bronze pipe tee with treaded NPT connections.
Series 380 BTU System Ordering Matrix
380 Type CS - Cold Service HS - Hot Service Size 0.75" 1" 1.25" 1.5" 2" Electronic Housing Polycarbonate Output Scaled Pulse and RS-485 (Modbus and BACnet) Display N/A O-Ring EPDM (CS - Cold Service) Aflas (HS - Hot Service) Shaft Tungsten Carbide [Standard] Impeller Stainless Steel Bearing Torlon (CS - Cold Service) Ketron (HS - Hot Service) 0 0 1 07 10 12 15 20 0 0 0 1 2 2 0 0 2 7 0 0 0 1 2 0 0
Impeller may strike sides of venturi cavity in tee if misaligned, causing damage to impeller and shaft. 3) Before pressurizing pipe, verify that all threaded connections are tight.
2"
Cold Service 380007000-1200 380010000-1200 380012000-1200 380015000-1200 380020000-1200 Hot Service 380107000-2202 380110000-2202 380112000-2202 380115000-2202 380120000-2202
Price $ 395.00 $ 405.00 $ 420.00 $ 435.00 $ 475.00 $ 405.00 $ 420.00 $ 445.00 $ 460.00 $ 500.00
Figure2
ELECTRICAL INSTALLATION
1 ) Connect your power supply (12-35VDC or 12-28VAC) to terminals 1 and 2 next to the "POWER" label. This connection is not polarity sensitive. 2 ) Proceed to step three if RS-485 is not being utilized. Using the terminals next to the "RS485" label, connect the positive side of the network cable to terminal 1 (+). Connect the negative side to terminal 2 (-) and the shield to the terminal 3 (GND). 3 ) If using RS-485, see step 2. Using the terminals next to the "PULSE OUTPUT" label, connect the negative side of a power supply (the same voltage as the "POWER") to terminal 2. Connect the positive side of the power supply to a counter's positive terminal. Lastly connect the negative side of the counter to terminal 1. NOTE: The pulse and RS-485 may be used simultaneously.
Figure2showthecommunicationparamterstab. HeretheusercanselectBACnetorModbusalong withthenetworkaddress.IfusingBACnettheuser willneedtoenterintheDeviceName,DeviceID BACnetBitRateandtheMaxMasternumberthatis appropriateforthenetworkthe380isbeing connectedto. IfthenetworkisModbusthentheuserwillneedto Figure 2 specifythemode(RTUorASCII).TheBitRatewillalso needtobeconfiguredforpropercommunicationfor Device Name, Device ID BACnet BitRate and the Max Master thenetworkthe380isbeingconnectedto(9600, number that is appropriate for the network that the 380 is being connected to. 19200,38400,76800).
If the network is Modbus then the user will need to specify the Dependingonthenetworkthatthe380isbeing mode (RTU or ASCII). The BitRate will also need to be configconnectedtonetworkpullup,networkpulldown, ured for proper communication for the network that the 380 is being connected to (9600, 19200, 38400, 76800). and/ornetworkterminationmaybeneeded.These Depending on the network that the 380 is being connected to, progammedinontheCommunicationParameters network pullup, network pulldown, and/or network termination may be needed. These parameters are not physical jumpers tab. but rather are progammed in on the Communication Parameters tab.
COMMISSIONING
All setup and commissioning of the 380 is done using a USB to Mini USB cable and the Badger Series 380 commisioning software (see next page). Figure 1 shows the main setup screen. Here the user can select the tee size that will automaticly input the correct K and Offset. Flow and Energy rate's and total's units can be selected or a custom unit can be put in with the correct conversion factor. For the temperature sensors the user can select the units along with the calculation mode (i.e. T1>T2, Absolute, or T1<T2). The Diff Zero parameter is the difference between T1 and T2 that will still read 0 energy rate. If the Scaled Pulse Output is going to be used the user can select what the pulse is representing (Energy or Flow) along with Units/Pulse and the pulse width. If the Scaled Pulse Output is not going to be used this can be set to Off. Filter Coefficents should be left at 5 for best readings of flow and temperature. Figure 2 shows the communication paramters tab. Here the user can select BACnet or Modbus along with the network address. If using BACnet the user will need to enter in the
parametersarenotphiscaljumpersbutratherare
Model380ModbusRegisterMap DataType RegisterName Add. Temp1 0 IEEE754Float Temp2 2 IEEE754Float 4 IEEE754Float VolumeRate EnergyRate 6 IEEE754Float 8 IEEE754Float VolumeTotal 10 IEEE754Float EnergyTotal 12 IEEE754Float TemperatureMode 14 IEEE754Float FlowCoefficient 16 IEEE754Float TempCoefficient 18 IEEE754Float SpecificHeatCoeff 20 IEEE754Float FluidDensityCoeff Model380BACnetRegisterMap Model380BACnetObjectMap DataType. RegisterName Add. ObjectName Instance ObjectType TempIn 1 AnalogInput TempOut 2 AnalogInput VolumeFlow 1 AnalogValue EnergyFlow 2 AnalogValue TotalVol 3 AnalogValue TotEnergy 4 AnalogValue TempMode 5 AnalogValue FFiltCoef 6 AnalogValue TFiltCoef 7 AnalogValue SpecHeat 8 AnalogValue Density 9 AnalogValue SerialNum 10 AnalogValue
Figure 1
Specifications
SensorAssembly Houseing:PEEK SPECIFICATIONS Sensor Assembly: Impeller:316SS Housing: PEEK Shaft:TungstonCarbide Impeller: 316SS CSSpecific:TorlonBearing,EDPMORings Shaft: Tungston Carbide HSSpecific:KetronBearing,AflasORings Tee
Tee: CS Specific: Torlon Bearing, EDPM O-Rings HS Specific: Ketron Bearing, Aflas O-Rings
<15lb
CastBronze
Cast Bronze
Temperature Rating For Wetted Materials: CS: CS:20Fto180F -20F to 180F HS: HS:30Fto250F 30F to 250F
TemperatureRatingForWettedMaterials
ELECTRICAL RTD Inputs Meets Power IEC751 Class B 1235VDC 928VACrms Output Pulse Width Modbus Communication 10, 50, 150, 200, or 250mS BACnet Output BACnet StandardizedOpenDrain ScaledPulse Device Profile
Device Profile Tested
MATERIALS Housing Polycarbonate Supported BIBBs FlowSensor PEEK Supported BIBBs BIBB Name PottingMaterial Polyurethane DS-RP-B ReadProperty - B Tee WriteProperty - B Brass DS-WP-B
BACnet Smart Actuator (B-SA)
Tested
PressureRatings
380CS and 380HS* Temp** F Temp F PSIG Type Range COMMENTS 40 400 380CS -20 > +180 Torlon Brgs & EPDM seals 60 400 380CS -20 > +180 Torlon Brgs & EPDM seals 80 400 380CS -20 > +180 Torlon Brgs & EPDM seals 100 380 380CS -20 > +180 Torlon Brgs & EPDM seals 120 365 380CS -20 > +180 Torlon Brgs & EPDM seals 140 350 380CS -20 > +180 Torlon Brgs & EPDM seals 160 340 380CS -20 > +180 Torlon Brgs & EPDM seals 180 320 380CS -20 > +180 Upper Limit for Torlon & EPDM 200 300 380HS +30 > +250 Ketron Brgs & Aflas seals*** 220 280 380HS +30 > +250 Ketron Brgs & Aflas seals 240 260 380HS +30 > +250 Ketron Brgs & Aflas seals 250 230 380HS +30 > +250 Ketron Brgs & Aflas seals *Rating is based on PvT of Brass RTD fitting. **Non-Freezing. ***Special: Ketron Brgs & EPDM seals for < +30F.
DM-DDB-B
Tested
Deletable
No No No
No No No
Accuracy
Device
Tested
FlowCalculation:1%ofRate Data Link Options TemperatureCalculation:1%9600, 19200, baud rates: MS/TP Slave BTUCalculation:1% 38400, 76800 bps
Window Size
(MS/TP product limited to 1)
Tested
Segmentation Capability OutputPulseWidth Type Segmentation Supported 10,50,150,200,or250mS Able to transmit segmented messages No Device Address Binding
Static Binding Supported Tested
N/A
MECHANICAL Mass:
PutImageofDimentionalDrawinghere
No
< 15lb
ELECTRICAL Inputs Power: 12-35VDC 9-28VAC rms Communication: Modbus BACnet Output Scaled Pulse: Open Drain MATERIALS Housing: Flow Sensor: Potting Material: Tee: Sensor Body Sizes Tee Sizes:
N/A
Character Sets
Character Sets supported Tested
ANSI X3.4
Badger and Data Industrial are registered trademarks of Badger Meter, Inc. Torlon is a registered trademark of Amco Performance Products. Ketron is a registered trademark of Polymer Corporation. Aflas is a registered trademark of Asahi Glass Co., Ltd.
Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists.