DMC1000

Digital Master Control

System Products

Provide the interface between paralleled generator sets and a facility Major Functions
Load Add/Shed Load Demand Operator Panel Power Transfer Control

DMC1000 - Configurations

DMC1000 - Configurations

DMC1000 - Configurations

DMC1000 - Configurations

AC Metering
3 Phase metering of genset bus and utility bus simultaneously Phase and Total/avg metering of V, A, kW, kVAR, kVA, PF, Hz Phase and total metering of +kWh, -kWh, +kVARh, kVARh, kVAh for each source

Master Sync Voltage Match


both phase synchronization and voltage matching 12 genset limit for synchronizer controls frequency and voltage via PCC kW and kVAR load share lines selectable phase synchronization (default) or slip frequency synchronization adjustable slip frequency adjustable control loop gains sync enable input for manual control mode synchronizer output limit diagnostic option to lock out synchronizer if fail to sync occurs; re-enabled upon fault reset
8

Permissive Sync Check


sync check function is independent of synchronizer adjustable frequency window, phase window, voltage window, and window time for permissive check sync check output fail to synchronize diagnostic

Power Transfer Control


open transition w/pgm transition delay, hard closed transition (<100msec), soft load closed transition sensors (uv, ov, freq, phase rot, loss of phase, gen bus capacity, and breaker failure) adjustable time delays (pgm transition, transfer, retransfer, max parallel, gensets start delay, gensets stop delay) source availability determination for both utility and genset source connected determination for both utility and genset

10

Power Transfer Control


gensets start/stop logic with single relay output transfer and retransfer inhibit inputs override input to override timers and transfer/retransfer inhibits for immediate transfer, retransfer or genset start auto/manual mode input test start input adjustable test with or without load option to do open transition retransfer if fail to sync occurs

11

Extended Paralleling
MANY options available for controlling kW and kVAR in extended paralleling mode kW and kVAR can be independently controlled in any combination of base load (control the power @ gen bus) or peak shave (control the power @ utility bus) load control operates independently of the number of gensets that are online setpoints can be set from InPower, HMI, Modbus, or via analog hardware 0-5V inputs extended parallel start input starts/stops the mode

12

Load Demand
load demand for up to 4 gensets fixed sequence OR run-hours based works only for non-utility paralleled operation (e.g. not available in peak shave) adjustable pickup and dropout levels as well as time delays 4 load demand driver outputs to connect to PCC genset control's load demand inputs

13

Load Add / Load Shed


load add / load shed capability using PCCNet I/O Modules for feeder breaker control control up to 6 feeder breakers or ATS

14

HARDWARE (AUX101/2)

AUX101/2 IO Module

15

Load Add / Load Shed

16

FEATURES

HMI 211

17

HMI
simple low cost operator panel connect via PCCNet HOME screen gives pertinent system status information access to AC data, controller state, etc... faults pop up

18

FEATURES

Bargraph (HMI 112)


Supports the PCCNet bargraph (HMI112) for display of AC data in bargraph form 9 Bars: L1,L2,L3 % Current, % Total kW, Power Factor, Frequency, L12, L23, L31 % Voltage Use One for each source (2 maximum)

Utility Bus

Genset Bus

19

Real Time Clock


on-board RTC used by Scheduler function clock keeps track of year, month, day, date, hour, minute, and second user must set the clock on first power-up clock automatically accounts for leap year clock setting will remain valid for at least 24 hours without B+ to the board diagnostic fault occurs if clock needs to be set (scheduler wont run)

20

System Scheduler
12 program run schedules run schedules configurable for start day, start time, duration, repeat interval, and run mode run modes can be no load, with load, or extended parallel provides up to 6 different schedule exceptions uses on-board Real Time Clock configurable automatic Daylight Savings Time clock correction
21

Modbus RTU
intended for PLC interface published register map read/write access operational data, control, and setup variables MCM3320 is Modbus slave RS232 or RS485 connection settable address (allowing multiple MCM3320 slaves on RS485) communications setup and diagnostics

22

Diagnostics
38 diagnostics (warnings and events) each event or warning is mappable to 8 customer low side driver outputs active warning codes can be read out on 7segment LED on board some warnings alter control operation warnings are latched until user fault reset

23

Diagnostics

24

Diagnostics

25

FEATURES

26

Painis Baixa Tenso

27

Switchgear Power Section


Power Section is available by RFQ.

28

Prisma P and IEC 60439-1: International Panorama


Prisma P is according to IEC 60439-1 standard and another international standards

UL

IEC IEC IEC IEC

IEC

29

Prisma P Form of Separation


Form 1:
No Separation

Form 2:
Separation between bus bar and components

30

FORM OF SEPARATION
IEC 60439-1 standard define types of separation, that are made to protect operator and instalation

Form 1: No Separation

Form 1
31

FORM OF SEPARATION
Form 2: Separation of bus bar from the breakers and other components

a- Cables connection not separated of the bus bar.

b- Cables connection separated from the bus bar


Form 2a
32

Form 2b

MV Switchgear
MV Products

33

Protection Relays

Functions 50/51, 67, 32, 27, 81, etc

34