Project : 2 X 750KW Hydro Power Plant Client : B.K.Saini Ref: 1. Standard method of calculation 2.

- Short circuit calculation - technical application papers.

Short Circuit Current Calculation

SUPPLY NETWORK: Rated Voltage Frequency Short Circuit power of the network ( Based on 25KA ) POWER TRANSFORMER DATA: Capacity HV Voltage LV Voltage % of Impedance Rated current GENERATOR DATA: Capacity Power Factor Generating Voltage Direct axis subtransient reactance 3.3KV XLPE POWER CABLE DATA: System Voltage 150Sqmm cable resistance 150Sqmm Cable reactance NETWORK DIAGRAM: 33KV Line : : : 3300 V 0.264 MilliOhm / Mtr 0.000079 MiliOhm / Mtr : : : : 750 0.85 3.3 16.4 KW pf KV % : : : : : 2500 33 3.3 6.25 437.4 KVA KV KV % A : : : 33 KV 50 Hz 1500 MVA

2500 KVA TR

C1 =

2R X 150 SQmm XPLE Cable

C2

1R X 150 Sqmm XLPE Cable 750 KW Gen.

C3

C4

Pages 1 of 3

Calculated by: S.Saravanan Sr.Manager - PMT

Project : 2 X 750KW Hydro Power Plant Client : B.K.Saini

Short Circuit Current Calculation

Now, Power Transformer MVA = = = = = = = = = = = = = = = = Zc Zc1 Zc2 Zc3 Zc4 Cable MVA C1 cable MVA C2 cable MVA C3 cable MVA C4 cable MVA SHORT CIRCUIT POWER NETWORK: Net work MVA = = = = = = = = = = TR Capacity % of Imp 40 MVA Generator capacity direct axis subtransient reactance 5.38 MVA 30 Mtr 28 Mtr 18 Mtr 15 Mtr 0.01584 0.000005 0.00792 0.000002 0.006600 0.000002 0.004752 0.000001 Ohms Ohms Ohms Ohms Ohms Ohms Ohms Ohms

Generator MVA

Cl cable Length C2 cable length C3 Cable Length C4 Cable length Now, C1 cable resistance C1 cable reactance C2 cable resistance C2 cable reactance C3 cable resistance C3 cable reactance C4 cable resistance C4 cable reactance

SQRT(R^2+X^2) 0.01584 Ohms 0.00792 Ohms 0.0066 Ohms 0.004752 Ohms System voltage^2 Cable Impedance 687.5000 MVA 1375 MVA 1650 MVA 2291.667 MVA

TR MVA

C1 MVA 3.3KV BUS

C2 MVA

C3 MVA

C4 MVA

GEN MVA

GEN MVA

GEN MVA

Pages 2 of 3

Calculated by: S.Saravanan Sr.Manager - PMT

Project : 2 X 750KW Hydro Power Plant Client : B.K.Saini

Short Circuit Current Calculation

Now, Short circuit power MVA at secondary of TR Short circuit current at secondary of TR Short circuit power MVA at 3.3KV Bus Short circuit current at 3.3KV Bus Generator #1 short circuit power MVA Generator #2 short circuit power MVA Generator #3 short circuit power MVA Overall generator short circuit power Short circuit current at generators = = = = = = = = = 38.961 MVA 6.817 KA 36.871 MVA 6.451 KA 5.359 MVA 5.363 MVA 5.367 MVA 16.089 MVA 11.201 KA

So for calculation of power house, we have to consider maximum short circuit current in 3.3KV network. Therefore, 11.201 KA is maximum short circuit current. and all equipment short circuit current rating minimum 11.201 KA required.

Pages 3 of 3

Calculated by: S.Saravanan Sr.Manager - PMT