ELECTRICAL INSTALLATION CERTIFICATE

Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations

Certificate Reference:

0039293

1. DETAILS OF THE CLIENT


Client Address:

P J Carey (contactors) Ltd, Carey House, Great Central Way, Wembley Middlesex, HAR OHR
The installation is: New An addition An alteration

2. DETAILS OF THE INSTALLATION


Installation Address: Extent of the installation covered by this certificate:

Retained Building, Kings Yard energy centre, Olympic Park Site, London Landlords Power and lighting

N/A N/A

3. DESIGN
I/We, being the person(s) responsible for the design of the electrical installation (as indicated by my/our signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying out the design, hereby CERTIFY that the design work for which I/we have been responsible is, to the best of my/our knowledge and belief, in accordance with BS 7671:

2008

amended to

2011

except for the departures, detailed as follows:

Details of departures from BS 7671, as amended (Regulations 120.3, 133.5):

None

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the DESIGN of the installation: Name: Position: Signature: Date:

Where there is divided responsibility for the design: Name: Position: Signature: Date:

4. CONSTRUCTION
I/We, being the person(s) responsible for the construction of the electrical installation (as indicated by my/our signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying out the construction, hereby CERTIFY that the construction work for which I/we have been responsible is, to the best of my/our knowledge and belief, in accordance with BS 7671: departures, if any, detailed as follows:

2008

amended to

2011

except for the

Details of departures from BS 7671, as amended (Regulations 120.3, 133.5):

None

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the CONSTRUCTION of the installation: Name:

Kevin Radway

Position:

Electrician

Signature:

Date:

23/11/2011

5. INSPECTION AND TESTING


I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and testing, hereby CERTIFY that the work for which I/we have been responsible is to the best of my/our knowledge and belief, in accordance with BS 7671: departures, if any, detailed as follows:

2008

amended to

2011 None

except for the

Details of departures from BS 7671, as amended (Regulations 120.3, 133.5):

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the INSPECTION AND TESTING of the installation: Name:

N/A N/A

Position:

N/A N/A

Signature:

N/A N/A

Date:

N/A N/A

Report reviewed and confirmed by: Name: Position: Signature: Date:

6. DESIGN, CONSTRUCTION, INSPECTION AND TESTING


I/We, being the person(s) responsible for the design, construction, inspection and testing of the electrical installation (as indicated by my/our signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying out the design, construction, inspection and testing, hereby CERTIFY that the said work for which I/We have been responsible is to the best of my/our knowledge and belief, in accordance with BS 7671:

2008

amended to

2011

except for the departures, if any, detailed as follows:

Details of departures from BS 7671, as amended (Regulations 120.3, 133.5):

None

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the DESIGN, the CONSTRUCTION, and the INSPECTION AND TESTING of the installation: Name:

N/A N/A

Position:

N/A N/A

Signature:

N/A N/A

Date:

N/A N/A
Page: 1 of 11

Report reviewed and confirmed by: Name: Position: Signature: Date:

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

7. DETAILS OF THE ELECTRICAL CONTRACTOR


DESIGN (1) Address: Trading Title:

HPEMS Ltd
Registration Number: Telephone Number: Postcode:

Paddon House Stortford Road Dunmow. Essex CM6 1DA

33898 / 01371 877250

DESIGN (2) Address:

Trading Title:

Same as Above
Registration Number: Telephone Number: Postcode:

CONSTRUCTION Address:

Trading Title:

HPEMS Ltd
Registration Number: Telephone Number: Postcode:

Paddon House Stortford Road Dunmow. Essex CM6 1DA

33898 / 01371 877250

INSPECTION AND TESTING

Trading Title:

Same as Above
Registration Number: Telephone Number: Postcode:

Address:

8. SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS


System Type(s) Number and Type of Live Conductors Nature of Supply Parameters

TN-S TN-C-S TNC TT IT

N/A

ac: 1-phase (2 wire): 2-phase (3 wire): 3-phase (3 wire): Other:

N/A N/A N/A

N/A N/A N/A

1-phase (3 wire): 3-phase (4 wire):

dc:

N/A N/A N/A N/A

N/A

2 pole: 3 pole:

Nominal U: 400 V Uo: voltage(s): Nominal frequency, f: Prospective fault current, lpf: External earth fault loop impedance, Ze: Number of supplies:

230 50 5.5 1

Characteristics of Primary Supply Overcurrent Protective Device(s)

Hz BS(EN): kA Type: Rated current: Short-circuit capacity:

N/A

N/A

Other:

0.05

A kA

9. PARTICULARS OF INSTALLATION AT THE ORIGIN


Means of Earthing Details of Installation Earth Electrode (where applicable)

Distributor's facility: Installation earth electrode:

N/A

Type: Electrode resistance, RA:

N/A N/A

Location: Method of measurement:

N/A N/A ADS

Maximum Demand (Load):


Main Switch or Circuit-Breaker

Protective measure(s) against electric shock:

Type BS(EN): Number of poles: Supply conductors material: Supply conductors csa:

60947-2 MCCB Voltage rating:

1000 250 N/A N/A

V A

Earthing and Protective Bonding Conductors Earthing conductor

3 Copper 25

Rated current, ln: RCD operating current:

Conductor material: Conductor material: Water service: Gas service:

Copper Copper

Conductor csa: Conductor csa:

25 16 N/A N/A

Continuity mm2 check: Continuity mm2 check: Lightning protection: Other services:


N/A N/A

Main protective bonding conductors

mA ms

Bonding of extraneous-conductive parts

RCD operating mm2 time:

N/A

Oil service: Structural Steel:

10. COMMENTS ON EXISTING INSTALLATION


Note: Enter 'NONE' or, where appropriate, the page number(s) of additional page(s) of comments on the existing installation.

None

11. NEXT INSPECTION


I/We, the designer(s), RECOMMEND that this installation is further inspected and tested after an interval of not more than: This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

5 Years
Ref: 0039293 Page: 2 of 11

12. SCHEDULE OF ITEMS INSPECTED


Methods of protection against electric shock Basic and fault protection:

N/A

(i) SELV

N/A

(ii) PELV

Prevention of mutual detrimental influence (a) Proximity of non-electrical services and other influences N/A (b) Segregation of Band I and Band II circuits or use of Band II insulation

(c) Segregation of safety circuits

Double or reinforced insulation:


N/A

(iii) Double or Reinforced Insulation (ii) Barriers or enclosures (iv) Placing out of reach **

Identification Presence of diagrams, instructions, circuit charts and similar information Presence of danger notices and other warning notices Labelling of protective devices, switches and terminals Identification of conductors

Basic protection: (i) Insulation of live parts (iii) Obstacles **

N/A

Fault protection: (i) Automatic disconnection of supply


N/A N/A N/A

Presence of earthing conductor Presence of circuit protective conductors Presence of main protective bonding conductors Presence of earthing arrangements for combined protective and functional purposes Presence of adequate arrangements for alternative source(s), where applicable FELV Choice and setting of protective and monitoring devices (for fault protection and/or overcurrent protection)

Cables and Conductors Selection of conductors for current carrying capacity and voltage drop Erection methods Routing of cables in prescribed zones or within mechanical protection Cables incorporating earthed armour or sheath, or run within an earthed wiring system, or otherwise adequately protected against nails, screws and the like Additional protection provided by 30mA RCD for cables in concealed walls (where required in premises not under the supervision of skilled or instructed persons) Connection of conductors

N/A

N/A

N/A N/A N/A N/A

(ii) Non-conducting location ** Absence of protective conductors

(iii) Earth-free local equipotential bonding ** Presence of earth-free local equipotential bonding

Presence of fire barriers, suitable seals and protection against thermal effects General Presence and correct location of appropriate devices for isolation and switching Adequacy of access to switchgear and other equipment

(iv) Electrical Separation Provided for one item of current-using equipment Provided for more than one item of current-using equipment ** Presence of residual current device(s) Presence of supplementary bonding conductors

N/A

Particular protective measures for special installations and locations Connection of single-pole devices for protection or switching in line conductors only Correct connection of accessories and equipment Presence of undervoltage protective devices Selection of equipment and protective measures appropriate to external influences Selection of appropriate functional switching devices Protection against direct contact by barrier or enclosure provided during erection Insulation of non-conducting floors or walls Polarity Earth fault loop impedance, Zs Verification of phase sequence Operation of residual current device(s) Functional testing of assemblies Verification of voltage drop

Additional protection:


LIM N/A

N/A

** For use in controlled supervised/conditions only

13. SCHEDULE OF ITEMS TESTED


External earth fault loop impedance, Ze Installation earth electrode resistance, RA Continuity of protective conductors Continuity of ring final circuit conductors Insulation resistance between live conductors Insulation resistance between live conductors and earth Protection by separation of circuits


N/A

N/A


N/A

N/A

14. SCHEDULE OF ADDITIONAL RECORDS (See attached schedule)


Note: Additional page(s) must be identified by the Electrical 8, 9, 10, 11 Installation Cert serial and page number(s). All boxes must be completed. 'tick' indicates that an inspection or test was carried out and that the result was satisfactory. 'X' indicates than an inspection or test was carried out and the result is not satisfactory. 'N/A' indicates that an inspection or test was not applicable to the particular installation. 'LIM' indicates that, exceptionally, a limitation agreed with the person ordering the work prevented the inspection or test being carried out.

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

Ref: 0039293

Page: 3 of 11

TO BE COMPLETED IN EVERY CASE Location of distribution board:

Electrical Riser Cupboard ground floor


Distribution board designation:

DBL-G 15. CIRCUIT DETAILS

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the N/A (if any) BS(EN): distribution circuit: Type RCD No Rating: 100 A of poles: N/A RCD ln: N/A mA 60947-2 MCCB BS(EN): Circuit conductors: csa
Number of points served

Max disconnect time permitted by BS7671

Overcurrent protective devices


Short-circuit Capacity

RCD

mm2 mm2

Rating

Live

cpc

BS(EN)

kA

Operating current

Circuit designation

Reference Method

Circuit number and phase

Type of wiring

mA

1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3

Grd mens WC HDs and cleaner socket

O -----

C ----C ----C ----C ----------C ----C ----C -----

3 ----4 ----1 ----1 ----------1 ----2 ----1 -----

4 ----4 ----4 ----4 ----------4 ----4 ----4 -----

2.5 0.4 ---------

60898 ----60898 ----60898 ----60898 ----------60898 ----60898 ----60898 -----

C ----C ----C ----C ----------C ----C ----C -----

20 ----20 ----20 ----20 ----------20 ----20 ----20 -----

10 ----10 ----10 ----10 ----------10 ----10 ----10 -----

N/A 1.15 ---------

Ground Floor tea station

O -----

1.5 0.4 ---------

N/A 1.15 ---------

Ground Floor water heater

O -----

2.5 0.4 ---------

N/A 1.15 ---------

Ground floor trace heating

O -----------

2.5 0.4 ---------------------

N/A 1.15 ---------------------

Grd WC shower disabled alarm

O -----

2.5 0.4 ---------

N/A 1.15 ---------

Ground Ladies WC, HDs

O -----

2.5 0.4 ---------

N/A 1.15 ---------

Ground floor lift supply

O -----

2.5 0.4 ---------

N/A 1.15 ---------

16. CODES FOR TYPE OF WIRING


A: PVC/PVC cables B: PVC cables in metallic conduit C: PVC cables in non-metallic conduit D: PVC cables in metallic trunking E: PVC cables in non-metallic trunking F: PVC/SWA cables G: XLPE/SWA cables H: Mineral-insulated cables O - Other: LSF/LSF Ref: 0039293 Page: 4 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

Maximum Zs permitted by BS7671

Type No

17. CHARACTERISTICS AT THIS D.B.


TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION

18. DETAILS OF TEST INSTRUMENTS N/A N/A N/A

Zs: lpf:

Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:

0.03 6.5

Test Instruments (serial numbers) used: Earth fault loop RCD: 8934065 impedance: Insulation Other: 8934065 ms Resistance: ms Continuity:

8934065

Other:

19. TEST RESULTS


Circuit impedances (Ohms)
Circuit number and phase

Insulation resistance (record lower or lowest value)

Line/ Line M

Line/ Neutral M

At ln ms

At 5 ln ms

r1 rn r2 (Line) (Neutral) (cpc)

R1+R2

R2 M M

1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3

------0.08 -----------------------------------------

------0.08 -----------------------------------------

------0.01 -----------------------------------------

------0.18 ----0.01 ----0.15 ----------0.09 ----0.06 ----0.05 -----

------N/A ----N/A ----N/A ----------N/A ----N/A ----N/A -----

------N/A -----------------------------------------

-------

-------

-------

-------

------0.19 ----0.2 ----0.21 ----------0.18 ----0.18 ----0.17 -----

------N/A ----N/A ----N/A ----------N/A ----N/A ----N/A -----

------N/A ----N/A ----N/A ----------N/A ----N/A ----N/A -----

> 200 > 200 > 200 -------------

-----

> 200 > 200 > 200 -------------

-----

> 200 > 200 > 200 -------------------------------

-----------

> 200 > 200 > 200 -------------

-----

> 200 > 200 > 200 -------------

-----

> 200 > 200 > 200 -------------

-----

20. TESTED BY
Name: Signature:

Kevin Radway

Position: Date of testing:

Electrician 23/11/2011
Ref: 0039293 Page: 5 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

Test button operation

Ring final circuits only (measured end to end)

All circuits (one column to be completed)

Maximum measured earth fault loop Polarity Line/ Neutral/ impedance Earth Earth Zs

RCD Operating times

-------------------------------------------------

TO BE COMPLETED IN EVERY CASE Location of distribution board:

Electrical Riser Cupboard ground floor


Distribution board designation:

DBL-G 15. CIRCUIT DETAILS

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the N/A (if any) BS(EN): distribution circuit: Type RCD No Rating: 100 A of poles: N/A RCD ln: N/A mA 60947-2 MCCB BS(EN): Circuit conductors: csa
Number of points served

Max disconnect time permitted by BS7671

Overcurrent protective devices


Short-circuit Capacity

RCD

mm2 mm2

Rating

Live

cpc

BS(EN)

kA

Operating current

Circuit designation

Reference Method

Circuit number and phase

Type of wiring

mA

9 L1 9 L2 9 L3

Grd mens Acces WC HDs & cleaner skt O ----O -----

C ----C ----C ----C -----

2 ----8 ----6 ----9 -----

4 ----2.5 ----2.5 ----2.5 -----

2.5 0.4 ---------

60898 ----60898 ----60898 ----60898 -----

C ----C ----C ----C -----

20 ----10 ----10 ----10 -----

10 ----10 ----10 ----10 -----

N/A 1.15 ---------

10 L1 Grd Flr hall, access wc, riser & tea stn ltg 10 L2 10 L3

1.5 0.4 ---------

N/A 2.30 --------------2.30 -----

11 L1 Grd flr mens WC & baby change lights O 11 L2 11 L3 12 L1 12 L2 12 L3


Grd Flr ladies WC , cleaners cupb and services void ltg

1.5 0.4 ---------

----O -----

1.5 0.4 ---------

N/A 2.30 ---------

16. CODES FOR TYPE OF WIRING


A: PVC/PVC cables B: PVC cables in metallic conduit C: PVC cables in non-metallic conduit D: PVC cables in metallic trunking E: PVC cables in non-metallic trunking F: PVC/SWA cables G: XLPE/SWA cables H: Mineral-insulated cables O - Other: LSF/LSF Ref: 0039293 Page: 6 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

Maximum Zs permitted by BS7671

Type No

17. CHARACTERISTICS AT THIS D.B.


TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION

18. DETAILS OF TEST INSTRUMENTS N/A N/A N/A

Zs: lpf:

Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:

0.03 6.5

Test Instruments (serial numbers) used: Earth fault loop RCD: 8934065 impedance: Insulation Other: 8934065 ms Resistance: ms Continuity:

8934065

Other:

19. TEST RESULTS


Circuit impedances (Ohms)
Circuit number and phase

Insulation resistance (record lower or lowest value)

Line/ Line M

Line/ Neutral M

At ln ms

At 5 ln ms

r1 rn r2 (Line) (Neutral) (cpc)

R1+R2

R2 M M

9 L1 9 L2 9 L3 10 L1 10 L2 10 L3 11 L1 11 L2 11 L3 12 L1 12 L2 12 L3

-------------------------

-------------------------

-------------------------

0.11 ----0.36 ----0.30 ----0.32 -----

N/A ----N/A ----N/A -----------

-------------------------

> 200 > 200 > 200 -------------

-----

0.19 ----0.61 ----0.46 ----0.04 -----

N/A ----N/A ----N/A ----N/A -----

N/A ----N/A ----N/A ----N/A -----

> 200 > 200 > 200 -------------

-----

> 200 > 200 > 200 -------------

-----

> 200 > 200 > 200 -------------

-----

20. TESTED BY
Name: Signature:

Kevin Radway

Position: Date of testing:

Electrician 23/11/2011
Ref: 0039293 Page: 7 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

Test button operation

Ring final circuits only (measured end to end)

All circuits (one column to be completed)

Maximum measured earth fault loop Polarity Line/ Neutral/ impedance Earth Earth Zs

RCD Operating times

-------------------------

TO BE COMPLETED IN EVERY CASE Location of distribution board:

Electrical Riser Cupboard first floor


Distribution board designation:

DBL-1 CIRCUIT DETAILS

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the (if any) BS(EN): distribution circuit: Type RCD No Rating: A of poles: RCD ln: mA BS(EN): Circuit conductors: csa
Number of points served

Max disconnect time permitted by BS7671

Overcurrent protective devices


Short-circuit Capacity

RCD

mm2 mm2

Rating

Live

cpc

BS(EN)

kA

Operating current

Circuit designation

Reference Method

Circuit number and phase

Type of wiring

mA

1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3 2nd floor ss wc HD 1st floor Acess WC disabled alarm 1st floor ss wc HD 2nd floor Acess WC disabled alarm 1st floor trace heating 2nd floor trace heating 1st floor water heater 2nd floor water heater 1st floor kitchen 2ndt floor kitchen
1st Flr SS wc and access wc HDs + cleaners sockets 2nd Flr SS wc and access wc HDs + cleaners sockets

--O O --O O --O O --O O --------O O --O ------O

--C C --C C --C C --C C --------C C --C ------C

--3 3 --4 4 --1 4 --1 1 --------2 1 --1 ------2

--4 4 --4 4 --4 4 --4 4 --------4 4 --4 ------4

---

---

--60898 60898 --60898 60898 --60898 60898 --60898 60898 --------60898 60898 --60898 ------60898

--C C --C C --C C --C C --------C C --C ------C

--20 20 --20 20 --20 2 --20 20 --------20 20 --20 ------20

--10 10 --10 10 --10 10 --10 10 --------10 10 --10 ------10

---

2.5 0.4 2.5 0.4 -----

N/A 1.15 N/A 1.15 -----

2.5 0.4 2.5 0.4 -----

N/A 1.15 N/A 1.15 -----

2.5 0.4 2.5 0.4 -----

N/A 1.15 N/A --N/A ---

2.5 0.4 2.5 0.4 -----------------

N/A 1.15 N/A 1.15 -----------------

2.5 0.4 2.5 0.4 -----

N/A 1.15 N/A 1.15 -----

2.5 0.4 -------------

N/A 1.15 -------------

2.5 0.4

N/A 1.15

CODES FOR TYPE OF WIRING


A: PVC/PVC cables B: PVC cables in metallic conduit C: PVC cables in non-metallic conduit D: PVC cables in metallic trunking E: PVC cables in non-metallic trunking F: PVC/SWA cables G: XLPE/SWA cables H: Mineral-insulated cables O - Other: LSF/LSF Ref: 0039293 Page: 8 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

Maximum Zs permitted by BS7671

Type No

---

CHARACTERISTICS AT THIS D.B.


TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION

DETAILS OF TEST INSTRUMENTS


Test Instruments (serial numbers) used: Earth fault loop RCD: 8934065 impedance: Insulation Other: 8934065 ms Resistance: ms Continuity:

Zs: lpf:

Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:

N/A N/A N/A

0.03 6.5

8934065

Other:

TEST RESULTS
Circuit impedances (Ohms)
Circuit number and phase

Insulation resistance (record lower or lowest value)

Ring final circuits only (measured end to end) r1 rn (Line) (Neutral) r2 (cpc)

All circuits (one column to be completed) R1+R2 R2

Line/ Line M

Line/ Neutral M

Line/ Earth M

Maximum measured earth fault loop Polarity Neutral/ impedance Earth Zs M

RCD Operating times

At ln ms

At 5 ln ms

1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3

-------------------------------------------------

-------------------------------------------------

-------------------------------------------------

--0.16 0.02 --0.08 0.11 --0.05 0.12 --0.04 0.09 --------0.06 0.07 --0.05 ------0.16

--N/A N/A --N/A N/A --N/A N/A --N/A N/A --------N/A N/A --N/A ------N/A

-------------------------------------------------

--> 200 > 200 --> 200 > 200 --> 200 > 200 --> 200 > 200 --------> 200 > 200 --> 200 ------> 200

--> 200 > 200 --> 200 > 200 --> 200 > 200 --> 200 > 200 --------> 200 > 200 --> 200 ------> 200

--> 200 > 200 --> 200 > 200 --> 200 > 200 --> 200 > 200 --------> 200 > 200 --> 200 ------> 200

---

--0.36 0.26 --0.14 0.12 --0.19 0.13 --0.15 0.12 --------0.1 0.1 --0.08 ------0.2

--N/A N/A --N/A N/A --N/A N/A --N/A N/A --------N/A N/A --N/A ------N/A

--N/A N/A --N/A N/A --N/A N/A --N/A N/A --------N/A N/A --N/A ------N/A


---


---


---


---------


---

-------

TESTED BY
Name: Signature:

Kevin Radway

Position: Date of testing:

Electrician 23/11/2011
Ref: 0039293 Page: 9 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011

TO BE COMPLETED IN EVERY CASE Location of distribution board:

Electrical Riser Cupboard first floor


Distribution board designation:

DBL-1 CIRCUIT DETAILS

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the (if any) BS(EN): distribution circuit: Type RCD No Rating: A of poles: RCD ln: mA BS(EN): Circuit conductors: csa
Number of points served

Max disconnect time permitted by BS7671

Overcurrent protective devices


Short-circuit Capacity

RCD

mm2 mm2

Rating

Live

cpc

BS(EN)

kA

Operating current

Circuit designation

Reference Method

Circuit number and phase

Type of wiring

mA

9 L1 9 L2 9 L3 10 L1 10 L2 Grd - 2nd stairs and landing s lighting 10 L3 11 L1 11 L2 1st fllor hall and wc lights 11 L3 2nd fllor hall and wc lights 12 L1 12 L2 12 L3
1st floor service void, kitchen + cupboard lights 2ndt floor service void, kitchen + cupboard lights

--------O ----O O --O O

--------C ----C C --C C

--------14 ----------7 7

--------1.5 ----2.5 2.5 --2.5 2.5

---------

---------

--------60898 ----60898 60898 --60898 60898

--------C ----C C --C C

--------10 ----10 10 --10 10

--------10 ----10 10 --10 10

---------

1.0 0.4 ---------

N/A 2.30 ---------

1.5 0.4 1.5 0.4 -----

N/A 2.30 N/A 2.30 -----

1.5 0.4 1.5 0.4

N/A 2.30 N/A 2.30

CODES FOR TYPE OF WIRING


A: PVC/PVC cables B: PVC cables in metallic conduit C: PVC cables in non-metallic conduit D: PVC cables in metallic trunking E: PVC cables in non-metallic trunking F: PVC/SWA cables G: XLPE/SWA cables H: Mineral-insulated cables O - Other: LSF/LSF Ref: 0039293 Page: 10 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.

Maximum Zs permitted by BS7671

Type No

---------

CHARACTERISTICS AT THIS D.B.


TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION

DETAILS OF TEST INSTRUMENTS


Test Instruments (serial numbers) used: Earth fault loop RCD: 8934065 impedance: Insulation Other: 8934065 ms Resistance: ms Continuity:

Zs: lpf:

Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:

N/A N/A N/A

0.03 6.5

8934065

Other:

TEST RESULTS
Circuit impedances (Ohms)
Circuit number and phase

Insulation resistance (record lower or lowest value)

Ring final circuits only (measured end to end) r1 rn (Line) (Neutral) r2 (cpc)

All circuits (one column to be completed) R1+R2 R2

Line/ Line M

Line/ Neutral M

Line/ Earth M

Maximum measured earth fault loop Polarity Neutral/ impedance Earth Zs M

RCD Operating times

At ln ms

At 5 ln ms

9 L1 9 L2 9 L3 10 L1 10 L2 10 L3 11 L1 11 L2 11 L3 12 L1 12 L2 12 L3

-------------------------

-------------------------

-------------------------

--------1.4 ----0.37 0.45 --0.39 0.42

--------N/A ----N/A N/A --N/A N/A

-------------------------

--------> 200 ----> 200 > 200 --> 200 > 200

--------> 200 ----> 200 > 200 --> 200 > 200

--------> 200 ----> 200 > 200 --> 200 > 200

---------

--------1 ----0.62 0.55 --0.6 0.48

--------N/A ----N/A N/A --N/A N/A

--------N/A ----N/A N/A --N/A N/A

-----


---

TESTED BY
Name: Signature:

Kevin Radway

Position: Date of testing:

Electrician 23/11/2011
Ref: 0039293 Page: 11 of 11

This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011

ELECTRICAL INSTALLATION CERTIFICATE

GUIDANCE FOR RECIPIENT (to be appended to the Certificate)

This safety Certificate has been issued to confirm that the electrical installation work to which it relates has been designed, constructed and inspected and tested in accordance with British Standard 7671 (as amended) (The IET Wiring Regulations). You should have received an original Certificate and the contractor should have retained a duplicate Certificate. If you were the person ordering the work, but not the user of the installation, you should pass this Certificate, or a full copy of it including the schedules, immediately to the user. The 'original' Certificate should be retained in a safe place and be shown to any person inspecting or undertaking further work on the electrical installation in the future. If you later vacate the property, this Certificate will demonstrate to the new owner that the electrical installation complied with the requirements of British Standard 7671 at the time the certificate was issued. The Construction (Design and Management) Regulations require that for a project covered by those regulations, a copy of this Certificate, together with schedules is included in the project health and safety documentation. For safety reasons, the electrical installation will need to be inspected at appropriate intervals by a competent person. The maximum time interval recommended before the next inspection it stated on Page 2 under 'Next Inspection'. This Certificate is intended to be issued only for a new electrical installation or new new work associated with an alteration or addition to an existing installation. It should not have been issued for the inspection of an existing electrical installation. An 'Electrical Installation Condition Report' should be issued for such an inspection. This Certificate is only valid if a Schedule of Inspections and Schedule of Test Results are appended.