Sr. Type of Instrument No. 1 External Displacer Level Instrument on Vessel 2 FLGD 4 FLGD 2 FLGD 1 S.

W / FLGD * 4 FLGD 2 FLGD 1 1/2 FLGD --2 FLGD 1 1/2 FLGD 2 FLGD 1 S.W / FLGD * --2 FLGD

Vessel/Standpipe First Block Connection Valve 2 FLGD 2 FLGD

Instrument Connection 2 FLGD 2 FLGD 4 FLGD 1 SW 1 SW 4 FLGD 3/4 SCRD 3/4 SCRD 1/2" SCRD 1/2" SCRD 3 FLGD 4 FLGD 1/2" SCRD 1/2" SCRD 6 FLGD

External Displacer Level Instrument on Standpipe

Internal Displacer Level Instrument

External Ball Float Level Instrument on Vessel

External Ball Float Level Instrument on Standpipe

Internal Ball Float Level Instrument

Level Gauge on Vessel

CORPORATE DESIGN GROUP, MUMBAI

Level Gauge on Stand Pipe

S. W / FLGD * 3/4" S. W / FLGD * 3/4 S. W / FLGD * 3/4 S. W / FLGD *

D. P. Instrument on Vessel

10

D. P. Instrument on Standpipe

11 12 13 14

Diaphragm Seal D. P. Instrument on Vessel 3 FLGD Extended D. P. Instrument on Vessel 4 FLGD D.P. Tube Level Instrument 1 1/2 FLGD Tank level Instrument (Mech.) ATM Pressurized 1 1/2 FLGD ATM Pressurized 6 FLGD 1 1/2 FLGD

INSTRUMENT CONNECTIONS ON VESSELS, STAND PIPES AND TANKS

15

Tank level Instrument (Servo)

16

Pressure Instrument on Vessel

3 FLGD --1/2 S.W (By Inst) --1 1/2" FLGD (BY INST.) --6" FLGD (BY INST ) 1 1/2 FLGD

1/2" SCRD

DOCUMENT NO. CDG/INS/CON/0020

PAGE NO. : 1 of 1

17 Diaphragm Seal Pressure Instrument on Vessel 1 1/2 FLGD 1 1/2 FLGD 1/2" SCRD 18 Diaphragm Seal Pressure Instrument on Vessel 1 1/2 FLGD 1 1/2 FLGD 1 1/2" SCRD 19 Thermo well 1 1/2 FLGD --1 1/2" SCRD 20 Standpipe 2 FLGD ----Notes: 1. For any other Instrument nor referred above, the connection details shall be as per individual requirement. 2. All Flange / SW Ratings shall be as per piping specification. 3. * In case of Direct Mounted Flanged Instruments and where Flanged First Isolation Valves are provided, Bolting and Gasket shall be in Piping Scope. As per Piping Specification.

REV.

Sr. No.

Type of Instrument

Where Piping Class Prescribes Screwed Connections

Where Piping Class Prescribes S. W. Connections

here Piping Class Prescribes Flanged Connections

Process Conn.

1 St Block Valve Process Conn.

Instrument Conn.

1 St Block Valve

Instrument Conn.

Process Conn.

1 St Block Valve

Instrument Conn.

1 1/2" SCRD 1/2" SCRD 1/2" SCRD 1/2" SCRD 1/2" S. W.

Orifice Flow Meter

1/2" SCRD

1/2" SCRD

1/2 FLGD

1/2" SCRD

CORPORATE DESIGN GROUP, MUMBAI


3/4" SCRD 3/4" S. W. 3/4" S. W. 3/4" SCRD 1/2" SCRD 3/4" SCRD 1/2" SCRD 3/4" S. W. 3/4" S. W. 1/2" SCRD 1/2" SCRD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD For any other Instrument not referred above, the connection details shall be as per individual requirement . All Flange / SW Rating shall be as per Piping Specification. Installation of all in line Instruments shall be in Piping Scope. * * Seal Welding Required Connections for D. P. Instruments 1/2" SCRD.

Averaging Pitot Tube

1 1/2" FLGD 1 1/2" FLGD 1 1/2 FLGD 1 1/2" FLGD 1 1/2" FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD (By Inst.) (By Inst.) (By Inst.) (By Inst.) 3/4 FLGD 3/4 FLGD 3/4 FLGD 3/4 FLGD 1/2" SCRD 1/2" SCRD

Pressure Instrument

Diaphragm Seal Pressure 3/4" SCRD Instrument (SCRD)

Diaphragm Seal Pressure 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD Instrument (SCRD) 1 1/2 FLGD 1 1/2 FLGD 1 1/2 FLGD

INSTRUMENT CONNECTION ON PIPING

Thermo well

Note:

1.

2.

I3.

n case of Direct Mounted Flanged Instruments and where Flanged First Isolation Valves are provided, Bolting and Gasket shall be in piping Scope

DOCUMENT NO. CDG/INS/CON/0021

PAGE NO. : 1 of 1

4.