Dynamic Simulation Model of a Hybrid Power System: Performance Analysis



I. Vechiu
1
, H. Camblong
1
, G. Tapia
2
, B. Dakyo
3
, C. Nichita
3
(1)
LIPSI-ESTIA, Technople Izarbel, 64 210 Bidart, France,
i.vechiu@estia.fr, h.camblong@estia.fr,
Tel: + 33 (0) 559 438 471, Fax: + 33 (0) 559 438 401
(2)
University of Basque Country (UPV-EHU), Spain, isptaotg@sp.ehu.es
Tel: + (34) 943 018 682, Fax: + (34) 943 017 130
(3)
GREAH University of Le Havre, France, dakyo@univ-lehavre.fr, nichita@univ-lehavre.fr
Tel: +33 232 74 43.31, Fax: +33 232 74 43 38


Key words: Hybrid Power System, Wind Turbine, Photovoltaic, DC-link, disturbance

Abstract- This paper reports an investigation to develop a dynamic hybrid power system simulation model to
maximize the renewable energy extraction and to analyze disturbances. The investigated model is based on two types
of renewable power generation: wind turbine generator and photovoltaic generator, connected to a three-phase
isolated grid constituted by a diesel generator. The interconnection between the renewable sources and the AC diesel
generator is made by a DC-link with buffer batteries and an inverter. First, the system is sized according to the
electric demand and the availability of renewable energy resources. Then, each component of the hybrid power
system is dynamically modelled in order to maximize the renewable energy to total energy ratio and to analyze the
disturbances that affect the correct operation.

1. INTRODUCTION

Diesel generator is generally used to provide an uninterrupted energy on islands and remote areas. For these regions,
the association of diesel generator (DG) and renewable energy sources, wind turbine (WT) generators and
photovoltaic (PV) panels, may be especially useful [1].
The increase of renewable energy penetration levels in isolated power system, as well as at the distribution grid level
of interconnected systems, has accentuated the difficulties related with the integration of this kind of energy in
isolated electric power system. Among the issues that frequently arise, are indicatively the following:
Voltage unbalance
Voltage dips (due to the short-circuit or starting up of a large load)
Voltage swells
Voltage flicker
Voltage and current harmonic distortion

For a proper analysis and evaluation of such issues a complete model of the investigated system is required.
Therefore, a dynamic hybrid power system simulation model has been developed in order to investigate some
problems encountered with this kind of systems.
The modelling capabilities include the dynamic representation of induction and synchronous generator, WT drive
train, PV panels, batteries, diesel engine, converters and controllers.

The purpose of the present work is to investigate a dynamic simulation model of the Hybrid Power System (HPS)
(Figure 1), after determining the most appropriate combination of components according to the variations in loads
and resources oscillation. The simulated system approach is outlined for the main system components and selected
architecture. The attention focuses on:
Maximizing the electric power produced by the WT generator and PV generator by detecting and tracking
the point of maximum power.
Analysis of voltage disturbances - symmetrical or unsymmetrical.

In this paper, the simulated system approach is outlined for the main system components (WT, PV generator, diesel
generator and controllers).

2. SYSTEM CONFIGURATION

The system (Fig. 1) consists of a WT, a PV array, buffer batteries and a diesel generator. The load is directly supplied
by the common AC point formed by the voltage source inverter and the DG. The connection of the WT and the PV
array is through a DC-link voltage. The system control associated with each converter maximizes and regulates the
flow of power from the sources.

2

=
=
3
=

PV
WT
Diesel
Generator
Buffer
Batteries

=
=
=
3
Load

Fig. 1: HPS architecture

After several simulations with HOMER (the optimization model for distributed power), the size of each source was
defined according with resources availability and load profile. The system must serve an electric demand of 500
KWh/d scaled annual average. The resources availability are: 8 m/s wind speed and 5 KWh/m
2
/d solar radiations
(annual average). The rated power of each source of the system and the annual electrical energy production are shown
in Table I.

System architecture Annual electrical energy production
1 * 22 KW WT 36%
18 KW PV 14%
1*33 KW DG 50%

Table 1. System sources rated power and annual electrical energy production

Short time excess energy is stored in a buffer battery with 4020 KWh throughput to control the DC-link voltage
according to disturbances. Fig. 2 shows the monthly average electric production of the system with 0.5 renewable
fraction.

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
0
10
20
30
PV
Wind
DG

Fig. 2. Monthly average electric production

This configuration of the HPS was modelled and dynamically simulated in order to analyze the complex interaction
of power sources with very different operating characteristics and outputs.

3. MODELLING APPROACH

MATLAB/Simulink is the software used for simulating the whole system. The main concern is the power sources
with their control and subsequent disturbances which may affect the correct operation of the system.

3.1. Wind Turbine

Because of robustness, low maintenance and relative cheapness, induction machine has been considered a good
choice as electrical generator of the WT. The model of the Squirrel Cage Induction Generator (SCIG) has been
expressed in a synchronous frame aligned to the rotating field (rotor flux
r
). The relationship between real and
imaginary components of the current space vector in the original stationary two-axis reference frame and the new
rotating reference frame is shown in Figure 3.

3

s
jsq
i
s

sd
Stationary
Real Axis

m
Rotating
Real Axis
Stationary
Imaginary Axis
Rotating
Imaginary Axis
i
sq

i
s

i
s

i
sd

js

r

Fig. 3. Relationship of current space vector components in stationary and rotating reference frame

Thus the voltage current equations can be written under the form:
sq s sd sd s sd
dt
d
i R u + =
(1a)
sd s sq sq s sq
dt
d
i R u + + =
(1b)
rq r rd rd r
dt
d
i R + = 0
(1c)
rd r rq rq r
dt
d
i R + + = 0
(1d)
In the mechanical system, the rotor frequency and the electromagnetic torque can be expressed:
m s r
p =
(2)
( )
rq sd rd sq em
i i p T =
2
3
(3)
where
s
is the stator supply frequency, p represents the pole pair number
rd
,
rq
rotor d and q axis fluxes.

The induction generator is driven by the aero dynamical part of the WT through a gear box.
To achieve maximum wind energy, the conversion system is variable speed and driven at the optimal shaft speed [2].
The control structure for the turbine feeding SCIG is shown in Figure 4.

abc
dq

dq

abc
opt
K
D
2
p

+
-
+
+
+
+
+
+
+

+
-
-
*
sd
i
*
sq
i *
em
T
s

m

r

*
s
v
*
s
v
*
sc
v
*
sb
v
*
sa
v
sa
i
sb
i
s
i
s
i
vdc
dt
d
sd
i
sq
i
rd
L
L
i L
r
m
sq s s

(


sd s rd
r
m
s
i L
L
L


t

SCIG
sd t
i K
1
sd
Ki
1


Fig. 4. Squirrel Cage Induction Generator control

4
The principle of the control scheme is similar to the one used in motor drive [3]. In fact, for a motor operating, we
control the flux and the rotor speed. In our case, the flux is kept to a constant value and the electromagnetic torque is
controlled according with maximum efficiency characteristics [4]:
m m opt em
D K T =
2 *
(4)
where
m
is measured or estimated generator speed, D, an equivalent friction coefficient and K
opt,
a constant defining
the relationship between the maximum power and shaft speed for a given blade characteristic [4].
By choosing a synchronous frame in order to have
rq
=0, the flux
rd
and the electromagnetic torque T
em
are given by:
s T
L
i L
r
m
sd m rd
+
= =
1

(5)
rd sq
r
m
em
i
L
L
p T
2
3
=
(6)
where L
m
, L
r
are magnetizing and rotor inductance. T
r
is the rotor time constant.



3.2. Solar Cell Modelling

A solar cell is usually represented by an electrical equivalent one-diode model as shown in Fig. 5.

Rs
I
ID
V
+
-
Iph
G
T

Fig. 5: Model for single solar cell

The output current source is the difference between the photocurrent I
ph
and the normal diode current I
D
[5] [6] and is
directly proportional to the light falling on the cell. The diode determines the current-voltage (I-V) characteristics of
the cell.
( )
|
|
.
|

\
|

+
= = 1 exp
0
c
s
ph D ph
mKT
R I V e
I I I I I
(7)
For this work, a model of moderate complexity was used. The model included temperature dependence of the
photocurrent I
ph
and the saturation current of the diode I
0
. A series resistance R
s
was included and it takes into
account the contact resistance between the metallic contacts and the semiconductor, as well as, the resistance of the
semiconductor material of the solar cell [5]. In the above equation m, K and T
c
represent respectively the diode
quality constant, Boltzmanns constant and temperature.
In PV system, cells are normally grouped into modules. The manufacturers supply PV cells in modules, consisting
of N
p
parallel branches, with N
s
solar cells in series each.
The PV modules current I
m
under arbitrary operating conditions can be described as:
(

|
|
.
|

\
| +
=
c
t s
m m
s
m
c
m
m
sc
m
V N
I R V V
I I
0
exp 1
(8)
The expression of the PV modules current I
m
is an implicit function, depending on short circuit current of the module
I
m
sc
, the open circuit voltage of the module V
m
0c
, the equivalent serial resistance of the module R
m
s
and the thermal
voltage in the semiconductor of a single solar cell V
c
t
.
The modules in PV system are typically connected in arrays with M
p
parallel branches with M
s
modules in series
each. If it is assumed that the modules are identical and the ambient irradiation is the same on all the modules, the
current of the array is:


5
m
p
a
I M I =
(9)

3.3. Maximum Power Point Tracker (MPPT)
Algorithm

The characteristics at Standard Test Conditions (STC)
provided by the manufactures, show that the power
supplied by PV module depends on the irradiation, cell
temperature and module voltage. Therefore MPPT device
is required to extract maximum power from the PV
module.

Several MPPT methods have been reported [7][8]. For
this research work, the sources incremental conductance
method is the used MPP search algorithm.
As shown in [7], the incremental conductance algorithm
tracks fast the MPP under rapid changing atmospheric
conditions. The output voltage and current from the
source are monitored, the MPPT controller relying on
them to calculate the conductance and incremental
conductance and to make its decision (to increase or
decrease duty ratio output).
This algorithm is described by the flowchart in Fig. 6 at
every MPP sampling, where t is the time step, d(t) is the
duty ratio at the present time step, d(t-t) is the duty ratio
at the previous time step and d is the incremental duty
ratio.

The output power from the PV source can be expressed
as:
pv pv pv
v i P = (10)
To demonstrate the algorithm, the equation 10 is
differentiated:
dv
di
v
i
dv
dP
v
+ =
1
(11)
The source conductance and incremental conductance are defined by G and G respectively:
pv
pv
v
i
G =
(12)
pv
pv
dv
di
G =

(13)
This algorithm searches the voltage operating point at which the conductance is equal to the incremental conductance.
These ideas are graphically shown in Fig. 7:

P
V
0 =
dv
dP
pv
0 >
dv
dP
pv
0 <
dv
dP
pv
( ) G G =
( ) G G <
( ) G G >

Fig. 7. Voltage operating point for maximum power extraction

The control of the voltage V
pv
of the PV panels (Fig. 8), with the help of the boost converter, allows tracking the
maximum power extraction.


Read :
V
pv
(t), I
pv
(t)
P
pv
/V
pv
>0

I
pv
=I
pv
(t)-I
pv
(t-t)
V
pv
=V
pv
(t)-V
pv
(t-t)
P
pv
/V
pv
<0

d(t)=d(t-t)+d d(t)=d(t-t) d(t)=d(t-t)-d
yes
yes
no
no
V
pv
(t-t)= V
pv
(t)
I
pv
(t-t)=I
pv
(t)
Return
Fig. 6. Incremental Conductance algorithm
flowchart

6

D
L
T
ipv
PWM
control
ig1
Vpv
VDC
iL
iCpv
PV Generator

Fig. 8. PV generator control block diagram

In the present work, the averaged model of boost converter [9][10] was used and its equations can be deduced from
Fig. 8:
( ) | |
pv DC
L
v v d
L dt
di
+ = 1
1
(14)
( )
L pv
pv
pv
i i
C dt
dv
=
1

(15)
The current generated by the PV generator on the DC-link can easily be calculated if the converter losses are
neglected:
( )
L g
i d i = 1
1
(16)

3.4. DC-link voltage

The DC-link voltage is kept at the reference voltage by controlling the energy flow from the batteries to the DC-link.
When energy from the WT and PV array is insufficient to supply sudden increments in load demand, the DC-link
voltage drops below the reference value. Energy is pumped to the DC-link from the batteries in order to maintain the
voltage at the set reference value. When there is excess energy, the batteries are recharged.

-
i
cb

v
bat
V
dc
Batteries
i
bat
C
dc
i
g3

i
cdc

PI
V
dc
V
dc
*

+
DC/DC
Converter

Fig. 9. DC link with batteries charging block diagram

Fig. 9 shows the architecture of the DC-link. The used DC/DC converter [9] has quite similar topology with the
DC/DC converter used in previous section but is current reversible and the control strategy is different. The voltage
PI controller enables the voltage error to be minimised in the steady-state operation.

3.5. AC side converter

The connection between the common DC bus and the AC bus is made by a bi-directional converter [3]. Its
configuration is shown in Fig. 10:

As for control of WT, a synchronous frame PI current regulator was chosen to control the converter. Synchronous
frame controllers operate by transforming the three-phase AC currents i
a
, i
b
and i
c
in the synchronous rotating frame.
This allows the steady-state error, that is normally associated with the application of PI control, to be eliminated and
also provides independent control of real and reactive power flow.
Once in the synchronous frame, the quantities i
d,
i
q
and i
0
are regulated using conventional PI feedback control loops
one for each current. The control of the zero sequence current, and thus, the zero sequence voltage, is employed to
attenuate the 0-channel disturbance [11].



7
dq0
0
0
abc abc

0
dq0
DG
Load V
dc

-
-
+
+
i
d
*
i
q
*
i
d
i
q

-
+
i
0
i
0
*


Fig. 10. Control principle AC side converter

In most cases, it is reasonable to assume that the converter switching frequency is significantly higher than the power
system frequency and will have negligible impact on the model of the inverter control loop dynamics. Therefore, the
inverter switches can be replaced by a function representing their averaged value [10].

3.6. Diesel Generator

Remote area or island grids are typically fed by conventional diesel power stations. Suitable dynamic models are
included in HPS for all important elements of conventional diesel power stations, namely the diesel engine, speed
governor and synchronous generator.

R
1
s
K
I
1
1 s
K
+
ref

r

f
m

Fig. 11. Speed governor block diagram of the diesel engine

For the diesel engine, simple or more sophisticated models available in the literature are employed, depending on the
data available [12]. However, experience has shown it is often sufficient to use the simple model of Fig. 11, where
the speed governor is represented by its droop and integral gain (PI controller), along with a first order lag for the
valve actuator mechanism.

The electrical side of the diesel generator is carried out by a simplified model of three-phase synchronous machine.
The simplified synchronous machine block models both the electrical and mechanical characteristics of a simple
synchronous machine. The electrical system for each phase consists of a voltage source in series with RL impedance,
which implements the internal impedance of the machine.

4. SIMULATION RESULTS

4.1. SCIG vector-control performance

Fig. 12a shows the speed tracking response to a wind-step of 5m/s to 9m/s, corresponding to an optimal shaft speed
of 65 and 117 rad/s respectively. The evolution of i
d
and i
q
currents is also shown in the Fig. 12. The time response of
the tracking strategy is dependent on the step size. The speed tracking performance was tested also with a typical
wind profile, Fig. 12b, obtained from [4]. The optimal speed corresponds to the instantaneous wind speed and the real
shaft speed is seen to follow well.

8
0 10 20 30 40 50 60 70 80 90 100
0
20
40
60
80
100
120
Time [s]
I
d
q

[
A
]
/

S
p
e
e
d

[
r
a
d
/
s
]
Id
Iq
r

0 50 100 150 200 250 300
6
7
8
9
10
11
12
13
14
Time [s]
S
p
e
e
d

[
r
a
d
/
s
]
t opt
t




4.2. PV panel and Power Point Tracker performance

Equation (8) was used in Matlab to model Shell SQ75 photovoltaic solar module. The I-V characteristics from
simulation Fig. 13, obtained with this model, correlate well with the I-V curves provided by the manufacturer, which
means that the model can be used with the above presented MPPT algorithm.
0 5 10 15 20 25
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
Voltage [V]
C
u
r
r
e
n
t

[
A
]
1000 W/m
2
800 W/m
2
600 W/m
2
400 W/m
2
200 W/m
2

0 5 10 15 20 25
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
Voltage [V]
C
u
r
r
e
n
t

[
A
]
20C
30C
40C
50C
60C




Fig. 14a shows the simulation result for PV generator with MPPT when the irradiation is variable and the temperature
is constant. The irradiation input data was measured every 15 s during 5 mn and the temperature was kept at 25 C.
The relationship between PV power and the temperature is displayed in figure 14b where the irradiation was kept
constant at 1000 W/m
2
.
0 50 100 150 200 250 300
0.4
0.6
0.8
1
1.2
1.4
1.6
x 10
4
Time [s]
P
o
w
e
r

[
W
]
0 50 100 150 200 250 300
300
400
500
600
700
800
900
1000
I
r
r
a
d
i
a
t
i
o
n

[
W
/
m
2
]
Ppv G

0 50 100 150 200 250 300
0.5
1
1.5
x 10
4
P
o
w
e
r

[
W
]
0 50 100 150 200 250 300
20
40
60
80
Time [s]
T

[

C
]
Ppv
T






Fig. 12a. SCIG vector-control performance
for step changes in wind velocity
WT rotating speed tracking performance
Fig. 13a. I-V characteristic at constant
temperature of 25C
Fig. 13b. I-V characteristic at constant
irradiation G=1000W/m
2
Fig. 14a. PV power tracking with variable
irradiation and constant temperature of 25C
Fig. 14b. PV power tracking with variable
temperature and constant irradiation of
1000W/m
2

9
4.3. DC-link controller during voltage disturbances

The effect of the voltage disturbances has been analyzed by comparing the DC-link voltage, which should ideally be
constant, and using the DC-link controller shown in Fig. 9. Two kind of voltage disturbances have been investigated
by operating the system in three-phase balanced and unbalanced load. In Fig. 15a, the DC-link voltage for the
proposed control is shown in case of balanced tree-phase load increase by about 90%. In this case the DC-link
voltage is constant, only during the short transient at the beginning and the end of the disturbance a peak value can be
noticed.
Unbalance condition was created by loading one phase with about 6.5 KW less than the two others. Voltage
unbalance in three-phase system causes voltage ripples in the DC-link with twice the fundamental frequency Fig.
15b.
0.95 1 1.05 1.1 1.15 1.2 1.25 1.3
690
692
694
696
698
700
702
704
706
708
710
Time [s]
V
d
c

[
V
]

0.98 0.99 1 1.01 1.02 1.03 1.04 1.05 1.06 1.07
698.5
699
699.5
700
700.5
701
701.5
Time [s]
V
d
c

[
V
]




5. CONCLUSIONS

A complete dynamic HPS has been modelled according to the complexity of the investigated subject. Generation-side
control and modelling of the voltage disturbances effects are emphasized. It is shown that the investigated model is
particularly interesting for designing control strategy and for analyzing the behaviour of the system affected by
different kinds of disturbances. In the near future, the developed model together with a test bench that emulates the
HPS will be used to test control strategy in order to mitigate voltage disturbances.

REFERENCES

1. S. Ruin, O. Carlson. Wind-hybrid systems with variable speed and DC-link. Wind Power for the 21
Century, Kassel, Germany, September 2000; 25-27.
2. Pea R., Crdenas R., Blasco R., Asher G. A Cage Induction Generator Using Back to Back PWM
Converter for Variable Speed Grid Connected Wind Energy System. Proceedings of IECON 2001,
IEEE Industrial Electronics Society, Denver USA.
3. Marian P. Kazmierkowski, Krishnan R. Control in Power Electronics; San Diego, California, USA,
2002; 161-351.
4. Camblong H. Minimisation de limpact des perturbations dorigine olienne sur la production
dlectricit par des arognrateurs vitesse variable ; Bordeaux, France, 2003 ; 94-97.
5. Anca D, Poul Sorensen, Lars H. Hansen, Henrik Bindner. Models for a Stand-Alone System. Riso
National Laboratory, Roskilde December 2000; 9-16.
6. Frederick M. Ishengoma, Lars E. Norum. Design and implementation of a digitally controlled stand-
alone photovoltaic power supply. Nordic Workshop on Power and Industrial Electronics (Norpie
2002), Stockholm, Sweden. 12-14 August 2002.
7. Hohm, Ropp M. E., Comparative Study of Maximum Power Point Tracking Algorithms. Prog.
Photovolt: Res. Appl. 2003 ; 47-62
8. Yu G. J., Jung Y. S, Choi J. Y., Kim G. S. A novel two-mode MPPT control algorithm based on
comparative study of existing algorithms. Solar Energy 2003; 455-463.
9. Lavabre M. Electronique de Puissance Conversion de lEnergie ; Paris, 1998 ; 248-253.
10. Pankow Y, Leclercq L., Franois B., Robyns B. Modelling and simulation of hybrid-photovoltaic
generating system. 10
th
International POWER ELECTRONICS and MOTION CONTROL
Conference, EPE-PEMC 2002, (CD Rom).
11. Zhang R. High performance power converter systems for nonlinear and unbalanced load/source;
Dissertation, Virginia Tech, 1998; 142-163.
12. Jurado F., Saenz R. J. Neuro-fuzzy control autonomous wind-diesel systems using biomass.
RENEWABLE ENERGY 2002; 39-56.
Fig. 15a. DC-link voltage under three-phase
balanced disturbance
Fig. 15b. DC-link voltage under three-phase
unbalanced disturbance