Electricity Meters IEC

INDUSTRIAL+COMMERCIAL
Landis+Gyr Dialog

ZMD300AT/CT TECHNICAL DATA


Frequency
Nominal Frequency fn tolerance 50 or 60 Hz 2%

Mesurement Accuracy
Accuracy ZMD310xT active energy to IEC 62053-21 reactive energy to IEC 62053-23 class 1 class 1

Measurement Behaviour
Starting Current ZxD310xT according to IEC 0.5 % In typical 0.3 % In The startup of the meter is controlled by the starting power and not by the starting current. Starting Power in M-Circuit nominal power x starting current single phase

Operating Behaviour
Voltage Failure (Power Down) bridging time according to IEC 0.5 s data storage after another 0.2 s switch off after approx. 2.5 s Voltage Restoration (Power Up) function standby 3 phases function standby 1 phase detection of energy direction + phase voltage

Voltage
Nominal Voltage Un ZMD310xT 3 x 110/190133/230 V 3 x 220/380240/415 V Voltage Range 80 % 115 % Un

after 2 s after 5 s after 2 to 3 s

Current
Base Current Ib selectable 5, 10, 20, 40 A

Power Consumption
Power Consumption per Phase in Voltage Circuit phase voltage 110 V 240 V active power (typical) 0.6 W 1.1 W apparent power (typical) 0.8 VA 1.5 VA Power Consumption per Phase in Current Circuit phase current 10 A apparent power (typical) 0.03 VA

Maximal Current Imax metrological selectable 40, 60, 80, 100, 120 A thermal 120 A Short Circuit 10 ms 5000 A

H 71 0200 0134 c en - ZMD300AT/CT - Technical Data

Landis+Gyr 1/4

Environmental Influences
Temperature Range operation storage to IEC 62052-11 -25 C +70 C -40 C +85 C

Display
Characteristics type LCD liquid crystal display digit size in value field 8 mm number of positions in value field up to 8 digit size in index field 6 mm number of positions in index field up to 8

Temperature Coefficent range von -25 C +70 C average value (typical) 0.012 % per K at cos=1 (from 0.05 Ib to Imax) 0.02 % per K at cos=0.5 (from 0.1 Ib to Imax) 0.03 % per K Impermeability according to IEC 60529 IP51

Inputs and Outputs


Control Inputs control voltage Us input current 100240 V AC < 2 mA ohmic at 230 V AC

Electromagnetic Compatibility
Electrostatic Discharges contact discharge Electromagnetic RF Fields 80 MHz 2 GHz Radio Interference Suppression according to IEC/CISPR 22 to IEC 61000-4-2 15 kV to IEC 61000-4-3 10 and 30 V/m

Output Contacts type voltage max current max switching freuquency Optical Test Output type number meter constant

solid state relay 12240 V AC/DC 100 mA 50 Hz

class B

Active and Reactive Energy red LED 2 selectable

Fast Transient Burst Test to IEC 61000-4-4 current and voltage circuits not under load 4 kV current and voltage circuits under load according to IEC 62053-21/22/23 2 kV auxiliary circuits > 40 V 1 kV Fast Transient Surge Test current and voltage circuits auxiliary circuits > 40 V to IEC 61000-4-5 4 kV 1 kV

Communication Interfaces
Optical Interface type max bit rate protocols according to IEC 62056-21 serial, bidirectional, half duplex 9600 bps IEC 62056-21 and dlms

Insulation Strenght
Insulation Strenght 4 kV @ 50 Hz during 1 min to IEC 62053-11 8 kV 6 kV 2

Communication Units Exchangeable communciation units for various applications.

Additional Power Supply (optional)


on extension board 025x nominal voltage range tolerance frequency max power consumption 100160 V DC 100240 V AC 80 115 % Un 50 or 60 Hz 2.2 W

Impulse Voltage 1.2/50s current and voltage circuits auxiliary circuits

Protection Class according to IEC 60050-131

Calendar Clock
Accuracy Backup Time (Power Reserve) with supercap loading time for max backup time with battery (optional) battery type < 5 ppm

Ripple Control Receiver (optional)


on extension board 043x or 003x nominal voltage frequency functional voltage Uf control frequency fs bandwidth 58 or 230 V 50 or 60 Hz 0.3 2.5 % Un 110 2000 Hz 0.6 6 % fs

> 20 days 300 h 10 years CR-P2

Landis+Gyr 2/4

H 71 0200 0134 c en - ZMD300AT/CT - Technical Data

Weight and Dimensions


Weight approx. 1.5 kg

Meter Dimensions (Standard Terminal Cover)


6.2 75

External Dimensions width height (with short terminal cover) height (with standard terminal cover) depth Suspension Triangle height (suspension eyelet open) height (suspension eyelet covered) widht Terminal Cover short standard long GSM ZxB-type 80 mm ZxB-type 110 mm Metcom3 adapter FTT4/5 adapter

177 244 281.5 75

mm mm mm mm

206

206 mm 190 mm 150 mm


150 177

40 60 60 80 110

no mm mm mm mm mm

free space free space free space free space free space free space

40

26

75

Terminal Layout
Inputs and/or output contacts of extension board Pulse inputs Communication interfaces Communication unit

Connections
Phase Connections type screw type terminals diameter for Imax 80 A 8.5 mm diameter for Imax > 80 A 9.5 mm minimal conductor cross section 4 mm2 2 max cross section cable 35 mm (up to 120 A) max cross section strand 25 mm2 (up to 80 A) screw head Pozidrive Combi No. 2 screw dimension M6 x 14 max screw head diameter 6.6 mm tightening torque < 3 Nm Other Connections type screwless spring-type terminal max current of voltage outputs 1A max voltage of inputs 250 V

U1

U2 U3

Control inputs and output contacts Voltage outputs

L1

L2

L3

Phase connections

Terminal Dimensions
8 or .5

9.5

19.75

14.5 14.5 14.5 14.5 14.5 14.5

12

Spacings of terminal openings Spacings of terminal stampings for smaller conductors

19

16

13

16

13

16

13

13.5

Material
Housing The meter housing is made of polycarbonate which is partly glass-fibre reinforced.

H 71 0200 0134 c en - ZMD300AT/CT - Technical Data

Landis+Gyr 3/4

15.3

281.5

190

Type Designation Network Type ZFD 3-phase 3 wire network (F-circuit) ZMD 3-phase 4 wire network (M-circuit) Connection Type 3: Direct connection 4: Transformer operated Accuracy Class 10: Active energy class 1 according to IEC 05: Active energy class 0.5 S according to IEC Measured Quantities C: Active and reactive energy A: Active energy Construction R: With integrated interface T: With exchangeable communication units

ZMD 4 10 C R 44 4207 . c1

Tariffication 21: Energy rates, external rate control via control inputs 24: Energy rates, internal rate control via time switch (additionally possible via control inputs) 41: Energy and demand rates, external rate control via control inputs 44: Energy and demand rates, internal rate control via time switch (additionally possible via control inputs) All versions with 3 control inputs and 2 output contacts Additional Functions 0000: 0600: 2400: 4200: 0030: 0430: 0250: no additional functions 6 outputs 2 control inputs, 4 outputs 4 control inputs, 2 outputs integrated ripple control receiver 4 outputs, integrated ripple control receiver 2 outputs, additional power supply 0007: + load profile 0607: + load profile 2407: + load profile 4207: + load profile 0037: + load profile 0437: + load profile 0257: + load profile

Integrated Interface (R-Types only) c1: RS232 interface c2: RS485 interface c3: CS interface

Landis+Gyr Ltd. Feldstrasse 1 CH 6301 Zug Switzerland Phone: +41 41 724 41 41 www.landisgyr.com

Landis+Gyr 4/4

H 71 0200 0134 c en - ZMD300AT/CT - Technical Data