Вы находитесь на странице: 1из 12

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

G
Generator G1 1MVA / 450 V T"= 20 ms T'= 400 ms Tdc= 40 ms

G
Generator G2 1MVA / 450 V T"= 20 ms T'= 400 ms Tdc= 40 ms

G
Generator G3 1MVA / 450 V T"= 20 ms T'= 400 ms Tdc= 40 ms

Bus B1

Motor M1 212.5 Sh-kW T"=20.5 ms Tdc=10 ms

Motor M2 212.5 Sh-kW T"=20.5 ms Tdc=10 ms

Motor M3 212.5 Sh-kW T"=20.5 ms Tdc=10 ms

Motor M4 212.5 Sh-kW T"=20.5 ms Tdc=10 ms

Bus B2

Motor M5 212.5 Sh-kW T"=20.5 ms Tdc=10 ms

Motor M6 212.5 Sh-kW T"=20.5 ms Tdc=10 ms

Figure 1.

Network under study (IEC3632.eds)

This tutorial will illustrate the proper use and application of the EDSA IEC 363 short circuit program. The exercise in question will be based on the single line diagram shown in figure 1 above. Additional information on the IEC 363 short circuit program can be found in the EDSA manual and Quality Control/Assurance literature. In addition to these sources, the user is strongly encouraged to run the following examples: IEC3632.eds/IEC3634.eds/IEC363a.eds/IEC363b.eds/SingleG.eds. All these examples constitute the verification/validation files for the QA/QC documents and can be found in the EDSA Samples folder. The network shown in Figure 1 consists of three generators supplying power to six induction motors fed via busses B1 and B2. The data for the generators and motors is as follows: Generator Data (All): Rating: T: T: Tdc: 1 MVA / 450 Volts 20 ms 400 ms 40 ms Motor Data (All): Rating: 212.5 Sh-kW / 450 Volts T: 20.5 ms Tdc: 10 ms

Page 1

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

Step 1. Open the file named iec3632.eds.

Step 2. The file under study is shown here.

1.1

Invoke the EDSA program, and proceed to load the pre-built file named IEC3632.eds, as indicated in the above screen-capture.

Page 2

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

Step 1. Select Generator G1, as indicated here. Step 2. Select Edit Data.

Step 3. Enter the generators Short Circuit information as indicated here.

Step 4. Select Time.

Step 5. Enter the generators Time Constants data, as indicated here.

Step 7. Select OK.

Step 6. Select OK.

1.2

Next, proceed to assign the Generator Time constant information for Generator G1 as indicted in the above screen-capture. Repeat this step for Generators G2 and G3. Remember that this information is identical for all three generators, and can be found in Figure 1.

Page 3

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

Step 2. Select Edit Data.

Step 1. Select Motor M1, as indicated here.

Step 3. Enter the Motors Short Circuit information as indicated here.

Step 7. Select OK.

Step 4. Select Time Constants.

Step 5. Enter the Motors Time Constants data, as indicated here.

Step 6. Select OK.

1.3

Finally, proceed to assign the Motor Time Constant information for Motor M1 as indicted in the above screen-capture. Repeat this step for Motors M2 to M6. Remember that this information is identical for all six motors, and can be found in Figure 1.

Page 4

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

Step 1. Select SC IEC363.

1.4

Once all the data has been entered, proceed to invoke the EDSA IEC 363 program interface. Follow the instructions shown in the above screen-capture.

Page 5

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

Step 1. Select Options to define the scope of the study.

Step 3. When done, select OK.

Step 2. Select the required Report Sections, Scenarios, PreFault Voltages and Fault components as indicated here.

1.5

Before running the analysis, proceed to define the scope of the study and other reporting options, as indicated in the above screen-capture.

Page 6

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

Step 1. Select the Run command.

Step 2. Select OK.

1.6

Run the analysis, as indicated in the above screen-capture.

Page 7

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

1.7

Once the calculations are completed, the results are shown in the IEC 363 Output screen. With the aid of the tool bar menu, the user has the following options: Scroll up and down to read the results, Print the results, and Copy the results into the clipboard for importing purposes. From here, press DONE to return to the main menu.

Page 8

EDSA IEC 363 SHORT CIRCUIT ANALYSIS 1.8 Validation of the data obtained using the EDSA IEC363 Program. The tabulated results of the longhand calculation method is shown in the following tables:

Cycles 0 0.5 3

Seconds 0 0.00833 0.05

(I"d-I'd)-

t/0.015

(I'd-Id)-

t/0.361

Id 0.00000 0.00000 0.00000

Iac 9.42132 8.54626 6.61139

Idc

Ip

2.12752 1.40278 0.17464 Table 1.

7.29380 7.14348 6.43676

12.23510 25.558855 9.93495 3.50541 22.021183 12.855336

Single generator contribution to Bus B1 (kA)

Cycles 0 0.5 3

Seconds 0 0.00833 0.05

Iac 1.74130 1.15985 0.15192

Idc 2.70172 1.17455 0.01820

Table 2. Single motor contribution to Bus B1 (kA)

Cycles 0 0.5 3 Table 3.

Seconds 0 0.00833 0.05

Iac 2.87480 2.01984 0.34554

Idc 4.54388 1.22634 0.00175

Contribution of two motors on Bus B2 to Bus B1 (kA)

4 Motors to Bus1 Seconds 0 0.0083 0.05 Iac 6.96520 4.63940 0.60769 Idc 10.80687 7.12552 0.88708

3 Generators to Bus1 Iac 28.26396 25.63878 19.83418 Idc Iac

All to Bus1 Idc Ip

36.70529 35.22916 47.51216 97.333717 29.80484 30.27818 47.51216 90.331967 10.51624 20.44187 11.40332 40.312487

Table 4. Contribution of 4 Motors and 3 Generators to Bus B1

to Bus B1. Fault on Bus1 (kA)

Page 9

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

4 Motors to Bus1 Seconds 0 0.0083 0.05 Iac 6.96520 4.63940 0.60769 Idc 10.80687 7.12552 0.88708

3 Generators to Bus1 Iac 28.26396 25.63878 19.83418 Idc 36.70529 29.80484 10.51624

2 Motors on Bus2 Iac 2.87480 2.01984 0.34554 Idc 4.54388 1.22634 0.00175 Iac 38.10396 32.29801 20.78740

All to Bus1 Idc 52.05604 38.15670 11.40507 Ip 105.943 83.833 40.8029

Table 5.

Contribution of all motors and generators to Bus B1. Fault on Bus1 (kA)

K"(t) Gen 26.08974 Motor 4.63940 Total 30.72914 T"d 0.02026

Time Constant T'd 0.40000 Tdc 0.02782

Table 6. Time-Constant calculation table for Equivalent Generator on Bus B1

Cycles

Seconds

AC (kA) Total Table 5 Equiv.

35.22916 35.22916 0.0 0.0000 30.27818 30.27818 0.5 0.0083 20.44187 20.44187 3.0 0.0500 Table 7. Comparison of AC Currents with the Equivalent time Constant

Cycles

Seconds

DC (kA) Total Table 6 Equiv.

47.51216 47.51216 0.0 0.0000 36.93036 36.93036 0.5 0.0083 11.40332 11.40332 3.0 0.0500 Table 8. Comparison of DC Currents with the Equivalent time Constant

c3 0.11699

Z" 0.03642

Z' 0.05863

Z 0.38335

X" 0.03617

X' 0.05848

X 0.38333

R 0.00423

Table 9. Equivalent Generator impedance of 3 generators and 4 motors on Bus B1

Page 10

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

T"e 0.02822

T'e 0.82430

Tdce 0.00286

Z" 0.1064749

Z'

I"(kA) 13.30176

I'(kA) 11.74132

0.124396 0.434154

Table 10. Equivalent Generator impedance and Time Constant of 3 Generators and 4 Motors on Bus B2

Cycles 0 0.5 3

Seconds (I"d-I'd)-t/0.02822 0 0.00833 0.05 Table 11. 1.56045 1.16163 0.26420

(I'd-Id)-

t/0.8243

Id 0.00000 0.00000 0.00000

Iac

Idc

Ip 37.6230672 19.5287889 16.0011046

11.74132 11.62326 11.05028

13.30176 18.81153 12.78489 11.31449 1.44823 0.00000

AC and DC Components of Equivalent Generator Current for Remote Bus Fault

4 Motors to Bus1 Seconds 0 0.0083 0.05 Iac 6.96520 4.63940 0.60769 Idc 10.80687 7.12552 0.88708

3 Generators to Bus1 Iac 28.26396 25.63878 19.83418 Idc 36.70529 29.80484 10.51624

2 Motors on Bus2 Iac 2.87480 2.01984 0.34554 Idc 4.54388 1.22634 0.00175 Iac 38.10396 32.29801 20.78740

All to Bus1 Idc 52.05604 38.15670 11.40507 Ip 105.943 83.833 40.8029

Table 12. Contribution of all motors and generators to Bus B1 when a fault occurs on Bus B1 (kA)

Cycles 0 0.5 3

Seconds 0 0.00833 0.05

Iac 1.74654 1.16334 0.15238

Idc 2.70985 1.17809 0.01826

Table 13. Contribution of a motor on Bus B2

3 Generators 4 Motors Seconds 0 0.00833 0.05 Iac 13.30176 12.78489 11.31449 Idc 18.81153 1.44823 0.00000 Iac

2 Motors Idc 5.41969 2.35617 0.03652 Iac

All to Bus2 Idc Ip 47.9827215 25.1753854 16.4686136

3.49308 2.32668 0.30476

16.79484 24.23123 15.11156 11.61924 3.80441 0.03652

Table 14. Contribution of all motors and generators to Bus B2 when a fault occurs on Bus B2 (kA)

Page 11

EDSA IEC 363 SHORT CIRCUIT ANALYSIS

The following table shows a comparison of results obtained using longhand calculations documented in the standard and the EDSA IEC 363 program. Results have been tabulated for Busses B1 and B2.

Location

Result Type Iac

Cycles T/2 3T

Longhand 32298.0 20787.4 35729.4 10590.8 81405.7 39988.6 15111.0 11619.0 3800.0 36.520 25170.2 16468.3 Variance (%)

Program 32314 20797 35733 10590 81431.9 40001.4 15348 11389 3770 37 25475.34 16143.47 Min Max Average

Variance (%) 0.0495 0.0462 0.0101 0.0076 0.0322 0.0319 1.5684 1.9795 0.7895 1.3143 1.2124 1.9722 0.0076 1.9795 0.7512

B1

Idc Ip

T/2 3T T/2 3T T/2 3T T/2 3T T/2 3T

Iac B2 Idc Ip Ikd/Io= 0 IEC3632.Job 3

Sample
Version

Table 15.

Results Comparison

Analysis for variances of the results (Max=1.979%)


This variance is caused by the different options and calculation methods between the longhand and computerized method. The conclusions are as follows 1. The program uses the most precise method. This method is called Transfer Impedance and Additive Sources. Here, the contribution effect of all the active sources is individually and accurately accounted for. The Longhand method usually resorts to approximations, in order to simplify complex calculations. In the particular case of this example, the generators were modeled as an equivalent source. The greater the number of generators and motors the greater the error will be using the abovementioned approximation method. The greater the impedance of cables being dealt with, also the greater the error will be using the approximation method.

2. 3. 4.

Page 12

Вам также может понравиться