Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations
Certificate Reference:
0039293
P J Carey (contactors) Ltd, Carey House, Great Central Way, Wembley Middlesex, HAR OHR
The installation is: New An addition An alteration
Retained Building, Kings Yard energy centre, Olympic Park Site, London Landlords Power and lighting
N/A N/A
3. DESIGN
I/We, being the person(s) responsible for the design of the electrical installation (as indicated by my/our signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying out the design, hereby CERTIFY that the design work for which I/we have been responsible is, to the best of my/our knowledge and belief, in accordance with BS 7671:
2008
amended to
2011
None
The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the DESIGN of the installation: Name: Position: Signature: Date:
Where there is divided responsibility for the design: Name: Position: Signature: Date:
4. CONSTRUCTION
I/We, being the person(s) responsible for the construction of the electrical installation (as indicated by my/our signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying out the construction, hereby CERTIFY that the construction work for which I/we have been responsible is, to the best of my/our knowledge and belief, in accordance with BS 7671: departures, if any, detailed as follows:
2008
amended to
2011
None
The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the CONSTRUCTION of the installation: Name:
Kevin Radway
Position:
Electrician
Signature:
Date:
23/11/2011
2008
amended to
2011 None
The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the INSPECTION AND TESTING of the installation: Name:
N/A N/A
Position:
N/A N/A
Signature:
N/A N/A
Date:
N/A N/A
2008
amended to
2011
None
The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. For the DESIGN, the CONSTRUCTION, and the INSPECTION AND TESTING of the installation: Name:
N/A N/A
Position:
N/A N/A
Signature:
N/A N/A
Date:
N/A N/A
Page: 1 of 11
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
HPEMS Ltd
Registration Number: Telephone Number: Postcode:
Trading Title:
Same as Above
Registration Number: Telephone Number: Postcode:
CONSTRUCTION Address:
Trading Title:
HPEMS Ltd
Registration Number: Telephone Number: Postcode:
Trading Title:
Same as Above
Registration Number: Telephone Number: Postcode:
Address:
N/A
dc:
N/A
2 pole: 3 pole:
Nominal U: 400 V Uo: voltage(s): Nominal frequency, f: Prospective fault current, lpf: External earth fault loop impedance, Ze: Number of supplies:
230 50 5.5 1
N/A
N/A
Other:
0.05
A kA
N/A
N/A N/A
Type BS(EN): Number of poles: Supply conductors material: Supply conductors csa:
V A
3 Copper 25
Copper Copper
25 16 N/A N/A
Continuity mm2 check: Continuity mm2 check: Lightning protection: Other services:
N/A N/A
mA ms
N/A
None
5 Years
Ref: 0039293 Page: 2 of 11
N/A
(i) SELV
N/A
(ii) PELV
Prevention of mutual detrimental influence (a) Proximity of non-electrical services and other influences N/A (b) Segregation of Band I and Band II circuits or use of Band II insulation
N/A
(iii) Double or Reinforced Insulation (ii) Barriers or enclosures (iv) Placing out of reach **
Identification Presence of diagrams, instructions, circuit charts and similar information Presence of danger notices and other warning notices Labelling of protective devices, switches and terminals Identification of conductors
N/A
N/A N/A N/A
Presence of earthing conductor Presence of circuit protective conductors Presence of main protective bonding conductors Presence of earthing arrangements for combined protective and functional purposes Presence of adequate arrangements for alternative source(s), where applicable FELV Choice and setting of protective and monitoring devices (for fault protection and/or overcurrent protection)
Cables and Conductors Selection of conductors for current carrying capacity and voltage drop Erection methods Routing of cables in prescribed zones or within mechanical protection Cables incorporating earthed armour or sheath, or run within an earthed wiring system, or otherwise adequately protected against nails, screws and the like Additional protection provided by 30mA RCD for cables in concealed walls (where required in premises not under the supervision of skilled or instructed persons) Connection of conductors
N/A
N/A
(iii) Earth-free local equipotential bonding ** Presence of earth-free local equipotential bonding
Presence of fire barriers, suitable seals and protection against thermal effects General Presence and correct location of appropriate devices for isolation and switching Adequacy of access to switchgear and other equipment
(iv) Electrical Separation Provided for one item of current-using equipment Provided for more than one item of current-using equipment ** Presence of residual current device(s) Presence of supplementary bonding conductors
N/A
Particular protective measures for special installations and locations Connection of single-pole devices for protection or switching in line conductors only Correct connection of accessories and equipment Presence of undervoltage protective devices Selection of equipment and protective measures appropriate to external influences Selection of appropriate functional switching devices Protection against direct contact by barrier or enclosure provided during erection Insulation of non-conducting floors or walls Polarity Earth fault loop impedance, Zs Verification of phase sequence Operation of residual current device(s) Functional testing of assemblies Verification of voltage drop
Additional protection:
LIM N/A
N/A
N/A
N/A
N/A
N/A
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
Ref: 0039293
Page: 3 of 11
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the N/A (if any) BS(EN): distribution circuit: Type RCD No Rating: 100 A of poles: N/A RCD ln: N/A mA 60947-2 MCCB BS(EN): Circuit conductors: csa
Number of points served
RCD
mm2 mm2
Rating
Live
cpc
BS(EN)
kA
Operating current
Circuit designation
Reference Method
Type of wiring
mA
1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3
O -----
O -----
O -----
O -----------
O -----
O -----
O -----
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
Type No
Zs: lpf:
Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:
0.03 6.5
Test Instruments (serial numbers) used: Earth fault loop RCD: 8934065 impedance: Insulation Other: 8934065 ms Resistance: ms Continuity:
8934065
Other:
Line/ Line M
Line/ Neutral M
At ln ms
At 5 ln ms
R1+R2
R2 M M
1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3
------0.08 -----------------------------------------
------0.08 -----------------------------------------
------0.01 -----------------------------------------
------N/A -----------------------------------------
-------
-------
-------
-------
-----
-----
-----------
-----
-----
-----
20. TESTED BY
Name: Signature:
Kevin Radway
Electrician 23/11/2011
Ref: 0039293 Page: 5 of 11
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
Maximum measured earth fault loop Polarity Line/ Neutral/ impedance Earth Earth Zs
-------------------------------------------------
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the N/A (if any) BS(EN): distribution circuit: Type RCD No Rating: 100 A of poles: N/A RCD ln: N/A mA 60947-2 MCCB BS(EN): Circuit conductors: csa
Number of points served
RCD
mm2 mm2
Rating
Live
cpc
BS(EN)
kA
Operating current
Circuit designation
Reference Method
Type of wiring
mA
9 L1 9 L2 9 L3
10 L1 Grd Flr hall, access wc, riser & tea stn ltg 10 L2 10 L3
----O -----
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
Type No
Zs: lpf:
Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:
0.03 6.5
Test Instruments (serial numbers) used: Earth fault loop RCD: 8934065 impedance: Insulation Other: 8934065 ms Resistance: ms Continuity:
8934065
Other:
Line/ Line M
Line/ Neutral M
At ln ms
At 5 ln ms
R1+R2
R2 M M
9 L1 9 L2 9 L3 10 L1 10 L2 10 L3 11 L1 11 L2 11 L3 12 L1 12 L2 12 L3
-------------------------
-------------------------
-------------------------
-------------------------
-----
-----
-----
-----
20. TESTED BY
Name: Signature:
Kevin Radway
Electrician 23/11/2011
Ref: 0039293 Page: 7 of 11
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
Maximum measured earth fault loop Polarity Line/ Neutral/ impedance Earth Earth Zs
-------------------------
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the (if any) BS(EN): distribution circuit: Type RCD No Rating: A of poles: RCD ln: mA BS(EN): Circuit conductors: csa
Number of points served
RCD
mm2 mm2
Rating
Live
cpc
BS(EN)
kA
Operating current
Circuit designation
Reference Method
Type of wiring
mA
1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3 2nd floor ss wc HD 1st floor Acess WC disabled alarm 1st floor ss wc HD 2nd floor Acess WC disabled alarm 1st floor trace heating 2nd floor trace heating 1st floor water heater 2nd floor water heater 1st floor kitchen 2ndt floor kitchen
1st Flr SS wc and access wc HDs + cleaners sockets 2nd Flr SS wc and access wc HDs + cleaners sockets
---
---
--60898 60898 --60898 60898 --60898 60898 --60898 60898 --------60898 60898 --60898 ------60898
---
2.5 0.4
N/A 1.15
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
Type No
---
Zs: lpf:
Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:
0.03 6.5
8934065
Other:
TEST RESULTS
Circuit impedances (Ohms)
Circuit number and phase
Ring final circuits only (measured end to end) r1 rn (Line) (Neutral) r2 (cpc)
Line/ Line M
Line/ Neutral M
Line/ Earth M
At ln ms
At 5 ln ms
1 L1 1 L2 1 L3 2 L1 2 L2 2 L3 3 L1 3 L2 3 L3 4 L1 4 L2 4 L3 5 L1 5 L2 5 L3 6 L1 6 L2 6 L3 7 L1 7 L2 7 L3 8 L1 8 L2 8 L3
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
--0.16 0.02 --0.08 0.11 --0.05 0.12 --0.04 0.09 --------0.06 0.07 --0.05 ------0.16
--N/A N/A --N/A N/A --N/A N/A --N/A N/A --------N/A N/A --N/A ------N/A
-------------------------------------------------
--> 200 > 200 --> 200 > 200 --> 200 > 200 --> 200 > 200 --------> 200 > 200 --> 200 ------> 200
--> 200 > 200 --> 200 > 200 --> 200 > 200 --> 200 > 200 --------> 200 > 200 --> 200 ------> 200
--> 200 > 200 --> 200 > 200 --> 200 > 200 --> 200 > 200 --------> 200 > 200 --> 200 ------> 200
---
--0.36 0.26 --0.14 0.12 --0.19 0.13 --0.15 0.12 --------0.1 0.1 --0.08 ------0.2
--N/A N/A --N/A N/A --N/A N/A --N/A N/A --------N/A N/A --N/A ------N/A
--N/A N/A --N/A N/A --N/A N/A --N/A N/A --------N/A N/A --N/A ------N/A
---
---
---
---------
---
-------
TESTED BY
Name: Signature:
Kevin Radway
Electrician 23/11/2011
Ref: 0039293 Page: 9 of 11
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION No of Nominal Supply to distribution PB-RBS/2 3 Voltage: 400 V phases: board is from: Associated RCD Overcurrent protective device for the (if any) BS(EN): distribution circuit: Type RCD No Rating: A of poles: RCD ln: mA BS(EN): Circuit conductors: csa
Number of points served
RCD
mm2 mm2
Rating
Live
cpc
BS(EN)
kA
Operating current
Circuit designation
Reference Method
Type of wiring
mA
9 L1 9 L2 9 L3 10 L1 10 L2 Grd - 2nd stairs and landing s lighting 10 L3 11 L1 11 L2 1st fllor hall and wc lights 11 L3 2nd fllor hall and wc lights 12 L1 12 L2 12 L3
1st floor service void, kitchen + cupboard lights 2ndt floor service void, kitchen + cupboard lights
--------14 ----------7 7
---------
---------
---------
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011.
Type No
---------
Zs: lpf:
Confirmation of supply polarity kA Operating times of associated RCD (if any) At ln: At 5ln:
0.03 6.5
8934065
Other:
TEST RESULTS
Circuit impedances (Ohms)
Circuit number and phase
Ring final circuits only (measured end to end) r1 rn (Line) (Neutral) r2 (cpc)
Line/ Line M
Line/ Neutral M
Line/ Earth M
At ln ms
At 5 ln ms
9 L1 9 L2 9 L3 10 L1 10 L2 10 L3 11 L1 11 L2 11 L3 12 L1 12 L2 12 L3
-------------------------
-------------------------
-------------------------
-------------------------
--------> 200 ----> 200 > 200 --> 200 > 200
--------> 200 ----> 200 > 200 --> 200 > 200
--------> 200 ----> 200 > 200 --> 200 > 200
---------
-----
---
TESTED BY
Name: Signature:
Kevin Radway
Electrician 23/11/2011
Ref: 0039293 Page: 11 of 11
This form is based on the model shown in Appendix 6 of BS 7671:2008 amended 2011
This safety Certificate has been issued to confirm that the electrical installation work to which it relates has been designed, constructed and inspected and tested in accordance with British Standard 7671 (as amended) (The IET Wiring Regulations). You should have received an original Certificate and the contractor should have retained a duplicate Certificate. If you were the person ordering the work, but not the user of the installation, you should pass this Certificate, or a full copy of it including the schedules, immediately to the user. The 'original' Certificate should be retained in a safe place and be shown to any person inspecting or undertaking further work on the electrical installation in the future. If you later vacate the property, this Certificate will demonstrate to the new owner that the electrical installation complied with the requirements of British Standard 7671 at the time the certificate was issued. The Construction (Design and Management) Regulations require that for a project covered by those regulations, a copy of this Certificate, together with schedules is included in the project health and safety documentation. For safety reasons, the electrical installation will need to be inspected at appropriate intervals by a competent person. The maximum time interval recommended before the next inspection it stated on Page 2 under 'Next Inspection'. This Certificate is intended to be issued only for a new electrical installation or new new work associated with an alteration or addition to an existing installation. It should not have been issued for the inspection of an existing electrical installation. An 'Electrical Installation Condition Report' should be issued for such an inspection. This Certificate is only valid if a Schedule of Inspections and Schedule of Test Results are appended.