Contactors
Contactors and reversing contactors types LCp-K and LPp-K
Environment
Conforming to standards Approvals Operating positions p p LCp and LPp-K06 to K12 Vertical axis Horizontal axis IEC/EN 60947-1, IEC/EN 60947-4-1, NF C 63-110, VDE 0660 UL, CSA, DEMKO, NEMKO, SEMKO, FI
Without derating
Without derating
1 80
2.2
Cabling Screw clamp connections Solid conductor Flexible cable without cable end Flexible cable with cable end Spring terminal connections Faston connectors Solder pins for printed circuit board Tightening torque Terminal referencing Rated insulation voltage (Ui) Solid conductor Flexible conductor without cable end Clip With locating device between power and control circuits Philips head n 2 and 6 Conforming to standards EN 50005 and EN 50012 Conforming to IEC/EN 60947-4-1 Conforming to VDE 0110 gr C Conforming to NF C 20-040 Conforming to CSA 22-2 n 14, UL 508 Rated impulse withstand voltage (Uimp) Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude Vibration resistance 5 ... 300 Hz Flame resistance Conforming to IEC 68 (DIN 50016) Conforming to VDE 0106 Storage Operation Without derating Contactor open Contactor closed Conforming to UL 94 Conforming to NF F 16-101 and 16-102 Shock resistance (1/2 sine wave, 11 ms) Safe circuit separation Contactor open Contactor closed Conforming to VDE 0106 and IEC 536 C C m V V V V kV N.m mm2 mm2 mm2 mm2 mm2 mm
Possible positions for LCp-K only. Contactor energisation voltage: 0.85 Uc Max to Min Max IEC/EN 60947 1 x 1.5 2x4 1 x 4 + 1 x 2.5 1 x 0.75 1 x 0.34 1 x 0.75 1 x 0.75 2x4 1 x 1.5 + 1 x 2.5 1 x 1.5 1 x 1.5 2 x 2.5 1 x 1.5 + 1 x 2.5 2 x 1.5 2 x 1.5
2 x 2.8 or 1 x 6.35 4 mm x 35 microns 0.81.3 Up to 5 contacts 690 750 690 600 8 TC (Klimafest, Climateproof) Protection against direct nger contact - 50+ 80 - 25+ 50 2000 2 gn 4 gn Self-extinguishing materials V1 Conforming to requirement 2 10 g 15 g VLSV (Very Low Safety voltage), up to 400 V
Characteristics
Contactors
Contactors and reversing contactors types LCp-K and LPp-K
Pole characteristics
Conventional thermal current (Ith) Rated operational frequency Frequency limits of operational current Rated operational voltage (Ue) Rated making capacity I rms to NF C 63-110 and IEC/EN 60947-4-1 p p p p LCp-K06, LPp-K06, LCp-K09, LPp-K09 p p LCp-K12, LPp-K12 For ambient temperature 50 C A Hz Hz V A A V I rms to NF C 63-110 and IEC/EN 60947-4-1 p p p p LCp-K06, LPp-K06, LCp-K09, LPp-K09 p p LCp-K12, LPp-K12 Permissible short time rating In free air for a time t from cold state ( 50 C) p p p p LCp-K06, LPp-K06, LCp-K09, LPp-K09 p p LCp-K12, LPp-K12 Short-circuit protection Average impedance per pole Utilisation in category AC-1 resistive circuits, heating, lighting (Ue 440 V) gG fuse U 440 V (aM fuse, see page 2/46) At Ith and 50 Hz Maximum rated operational current for a temperature 50 C Maximum rated operational current for a temperature 70 C Rated operational current limits in relation to on-load factor and operating frequency A A A m A A A A A 20 50/60 Up to 400 690 110 144 220/ 240 110 1s 90 115 25 3 20 16 for Ue only On-load factor 90% 300 op. cycles/hour 120 op. cycles/hour 30 op. cycles/hour Increase in operational current by paralleling of poles 60 % 13 15 19 30 % 15 18 20 18 19 20 380/ 400 110 5s 85 105 415 110 10 s 80 100 440 110 110 30 s 60 75 500 80 80
1 min
2
660/ 690 70 70
3 min 15 min
2.2
45 55
40 50
20 25
Apply the following coefcients to the current values above. These take into account the often unbalanced current distribution between poles 2 poles in parallel: K = 1.60 3 poles in parallel: K = 2.25 4 poles in parallel: K = 2.80
Voltage 50 or 60 Hz V
115 1-ph
p p LCp-K06, LPp-K06 kW p p LCp-K09, LPp-K09 kW p p LCp-K12, LPp-K12 kW % utilisation of operational power in relation to the maximum operating rate
0.37 0.55
5.5/ 4 4 (480)
900 75%
Characteristics (continued)
Contactors
Contactors and reversing contactors types LCp-K and LPp-K
2.2
Heat dissipation Operating time at 20 C and at Uc Between coil energisation and: - opening of the N/C contacts - closing of the N/O contacts Between coil de-energisation and: - opening of the N/O contacts - closing of the N/C contacts Maximum immunity to micro-breaks Maximum operating rate Mechanical durability at Uc In millions of operating cycles In operating cycles per hour 50/60 Hz coil c coil
1.3
ms ms
515 1020
2535 3040
2535 3040
ms ms
1020 1525
30 40
10 15
ms
2 3600 10 5
2 3600 10 5
2 3600 10 5
(1) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LAF-KE1UG (130250 V), see page 2/38.
Characteristics
Contactors
Contactors and reversing contactors types LCp-K and LPp-K
2.2
d.c. supply, category DC-13 Electrical durability (valid up to 1200 operating cycles per hour), on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load. V W W W W 24 120 55 15 720 48 80 38 11 600 110 60 30 9 400 220 52 28 8 300 440 51 26 7 230 600 50 25 6 200
1 million operating cycles 3 million operating cycles 10 million operating cycles Occasional making capacity
1 Breaking limit of contacts valid for: - maximum of 50 operating cycles at 10 s intervals (breaking current = making current x cos 0.7). 2 Electrical durability of contacts for: - 1 million operating cycles (2a) -3 million operating cycles (2b) -10 million operating cycles (2c). 3 Breaking limit of contacts valid for: - maximum of 20 operating cycles at 10 s intervals with current passing for 0.5 s per operating cycle. 4 Thermal limit.
Power broken in VA 16 000 10 000 8000 6000 5000 4000 3000 2000 1000 800 600 500 400 300 200 100 80 60 40 24 48 110 120 220 380 500 440 690 V
Power broken in W
3
300 200 100 80 60 50 40 30 20
250
2a 2b
2a
50
2c 2b 2c
20 12 24 48 110 220 440 600 V 10 8 6
References
Contactors
Contactors for motor control, 6 to 12 A in utilisation category AC-3 Control circuit: a.c.
2
LC1-K0610pp
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 220 V 380 V 440/500 V 240 V 415 V 660/690 V kW kW kW Screw clamp connections 1.5 2.2 3
N/O N/C
kg
1 1 1
2.2
2.2
5.5
12
Spring terminal connections 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440) 5.5 (440) 12 1 1 1 1
p LC1-K06103pp p LC1-K06013pp p LC1-K09103pp p LC1-K09013pp p LC1-K12103pp p LC1-K12013pp
LC1-K09103pp
(1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Contactors LC1K (0.81.15 Uc) (0.851.1 Uc) Volts a 12 20 24(3) 36 42 48 110 115 120 127 200/ 220/ 230 230/ 256 277 380/ 400 50/60 Hz 208 230 240 400 Code J7 Z7 B7 C7 D7 E7 F7 FE7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 400/ 440 480 500 575 600 660/ Volts a 50/60 Hz 415 690 Code N7 R7 T7 S7 SC7 X7 Y7 Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72 (2) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References
Contactors
Contactors for motor control, 6 to 12 A in utilisation category AC-3 Control circuit: a.c.
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 LC1-K06107pp 220 V 380 V 440/500 V 240 V 415 V 660/690 V kW kW kW
Basic reference. Complete with code indicating control circuit voltage (1) (2)
Weight
2
kg
N/O N/C
Faston connectors, 1 x 6.35 or 2 x 2.8 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440) 5.5 (440) 12 1 Solder pins for printed circuit boards 1.5 2.2 3 6 1 2.2 LC1-K06105pp 3 5.5 4 (> 440) 5.5 (440) 12 1 1 1
p LC1-K09015pp p LC1-K12105pp p LC1-K12015pp
1 1 1
0.180
2.2
0.180 0.180 0.180 0.180 0.180
(1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Contactors LC1K (0.81.15 Uc) (0.851.1 Uc) Volts a 12 20 24(3) 36 42 48 110 115 120 127 200/ 220/ 230 230/ 256 277 380/ 400 50/60 Hz 208 230 240 400 Code J7 Z7 B7 C7 D7 E7 F7 FE7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 400/ 440 480 500 575 600 660/ Volts a 50/60 Hz 415 690 Code N7 R7 T7 S7 SC7 X7 Y7 Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72 (2) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References (continued)
Contactors
Contactors for motor control, 6 to 12 A in utilisation category AC-3 Control circuit: a.c.
2
LC7-K06105pp
Weight
kg
2.2
1.5
2.2
1 1 1
2.2
5.5
12
Faston connectors, 1 x 6.35 or 2 x 2.8 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440) 5.5 (440) 12 1 Solder pins for printed circuit boards 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440) 5.5 (440) 12 1 1 1
p LC7-K06105pp p LC7-K06015pp p LC7-K09105pp p LC7-K09015pp p LC7-K12105pp
1 1 1
p LC7-K12015pp 0.255 1 (1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Contactors LC7-K (0.851.1 Uc) Volts a 24 42 48 110 115 220 230/ 50/60 Hz 240 Code B7 D7 E7 F7 FE7 M7 U7 (2) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References
Contactors
Contactors for motor control, 6 to 12 A in utilisation category AC-3 Control circuit: d.c.
3-pole contactors
- Contactor selection according to the utilisation category, see pages 1/14 to 1/21. - Mounting on 35 mm 7 rail or 4 screw xing. - Screws in open ready-to-tighten position. - Auxiliary contact blocks and accessories, see pages 2/36 to 2/39. Standard power ratings Rated Instantaneous Basic reference. of 3-phase motors operational auxiliary Complete with code 50/60 Hz in category voltage contacts indicating control AC-3 in AC-3 circuit voltage (1) up to 220 V 380 V 440/500 V 440 V 240 V 415 V 660/690 V kW kW kW A N/O N/C Screw clamp connections 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440 V) 5.5 (440 V) 12 1 Spring terminal connections 1.5 2.2 3 6 1 LP1-K06107pp 2.2 4 4 9 1 3 5.5 4 (> 440 V) 5.5 (440 V) 12 1 Faston connectors, 1 x 6.35 or 2 x 2.8 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440 V) 5.5 (440 V) 12 1 Solder pins for printed circuit boards 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440 V) 5.5 (440 V) 12 1 1 1
p LP1-K06105pp p LP1-K06015pp p LP1-K09105pp p LP1-K09015pp p LP1-K12105pp
Weight
2
kg
LP1-K0610pp
1 1 1
2.2
1 1 1
1 1 1
LP1-K12015pp 0.255 1 (1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Contactors LP1-K (0.81.15 Uc) 12 20 24(2) 36 48 60 72 100 110 125 155 174 200 220 230 240 250 Volts c Code JD ZD BD CD ED ND SD KD FD GD PD QD LD MD MPD MUD UD Coil with suppression device available: add 3 to the code required. Example: JD3. (2) When connecting an electronic sensor or timer in series with the coil of the contactor, select a 20 V coil (a control circuit voltage code Z7, c control circuit voltage code ZD) so as to compensate for the incurred voltage drop.
References
Contactors
K 3 and 4-pole contactors for control in utilisation category AC-1 Control circuit: a.c.
2
LC1-K09004ii
Basic reference. Complete with code indicating control circuit voltage (1)
Weight
kg 0.225 0.225 0.180 0.180 0.225 0.225 0.180 0.180 0.255 0.255 0.210 0.210
2.2
Faston connectors 1 x 6.35 or 2 x 2.8
LC7-K090047ii
2 2 LC7-K090085ii (1) Standard control circuit voltages, see page opposite. (2) To order a spring terminal version, add 3 immediately before the coil code. Example: LC1-K09103ii.
References
Contactors
K 3 and 4-pole contactors for control in utilisation category AC-1 Control circuit: d.c.
Basic reference. Complete with code indicating control circuit voltage (1)
Weight
2
kg 0.225 0.225 0.225 0.225 0.225 0.225 0.225 0.225 0.255 0.255 0.255 0.255
LP1-K09004ii
LP1-K0910ii LP1-K0901ii LP1-K09004ii LP1-K09008ii LP1-K09107ii LP1-K09017ii LP1-K090047ii LP1-K090087ii LP1-K09105ii LP1-K09015ii LP1-K090045ii LP1-K090085ii
2.3
(1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Contactors LC1-K (0.81.15 Uc) (0.851.1 Uc) Volts c 12 20 24 36 42 48 110 120 127 200/ 220/ 230 230/ 256 277 380/ 400 50/60 Hz 208 230 240 400 Code J7 Z7 B7 C7 D7 E7 F7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 400/ 440 500 575 600 660/ Volts c 50/60 Hz 415 690 Code N7 R7 S7 SC7 X7 Y7 Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72 Contactors LC7-K (0.851.1 Uc) Volts c 24 42 48 110 50/60 Hz Code B7 D7 E7 F7 220 M7 230/ 240 U7 220 MD 230 240 250 MPD MUD UD
Contactors LP1-K (0.81.15 Uc) Volts a 12 20 24 36 48 60 72 100 110 125 155 174 200 Code JD ZD BD CD ED ND SD KD FD GD PD QD LD Coil with integral suppression device available: add 3 to the code required. Example: JD3
(2) To order a spring terminal version, add 3 immediately before the coil code. Example: LP1-K09103ii.
References
Contactors
Reversing contactors for motor control 6 to 12 A in utilisation category AC-3 Control circuit: a.c.
2
LC2-K0610pp
Weight
kg
2.2
1.5
2.2
1 1 1
2.2
5.5
12
Spring terminal connections 1.5 2.2 3 6 1 2.2 4 4 9 1 3 5.5 4 (> 440) 5.5 (440) 12 1 1 1 1
p LC2-K06103pp p LC2-K06013pp p LC2-K09103pp p LC2-K09013pp p LC2-K12103pp p LC2-K12013pp
(1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LC2-K (0.81.15 Uc) (0.851.1 Uc) Volts a 12 20 24 36 42 48 110 115 120 127 200/ 220/ 230 230/ 256 277 380/ 400 50/60 Hz 208 230 240 400 Code J7 Z7 B7 C7 D7 E7 F7 FE7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 400/ 440 480 500 575 600 660/ Volts a 50/60 Hz 415 690 Code N7 R7 T7 S7 SC7 X7 Y7 Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72 (2) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References
Contactors
Reversing contactors for motor control 6 to 12 A in utilisation category AC-3 Control circuit: a.c.
Weight
LC2-K06107pp
kg
1 1 1
2.2
(1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LC2-K (0.81.15 Uc) (0.851.1 Uc) Volts a 12 20 24 36 42 48 110 115 120 127 200/ 220/ 230 230/ 256 277 380/ 400 50/60 Hz 208 230 240 400 Code J7 Z7 B7 C7 D7 E7 F7 FE7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 400/ 440 480 500 575 600 660/ Volts a 50/60 Hz 415 690 Code N7 R7 T7 S7 SC7 X7 Y7 Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72 (2) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References (continued)
Contactors
Reversing contactors for motor control 6 to 12 A in utilisation category AC-3 Control circuit: a.c.
2
LC8-K06105pp
Weight
2.2
kg
1 1 1
1 1 1
p LC8-K12015pp 0.520 1 (1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LC8-K (0.851.1 Uc) 24 42 48 110 115 220 230/ Volts a 50/60 Hz 240 Code B7 D7 E7 F7 FE7 M7 U7 (2) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References
Contactors
Reversing contactors for motor control 6 to 12 A in utilisation category AC-3 Control circuit: d.c.
Weight
LP2-K0610pp
kg
2.2
Spring terminal connections 1.5 LP2-K06107pp 2.2 3 4 5.5 4 4 (> 440) 5.5 (440) 9 12 2.2 3 6 1 1 1 1 1 1
p LP2-K06103pp p LP2-K06013pp p LP2-K09105pp p LP2-K09015pp p LP2-K12105pp p LP2-K12015pp
Faston connectors, 1 x 6.35 or 2 x 2.8 1.5 2.2 3 2.2 4 5.5 3 4 4 (> 440) 5.5 (440) 6 9 12 1 1 1 1 1 1
LP2-K06107pp LP2-K06017pp LP2-K09107pp LP2-K09017pp LP2-K12107pp LP2-K12017pp
Solder pins for printed circuit boards 1.5 2.2 3 2.2 4 5.5 3 4 6 9 1 1 1 1
LP2-K06105pp LP2-K06015pp LP2-K09105pp LP2-K09015pp
4 (> 440) 12 1 LP2-K12105pp 0.520 LP2-K12015pp 0.520 5.5 (440) 1 (1) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LP2-K (0.81.15 Uc) 12 20 24 36 48 60 72 100 110 125 155 174 200 220 230 240 250 Volts c Code JD ZD BD CD ED ND SD KD FD GD PD QD LD MD MPD MUD UD Coil with integral suppression device available: add 3 to the code required. Example: JD3. (2) When connecting an electronic sensor or timer in series with the coil of the contactor, select a 20 V coil (a control circuit voltage code Z7, c control circuit voltage code ZD) so as to compensate for the incurred voltage drop.
References
Contactors
Reversing contactors for control in utilisation category AC-1, 20 A Control circuit: a.c.
a
(1)
- Warning: reversing contactors LC2-K0910pp and LC2-K0901pp are pre-wired for reverse motor operation as standard. - Reversing contactor selection according to utilisation category, see pages 1/12 and 1/13. - Integral mechanical interlock. It is essential to link the contacts of the electrical interlock. - Mounting on 35 mm 7 or 4 mm screw xing. - Screws in open ready-to-tighten position. - Auxiliary contact blocks and accessories, see pages 2/36 to 2/39. Non inductive loads category AC-1 Maximum current at 50 C A Number of poles Instantan. auxiliary contacts Basic reference. Complete with code indicating control circuit voltage (2) Weight
N/O N/C
kg
2.2
p LC2-K0910pp
or LC2-K1210pp 3 1
LC2-K0901pp
or LC2-K1201pp 4
LC2-K09004pp
or LC2-K12103pp 3 1
LC2-K09013pp
or LC2-K12013pp 4
LC2-K090043pp
or LC2-K120043pp
(1) Choice between 9 and 12 A depends on number of operating cycles, see AC-1 curve on page 1/12. (2) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LC2-K (0.81.15 Uc) (0.851.1 Uc) Volts a 12 20 24(3) 36 42 48 110 115 120 127 200/ 220/ 230 230/ 256 277 380/ 400 50/60 Hz 208 230 240 400 Code J7 Z7 B7 C7 D7 E7 F7 FE7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 400/ 440 480 500 575 600 660/ Volts a 50/60 Hz 415 690 Code N7 R7 T7 S7 SC7 X7 Y7 Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72 (3) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References
Contactors
Reversing contactors for control in utilisation category AC-1, 20 A Control circuit: a.c.
(1)
- Warning: reversing contactors LC2-K0910pp and LC2-K0901pp are pre-wired for reverse motor operation as standard. - Reversing contactor selection according to utilisation category, see pages 1/12 and 1/13. - Integral mechanical interlock. It is essential to link the contacts of the electrical interlock. - Mounting on 35 mm 7 or 4 mm screw xing. - Screws in open ready-to-tighten position. - Auxiliary contact blocks and accessories, see pages 2/36 to 2/39. LC2-K090045pp Non inductive loads category AC-1 Maximum current at 50 C A Faston connectors, 1 x 6.35 or 2 x 2.8 20 3 1
LC2-K09107pp
Number of poles
Basic reference. Complete with code indicating control circuit voltage (2)
Weight
N/O N/C
kg
2.2
0.370 0.370 0.370 0.370 0.370 0.370
or LC2-K12107pp 3 1
LC2-K09017pp
or LC2-K12017pp 4
LC2-K090047pp
or LC2-K12105pp 3 1
LC2-K09015pp
or LC2-K12015pp 4
LC2-K090045pp
or LC2-K120045pp
(1) Choice between 9 and 12 A depends on number of operating cycles, see AC-1 curve on page 1/12. (2) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LC2-K (0.81.15 Uc) (0.851.1 Uc) Volts a 12 20 24(3) 36 42 48 110 115 120 127 200/ 220/ 230 230/ 256 277 380/ 400 50/60 Hz 208 230 240 400 Code J7 Z7 B7 C7 D7 E7 F7 FE7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 400/ 440 480 500 575 600 660/ Volts a 50/60 Hz 415 690 Code N7 R7 T7 S7 SC7 X7 Y7 Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72 (3) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References (continued)
Contactors
Reversing contactors for control in utilisation category AC-1, 20 A Control circuit: a.c.
a
(1)
2
LC8-K09105pp
- Warning: reversing contactors LC2-K0910pp and LC2-K0901pp are pre-wired for reverse motor operation as standard. - Reversing contactor selection according to utilisation category, see pages 1/12 and 1/13. - Integral mechanical interlock. It is essential to link the contacts of the electrical interlock. - Mounting on 35 mm 7 or 4 mm screw xing. - Screws in open ready-to-tighten position. - Auxiliary contact blocks and accessories, see pages 2/36 to 2/39. Non inductive loads category AC-1 Maximum current at 50 C A Screw clamp connections 20 3 1
LC8-K0910pp
Number of poles
Basic reference. Complete with code indicating control circuit voltage (2) (3)
Weight
2.2
N/O N/C
kg
or LC8-K1210pp 3 1
LC8-K0901pp
or LC8-K1201pp 4
LC8-K09004pp
or LC8-K12107pp 3 1
LC8-K09017pp
or LC8-K12017pp 4
LC8-K090047pp
or LC8-K12105pp 3 1
LC8-K09015pp
or LC8-K12015pp 4
LC8-K090045pp
or LC8-K120045pp 0.520 (1) Choice between 9 and 12 A depends on number of operating cycles, see AC-1 curve on page 1/12. (2) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LC8-K (0.851.1 Uc): coil with integral rectifier and suppression device as standard. Volts a 24 42 48 110 115 220 230/ 50/60 Hz 240 Code B7 D7 E7 F7 FE7 M7 U7 (3) For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4-KE1FC (50129 V) or LA4-KE1UG (130250 V), see page 2/38.
References
Contactors
Reversing contactors for control in utilisation category AC-1, 20 A Control circuit: d.c.
Number of poles
Basic reference. Complete with code indicating control circuit voltage (2) (3)
Weight
N/O N/C
kg
2.2
1 1
LP2-K0910pp or LP2-K1210pp LP2-K0901pp or LP2-K1201pp LP2-K09004pp or LP2-K12004pp
LP2-K090045pp 0.520 0.520 or LP2-K120045pp (1) Choice between 9 and 12 A depends on number of operating cycles, see AC-1 curve on page 1/12. (2) Standard control circuit voltages (for other voltages, please call our Customer information centre on 0870 608 8 608). Reversing contactors LP2-K (0.81.15 Uc) 12 20 24(3) 36 48 60 72 100 110 125 155 174 200 220 230 240 250 Volts c Code JD ZD BD CD ED ND SD KD FD GD PD QD LD MD MPD MUD UD Coil with suppression device available: add 3 to the code required. Example: JD3 (3) When connecting an electronic sensor or timer in series with the coil of the contactor, select a 20 V coil (a control circuit voltage code Z7, c control circuit voltage code ZD) in order to compensate for the incurred voltage drop
2
LC1, LC7, LP1-K
2.2
LC1, LP1-K
2/36
Schneider Electric
References
Contactors
Contactors and reversing contactors, types LCp-K and LPp-K Instantaneous and time delay auxiliary contacts
N/O N/C Screw clamp LC1, LC2 LC7, LC8 LP1, LP2 3 or 4-pole 2 1 4 3 2 1 2 1 4 3 2 1 2 1 4 3 2 1 2 1 1 2 3 4 2 1 1 2 3 4 2 1 1 2 3 4
LA1-KN20 LA1-KN02 LA1-KN11 LA1-KN40 LA1-KN31 LA1-KN22 LA1-KN13 LA1-KN04 LA1-KN203 LA1-KN023 LA1-KN113 LA1-KN403 LA1-KN313 LA1-KN223 LA1-KN133 LA1-KN043 LA1-KN207 LA1-KN027 LA1-KN117 LA1-KN407 LA1-KN317 LA1-KN227 LA1-KN137 LA1-KN047
kg 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0,045 0,045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045
Spring terminal
2.2
With terminal referencing conforming to standard EN 50012. Clip-on front mounting, 1 block per contactor Screw clamp with terminal referencing conforming to standard EN 50012 LC1, LC2 LC7, LC8 LP1, LP2 3-pole + N/O LC1, LC2 LC7, LC8 LP1, LP2 4-pole 1 3 2 1 1 2 2 1 1 2 3 1 2
LA1-KN02M LA1-KN11M LA1-KN31M LA1-KN22M LA1-KN13M LA1-KN11P LA1-KN22P
Clip-on front mounting, 1 block per contactor Voltage Type Timing range
Composition
Reference
Weight
V a or c 2448 On-delay
s 130
C/O 1
LA2-KT2E
kg 0.040
a 110240
On-delay
130
LA2-KT2U
0.040
References
Contactors
Contactors and reversing contactors, types LCp-K and LPp-K Suppressor modules incorporating LED indicator
Mounting and connection Clip-on xing on the front of contactors LC1 and LP1, with locating device. No tools required.
Sold in lots of 5
Unit reference
LA4-KE1B
Weight kg 0.010
a and c 3248 V
LA4-KE1E
0.010
0.010
2.2
a and c 201250 V
LA4-KE1UG
0.010
LA4-KC1B
0.010
c 3248 V
LA4-KC1E
0.010
RC (3)
a 220250 V
LA4-KA1U
0.010
(1) Protection by limitation of the transient voltage up to 2 Uc maximum. Maximum reduction of transient voltage peaks. Slight time delay on drop-out (1.1 to 1.5 times the normal time). (2) No overvoltage or oscillation frequency. Polarised component. Slight time delay on drop-out (1.1 to 1.5 times the normal time). (3) Protection by limitation of the transient voltage up to 3 Uc maximum and limitation of the oscillation frequency. Slight time delay on drop-out (1.2 to 2 times the normal time).
References
Contactors
Contactors and reversing contactors, types LCp-K and LPp-K Accessories
Unit reference
LA9-D973
Weight kg 0.025
2
For xing on 2 4 rails 110/120 mm xing centres
1 DX1-AP25
0.065
Marker holder
Clip-on
100
LA9-D90
0.001
2.2
DX1-AP25
Clip-in markers
25
p AB1-Rp (2)
0.002
25
p AB1-Gp (2)
0.002
Cabling accessories
Description Paralleling links Application For 2 poles With screw clamp terminals
Sold in lots of 4
Unit reference
LA9-E01
Weight kg 0.010
For 4 poles
LA9-E02
0.015
100
LA9-K0969
0.010
100
LA9-K0970
0.010
(1) Order 1 mounting plate for xing a contactor and 2 mounting plates for xing a reversing contactor. (2) Complete the reference by replacing the p with the required character.
Dimensions, mounting
Contactors
Contactors, types LCp-K and LP1-K
58
50
2
35 57 = 35 45 = =
58
57
45
DX1-AP25
DZ5-ME5
2.2
5
120
50
57
21
35 45
57
27
45
58
50
45
A2
53
27
38
38 38 57
On contactor
25
22
6 22 57
58
58
110
Schemes
Contactors
Contactors, types LCp-K and LPp-K
A1
A2
14
A2
A1
T1/2
T1/2
T2/4
T3/6
T2/4
T3/6
A2
T3/6
T1/2
T2/4
T4/8
A2
R2
R4
2.2
Instantaneous auxiliary contacts LA1-K For contactors LCp-K and LPp-K 2 N/O 2 N/C LA1-KN20 LA1-KN02 LA1-KN207 LA1-KN027
51/NC 53/NO 63/NO 61/NC
52
54
64
62
54
62
A2
54
62
72
54
62
72
54
64
74
84
84
82
52 21/NC 22
54
62
74
Terminal referencing conforming to standard EN 50012 For 3-pole contactors 2 N/C 1 N/O + 1 N/C LA1-KN02M LA1-KN11M
21/NC 31/NC 33/NO 21/NC
84
22
32
22
34
22
32
44
22
32
42
14
22
14
22
32
Electronic time delay auxiliary contact blocks LA2-KT For contactors LCp-K and LPp-K 1 C/O
44
54
LA4-KE
A1
16
A2
15
18
+
Selection: pages 1/12 to 1/35
Schneider Electric
54
62
Dimensions, mounting
Contactors
Reversing contactors, types LCp-K and LP2-K
58
50
35
57
80 90
58
57
90
On one asymmetrical rail DZ5-MB with 2 clip-on mounting plates LA9-D973 or on 2 mounting plates DX1-AP25. 2 x LA9-D973 2 x DX1-AP25
DZ5-ME5 5 50
2.2
57
21
35 90
57
27
120
90
On printed circuit board for reversing contactors or 2 contactors mounted side by side
8,65
===
===
8,65
A1 58 A2
A1 50 A2 53
45
45
38
38 38 57
27
On reversing contactors
25
22
6 22 57
58
58
110
Schemes
Contactors
3 and 4-pole reversing contactors, types LCp-K and LPp-K
3-pole reversing contactors LC2-K, LC8-K, LP2-K With screw clamp terminals 3 P + N/O
3/L2
5/L3
3/L2
1/L1
13/NO
1/L1
5/L3
13/NO
21/NC
1/L1
5/L3
A1
21/NC 22
A1
A1
A2
A2
A2
14
14
T3/6
T1/2
T2/4
T1/2
T3/6
T1/2
T2/4
T1/2
T2/4
T3/6
T2/4
T3/6
A2
22
A1
With Faston connectors or solder pins (printed circuit board) 3 P+ N/O 3 P + N/C
5/L3 3/L2 3/L2 3/L2 5/L3 5/L3 3/L2 1/L1 1/L1 1/L1 13/NO 13/NO 21/NC 1/L1 5/L3 21/NC
A1
A1
A1
A2
A2
A2
A2
14
22
A1
A2
T3/6
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
T1/2
T2/4
T1/2
4-pole reversing contactors LC2-K, LC8-K, LP2-K With screw clamp terminals 4P
1N 1/L1 1/L2 1/L3 2/L1 2/L2 2/L3 2N
T2/4
T3/6
2.2
Integral suppression device LC8-K
14
A2
A1
22
L1
L2
L3
Instantaneous auxiliary contact blocks LA1-K For contactors LCp-K and LP2-K 2 N/O 2 N/C LA1-KN20 LA1-KN02 LA1-KN207 LA1-KN027
53/NO 63/NO 51/NC 61/NC
54
64
52
62
For contactors LCp-K, LP2-K 4 N/O 3 N/O + 1 N/C LA1-KN40 LA1-KN31 LA1-KN407 LA1-KN317
53/NO 73/NO 53/NO 63/NO 73/NO 83/NO 83/NO 61/NC
54
62
A2
62
54
74
54
64
74
84
84
54
62
72
84
52
54
62
72
Auxiliary contacts with terminal referencing conforming to standard EN 50012 see page 2/41 Electronic time delay contact blocks Suppressor modules LA2-KT LA4-KC For contactors LCp-K and LPp-K 1 C/O
A1
16 18
LA4-KE
A2
15
+
Selection: pages 1/12 to 1/35
Schneider Electric
82
62