www.hilti.us Company: Specifier: Address: Phone I Fax: E-Mail: Specifier's comments: Page: Project: Sub-Project I Pos. No.

: Date:

PROFIS Anchor 2.0.9


1

-|-

11/1/2010

1. Input data

Anchor type and diameter: Effective embedment depth: Material: Evaluation Service Report:: Issued I Valid: Proof: Stand-off installation: Anchor plate: Profile Base material: Installation: Reinforcement:

HIT-RE 500-SD + HAS, 1 h ef,act = 8.260 in. (h ef,limit = - in.) ASTM F 568M Class 5.8 ESR 2322 11/1/2007 | design method ACI 318 / AC308 without clamping (anchor); restraint level (anchor plate): 2.0; eb = 1.000 in.; t = 1.000 in. lx x l y x t = 10.000 x 14.000 x 1.000 in. (Recommended plate thickness: not calculated) W shape (AISC); (L x W x T x FT) = 12.200 in. x 8.080 in. x 0.370 in. x 0.640 in. uncracked concrete , 4000, fc ' = 4000 psi; h = 29.520 in., Temp. short/long: 32/32F hammer drilled hole, installation condition: dry condition A; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar

Geometry [in.] y z

x 10.000 t=1.000 e b=1.000 h ef =8.260 3 14.000 x h = 29.520

6.000

2 24.950

lx = 10.000 20.420 6.000

Loading [lb, in.-lb] Governing loads Governing loads (Load case 1) N Vx Vy Mx My Mz 28486 -3955 15047 0.000 0.000 0.000

Eccentricity (structural section) [in.] e x = 0.000; ey = 0.000 Seismic loads (cracked concrete assumed; categories C, D, E, or F): no

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.us Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.9


2

-|-

11/1/2010

2. Load case/Resulting anchor forces


Load case (governing): Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor 1 2 3 4 Tension force 7122 7122 7122 7122 Shear force 3889 3889 3889 3889 Shear force x -989 -989 -989 -989 Shear force y 3762 3762 3762 3762 1 Tension x max. concrete compressive strain []: 0.00 max. concrete compressive stress [psi]: 0 resulting tension force in (x/y)=(0.000/0.000) [lb]: 28483 resulting compression force in (x/y)=(0/0) [lb]: 0 y 3

3. Tension load
Proof Steel Strength* Bond Strength** Concrete Breakout Strength** Load Nua [lb] 7121 28486 28486 Capacity fN n [lb] 28542 44002 36137 Utilization bN [%] = Nua /fNn 25 65 79 Status OK OK OK

* most unfavorable anchor **anchor group (anchors in tension) Steel Strength Nsa [lb] 43910 Bond Strength ANa [in] 850.50 k c,uncr 24 e c1,N [in.] 0.000 Na0 [lb] 50471 ANa0 [in] 536.54 t k,uncr,2500 [psi] 1945 y ec1,Na 1.000 f 0.550 s cr,Na [in.] 23.163 k dry 1.00 e c2,N [in.] 0.000 fNag [lb] 44002 c cr,Na [in.] 11.582 t k,uncr [psi] 1945 y ec2,Na 1.000 Nua [lb] 28486 c [in.] 20.420 t k,max,uncr [psi] 1389 y p,Na 1.000 c ac [in.] 12.390 y g,Na0 1.000 y ed,Na 1.000 y g,Na 1.000 f 0.650 fNsa [lb] 28542 Nua [lb] 7121

Concrete Breakout Strength ANc [in] 947.41 e c1,N [in.] 0.000 Nb [lb] 36034 ANco [in] 614.05 y ec1,N 1.000 f 0.650 c [in.] 20.420 e c2,N [in.] 0.000 fNcbg [lb] 36137 c ac [in.] 12.390 y ec2,N 1.000 Nua [lb] 28486 y ed,N 1.000 y cp,N 1.000 k uncr 24.000

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.us Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.9


3

-|-

11/1/2010

4. Shear load
Proof Steel Strength* Steel failure (with lever arm)* Pryout Strength** Concrete edge failure in direction x-** * most unfavorable anchor **anchor group (relevant anchors) Steel Strength Vsa [lb] 26345 f 0.600 fe b 0.800 fVsa [lb] 12646 Vua [lb] 3889 Load V ua [lb] 3889 3889 15558 15558 Capacity fVn [lb] 12646 2603 77834 55517 Utilization bV [%] = Vua /fVn 31 150 20 28 Status OK not recommended OK OK

Steel failure (with lever arm) lb [in.] 2.000 N u/fN s 0.250 Vs = aM * Ms / lb [lb] 4339
M

aM 2.00 1 - Nu/fN s 0.750 f 0.600 M s [in.-lb] 5784.998 fV s [lb] 2603


M 0

M s=Ms (1 - Nu/fNs) [in.-lb] 4338.748 Vua [lb] 3889

Pryout Strength (concrete breakout relevant) ANc [in] 947.41 e c1,V [in.] 0.000 Nb [lb] 36034 ANco [in] 614.05 y ec1,N 1.000 f 0.000 c [in.] 20.420 e c2,V [in.] 0.000 fVcpg [lb] 77834 k cp 2.000 y ec2,N 1.000 Vua [lb] 15558 y ed,N 1.000 y cp,N 1.000 k uncr 24.000

Concrete edge failure in direction xle [in.] 8.000 y ed,V 0.944 Vb [lb] 61920 d o [in.] 1.000 y a,V 1.000 f 0.000 c 1 [in.] 20.420 e c,V [in.] 0.000 fVcbg [lb] 55517 AVc [in] 1817.85 y ec,V 1.000 Vua [lb] 15558 AVco [in] 1876.41 y c,V 1.400

5. Combined tension and shear loads


bN = N u /fN n 0.788 bNV = bN + bV <= 1
z z

bV = V u /fVn 0.308

z 5/3

Utilization bN,V [%] 81

Status OK

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.us Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.9


4

-|-

11/1/2010

6. Warnings
Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs. The ACI318 is not dealing with anchor shaft bending, nevertheless, Hilti recommends to observe this capacity during design! Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the Evaluation Service Report for cleaning and installation instructions The present version of the software does not account for special design provisions for overhead applications. Refer to related approval (e.g. section 4.1.1 of the ICC-ESR 2322) for details. IBC 2006, Section 1908.1.16, requires that the governing design strength of an anchor or group of anchors be limited by ductile steel failure, if this is NOT the case, ACI 318-D Section D.3.3.5 requires that the attachment that the anchor is connecting to the structure shall be designed so that the attachment will undergo ductile yielding at a load level corresponding to anchor forces no greater than the design strength of anchors specified in ACI 318-D section D.3.3.3, or the minimum design strength of the anchors shall be at least 2.5 times the factored forces transmitted by the attachment. Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI318 or the relevant standard! The anchor plate is assumed to be sufficiently stiff in order to be not deformed when subjected to the actions!

Fastening does not meet the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.us Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.9


5

-|-

11/1/2010

7. Installation data
Anchor plate, steel: Profile: W shape (AISC), 12.200 in. x 8.080 in. x 0.370 in. x 0.640 in. Hole diameter in the fixture: df = 1.125 in. Plate thickness (input): 1.000 in. Recommended plate thickness: not calculated Anchor type and diameter: HIT-RE 500-SD + HAS, 1 Installation torque: 1800.000 in.-lb Hole diameter in the base material: 1.125 in. Hole depth in the base material: 8.260 in. Minimum thickness of the base material: 10.510 in.

4.0000 1 3 x 2 4 4.0000 2.0000 5.0000 5.0000 2.0000 Coordinates Anchor [in.] Anchor x y 1 -3.000 3.000 2 -3.000 -3.000 3 3.000 3.000 4 3.000 -3.000 c -x 20.420 20.420 26.420 26.420 c +x c -y 30.950 24.950 30.950 24.950 c +y Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7.0000

7.0000