Академический Документы
Профессиональный Документы
Культура Документы
STATE
ELECTRICITY
TRANSMISSION
CO. LTD.
TESTING & COMMUNICATION CIRCLE,NAGPUR . if P 0712 - 2228393 (0) 0712 -2221873 (R) 0712 -222731 I Fax - 0712 -2234220 E-mail: se4500nagpur@mabatransco.in Testing And Communication Circle, G8, Near Baljagat, Laxminagar, Nagpur 440022 NO.SE/T&CINGP/Techl M41 Date:-
Dear Sir With reference to above subject, on your request C and Tanf measurements carried out at Abhijeet energy plant, Mondha, Nagpur on dt 26112/11, 30112111. Reports are enclosed. 27112111,2911211 [ &
Thanking You
Yours Faithfully
..-
TESTING AND COMMUNICATION CIRCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date of Testing:- 26/12/2011 Name of Sub-station:- 220 KV ABHIJEET POWER PLANT Name of Bay:- GT-4 220KV
crs
Measurement done in U5T Mode
Voltage 2.0 10.0 2.0 10.0 2.0 10.0 Power. inmW 0.00 0.05 0.00 0.04 0.00 0.05 Capacitance in pF 689.52 689.52 689.86 688.21 689.38 698.38
Temp:- 36 0 C
Maker- AREVA Sr no. CT's 42100300192 Phase R 42100300193 Phase Y 42100300194 Phase B Measured Tan 0 Corrected Tan 0 at ambient temp. 0.0022 0.0022 -0.0051 0.0020 0.0022 0.0023 at 20
°C
0.0018 0.0018 -0.0042 0.0017 0.0018 0.0019
C &Tan Delta values for 220 KV CTs are within permissible limit
Name of Bay:- 5T-2 220KV crs Make- AREVA
Sr no. CT's 42100100044 Phase R 42100100045 Phase Y 4210010041 Phase B Voltage 2.0 10.0 2.0 10.0 2.0 10.0 Power inmW 0.00 0.06 0.00 0.05 -0.06 0.05 Capacitance in pF 678.43 678.65 674.00 674.22 939.46 696.40
0.007 at 20 0c).
Measured Tan 0 Corrected Tan 0 at ambient temp. at 20 0 C 0.0024 0.0020 0.0028 0.0023 0.0021 0.0028 -0.0582 0.0023 0.0020 0.0023 -0.0477 0.0019
C &Tan Delta values for 220 KV CTs are within permissible limit
0.007 at 20 0c).
DyEE/TCC(M)/Nagpur
~ SE/TCC/Nagpur
cwd_Tandelta_results_mod
11-01-2012
TESTING AND COMMUNICATION CmCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date ofTesting:26/12/2011 Name of Sub-station:220 KV A8HIJEET Name of 8ay:- GT-4 220KVCVT'S Makc:- AREV A Measurement Sr no. CT's 21090701115 Phase R 21100100008 Phase Y 21100400714 Phase B Voltage 2.0 10.0 2,0 10.0 2.0 10.0 , Power inmW -0.18 -4.18 -0.17 -4.02 -0.18 -4.05 done in UST Mode Capacitance in pF 6621.80 6605.30 6750.70 6728.30 6623.50 6607.20 Measured Tan Temp:- 360 C
POWER PLANT
Corrected Tan at 20
0
-0,0163 -0.0152
eVT' S
Capacitance values for 220 KV CVTs are within limit. Tan Delta values for CVT's are negative because while measuremeant, inductive transformere comes parallel with capcitor C2.
~/
~SE/TCClNagpur
DyEE/TCC(M)/Nagpur
Sheet 603
Page 1
11-01-2012
TESTING AND COMMUNICATION CIRCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date of Testing:- 27/12/2011 Name of Sub-station:- 220 KV ABHIJEET POWER PLANT Name of Bay:- 220/6.9 KV 20 MVA T-6798/B-30451 220KV Bushing's
Make:- AREV A
M.Yr-2009
Sr no. Bushing's 0812345 Phase R 0812346 Phase Y 0812353 Phase B
C& Tand delta values for 220 KV Bushing's are within limit .
3939.60
3504.20 3502.20 7792.30 7799.70
Measured Tan 0 Corrected Tan 0 at ambient temp. a! 20 0 C 0.0026 0.0021 0.0026 0.0023 0.0031 0.0032 0.0030 0.0027 0.0026 0.0027 0.0025 0.0022
DyEEITCC(M)/Nagpur
~/
~~ SE/TCC/Nagpur
cwd_Tandelta_results_mod
11-01-2012
TESTING AND COMMUNICATION CIRCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date of Testing:27/1212011 220 KV ABHIJEET KV 85 MVA POWER PLANT 679611-B-30464 GT-2 Measurement Voltage 2.0 10.0 2.0 10.0 2.0 10.0 Power inmW 0.20 0,04 0.00 0.04 0.00 0.04 done in UST Mode Capacitance in pF 310.47 310.27 317.50 317.34 316.07 315.87 at ambient temp. 0.0030 0.0036 0.0039 0.0041 0.0041 0.0042 Measured Tan 0 Corrected Tan 0 at 20 0 C 0.0028 0.003 0.0032 0.0034 0.0032 0.0034 Temp:- 360 C
Name of Sub-atatlorrName of 8ay:-111220 220KV Bushing's Make:- AREV A M.Yr-2008 Sr no. Bushing's 0810035 Phase R 0812196 Phase Y 0812340 Phase B
C& Tand delta values for 220 KV Bushing's are within limit.
T/F Winding's
HV-LV UST HV-E GST-g LV-E GST-g
Measured Tan 5 Corrected Tan is at ambient temp. at 20 0 C 0.0026 0.0021 0.0026 0.0021 0.0028 0.0029 0.0027 0.0028 0.0023 0.0024 0.0022 0.0023
t,.J i I"-rJ
DyEE/TCC(M)/Nagpur
h/
SE/TCC/Nagpur
11-01·2012
TESTING AND COMMUNICATION CIRCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date ofTesting:. 29/12/2011
220 KV ABHIJEET
KV 20 MVA Startup
M.Yr·2009
Sr no. Bushing's 0810306 Phase R 0809021 Phase Y 0809022 Phase B Voltage 2 ..0 10.0 2.0 10.0 2.0 10.0
dona in UST Mode Capacitance in pF 304.19 303.99 309.64 309.55 310.23 310.05 at ambient temp. 0.0030 0.0033 0.0037 0.0038 0.0033 0.0035 Measured Tan 0 Corrected Tan 0 at 20 0 C 0.0025 0.0027 0.0031 0.0031 0.0027 0.0028
C& Tand delta values for 220 KV Bushing's are within limit.
Measured Tan 0 Corrected Tan 0 at ambient temp. at 20 0 C 0.0026 0.0021 0.0027 0.0022 0.0029 0.0032 0.0034 0.0030 0.0024 0.0026 0.0028 0.0025
II
I
~y
DyEE/TCC(M)/Nagpur SE/TCCINagpur
.\
cwd_ Tande/ta_results_mod
11·01-2012
TESTING AND COMMUNICA nON cmCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date of Testing:27/12/2011 2.20 .KV ABHIJEET POWER PLANT
Name of Sub-station>
Name of Bay:- 220 .KV SEZ -2 220.KVerS Temp:- 36 Measurement Voltage , Power inmW 0.00 0.05 , 42090701071 Phase Y 42090701075 Phase 8 2.0 10.0 2.0 10.0 0.00 0.05 0.00 0.05 693.95 693.95 683.91 683.88 0.0022 0 .. 022 0 0.0022 0.0022 0.0018 0.0018 0.0018 0.0019 done in UST Mode Capacitance in pF 673.34 673.21 Measured Tan 5 at ambient temp. 0.0023 0.0023 Corrected Tan 5 a! 20 o C 0.0019 0.0019
0
Maker- AREVA
Sr no.
crs
42090701070 Phase R
2.0
10.0
C &Tan Delta values for 220 KV CTs are within permissible limit
Name of Bay:- SEZ-2 220.KV CVT'S Make- AREVA Sr no. CVT's Voltage 2.0 10.0 2.0 Phase Y 10.0 2.0 Phase 8 10.0 Power inmW -0.17 -4.22 -0.18 -4.04 -0.17 -3.97 Capacitance in_l)F 6781.60 6757.30
0,007 at 20 0c),
Phase R
Measured Tan Corrected Tan 0 at ambient temQ_. at 20 0 C -0.0192 -0.0161 -0.0196 -0.0165 -0.0197 -0.0192 -0.0188 -0.0188 -0.0166 -0.0169 -0.0158 -0.0158
Capacitance
Ls/
DyEEITCC(M)lNagpuf
cwd_Tandelta_results_mod
·i
11·01·2012
TESTING AND COMMUNICATION CIRCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date cf Testlnqt- 29/12/2011 Name of Sub-statlon.220 KV ABHIJEET -Bay Tempt- 36 Measurement Sr no. CT's Voltage 2.0 10.0 2.0 10.0 2.0 10.0 Power inmW 0.00 0.05 0.00 0.05 0.00 0.05 done in UST Mode Capacitance in pF 699.56 698.78 688.87 688.36 Measured Tan 5 at ambient temp. 0.0045 0.0024 0.0012 0.0024 0.0025 0.0024 Corrected Tan at 20 0 C 0.0037 0.002 0.0010 0.0019 0.0020 0.002
0
POWER PLANT
Phase R
Phase Y
Phase B
685.83 686.14
C &Tan Delta values for 220 KV CTs are within permissible limit
0,007 at 20 0c),
220KVCVT'S Make· AREVA Sr no. CVT's Voltage 2.0 10.0 2.0 Phase Y 10.0 2.0 Phase B 10.0 Power inmW -0.28 -6.01 -18.55 -2.08 -0.13 -4.53 ' Capacitance in pF 6645.10 6627.50 6622.70 6608.20 6644.80 6626.80 Measured Tan 5 Corrected Tan 5 , at ambient temp. a! 20 0 C -0.0315 -0.0258 -0.0288 -0.0236 -0.0288 -0.0104 -0.0143 -0.0220 -0.8817 -0.0085 -0.0117 -0.01
Phase R
Capacitance
\\
~/
DyEEITCC(M)/Nagpur
SE/TCClNagpur
cwd_ Tandelta_resulls_mod
11-01·2012
TESTING AND COMMUNICA nON CIRCLE, NAGPUR Capacitance and Tan Delta Measurement Report
Date of Testing:- 30/12/2011 Name of Sub-station:- 220 KVABHIJEET POWER PLANT Name of Bay:- 220 KV SEZ -1 220KV CT'S
Mak.e:- AREVA
Sr no. CT's
Phase R
Phase Y
0.00
0.05
673.05
673.05
Phase B
0.0023
C &Tan Delta values for 220 KV CTs are within permissible limit
0.007 at 20°C),
10.0
2.0
Phase Y
10.0 2.0
-0.0161 -0.0162
Phase 8
10.0
Capacitance
DyEE/TCC(M)/Nagpul'
~v
SE/TCC/Nagpur
cwd_Tandelta _results_mod
.\
11-01-2012