Application Guide
LV Circuit Breaker
Application Guide
Table of Contents
Page
1.
2.
3.
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.
Tripping curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.
6.
7.
8.
Utilisation in 400 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
39
40
43
45
58
1.
overview of the modular offer
c Technical data of the circuit to be
protected:
v the circuit-breaker tripping curve:
- C curve: standard
- B curve: for a generator only able to
supply a small short-circuit current
- curve D: when the starting current is high,
v the number of poles imposed by the loads.
tripping
curves
C
B
C60a
C60N
C60H
C120N
C120H
NG125H
NG125LMA
motor
C32H-DC
direct
current
MA
c
c
ratings
number of
(A)
poles
voltage Ue (V)
663
440
0.563
440
0.563
440
63125
440
10125
440
1080
500
480
500
140
125 V DC
250 V DC
15
20
25
36
50
1
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
2, 3
1
2
DPN
DPN Vigi
sensitivity
instantaneous
30
300
mA mA
c
c
c
c
500
mA
selective s
300 500 1 A
mA mA
adjustable I/S*
300 500 1 A
mA mA
3A
300
mA
adjustable I/S/D*
500 1 A 3 A
mA
C60N
C60 Vigi
C60H
C60 Vigi
C120N
C120 Vigi
C120H
C120 Vigi
NG125H
NG125 Vigi
NG125LMA
NG125 Vigi
C32H-DC
*I/S: instantaneous or selective
I/S/D: instantaneous, selective or delayed (150 ms).
1.
overview of the modular offer
tripping
curves
C
B
C60a
C60N
C60H
C120N
C120H
ratings
number of
(A)
poles
voltage Ue (V)
1040
440
0.563
440
0.563
440
63125
440
10125
440
15
20
25
36
50
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
C60N
C60 Vigi
sensitivity
instantaneous
30
mA
c
C60H
C60 Vigi
C120N
C120 Vigi
C120H
C120 Vigi
300
mA
c
500
mA
c
selective s
300
mA
c
2.
selection of circuit breakers
P
lb = for three phase
Ue
(1) Note: 3.5 kW.240 V single phase/20A or
6kW.240 V 3-phase/20A or 10kW.415 V 3phase/20A = maximum power for remote
controlled devices (reflex - contactor, etc) for
incandescent lighting uses.
18
36
58
18
36
58
36
72
1
4
2
1
7
3
2
3
1
2
9
4
3
14
7
4
7
3
3
14
7
4
21
10
6
10
5
6
29
14
9
42
21
13
21
10
10
49
24
15
70
35
21
35
17
16
78
39
24
112
56
34
56
28
20
98
49
30
140
70
43
70
35
25
122
61
38
175
87
54
87
43
32
157
78
48
225
112
69
112
56
40
196
98
60
281
140
87
140
70
50
245
122
76
351
175
109
175
87
63
309
154
95
443
221
137
221
110
80
392
196
121
562
281
174
281
140
100
490
245
152
703
351
218
351
175
118
10
17
21
27
34
43
54
68
87
109
rat.
(A)
6
10
16
mercury vapour +
metallic halides
P 375W
P 1000W
P 2000W
6
10
16
high pressure
sodium vapour lamps
P 400W
P 1000W
6
10
18
36
58
18
36
58
36
72
1
2
1
0
4
2
1
2
1
2
5
2
1
8
4
2
4
2
3
8
4
2
12
6
3
6
3
6
16
8
5
24
12
7
12
6
10
28
14
8
40
20
12
20
10
16
45
22
14
64
32
20
32
16
20
56
28
17
81
40
25
40
20
25
70
35
21
101
50
31
50
25
32
90
45
28
127
64
40
64
32
40
113
56
35
162
81
50
81
40
50
141
70
43
203
101
63
101
50
63
178
89
55
255
127
79
127
63
80
226
113
70
324
162
100
162
81
100
283
141
87
406
203
126
203
101
118
10
12
15
20
25
31
39
50
63
2.
C60 circuit breaker selection tables
type
C60a
663
AC 440
DC 60 V/pole
min. voltage rating Ue min (V AC-DC)
12
insulation voltage Ui (V)
500
impulse voltage Uimp (kV)
6
number of poles
1
breaking capacity AC
AS/NZS 4898 Icn
240/415 V
4500
(A)
Ics
240/415 V
4500
AS 3947-2
Icu
130 V
10
(kA)
240 V
5
415 V
3
440 V
Ics
75 % Icu
breaking capacity DC
AS 3947-2
Icu
60 V (1P)
10
(kA)(1)
125 V (2P)
125 V (3P)
250 V (4P)
fast closing
c
isolation with positive
c
break indication
adaptable Vigi module
auxiliaries
OF, SD, OF+SD/OF
c
MN, MNs, MX-OF
c
Tm
c
connection
screwdriver (mm)
6.5 mm maximum blade (POSIDRIV No. 2)
tightening torque (N.m)
25 A: 2
63 A: 3.5
inlet dimension (mm)
HxL
25 A
8 x 6.9
(6.9)
63 A
8x8
(8.7)
utilisation temperature (C)
-5 to +60
storage temperature (C)
-40 to +70
insulating material
self-extinguishing 960 C
(1)
C60N
C60H
163
163
23
234
6000
6000
20
10
3
6000
6000
10000
7500
30
15
4
10000
7500
20
10
6
75 % Icu
30
15
10
50 % Icu
15
20
c
c
20
30
40
c
c
c
c
25
40
50
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
type
thermal magnetic trip units
magnetic Im
curve
thermal In (A)
setting current at 30 C
C60a
1
2
4
6
10
16
20
25
32
40
50
63
C60N
C60H
B
c
c
c
c
c
c
c
c
c
c
c
c
C
c
c
c
c
c
c
c
c
c
c
c
c
D
c
c
c
c
c
c
c
c
c
c
c
c
2.
C120 circuit breaker selection tables
type
current rating (A)
maximum voltage rating Ue (V)
AC
DC
minimum voltage rating Ue min (V AC-DC)
insulation voltage Ui (V)
impulse voltage Uimp (kV)
number of poles
breaking capacity AC
AS/NZS 4898 (A)
Icn
240/415 V
Ics
AS 3947-2 (kA)
Icu
130 V
230240 V
400415 V
440 V
Ics
breaking capacity DC
AS 3947-2
Icu
125 V (1P)
(kA)(2)
125 V (2P)
250 V (2P)
fast closing
isolation with positive break indication
adaptable Vigi module
auxiliaries
OF-SD, OF+SD/OF
MN, MX-OF
Tm
connection
screwdriver (mm)
tightening torque(N.m)
inlet dimension (mm)
utilisation temperature (C)
storage temperature (C)
insulating material
(1)
(2)
C120H
63125
440
125 V/pole
12
500
6
1
10125
10000
7500
20
10
3(1)
234
234
10000
15000
7500
30
15
4.5(1)
15000
20
10
6
75 % Icu
30
15
10
50 % Icu
15
25
25
40
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
6.5 mm maximum blade (POSIDRIV No. 2)
3.5
H x L: 10 x 10
-30 to +60
-40 to +70
self-extinguishing 960 C
30
50
c
c
c
c
c
c
type
thermal magnetic trip units
magnetic Im
thermal In (A)
setting current at 30 C
C120N
C120N
C120H
curve
10
16
20
25
32
40
50
63
80
100
c
c
c
c
c
c
125
c
c
c
B
c
c
c
c
c
c
c
c
c
c
C
c
c
c
c
c
c
c
c
c
c
D
c
c
c
c
c
c
c
c
c
c
3.
technical data
C60-C120 Vigi module selection tables
type
standard
class
number of poles
voltage rating Ue (V) at 50 Hz(1)
current rating (A)
sensitivity (In) at 50 Hz (mA) 30
instantaneous
300
500
selective s
300 s
resetting
simultaneous (by circuit-breaker)
separate
utilisation temperature (C)
storage temperature (C)
test button: minimum operating
130 V
thresholds at 50 Hz (V)
230/415 V
rated breaking and making capacity
of the residual current device Im (EN 61009)
connection
screwdriver
tightening torque (N.m) 25 A
63 A
terminal capacity (mm2)
25 A
Cu stranded cable
63 A
125 A
(1)
Vigi C60
Vigi C120
3.5
50
3.
technical data
auxiliary contacts and releases
OF 26924, SD 26927, OF + SD/OF 26929 auxiliary contacts
contact capacity (AS/NZS 3947-5)
le (A)
AC
cat. AC 12
DC
cat. DC 12
415 V
240 V
24 V
48 V
60 V
125 V
3
6
6
2
1.5
1.5
26946
AC
220
0.20
8
20
50
80
26947
AC
DC
415
0.30
110
0.07
120
10
60
130
0.07
48
0.46
130
1.5
48
0.23
26948
AC
DC
24
5
22
30
200
22
20
120
16
DC
26949
AC
DC
12
1.7
20
5
26979
AC
26980
AC
230
0.2
8
400
0.3
8
50
285
120
285
26960
AC
220
0.02
3
240
0.017
26961
AC
48
0.09
3
4.1
4.3
185
40
between 0.35 and 0.70 Un
-20, +50
4 mm blade (POSIDRIV No. 1)
1
26969
AC
230
0.20
8
20
50
80
0.006
3
26971
AC
400
0.30
120
0.003
3
1.2
1.3
90
290
tripping by pushbutton
1.4
1.7
26962
DC
48
0.045
3
26963
AC
220 240
0.02 0.017
200
2
20
4.1
185
3.
technical data
utilisation limits-electrical clearances
utilisation limits
utilisation limits
C60/C120
6G
30 G/11 ms
electrical clearances
blank metal plate
front door
side plate
20 mm
OFF
OFF
OFF
OFF
A=0
C=0
20 mm
B=0
D=0
SD and
OF
MN
MX
connection
by wire if
auxiliaries
max.
width 54mm
connection
by "clip"
Tm
or
OFF
ACTt
or
ACTc
or
ATB 1s
C60/C120
circuit-breaker
C60/C120
Vigi
OFF
3.
technical data
MSU release
MSU voltage threshold release
associated with the DPN, C60 and C120 circuitbreaker or with the ID residual current circuitbreaker:
tripping curve
t (s)
3
tripping curve
non-tripping curve
0
U (V)
250 270 290
310 330
350
430 450
Phase-to-neutral voltage
automatic tripping values in event of overvoltage at power frequency
between a phase and the neutral
phase-to-neutral
minimum non-tripping
voltage
time
(root mean square value in V) (in s)
maximum tripping
time
(in s)
285
310
360
410
440
no tripping
2.5
1
0.6
0.6
no tripping
0.6
0.4
0,2
0.2
application
connection
MSU 1Ph + N
U>>
MSU 3Ph + N
U>>
10
L1
L2
3.
technical data
MSU release
origin of the overvoltages
The MSU module detects overvoltages linked to
breaking of the neutral, that may be caused by:
presence of harmonics
faulty connection
operation or inspection accident
diagram
L1
L2
L3
N
Z1
Z2
Z3
U1
U2
U3
Should the neutral break, homes 2 and 3 are supplied with an artificial neutral, created by the
downstream network.
Phase-to-neutral voltage is then distributed in the impedance ratio and may assume high values.
example
in normal operation, each load (Z1, Z2, Z3) is supplied by a phase voltage
should the neutral break, the loads (Z2 and Z3) will be serial-connected and supplied by U12
(mesh voltage equal to 400V)
There are then two possibilities:
if Z2 = Z3 overvoltage does not occur and the load terminals are supplied with 230V
if Z2 Z3 overvoltages and undervoltages occur
1
U1
U1
240 V
415 V rms
U3
415 V rms
415 V rms
240 V
415 V rms
U2
240 V
U3
240 V
415 V rms
U2
415 V rms
11
4.
tripping curves
C60 circuit-breaker
B, C and D curves,
as in standard AS/NZS 4898
The operating range of the magnetic release
is as follows:
c for B curve: between 3 In and 5 In
c for C curve: between 5 In and 10 In
c for D curve: between10 In and14 In
The curves show the cold thermal tripping
limits when poles are charged and the
electromagnetic tripping limits with 2
charged poles.
C60 B curve
C60 C curve
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
10 000
5 000
1h
2 000
1 000
500
500
200
100
50
200
100
50
20
20
10
10
2
1
.5
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.02
.01
.005
.002
.001
.5 .7 1
I / In
2
3 4 5 7 10
20 30
50 70100
200300
3 4 5 7 10 14 20 30
50 70100
200300
C60 D curve
t(s)
10 000
5 000
1h
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1
12
I / In
2
.002
.001
.5 .7 1
I / In
2
3 4 5 7 10
20 30
50 70100
200300
4.
tripping curves
C60 circuit-breaker
B, C and D curves,
as in standard AS 3947.2
The operating range of the magnetic release
is as follows:
c for B curve: between 3.2 In and 4.8 In
c for C curve: between 7 In and 10 In
c for D curve: between 10 In and 14 In
The curves show the cold thermal tripping
limits when poles are charged and the
electromagnetic tripping limits with 2
charged poles.
C60 B curve
C60 C curve
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
10 000
5 000
1h
2 000
1 000
500
500
200
100
50
200
100
50
20
10
20
10
2
1
.5
2
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.02
.01
.005
.002
.001
I / In
.5 .7 1
3 4 5 7 10
20 30
50 70100
200300
3 4 5 7 10
20 30
50 70100
200300
.002
.001
I / In
.5 .7 1
3 4 5 7 10
20 30
50 70100
200300
C60 D curve
t(s)
10 000
5 000
1h
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
I / In
.5 .7 1
13
4.
tripping curves
NC100 circuit-breaker
B, C, D and MA curves
as in standard AS 3947.2
The operating range of the magnetic release
is as follows:
c for B curve: between 3.2 In and 4.8 In
c for C curve: between 7 In and 10 In
c for D curve: between 10 In and 14 In
c for MA curve: between 9.6 In and 14.4 In
The curves show the cold thermal tripping
limits when poles are charged and the
electromagnetic tripping limits with 2
charged poles.
NC100 B curve
NC100 C curve
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
10 000
5 000
1h
2 000
1 000
500
500
200
100
50
200
100
20
10
20
2
1
.5
50
10
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.02
.01
.005
.002
.001
I / In
.5 .7 1
3 4 5 7 10
20 30
50 70100
.002
.001
2
3 4 5 7 10
20 30
50 70100
200300
NC100 MA curve
NC100 D curve
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
10 000
5 000
500
500
200
100
50
200
100
50
20
10
20
2
1
.5
2
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.02
.01
.005
2 000
1 000
10
.002
.001
I / In
.5 .7 1
3 4 5 7 10
DPN circuit-breaker
10 000
5 000
1h
2 000
1 000
20 30
50 70100
200300
20 30
50 70100
200300
t(s)
500
200
100
50
20
10
5
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
I / In
.5 .7 1
14
I / In
.5 .7 1
200300
3 4 5 7 10
.002
.001
.5 .7 1
I / In
2
3 4 5 7 10
20 30
50 70100
200300
4.
tripping curves
C120N, H circuit-breaker
B and C curve, as in standard
AS/NZS 4898
D curve, as in standard AS 3947.2
The operating range of the magnetic release
is as follows:
c for B curve: between 3 In and 5 In
c for C curve: between 5 In and 10 In
c for D curve: between10 In and14 In
The curves show the cold thermal tripping
limits when poles are charged and the
electromagnetic tripping limits with 2
charged poles.
C120N B curve
C120H B curve
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
10 000
5 000
1h
2 000
1 000
500
500
200
100
200
100
50
50
20
20
10
10
2
1
.5
2
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
t < 10ms
.005
.002
.001
.5 .7 1
I / In
2
3 4 5 7 10
20 30
50 70100
200300
C120N C curve
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70100
200300
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
500
500
200
100
200
100
50
50
20
10
20
10
1
.5
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.02
.01
.005
t < 10ms
I / In
2
3 4 5 7 10
20 30
50 70100
200300
C120N D curve
t < 10ms
.002
.001
.5 .7 1
I / In
2
3 4 5 7 10
20 30
50 70100
200300
C120H D curve
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
10 000
5 000
1h
2 000
1 000
500
500
200
100
200
100
50
50
20
10
20
10
2
1
.5
2
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.002
.001
.5 .7 1
I / In
2
C120H C curve
10 000
5 000
1h
2 000
1 000
.002
.001
.5 .7 1
t < 10ms
.005
.02
.01
.005
t < 10ms
I / In
2
3 4 5 7 10
20 30
50 70100
200300
.002
.001
.5 .7 1
t < 10ms
I / In
2
3 4 5 7 10
20 30
50 70100
200300
15
4.
tripping curves
NG125 circuit-breaker
NG125 B curve
NG125 C curve
B, C and D curves
as in standard AS 3947.2
The operating range of the magnetic trip unit
is as follows:
c for B curve: between 3 In and 5 In
c for C curve: between 5 In and 10 In
c for D curve: between 10 In and 14 In
c for MA curve: between 9.6 In and 14.4 In
The curves show the cold thermal tripping
limits when poles are charged and the
electromagnetic tripping limits with 2
charged poles.
t(s)
10 000
5 000
1h
2 000
1 000
10 000
5 000
1h
2 000
1 000
500
500
200
100
50
200
100
50
20
10
20
10
2
1
.5
2
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.02
.01
.005
.002
.001
I / In
.5 .7 1
3 4 5 7 10
20 30
50 70100
.002
.001
200300
NG125 D curve
3 4 5 7 10
20 30
50 70100
200300
20 30
50 70100
200300
t(s)
t(s)
10 000
5 000
1h
2 000
1 000
500
500
200
100
50
200
100
50
20
10
20
10
2
1
.5
2
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.005
.02
.01
.005
.002
.001
16
NG125 MA curve
10 000
5 000
1h
2 000
1 000
I / In
.5 .7 1
I / In
.5 .7 1
3 4 5 7 10
20 30
50 70100
200300
.002
.001
I / In
.5 .7 1
3 4 5 7 10
4.
discrimination of earth leakage protection devices
practical rule
c sensitivity
upstream In > than downstream 2In.
c time:
upstream non-response time 1.2 times the
total opening time of the downstream device.
time
selective s
instantaneous
(s)
30 mA
100 mA 300 mA
500 mA
1000 mA
3000 mA
1000
sensitivity, Index II
100
10
1
0.37
0.20
0.15
(1)
(1)
0.05
0.03
(A)
0.030
0.100
0.300
0.500
1000
3000
current
17
5.
thermal stress and peak current limitation curves
thermal stress
limitation
5s
C60a, N, H, L (B curve)
240/415 V
c Ue:
v 240 V with 1P
v 415 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60H
63A
50A
40A
32A
25A
10 7
5
10ms
20A
16 A
10 6
10A
6A
4A
10 5
5
3A
50-63A
32-40A
20-25A
10-16A
2A
6A
10 4
1A
4A
3A
0,75 A
2A
0,5 A
10 3
1A
0,75 A
10 2
5
0,5 A
10 1
5
10 0
5
10 -1
5
t-circuit current
10-2
100
101
102
103
104
105
thermal stress
limitation
A rms
5s
C60a, N, H, L (B curve)
440 V
c Ue:
v 440 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60H
63A
50A
40A
32A
25A
10 7
5
10ms
20A
16 A
10 6
10A
3
2
6A
4A
10 5
5
3A
10-16A
6A
2A
10 4
4A
1A
3A
0,75 A
10 3
50-63A
32-40A
20-25A
2A
0,5 A
1A
0,75 A
10 2
5
0,5 A
10 1
5
10 0
5
10 -1
5
10-2
100
101
102
18
103
104
105
A rms
5.
thermal stress and peak current limitation curves
thermal stress
limitation
5s
C60a, N, H, L (C curve)
240/415 V
c Ue:
v 240 V with 1P
v 415 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60H
63A
50A
40A
32A
25A
10 7
5
10ms
20A
16 A
10 6
10A
6A
4A
10 5
5
3A
50-63A
32-40A
20-25A
10-16A
2A
6A
10 4
1A
4A
3A
0,75 A
10 3
2A
0,5 A
1A
0,75 A
10
2
5
0,5 A
10 1
5
10 0
5
10 -1
5
10
t-circuit current
-2
5
100
101
102
103
104
105
thermal stress
limitation
A rms
5s
C60a, N, H, L (C curve)
440 V
c Ue:
v 440 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60H
63A
50A
40A
32A
25A
10 7
5
10ms
20A
16 A
10 6
10A
3
2
6A
4A
10 5
5
3A
10-16A
6A
2A
10 4
4A
1A
3A
0,75 A
10 3
50-63A
32-40A
20-25A
2A
0,5 A
1A
0,75 A
10 2
5
0,5 A
10 1
5
10 0
5
10 -1
5
10-2
100
101
102
103
104
105
A rms
19
5.
thermal stress and peak current limitation curves
thermal stress
limitation
5s
C60a, N, H, L (D curve)
240/415 V
63A
50A
40A
32A
25A
10 7
5
10ms
20A
c Ue:
v 240 V with 1P
v 415 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60H
16 A
10 6
10A
6A
4A
10 5
5
3A
50-63A
32-40A
20-25A
10-16A
2A
6A
10 4
1A
4A
3A
0,75 A
10 3
2A
0,5 A
1A
0,75 A
10 2
5
0,5 A
10 1
5
10 0
5
10 -1
ms
10-2
100
101
102
103
104
105
thermal stress
limitation
A rms
5s
C60a, N, H, L (D curve)
440 V
63A
50A
40A
32A
25A
10 7
5
10ms
20A
c Ue:
v 440 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60H
16 A
10 6
10A
3
2
6A
4A
10 5
5
3A
10-16A
6A
2A
10 4
4A
1A
3A
0,75 A
10 3
50-63A
32-40A
20-25A
2A
0,5 A
1A
0,75 A
10 2
5
0,5 A
10 1
5
10 0
5
10 -1
5
10-2
100
101
102
20
103
104
105
A rms
5.
thermal stress and peak current limitation curves
peak current
limitation
C60a, N, H, L
240 V
c Ue:
v 240 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60N-B
v 4: C60H-C, D
20
15
= 0.5
63A
40A
25A
10
9
8
= 0.7
10A
7
2
= 0.8
6A
5
4
= 0.9
2
= 0.95
3ms 4
5 6 7 8 9 10 12 15
30
20
40 50
kA rms
prospective short-circuit current
peak current
limitation
C60a, N, H, L, LMA
240/415 V
c Ue:
v 240 V with 1P
v 415 V with 2, 3, 4P
v 415 V C60LMA with 2, 3P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60N
v 4: C60H-D
20
15
= 0.5
10
9
8
63A
40A
= 0.7
25A
7
6
= 0.8
10A
6A
4
= 0.9
2
= 0.95
1
1
6 7 8 9 10
15
20
30
kA rms
prospective short-circuit current
21
5.
thermal stress and peak current limitation curves
peak current
limitation
C60a, N, H, L
440 V
c Ue:
v 440 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C60a
v 2: C60N
v 3: C60H
20
15
= 0.5
10
9
8
63A
40A
25A
= 0.7
7
6
10A
= 0.8
6A
4
= 0.9
2
= 0.95
1
1
1
ms 3
6 7 8 9 10
15
20
30
kA rms
22
5.
thermal stress and peak current limitation curves
thermal stress
limitation
10
8
5
C120N, H (C curve)
240 V
c Ue:
v 240 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C120N
v 2: C120H
63A
10
5s
125A
100A
80A
10ms
50A
40A
32A
25A
7
5
20A
10 6
16A
10A
2
1
125A
100A
80A
63A
50A
40A
32A
25A
20A
16A
10A
10 5
5
10 4
5
10 3
5
10 2
5
10 1
101
102
103
104
105
thermal stress
limitation
10 8
5
C120N, H (C curve)
240/415 V
c Ue:
v 240 V with 1P
v 415 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C120N
v 2: C120H
A rms
63A
5s
125A
100A
80A
10ms
50A
40A
32A
25A
10 7
5
20A
10 6
16A
10A
10 5
5
10 4
125A
100A
80A
63A
50A
40A
32A
25A
20A
16A
10A
10 3
5
10 2
5
10 1
101
102
103
104
105
A rms
23
5.
thermal stress and peak current limitation curves
peak current
limitation
C120N, H
240 V
c Ue:
v 240 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C120N
v 2: C120H
v 5: 10-16 A
v 6: 20-25 A
v 7: 32-40 A
v 8: 50-63 A
v 9: 80-100-125 A
20
15
= 0.5
2
1
10
9
8
= 0.7
= 0.8
5
6
= 0.9
2
= 0.95
6 7 8 9 10
15
20
30
kA rms
prospective short-circuit current
peak current
limitation
C120N, H
240/415 V
c Ue:
v 240 V with 1P
v 415 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: C120N
v 2: C120H
v 5: 10-16 A
v 6: 20-25 A
v 7: 32-40 A
v 8: 50-63 A
v 9: 80-100-125 A
20
15
= 0.5
2
10
9
8
1
9
= 0.7
= 0.8
4
= 0.9
2
= 0.95
1
1
6 7 8 9 10
15
20
30
kA rms
prospective short-circuit current
24
5.
thermal stress and peak current limitation curves
thermal stress
limitation
10 8
NG125, N, H, L (C curve)
240 V
c Ue:
v 240 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: NG125a 80-100-125 A
v 2: NG125N
v 3: NG125H
v 4: NG125L
63A
5s
125A
100A
80A
10ms
50A
40A
32A
25A
10 7
5
20A
10 6
16A
10A
125A
100A
80A
63A
50A
40A
32A
25A
20A
16A
10A
10 5
5
10 4
5
10 3
5
10 2
5
10 1
10 1
10 2
10 3
5 10 5
10 4
thermal stress
limitation
10 8
NG125, N, H, L (C curve)
240/415 V
c Ue:
v 240 V with 1P
v 415 V with 2, 3, 4P
c circuit-breaker type in accordance with the
mark:
v 1: NG125a 80-100-125 A
v 2: NG125N
v 3: NG125H
v 4: NG125L
A rms
125A
100A
80A
63A
50A
40A
10 7
5s
10ms
32A
25A
20A
16A
10 6
3
1 2
10A
125A
100A
80A
63A
50A
40A
32A
25A
20A
16A
10A
10 5
5
10 4
5
10 3
5
10 2
5
10 1
10 1
10 2
10 3
10 4
10 5
A rms
25
5.
thermal stress and peak current limitation curves
peak current
limitation
NG125a, N, H, L
240 V
20
15
4
= 0.5
c
v
c
v
v
v
v
v
v
v
v
v
Ue:
240 V with 2, 3, 4P
legend:
1: NG125a
2: NG125N
3: NG125H
4: NG125L
5: 10-16 A
6: 20-25 A
7: 32-40 A
8: 50-63 A
9: 80-100-125 A
3
2
10
9
8
9
= 0.7
= 0.8
5
4
= 0.9
2
= 0.95
2
3 4 5 6 7 8 9 10
1
prospective short-circuit current
peak current
limitation
30 40 50
20
100
kA rms
NG125a, N, H, L
240/415 V
20
4
3
15
2
= 0.5
c
v
v
c
v
v
v
v
v
v
v
v
v
Ue:
240 V with 1P
415 V with 2, 3, 4P
legend:
1: NG125a
2: NG125N
3: NG125H
4: NG125L
5: 10-16 A
6: 20-25 A
7: 32-40 A
8: 50-63 A
9: 80-100-125 A
1
10
9
8
8
7
= 0.7
= 0.8
5
4
= 0.9
= 0.95
2
3 4 5 6 7 8 9 10
1
prospective short-circuit current
26
20
30 40 50
100
kA rms
6.
temperature derating
according to ambient
temperature
20
25
30
35
40
45
50
55
60
rating (A)
1
2
3
4
6
10
16
20
25
32
40
50
63
1.05
2.08
3.18
4.24
6.24
10.6
16.8
21.0
26.2
33.5
42.0
52.5
66.2
1.02
2.04
30.9
4.12
6.12
10.3
16.5
20.6
25.7
32.9
41.2
51.5
64.9
1.00
2.00
3.00
4.00
6.00
10.0
16.0
20.0
25.0
32.0
40.0
50.0
63.0
0.98
1.96
2.91
3.88
5.88
9.70
15.5
19.4
24.2
31.4
38.8
48.5
61.1
0.95
1.92
2.82
3.76
5.76
9.30
15.2
19.0
23.7
30.4
38.0
47.4
58.0
0.93
1.88
2.70
3.64
5.64
9.00
14.7
18.4
23.0
29.8
36.8
45.5
56.7
0.90
1.84
2.61
3.52
5.52
8.60
14.2
17.8
22.2
28.4
35.6
44.0
54.2
0.88
1.80
2.49
3.36
5.40
8.20
13.8
17.4
21.5
28.2
34.4
42.5
51.7
0.85
1.74
2.37
3.24
5.30
7.80
13.3
16.8
20.7
27.5
33.2
40.5
49.2
temperature (C)
20
25
30
35
40
45
50
55
60
rating (A)
1
2
3
4
6
10
16
20
25
32
40
50
63
1.10
2.18
3.42
4.52
6.48
11.4
17.9
22.2
27.7
35.2
44.4
56.0
71.8
1.08
2.14
3.30
4.40
6.36
11.1
17.4
21.6
27.0
34.2
43.6
54.5
69.9
1.05
2.08
3.21
4.24
6.24
10.7
16.9
21.2
26.5
33.6
42.4
53.0
67.4
1.03
2.04
3.12
4.12
6.12
10.4
16.4
20.6
25.7
32.9
41.2
51.5
65.5
1.00
2.00
3.00
4.00
6.00
10.0
16.0
20.0
25.0
32.0
40.0
50.0
63.0
0.97
1.96
2.88
3.88
5.88
9.60
15.5
19.4
24.2
31.0
38.8
48.5
60.4
0.95
1.90
2.77
3.72
5.76
9.20
15.0
18.8
23.5
30.4
37.6
46.5
57.9
0.92
1.86
2.64
3.56
5.58
8.80
14.4
18.2
22.7
29.4
36.4
45.0
55.4
0.89
1.80
2.52
3.44
5.46
8.40
13.9
17.6
21.7
28.4
34.8
43.0
52.9
C60H: D curve
27
6.
temperature derating
according to ambient
temperature (continued)
DPN Vigi
temperature (C)
20
25
30
35
40
45
50
55
60
rating (A)
1
2
3
6
10
16
20
25
32
40
1.04
2.08
3.16
6.26
10.5
16.8
21
26.1
33.4
41.6
1.02
2.04
30.8
6.13
10.2
16.4
20.5
25.5
32.7
41.8
1
2
3
6
10
16
20
25
32
40
0.98
1.96
2.92
5.87
9.75
15.6
19.5
24.4
31.2
39.2
0.96
1.91
2.83
5.73
9.49
16.2
19
23.9
30.5
38.3
0.93
1.87
2.75
5.60
9.23
14.8
18.5
23.3
29.7
37.4
0.91
1.82
2.66
5.45
8.96
14.3
17.9
22.7
28.9
36.5
0.89
1.77
2.57
5.31
8.67
14.9
17.4
22.1
28
35.6
0.86
1.72
2.47
5.16
8.38
13.4
16.8
21.4
27.1
34.6
temperature (C)
20
25
30
35
40
45
50
55
60
rating (A)
1
2
3
6
10
16
20
25
32
40
1.1
2.2
3.3
6.6
11
17.6
22
27.5
35.5
44.5
1.1
2.2
3.3
6.5
10.7
17.4
21.5
27
35
43.5
1
2.1
3.2
6.3
10.5
17
21
26
34
42.5
1
2.1
3.1
6.1
10.3
16.5
20.5
25.5
33
41
1
2
3
6
10
16
20
25
32
40
0.95
1.95
2.9
5.8
9.7
15.4
19.5
24
31
38.5
0.9
1.9
2.8
5.7
9.5
15
19
23.5
30
37
0.9
1.8
2.7
5.5
9
14.4
18.5
23
29
36
0.9
1.7
2.6
5.3
8.5
13.9
18
22
28
34
temperature (C)
20
25
30
35
40
45
50
55
60
rating (A)
10
16
20
25
32
40
50
63
80
100
125
11
17.6
22
27.5
35.2
44
55
69.3
88
110
137.5
10.75
17.2
21.5
26.87
34.4
43
53.75
67.72
86
107.5
134.3
10.5
16.8
21
26.25
33.6
42
52.5
66.15
84
105
131.2
10.25
16.4
20.5
25.62
32.8
41
51.25
64.57
82
102.5
128.1
10
16
20
25
32
40
50
63
80
100
125
9.75
15.6
19.5
24.37
31.2
39
48.75
61.42
78
97.5
121.8
9.5
15.2
19
23.75
30.4
38
47.5
59.85
76
95
118.7
9.25
14.8
18.5
23.12
29.6
37
46.25
58.27
74
92.5
121.8
9
14.4
18
22.5
28.8
36
45
56.7
72
90
112.5
C32H - DC
NG125
28
6.
temperature derating
according to ambient
temperature (continued)
C120
according AS/NZS 4898
temperature (C)
20
25
30
35
40
45
50
55
60
rating (A)
10
16
20
25
32
40
50
63
80
100
125
10.8
17.0
21.5
27.3
34.3
43.3
54.4
68.1
85.9
109.1
136.7
10.4
16.5
20.7
26.2
33.2
41.7
52.2
65.6
83.0
104.7
131.0
10
16
20
25
32
40
50
63
80
100
125
9.6
15.5
19.2
23.7
30.8
38.3
47.7
60.3
76.9
95.1
118.7
9.2
14.9
18.4
22.4
29.5
36.4
45.2
57.5
73.6
90.0
112.1
8.7
14.3
17.6
21.0
28.2
34.5
42.6
54.5
70.2
84.5
105.0
8.2
13.7
16.7
19.5
26.8
32.5
39.8
51.3
66.6
78.7
97.4
7.7
13.1
15.7
17.8
25.4
30.3
36.9
48.0
62.8
72.4
89.2
7.2
12.4
14.8
16.0
23.8
28.0
33.6
44.4
58.7
65.4
80.1
according AS 3947
temperature (C)
20
25
30
35
40
45
50
55
60
rating (A)
10
16
20
25
32
40
50
63
80
100
125
11.7
18.6
23.4
29.8
37.4
47.2
59.3
74.2
93.7
118.9
149.0
11.3
18.0
22.6
28.6
36.2
45.4
56.9
71.5
90.5
114.1
142.8
11
17
22
27
35
44
55
69
87
109
136
10.5
16.9
21.0
25.9
33.6
41.7
52.0
65.7
83.8
103.7
129.4
10.0
16.3
20.1
24.4
32.2
39.7
49.3
62.6
80.2
98.1
122.1
9.5
15.6
19.2
22.9
30.8
37.6
46.4
59.4
76.5
92.1
114.4
9.0
15.0
18.2
21.2
29.2
35.4
43.4
56.0
72.6
85.7
106.2
8.4
14.3
17.2
19.4
27.7
33.0
40.2
52.3
68.4
78.9
97.2
7.8
13.6
16.1
17.5
26.0
30.5
36.7
48.4
64.0
71.3
87.3
according to the
installation mode
temperature (C)
25
30
40
50
60
rating (A)
25
40
63
80
100
125
32
46
75
95
123
135
30
44
70
90
120
133
25
40
63
80
100
125
23
36
56
72
105
128
20
32
50
65
90
110
29
6.
temperature derating
example
C60 only
temperature (C)
30 C
40 C
real
rating (A)
20
25
32
real
rating (A)
19
23.7
30.4
real
rating (A)
20 x 0.8 = 16
25 x 0.8 = 20
32 x 0.8 = 25.6
C60a
30
nominal
rating (A)
20
25
32
real
rating (A)
19 x 0.8 = 15.2
23.7 x 0.8 = 18.96
30 x 0.8 = 24
6.
power loss
circuit breakers and switches
How much power is lost per pole?
The table below gives the power loss of the devices in Watts for each rating, per pole, for the rated current:
rating
1.6
2.5
2.4
2.4
2
3
6.3
10
3
2
1.7
2
2
12.5
16
20
25
3.4
2.6
2.3
2.5
2.5
3.7
2.9
2.65 2.7
3
3.2
3
3.2
32
40
50
63
80
100
125
4.7
3
3.8
3.5
3.5
3.5
3.6
4
4
4.6
4.5
4.7
4.7
4.5
4.8
5.5
5.5
6.6
4.5
6
6
6
7
7
8
9
9
5.5
circuit-breakers
DPN
C60
C120
NG125
NG125LMA
2.3
2.5
1.5
switches
NG125NA
31
7.
protection of LV/LV transformers
current inrushes
on energisation
I
10 to 25 ln
In
choice of protection
primary
winding
32
7.
protection of LV/LV transformers
three-phase transformers
(400 V primary)
transformer
P (kVA)
In (A)
D curve circuit-breaker
Usc (%)
type
5
6.3
8
10
12.5
16
20
25
31.5
40
50
63
7.9
9
11.5
14.4
18
23
29
36
45.4
57.7
72.1
108
4.9
4.9
4.3
5.9
5.2
4.9
5.6
5.3
5
5
5
5
10
16
20
25
32
40
40
50
63
80
100
125
three-phase transformers
(230 V primary)
transformer
P (kVA)
In (A)
D curve circuit-breaker
Usc (%)
type
5
6.3
8
10
12.5
16
20
25
32
12.5
15.8
20
25
31
40
50.2
62.7
80
4.9
4.9
4.3
5.9
5.2
4.9
5.6
5.3
5.3
20
25
32
40
40
50
63
80
100
single-phase transformers
(400 V primary)
transformer
P (kVA)
In (A)
D curve circuit-breaker
Usc (%)
type
1
1.6
2.5
4
5
6.3
8
10
12.5
16
20
25
5
4
6.25
10
12.5
15.7
20
25
31.2
40
50
62.7
5.2
4
3
2.1
1.9
5
5
5
5
4.5
4.5
5.3
6
10
16
20
32
40
50
63
63
80
100
125
single-phase transformers
(230 V primary)
transformer
P (kVA)
In (A)
D curve circuit-breaker
Usc (%)
type
0.1
0.16
0.25
0.4
0.63
1
1.6
2.5
4
5
6.3
8
10
12.5
16
0.4
0.7
1.1
1.8
2.8
4.5
7
11
18
22
27.4
34.8
43.5
54.3
65.6
13
10.5
9.5
7.5
7
5.2
4
3
2.1
5
5
5
5
5
5
1
2
3
4
6
10
16
20
25
32
63
80
100
100
125
C60
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
NC100 / C120 / NG125
NC100 / C120 / NG125
C120 / NG125
C60
C60
C60
C60
C60
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
C60 / NC100 / C120 / NG125
NC100 / C120 / NG125
NC100 / C120 / NG125
NC100 / C120 / NG125
C120 / NG125
33
8.
utilisation in 400Hz
ID
1
2
3
4
class rating
(A)
1.5
curve number
sensitivity (mA)
sens. (A)
10 30 100 300 1 A 3 A
ID
AC
25
25-40
63-80-100
2
-
1
1
2
1
1
1
1
1
all types
s
0.5
10
DPN Vigi
50 60
90
150
250
350 400 Hz
4
8
2
class rating
(A)
curve number
sensitivity (mA)
10
30
300
DPN Vigi
AC
1.5
0.5
10
34
50 60
90
150
250
350 400 Hz
25
8.
utilisation in 400Hz
C60 Vigi
1
2
3
4
class rating
(A)
1.5
curve number
sensitivity (mA)
sens. (A)
10 30 100 300 1 A 3 A
25
63
2
-
1
2
1
1
0.5
10
50 60
90
150
250
350 400 Hz
25
40-63
2
-
1
2
1
1
all types
s
Note:
In 400 Hz, threshold variation means there is
a risk of the residual current device test
circuit failing to operate when the test button
is pressed.
According to international publications
(IEC 60479-2), the human body is less
sensitive to current flow at 400 Hz, so that,
despite frequency desensitisation of residual
current devices, the latter continue to
provide protection of persons. The method
for choosing residual current devices in 400
Hz is thus the same as in 50 Hz.
35
9.
circuits supplied with DC current
choosing a circuit breaker
c nominal current which is used to choose
current rating
c nominal voltage which is used to
determine the number of serial-connected
poles contributing to breaking
types of network
earthed networks
unearthed networks
a
U/2
+
U/2
analysis
of each
fault
fault A
fault B
fault C
the most unfavourable case
distribution of the
breaking poles
maximum lsc
only the positive polarity is
concerned
maximum lsc
both polarities are concerned
no effect
fault A
all the poles effectively contributing
to breaking are serial-connected
on the positive polarity (1) (2)
A
b
no effect
maximum lsc
both polarities are concerned
no effect
fault B
distribute the number of poles
required for breaking
on each polarity
Example
What is the short-circuit current at the
terminals of a stationary battery with the
following characteristics:
c capacity: 500 Ah
c maximum discharge voltage: 240 V
(110 x 2.2 V cells)
c discharge current: 300 A
c backup time: 1/2 hour
c internal resistance: 0.5 m per cell
240 V DC
300 A
500 Ah
Ri = 0.5 m/cell
36
Isc
Answer
Ri = 110 x 0.5.10-3 = 55.10-3
240
= 4.4 kA
55.10-3
As shown in the calculation above, shortcircuit currents are relatively small.
Note: if internal resistance is not known, the
following approximate formula can be used:
lsc = kC where C is the battery capacity
expressed in Ampere/hour and k is a
coefficient close to 10 and in all cases
always less than 20.
lsc =
9.
circuits supplied with DC current
choosing a circuit breaker
choosing DC circuit-breakers
type
overload
protection
(thermal)
1-2-3-6-10-16-20-25-32-40
10-15-20-25-32-38
10-16-20-25-32-40
6-10-16-20-25-32-40-50-63
1-2-3-4-6-10-16-20-25-32-40-50-63
1-2-3-4-6-10-16-20-25-32-40-50-63
50-63-80-100
10-16-20-25-32-40-50-63
63-80-100-125
10-16-20-25-32-40-50-63-80-100-125
10-16-20-25-32-40-50-63-80-100-125
10-16-20-25-32-40-50-63-80-100-125
10-16-20-25-32-40-50-63-80-100-125
20 (1P)
15 (1P)
10 (1P)
15 (1P)
20 (1P)
25 (1P)
20 (1P)
50 (1P)
15 (IP) 15(IP)
25(IP)
25(IP)
25 (1P)
36 (1P)
50 (1P)
10 (1P)
20 (2P)
10 (2P)
20 (2P)
25 (2P)
30 (2P)
30 (2P)
50 (1P)
15(IP)
25(IP)
25 (1P)
36 (1P)
50 (1P)
magnetic
threshold
overrating
coefficient
special DC
1.43
1.38
1.38
1.38
1.38
1.42
1.42
1.42
1.42
1.42
16-25-40-63-80-100
16-25-40-63-80-100
16-25-40-63-80-100
80-100-125-160
80-100-125-160
80-100-125-160
160-200-250
160-200-250
160-200-250
MP1/MP2
MP1/MP2/MP3
P21/P41-1250
50 (1P)
85 (1P)
100 (1P)
50 (1P)
85 (1P)
100 (1P)
50 (1P)
85 (1P)
100 (1P)
85 (1P)
85 (1P)
50 (1P)
100 (3P)
100 (3P)
100 (3P)
100 (4P)
100 (4P)
multi 9
C32H-DC(1)
XC40
C60a
C60N
C60H
C60L
NC100H
NC100LH
C120N
C120H
NG125N
NG125H
NG125L
20 (2P)
45 (3P)
20 (3P)
30 (3P)
40 (3P)
50 (3P)
40 (3P)
10 (2P)
50 (4P)
25 (4P)
40 (4P)
50 (4P)
60 (4P)
20 (4P)
50 (1P)
40(2P)
50(2P)
25 (2P)
36 (2P)
50 (2P)
50 (3P)
special DC
ditto AC
ditto AC
ditto AC
ditto AC
ditto AC
ditto AC
ditto AC
25 (4P)
36 (4P)
50 (4P)
ditto AC
ditto AC
ditto AC
50 (1P)
85 (1P)
100 (1P)
50 (1P)
85 (1P)
100 (1P)
50 (1P)
85 (1P)
100 (1P)
85 (1P)
85 (1P)
50 (1P)
50 (1P)
85 (1P)
100 (1P)
50 (1P)
85 (1P)
100 (1P)
50 (1P)
85 (1P)
100 (1P)
85 (1P)
85 (1P)
50 (2P)
50 (2P)
85 (2P)
100 (2P)
50 (2P)
85 (2P)
100 (2P)
50 (2P)
85 (2P)
100 (2P)
85 (2P)
85 (2P)
50 (3P) 25 (3P)
100 (3P)
100 (3P)
100 (3P)
100 (4P)
100 (4P)
25(2P)
30(2P)
compact
NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
NS400H
NS630H
C1251N-DC
thermal
inoperative,
provide an
external relay
(if necessary)
special
MP1/MP2/MP3
P21/P41
DC current (2)
trip units
masterpact
M10-DC
M20-DC
M40-DC
M60-DC
M80-DC
1000
2000
4000
6000
8000
dina(3)1.5 to 20 kA
dina(3)1.5 to 20 kA
dina(3)1.5 to 20 kA
dina(3) 9 to 40 kA
dina(3) 9 to 40 kA
(1) the C32H-DC special DC circuit-breaker is equipped with a permanent magnet, which requires strict respect of polarities
(2) for memory:
MP1 Im adjustable from 800 to 1600 A
MP2 Im adjustable from 1200 to 2500 A
MP3 Im adjustable from 2000 to 4000 A
P21-1250 Im adjustable from 1600 to 3200 A
P41-1250 Im adjustable from 3200 to 6400 A
(3) there are 7 versions of the dina 1500/3000 A trip units - 3/6 kA - 6/12 kA - 12/20 kA - 9/18 kA - 12/24 k A - 20/40 kA.
Note: the masterpact switches, HI type in the three-pole version with a rating from M08 to M63, can be used in DC up to 125 V DC (one pole on the positive polarity, one pole on the negative
polarity and one pole not used).
examples
How to provide protection of a 80 A
outgoer on a 125 V DC network whose
negative polarity is earthed: lsc = 15 kA?
+
125 V =
+
250 V =
250 V =
100 A
four-pole
NC100H
80 A
three-pole
NC100H
load
load
400 A
two-pole
NS400H
load
37
10.
determination of short circuit current
calculation of Isc
Maximum short-circuit current downstream of an MV/LV transformer
The values indicated in the table below correspond to a bolted 3-phase short-circuit
across the LV terminals of an MV/LV transformer connected to a network with a shortcircuit power of 500 MVA.
433 V (1)
In (A)
Isc (kA)
Usc (%)
315
420.0
10.5
4
400
533.3
13.3
4
500
666.7
16.7
4
433 V (1)
In (A)
Isc (kA)
Usc (%)
2000
2667
41.0
6.5
2500
3333
47.6
7
3150
4200
60.0
7
630
840
21.0
4
Notes:
(1)
Rated voltage between phases of the
transformer under noload conditions.
(2)
To connect several transformers in
parallel, the transformers should have the
same Usc, the same transformation ratio
and the same coupling.
The power ratio between the 2
transformers should be a maximum of 2.
estimation of Isc
The tables quickly give a good evaluation of
the short circuit current at a point in the network
when the short circuit current upstream the
CSA, constitution and length of the cable are
known.
To obtain more precise values, particularly
in the case of major installations, a detailed
calculation has to be carried out. In addition,
the cascading technique enables a circuit
breaker with a breaking capacity less than the
prospective short-circuit current to be installed
downstream provided a current limiting circuit
breaker is fitted upstream.
The values are calculated using the resistivity
of copper at 25C.
Example
In the 415V switchboard, choose on the line
corresponding to the cable cross-sectional area:
70 sq. mm, the nearest lower value to the cable length:
75m. The crossing of this column with the line which
corresponds to the nearest higher value of the upstream
short-circuit current Isc1=40kA, gives the required
short-circuit current value: 8kA.
38
CSA per
phase
conductor (mm2)
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
0.8
1
1.2
1.5
0.9
1
1.1
1.4
1.7
1
1.1
1.3
1.6
1.9
0.9
1.1
1.2
1.5
1.8
2.2
94
85
76
67
58
49
39
34
29
25
20
15
10
7
5
93
84
75
66
57
48
39
34
29
25
20
15
10
7
5
92
83
75
66
57
48
39
34
29
24
20
15
10
7
5
1
1.3
1.4
1.6
2
2.4
1.1
1.5
2
2.5
2.7
3
4
5
1
1.5
2.1
3
4
5
5.5
6.5
8
9.5
91
83
74
65
57
48
39
34
29
24
20
15
10
7
5
83
76
69
61
54
46
37
33
28
24
19
15
10
7
5
71
66
61
55
48
42
35
31
27
23
19
14
9.5
7
5
0.9
1.3
1.9
2.7
3.5
5
6.5
7
8
10
12
67
62
57
52
46
40
33
30
26
22
18
14
9.5
7
5
Upstream
Isc (kA)
100
90
80
70
60
50
40
35
30
25
20
15
10
7
5
94
85
76
67
58
49
39
34
30
25
20
15
10
7
5
1
1.6
2.2
3
4.5
6
7.5
8
9.5
12
15
0.8
1.4
2.1
3
4
6
8
10
11
13
16
19
1.1
1.7
2.6
3.5
5.5
7.5
10
13
14
16
20
24
0.8
1.3
2.1
3.5
5
7.5
11
15
20
25
27
32
40
49
1
1.7
2.5
4
7
10
15
21
30
40
50
55
65
80
95
0.8
1.3
2.1
3
5.5
8.5
13
19
27
37
50
65
70
80
100
120
1
1.6
2.5
4
6.5
10
16
22
32
44
60
75
80
95
120
150
1.3
2.1
3.5
5
8.5
14
21
30
40
60
80
100
110
130
160
190
1.6
2.6
4
6.5
11
17
26
37
55
75
100
130
140
160
200
240
3
5
8.5
13
21
34
50
75
110
150
200
250
270
320
400
6.5
10
17
25
42
70
100
150
210
300
400
8
13
21
32
55
85
130
190
270
370
9.5
16
25
38
65
100
160
220
320
13
21
34
50
85
140
210
300
16
26
42
65
110
170
260
370
32
50
85
130
210
340
17
16
16
16
15
14
13
13
12
11
10
8.5
6.5
5
4
14
14
14
14
13
13
12
11
11
10
9
8
6.5
5
4
11
11
11
11
10
10
9.5
9
9
8.5
7.5
7
5.5
4.5
3.5
9
9
9
9
8.5
8.5
8
8
7.5
7
6.5
6
5
4
3.5
5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4
4
4
3.5
2.9
2.5
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.3
2.3
2.3
2.2
2.1
2
1.8
1.7
2
2
2
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.8
1.8
1.7
1.6
1.4
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.4
1.3
1.3
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.1
1.1
1.1
1
1
1
1
1
1
1
1
1
1
1
0.9
0.9
0.9
0.8
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Downstream
Short circuit current (kA)
63
58
54
49
44
39
32
29
25
22
18
14
9.5
6.5
5
56
52
49
45
41
36
30
27
24
21
17
13
9.5
6.5
5
50
47
44
41
38
33
29
26
23
20
17
13
9
6.5
5
33
32
31
29
27
25
22
21
19
17
14
12
8.5
6
4.5
20
20
19
18
18
17
15
15
14
13
11
9.5
7
5.5
4
11.
coordination
upstream: fuse
downstream: circuit breaker
Combination rules
t (s)
D1
discrimination
Discrimination is guaranteed by:
c placing a fuse upstream with the lowest
possible rating,
v its value is determined by the magnetothermal tripping characteristics of the
downstream circuit-breaker.
c ensuring that the lower threshold of the
fuse is greater than the highest threshold of
the circuit-breaker.
cascading
Cascading is guaranteed by:
c placing a fuse upstream with the highest
possible rating.
v its value is determined by the pre-arcing
characteristic of the fuse
v if it is too high, cascading will not occur,
and the circuit-breaker alone will protect the
circuit.
c ensure that:
v the thermal stress (I2t) and the current
limited by the fuse () are compatible with
the breaking capacity of the circuit-breaker
only,
v the maximum thermal stress of the
circuit-breaker (Icu) is equal to the
pre-arcing thermal stress of the upstream
fuse.
D2
I (A)
l2t (A2S)
C
A
Icu
I (A)
39
11-1.
backup
upstream: C60, NC100, NG125, NS100 or NS160
downstream: isolator
short-circuit current withstand of the circuit-breaker / switch combination
standard: IEC 947.2
unit: kA rms
upstream
downstream
Multi 9 switch (240 V)
l 20
l 32
l 40 - 63
l 100 - 125
Multi 9 switch (415 V)
l 20
l 32
l 63
l 100
NG125NA
63 - 80 A
100 A
125 A
Interpact switch (415 V)
INS40
INS63
INS100
INS125
INS160
circuit-breaker
C60
a
N
H
6.5
5.5
7
6.5
5.5
7
6.5
5.5
7
4.5
4
5
4.5
4
5
4.5
4
5
10
10
10
10
NC100
H
C120
N
6.5
5.5
7
3
3
5
7
3
3
5
7
4.5
4.5
6.5
15
4.5
4.5
6.5
15
4.5
4.5
6.5
15
4.5
4
5
2
2
3
5
2
2
3
5
3
3
6
10
3
3
6
10
3
3
6
10
10
10
10
10
10
10
16
16
16
36
36
36
10
10
10
10
10
10
10
10
10
10
16
16
16
16
16
36
36
36
36
36
10
10
NG125
circuit-breaker
C60
a
N
H
NC100
H
C120
N
NG125
N
H
40
50/63
100/125
21
21
42
42
63
63
84
63
42
42
42
42
42
63
63
63
105
105
105
154
154
154
220
220
220
40 A
50/63 A
100 A
125 A
10.5
10.5
21
21
32
32
42
32
21
21
21
21
21
21
21
32
32
32
32
53
53
53
53
75
75
75
75
105
105
105
105
downstream
Switch (240 V AC)
40
NS100
N
H
NS160
N
H
50
50
50
25
25
36
70
36
70
25
36
36
25
70
70
25
70
70
50
50
50
50
50
25
25
25
36
36
70
36
36
70
25
25
36
36
36
25
25
70
70
70
25
25
70
70
70
11-1.
backup
upstream: C60, NC100, C120, NG125 circuit breaker or fuses
downstream: ID, RCCB residual current circuit breakers
residual current circuit-breaker
Example
2P ID + downstream C60 combination
Isc withstand: 25kA.
NG125N
ID 2P
80 A
C60N
2P
electrodynamic protection
short-circuit current (kA rms)
upstream
downstream
residual current circuitbreakers
2 P (220240 V)
25 A
40 A
63 A
80/100 A
4 P (380415 V)
25 A
40 A
63/80 A
100 A
circuit-breaker
DPN C60a C60N C60H C60L NC100H C120 NG125N NC100L NC100LS
NG125H
6
6
10
10
6
6
16
16
16
20
20
20
45
45
30
10
10
10
10
8
8
8
10
10
10
25
20
15
7
7
7
5
gl or gG fuse (a)
NC100LH 16 25 32 40
50
63
80
100
10
10
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
100
100
100
100
100
100
100
100
100
100
100
100
80
80
80
80
50
50
50
50
30
30
30
30
20
20
20
20
10
10
10
10
7
7
15
15
15
15
15
15
15
7
18
18
18
8
20
20
20
20
20
20
20
10
100
100
100
100
100
100
100
100
100
100
100
80
80
80
80
50
50
50
50
30
30
30
30
10
20
20
20
3
10
10
10
3
41
11-1.
backup
upstream: DS/DIN fuses
downstream: C60, V40H, QO, Isolator, ID RCCB's
upstream: BS/DIN fuses (415V)
downstream: multi 9 MCB's
UPSTREAM FUSE
T type (BS88 or gG)
160A
Inc (kA)
125A
C60N
C60H
V40H
QOE (rcd/mcb)
QO---EC10
63kA
50kA
Is
160A
200A
C60N
C60H
V40H
QOE (rcd/mcb)
QO---EC10
C60N
C60H
V40H
QOE (rcd/mcb)
QO---EC10
C60N
C60H
C60N
C60H
3.0kA
3.8kA
3.8kA
4.5kA
2.3kA
This table is based on test data and complies with the requirements for switchboards to AS3439-1 (referenced standards
AS3947.2, AS/NZS4898). tests were carried out using GEC fuses.
Refer to AS3000 wiring rules, Clauses 2.4.4.3 and 2.8.3.3.1 regarding requirement for back up protection and control.
Fuse ratings are maximum sizes.
Where 200A fuses and C60 MCBs are used in association, it is recommended that in the event of a fault where the fuses
are blown, that the downstream MCB should be inspected.
downstream
(kA rms)
upstream
gG or BS fuses
20A
I 20
I 32
I 40-63
I 100
I 125
32A
63A
100A
8
10
6
6
downstream
(kA rms)
42
125A
upstream
gG or BS fuses
25A
ID25
ID40
ID63
ID80
100
40A
63A
80A
80
30
20
11-2.
IEC 60947.2 cascading
230...240V
upstream: multi 9
downstream: multi 9
reinforced breaking capacity (kA)
upstream
DPN
C60a
C60N
C60H
C120N
C120H
NG125H
NG125LMA
10
20
30
20
30
70
100
20
30
15
20
50
40
50
50
70
70
70
70
50
70
70
70
100
100
100
70
70
100
downstream
rated breaking
capacity
DPN
6
C60a
10
C60N
20
C60H
30
C60L (25)
50
C60L (32-40)
40
C60L (50-63)
30
C120N
20
C120H
30
NG125H
70
10
20
15
30
30
20
40
30
30
30
upstream: Compact NS
downstream: multi 9
reinforced breaking capacity (kA)
upstream
NSA160N
NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
50
85
100
150
85
100
150
85
100
150
25
25
25
25
25
30
40
50
50
50
80
100
100
60
80
85
100
80
60
80
60
80
100
150
30
50
60
40
60
80
30
40
60
80
30
30
50
60
25
25
40
60
80
30
85
100
85
100
40
60
80
30
25
70
85
downstream
rated breaking
capacity
C60a
10
C60N
20
C60H
30
C120N
20
C120H
30
NG125H
70
NG125L/MA
100
70
85
43
11-2.
IEC 60947.2 cascading
400...415V
upstream: multi 9
downstream: multi 9
reinforced breaking capacity (kA)
C60N
upstream
C60H
C60L
i 25 A
32/40 A 50/63 A
C120N
C120H
NG125a
NG125N
NG125H
NG125L
NG125LMA
downstream
C60a
C60N
C60H
C120N
C120H
NG125H
rated breaking
capacity
5
10
15
10
15
36
10
15
25
20
15
10
15
16
25
36
50
10
15
15
25
25
25
25
25
20
20
15
15
10
15
15
15
20
15
15
25
25
25
25
20
25
36
25
36
25
36
36
36
36
50
15
15
upstream: Compact NS
downstream: multi 9
reinforced breaking capacity (kA)
upstream
NS100 N
NSA160N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
25
70
150
36
70
150
36
70
150
25
25
25
25
25
25
30
50
40
30
25
25
50
70
30
50
40
30
25
25
100
150
25
30
30
25
25
25
30
50
40
30
25
25
50
70
30
50
40
30
25
25
70
100
25
30
30
25
25
25
30
40
40
30
25
25
36
50
30
40
40
30
25
25
50
70
downstream
rated breaking
capacity
C60N
6
C60H ( 40A)
10
C60H (50-63A)
10
(NC100H)
10
C120N
10
C120H
15
NG125H
36
NG125L/MA
50
44
11-3.
discrimination
downstream circuit-breaker
The values indicated in the tables are
guaranteed irrespective of the settings.
downstream device
The values indicated in the tables are
guaranteed irrespective of the settings.
upstream circuit-breaker
The values indicated in the tables are
guaranteed provided that the following
conditions are met:
c thermal magnetic trip units: highest
thermal and magnetic settings
c STR22SE/STR23SE electronic trip units:
short delay settings u 1.5 times the
downstream short-circuit protection setting
(magnetic or instantaneous)
c STR53UE electronic trip units:
v short delay setting u 1.5 times the
downstream short-circuit protection setting,
v time delay index > downstream trip unit
time delay index
upstream device
The tables give the discrimination limits for
the various trip unit ratings.
The values indicated in the tables are
guaranteed provided that the following
conditions are met:
c thermal magnetic trip units:
highest magnetic setting, highest thermal
setting, u 3 times the rating of the
downstream trip unit or thermal relay
c STR22SE/STR23SE and STR53UE
electronic trip units:
v short delay setting u 1.5 times the
downstream short-circuit protection setting
(magnetic or instantaneous)
v short time delay index (if STR53UE) >
downstream device time delay index
v long delay setting u 3 times the rating of
the downstream trip unit or thermal relay.
45
11-3.
discrimination
upstream: NG125H/C120N, H, B, C curves
downstream: DPN
upstream
ln (A)
downstream
rating
discrimination limit (A)
DPN
1
B, C curves
2
3
6
10
16
20
25
32
40
NG125 H, C curve
10
16
20
300
150
80
500
300
140
700
500
300
170
25
32
40
50
63
80
100
125
1000
700
500
400
200
1500
1000
700
500
350
270
2000
1500
1000
700
500
340
320
2500
2000
1500
800
600
450
400
400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
3300
2500
2100
1800
1600
3700
3700
3700
2700
2400
3000
1800
1250
1000
800
600
3000
2000
1600
1300
1000
700
The above table indicates the discrimination limits in the following cases:
- phase-to-neutral short-circuit on a 240 V single-phase distribution network, downstream of a
3 Ph + N or single-phase network.
"T" total discrimination, up to the breaking capacity of the downstream circuit-breaker.
46
11-3.
discrimination
upstream: NG125H/C120N, H, B, curves
downstream: C60 N, H, L, L-MA
upstream
ln (A)
downstream
rating
discrimination limit (A)
C60N
0.5
B, C, curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60 H, L
0.5
B, C, curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60N
0.5
D curve
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60H, L
1
D, MA curves
2
3
4
6
10
16
20
25
32
40
50
63
32
40
50
63
80
100
125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
550
300
150
700
450
300
150
1500
700
300
200
150
2200
1500
950
600
400
3100
2100
1500
1200
950
600
3500
2500
1600
1300
1000
600
4000
2800
1800
1400
1000
750
600
4500
4000
3400
2800
2500
2100
10000 10000
10000 10000
550
700
300
450
150
300
150
5500
4500
3500
2800
2500
10000
10000
2200
1500
950
600
400
10000
10000
3100
2100
1500
1200
950
600
10000
10000
3500
2500
1600
1300
1000
600
10000
10000
4000
2800
1800
1400
1000
750
600
10000
10000
6000
4500
4000
3400
2800
2500
2100
10000
10000
7000
6000
6000
6000
5000
4000
3500
2500
1600
10000
10000
10000
8000
7000
6000
6000
5500
4500
3500
2500
10000
10000
10000
10000
10000
8000
6500
6000
5500
4500
3500
2800
2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
550
700
450
1500
700
300
2200
1500
950
3100
2100
1500
1200
3500
2500
1600
1300
4000
2800
1800
1400
1000
700
450
5500
4500
3500
2500
10000
10000
1500
700
300
200
150
T
T
550
5000
4000
3500
2500
1600
1500
700
300
2200
1500
950
3100
2100
1500
1200
3500
2500
1600
1300
4000
2800
1800
1400
1000
4500
4000
3400
2800
6000
4500
4000
3400
2800
5000
4000
3500
5500
4500
7000
6000
6000
6000
5000
4000
3500
10000
8000
7000
6000
6000
5500
4500
5500
4500
3500
10000
10000
10000
8000
6500
6000
5500
4500
3500
The above tables indicate the discrimination limits in the following cases:
- phase-to-neutral short-circuit on a 230 V single-phase distribution network, downstream of a
3 Ph + N or single-phase network.
- short-circuit between two phases on a three-phase distribution network with a nominal
voltage of 230 V.
"T" total discrimination, up to the breaking capacity of the downstream circuit-breaker.
47
11-3.
discrimination (short circuit under 240V)
upstream: NG125N, H, L / C120N, H, C, curves
downstream: C60 N, H, L, L-MA
upstream
ln (A)
downstream
rating
discrimination limit (A)
C60N
0.5
B, C, Z curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60 H, L
0.5
B, C, Z curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60N
0.5
D curve
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60H, L
1
D, K, MA curves 2
3
4
6
10
16
20
25
32
40
50
63
T
T
T
T
T
T
T
T
T
T
800
400
200
1000
600
400
200
2000
1000
400
300
200
3000
2000
1300
900
500
300
4500
3000
2100
1600
1300
800
500
10000 10000
10000 10000
800
1000
400
600
200
400
200
63
80
100
125
T
T
T
T
T
T
3500
2300
1800
1400
900
650
400
4000
2500
2000
1500
1000
800
700
500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4000
3500
3000
2000
1000
700
5000
3600
2200
1500
1300
5500
3500
2500
1800
1500
5000
4000
3600
2500
2100
10000
10000
3000
2000
1300
900
500
300
10000
10000
4500
3000
2100
1600
1300
800
500
10000
10000
5500
3500
2300
1800
1400
900
650
400
10000
10000
7000
4000
2500
2000
1500
1000
800
700
500
10000
10000
10000
6000
6000
5000
4000
3500
3000
2000
1000
700
10000
10000
10000
10000
10000
8000
6500
6000
5000
3600
2200
1500
1300
10000
10000
10000
10000
10000
10000
8500
6500
6000
5500
3500
2500
1800
1500
10000
10000
10000
10000
10000
10000
10000
8000
7000
6000
5000
4000
3600
2500
2100
T
T
T
T
T
T
3500
2300
1800
1400
900
4000
2500
2000
1500
1000
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
1000
600
2000
1000
400
3000
2000
1300
900
4500
3000
2100
1600
1300
1000
600
50
10000
10000
2000
1000
400
300
200
T
T
800
40
2000
1000
400
3000
2000
1300
900
4500
3000
2100
1600
1300
5500
3500
2300
1800
1400
900
7000
4000
2500
2000
1500
1000
800
4000
3500
3000
2000
10000
8000
7000
5000
4000
3500
3000
2000
5000
3600
2200
10000
10000
10000
8000
6500
5500
5000
3600
2200
5500
3500
2500
10000
10000
10000
10000
8500
6500
6000
5500
3500
2500
5000
4000
3600
10000
10000
10000
10000
10000
8000
7000
6000
5000
4000
3600
The above tables indicate the discrimination limits in the following cases:
- phase-to-neutral short-circuit on a 240 V single-phase distribution network, downstream of a
3 Ph + N or single-phase network.
- short-circuit between two phases on a three-phase distribution network with a nominal
voltage of 240 V.
"T" total discrimination, up to the breaking capacity of the downstream circuit-breaker.
48
11-3.
discrimination (short circuit under 240V)
upstream: NG125H/C120N, H, D curves
downstream: C60 N, H, L, L-MA
upstream
ln (A)
downstream
rating
discrimination limit (A)
C60N
0.5
B, C curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60 H, L
0.5
B, C curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60N
0.5
D curve
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60H, L
1
D, MA curves
2
3
4
6
10
16
20
25
32
40
50
63
T
T
900
450
250
32
40
50
63
80
100
125
T
T
1100
700
450
200
T
T
2300
1100
450
350
250
T
T
3400
2300
1500
1000
600
350
T
T
5000
3400
2400
1800
1500
900
600
T
T
6000
4000
2600
2000
1600
1000
750
500
T
T
T
4500
2800
2300
1700
1200
900
800
600
T
T
T
6000
6000
6000
4500
4000
3400
2300
1200
800
600
T
T
T
T
T
T
6000
6000
5600
4000
2500
1700
1500
T
T
T
T
T
T
T
T
6000
6000
4000
2800
2200
1700
T
T
T
T
T
T
T
T
T
T
5500
4500
4000
2800
2300
10000 10000
10000 10000
900
1100
450
700
250
450
200
10000
10000
2300
1100
450
350
250
10000
10000
3400
2300
1500
1000
600
350
10000
10000
5000
3400
2400
1800
1500
900
600
10000
10000
6000
4000
2600
2000
1600
1000
750
500
10000
10000
7000
4500
2800
2300
1700
1200
900
800
600
10000
10000
10000
8000
7000
6000
4500
4000
3400
2300
1200
800
600
10000
10000
10000
10000
8000
6500
6000
6000
5600
4000
2500
1700
1500
10000
10000
10000
10000
10000
10000
8500
6500
6000
6000
4000
2800
2200
1700
10000
10000
10000
10000
10000
10000
10000
10000
8000
7000
5500
4500
4000
2800
2300
T
T
900
T
T
1100
700
T
T
2300
1100
450
T
T
3400
2300
1500
1000
T
T
5000
3400
2400
1800
1500
T
T
6000
4000
2600
2000
1600
1000
T
T
T
4500
2800
2300
1700
1200
900
T
T
T
6000
6000
6000
4500
4000
3400
2300
1200
T
T
T
T
T
T
6000
6000
5600
4000
2500
T
T
T
T
T
T
T
T
6000
6000
4000
2800
T
T
T
T
T
T
T
T
T
T
5500
4500
4000
900
1100
700
2300
1100
450
3400
2300
1500
1000
5000
3400
2400
1800
1500
6000
4000
2600
2000
1600
1000
7000
4500
2800
2300
1700
1200
900
10000
8000
7000
6000
4500
4000
3400
2300
1200
10000
10000
8000
6500
6000
6000
5600
4000
2500
10000
10000
10000
10000
8500
6500
6000
6000
4000
2800
10000
10000
10000
10000
10000
10000
8000
7000
5500
4500
4000
The above tables indicate the discrimination limits in the following cases:
- phase-to-neutral short-circuit on a 240 V single-phase distribution network, downstream of a
3 Ph + N or single-phase network.
- short-circuit between two phases on a three-phase distribution network with a nominal
voltage of 240 V.
"T" total discrimination, up to the breaking capacity of the downstream circuit-breaker.
49
11-3.
discrimination (short circuit under 415V)
upstream: NG125N, H, / C120N, H, B curves
downstream: C60 N, H, L, L-MA
upstream
ln (A)
downstream
rating
discrimination limit (A)
C60N
0.5
B, C curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60 H, L
0.5
0.75
1
B, C curves
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60N
0.5
0.75
1
D curve
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60H, L
1
D, MA curves
2
3
4
6
10
16
20
25
32
40
50
63
16
20
25
32
40
50
63
80
100
125
T
T
200
100
60
T
T
300
220
150
100
T
T
450
300
220
150
120
T
T
700
450
350
250
200
T
T
1000
550
450
400
300
200
T
T
1300
900
700
650
500
300
T
T
1600
1260
1150
1000
700
600
450
T
T
2800
2500
2300
2000
1750
1100
700
T
T
3500
3000
2600
2300
2000
1500
1000
800
700
T
T
5000
4500
4000
3300
3000
2600
2300
1900
1700
T
T
T
T
4500
4000
3500
3300
2900
2500
2200
1550
1100
6000
6000
200
100
60
6000
6000
300
220
150
100
6000
6000
450
300
220
150
120
6000
6000
700
450
350
250
200
6000
6000
1000
550
450
400
300
200
6000
6000
1300
900
700
650
500
300
6000
6000
1600
1260
1150
1000
700
600
450
6000
6000
2800
2500
2300
2000
1750
1100
700
6000
6000
3500
3000
2600
2300
2000
1500
1000
800
700
6000
6000
5000
4500
4000
3300
3000
2600
2300
1900
1700
6000
6000
6000
6000
4500
4000
3500
3300
2900
2500
2200
1550
1100
T
T
200
T
T
300
220
T
T
450
300
220
T
T
700
450
350
T
T
1000
550
450
400
T
T
1300
900
700
650
T
T
1600
1260
1150
1000
700
T
T
2800
2500
2300
2000
1750
T
T
3500
3000
2600
2300
2000
1500
1000
T
T
5000
4500
4000
3300
3000
2600
2300
T
T
T
T
4500
4000
3500
3300
2900
2500
2200
200
300
220
450
300
220
700
450
350
1000
550
450
400
1300
900
700
650
1600
1260
1150
1000
700
2800
2500
2300
2000
1750
3500
3000
2600
2300
2000
1500
1000
5000
4500
4000
3300
3000
2600
2300
6000
6000
4500
4000
3500
3300
2900
2500
2200
The above tables indicate the discrimination limits in the following cases:
- short-circuit between two phases on a three-phase 240/415 V distribution network .
"T" total discrimination, up to the breaking capacity of the downstream circuit-breaker.
50
11-3.
discrimination (short circuit under 415V)
upstream: NG125H/C120N, H, C curves
downstream: C60 N, H, L, L-MA
upstream
ln (A)
downstream
rating
discrimination limit (A)
C60N
0.5
B, C curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60 H, L
0.5
0.75
1
B, C curves
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60N
0.5
0.75
1
D curve
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60H, L
1
D, MA curves
2
3
4
6
10
16
20
25
32
40
50
63
40
50
63
80
100
125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
300
150
80
450
300
200
160
600
450
300
250
170
1000
600
450
350
300
210
1600
800
600
500
400
270
270
2000
1300
1000
1000
800
500
400
340
2500
2000
1600
1600
1200
800
600
500
420
5000
4000
2500
1000
1000
800
600
530
5000
4000
3200
1600
1200
1000
1000
680
5000
3600
3000
2500
1600
1000
850
5500
4000
3200
2500
1600
1300
1200
6000
6000
300
150
80
6000
6000
450
300
200
160
6000
6000
600
450
300
250
170
6000
6000
1000
600
450
350
300
210
6000
6000
1600
800
600
500
400
270
270
6000
6000
2000
1300
1000
1000
800
500
400
340
6000
6000
2500
2000
1600
1600
1200
800
600
500
420
6000
6000
6000
6000
5000
4000
2500
1000
1000
800
600
530
6000
6000
6000
6000
6000
5000
4000
3200
1600
1200
1000
1000
680
6000
6000
6000
6000
6000
6000
6000
5000
3600
3000
2500
1600
1000
850
6000
6000
6000
6000
6000
6000
6000
6000
5500
4000
3200
2500
1600
1300
1200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
300
450
300
600
450
300
1000
600
450
350
1600
800
600
500
400
2000
1300
1000
1000
800
500
2500
2000
1600
1600
1200
800
600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
300
450
300
600
450
300
1000
600
450
350
1600
800
600
500
400
2000
1300
1000
1000
800
500
2500
2000
1600
1600
1200
800
600
5000
4000
2500
1000
1000
800
6000
6000
5000
4000
2500
1000
1000
800
5000
4000
3200
1600
1200
1000
6000
6000
6000
5000
4000
3200
1600
1200
1000
5000
3600
3000
2500
1600
6000
6000
6000
6000
6000
5000
3600
3000
2500
1600
5500
4000
3200
2500
1600
6000
6000
6000
6000
6000
6000
5500
4000
3200
2500
1600
The above tables indicate the discrimination limits in the following cases:
- short-circuit between two phases on a three-phase 240/415 V distribution network .
"T" total discrimination, up to the breaking capacity of the downstream circuit-breaker.
51
11-3.
discrimination (short circuit 415V)
upstream: NG125H/C120N, H, D curves
downstream: C60 N, H, L, L-MA
upstream
ln (A)
downstream
rating
discrimination limit (A)
C60N
0.5
B, C curves
0.75
1
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60 H, L
0.5
0.75
1
B, C curves
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60N
0.5
0.75
1
D curve
2
3
4
6
10
16
20
25
32
40
50
63
discrimination limit (A)
C60H, L
1
D, MA curves
2
3
4
6
10
16
20
25
32
40
50
63
32
40
50
63
80
100
125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
200
130
550
400
250
140
900
550
350
270
220
1400
900
650
450
400
260
1900
1200
900
700
600
500
370
2400
1600
1300
1100
900
600
500
450
3000
2100
1900
1700
1300
900
700
600
500
4000
3000
2000
1400
1100
1000
800
500
4300
3300
2000
1800
1300
1300
1000
4300
3500
3000
1800
1300
1100
6000
6000
400
200
130
6000
6000
550
400
250
140
6000
6000
900
550
350
270
220
6000
6000
1400
900
650
450
400
260
6000
6000
1900
1200
900
700
600
500
370
6000
6000
2400
1600
1300
1100
900
600
500
450
6000
6000
3000
2100
1900
1700
1300
900
700
600
500
6000
6000
6000
6000
6000
4000
3000
2000
1400
1100
1000
800
500
6000
6000
6000
6000
6000
6000
4300
3300
2000
1800
1300
1300
1000
6000
6000
6000
6000
6000
6000
6000
6000
4300
3500
3000
1800
1300
1100
6000
6000
6000
6000
6000
6000
6000
6000
6000
4500
3600
2600
2200
1800
1500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
200
550
400
250
900
550
350
270
1400
900
650
450
400
1900
1200
900
700
600
500
2400
1600
1300
1100
900
600
500
3000
2100
1900
1700
1300
900
700
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
200
550
400
250
900
550
350
270
1400
900
650
450
400
1900
1200
900
700
600
500
2400
1600
1300
1100
900
600
500
3000
2100
1900
1700
1300
900
700
4000
3000
2000
1400
1100
1000
6000
6000
6000
4000
3000
2000
1400
1100
1000
4300
3300
2000
1800
1300
1300
6000
6000
6000
6000
4300
3300
2000
1800
1300
1300
4300
3500
3000
1800
1300
6000
6000
6000
6000
6000
6000
4300
3500
3000
1800
1300
The above tables indicate the discrimination limits in the following cases:
- short-circuit between two phases on a three-phase 240/415 V distribution network .
"T" total discrimination, up to the breaking capacity of the downstream circuit-breaker.
52
4500
3600
2600
2200
1800
1500
4500
3600
2600
2200
1800
6000
6000
6000
6000
6000
6000
6000
4500
3600
2600
2200
1800
11-3.
discrimination
upstream: NG125H/C120N, H, B, C curves
downstream: NG125, C120
upstream
ln (A)
downstream
discrimination limit
NG125
C120
B curve
rating
(A)
10
16
20
25
32
40
50
63
80
100
discrimination limit (A)
NG125
10
C120
16
C curve
20
25
32
40
50
63
80
100
discrimination limit (A)
NG125
10
C120
16
D curve
20
25
32
40
50
63
80
100
upstream
ln (A)
downstream
discrimination limit (A)
NG125
10
C120
16
B curve
20
25
32
40
50
63
80
100
discrimination limit (A)
NG125
10
C120
16
C curve
20
25
32
40
50
63
80
100
discrimination limit (A)
NG125
10
C120
16
D curve
20
25
32
40
50
63
80
100
32
40
50
63
80
100
125
40
128
160
200
252
320
400
500
128
160
200
252
320
400
500
200
252
320
400
500
64
80
100
32
40
50
63
80
100
125
80
128
160
200
256
320
400
504
640
800
1000
80
128
160
200
256
320
400
504
640
800
1000
256
320
400
504
640
800
1000
discrimination zone
53
11-3.
discrimination
upstream: NG125H/C120N, H, D curve
downstream: NG125, C120
upstream
ln (A)
downstream
discrimination limit
NG125
C120
B curve
rating
(A)
10
16
20
25
32
40
50
63
80
100
discrimination limit (A)
NG125
10
C120
16
C curve
20
25
32
40
50
63
80
100
discrimination limit (A)
NG125
10
C120
16
D curve
20
25
32
40
50
63
80
100
32
40
50
63
80
100
125
192
240
300
384
480
600
756
960
1200
1500
192
240
300
384
480
600
756
960
1200
1500
192
240
300
384
480
600
756
960
1200
1500
discrimination zone
54
11-3.
discrimination
upstream: Compact NS
downstream: DPN, C60, C120, NG125
upstream
NS100N/H/L NS160N/HL
ln (A)
100
NS250N/H/L
125
160
160
200
250
NS100N/H/L - NS160N/H/L
NS250N/H/L
STR22SE trip unit
100
160
200
250
downstream
rating (A)
DPNa, DPN N
i 40
1.2
C60a
i 50
63
1.2
1.2
1.2
1.2
C60N
i 25
32/50
63
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
C60H
i 25
32/50
63
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
C60L
i 25
50
63
1.2
1.2
1.2
1.2
1.2
C120N
C120H
i 50
63
80
100
125
1.2
1.2
1.2
1.2
1.2
NG125H
25/32
40
50
63
80
100
125
i 16
20
25/32
40
50
63
80
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
NG125L
1.2
1.2
1.2
1.2
15
10
7
4
10
7
7
4
2.5
10
7
4
7
4
2.5
25
10
7
4
1.2
1.2
1.2
1.2
1.2
1.2
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
55
11-3.
discrimination
upstream: BS88 fuses
downstream: C120N, H, B, C, D curves
upstream
ln (A)
BS88 fuses
2
4
downstream
Isc max. (kA)
C120N
B curve
In (A)
downstream
Isc max. (kA)
C120N
C curve
In (A)
downstream
Isc max. (kA)
C120N
D curve
In (A)
downstream
Isc max. (kA)
C120H
B curve
In (A)
downstream
Isc max. (kA)
C120H
C curve
In (A)
downstream
Isc max. (kA)
C120H
D curve
In (A)
10
16
20
25
32
35
50
63
63
80
100
125
80
100
125
160
200
80
1600
80
2000
1800
80
2500
2200
1800
80
5000
4800
4000
3200
80
T
T
7000
6000
80
2500
80
6000
4800
80
T
T
7000
80
6000
80
T
T
7000
63
80
100
125
63
80
100
125
10
16
20
25
32
40
50
63
80
100
125
10
16
20
25
32
40
50
63
80
100
125
10
16
20
25
32
40
50
63
80
100
125
80
350
80
500
80
700
600
80
1100
950
800
80
1800
1500
1200
1000
80
2500
2000
1800
1500
1200
80
4500
3800
3000
2500
2000
1800
80
6000
4700
4000
3000
2500
2100
1800
1600
80
7000
5500
4500
3500
3000
2500
2200
2000
1800
80
10000
8500
7000
5000
4200
3500
3000
2500
2200
1800
80
T
T
T
T
T
10000
7500
6000
4800
4000
3200
80
T
T
T
T
T
T
T
T
10000
7000
6000
80
700
80
1100
80
1800
1500
80
2500
2000
1800
80
4500
3800
3000
2500
80
6000
4700
4000
3000
2500
2100
80
7000
5500
4500
3500
3000
2500
2200
80
10000
8500
7000
5000
4200
3500
3000
2500
80
T
T
T
T
T
10000
7500
6000
4800
80
T
T
T
T
T
T
T
T
10000
7000
80
700
80
1100
80
1800
80
2500
2000
80
4500
3800
3000
80
6000
4700
4000
3000
2500
80
7000
5500
4500
3500
3000
2500
80
10000
8500
7000
5000
4200
3500
3000
80
T
T
T
T
T
10000
7500
6000
80
T
T
T
T
T
T
T
T
10000
7000
56
40
11-3.
discrimination
upstream: BS88 fuses
downstream: NG125 H
upstream
In (A)
downstream
In (A)
NG125H
C curve
10
16
20
25
32
40
50
63
80
100
125
BS88 fuses
2
4
3000
10
16
20
25
32
35
40
50
63
80
100
125
160
200
100
1100
100
1700
1200
100
2800
2000
1500
100
4100
3000
2400
2000
100
8500
5800
4400
3400
2600
100
10000
7000
5000
4000
3000
2600
2000
100
16000
10000
7000
5000
3800
3000
2600
2000
36
30000
18000
12000
8000
5500
4000
3200
2600
36
36
30000
15000
8000 22000
6200 14000
4800 9000
7000
total discrimination
discrimination limit = 3 000A
no discrimination
57
Example
Consider a combination between:
a Compact NS250N with trip unit TM250D
a Compact NS100N with trip unit TM100D.
Enhanced discrimination
tables
Technical principle
downstream device
breaking capacity
enhanced by cascading
15/25
The shaded background indicates that the two
values are equal, i.e.
enhanced selectivity limit
for all faults likely to
occur downstream, only the downstream
device trips (total discrimination).
Upstream circuit breaker: Compact NS160 to NS250. Downstream circuit breaker: Multi 9
Upstream
NS160N
NS250N
NS160H/L
NS250H/L
36 kA
36 kA
70/150 kA
70/150 kA
rating
80
100
125
160
160
200
250
80
100
125
160
160
200
250
C60N 6 kA
16
25/25
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
30/30
30/30
or
20 - 25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
30/30
30/30
QOE 10 kA
32 - 40
15/25
25/25
25/25
25/25
25/25
25/25
25/25
15/30
30/30
30/30
30/30
30/30
30/30
30/30
50
15/25
25/25
25/25
25/25
25/25
25/25
25/25
15/30
30/30
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
30/30
C60H 10 kA
63
16
30/30
30/30
30/30
30/30
30/30
30/30
30/30
50/50
50/50
50/50
50/50
40/40
40/40
40/40
or
20 - 25
30/30
30/30
30/30
30/30
30/30
30/30
30/30
50/50
50/50
50/50
50/50
40/40
40/40
40/40
V40H 10 kA
32 - 40
15/30
30/30
30/30
30/30
30/30
30/30
30/30
15/50
50/50
50/50
50/50
40/40
40/40
40/40
50
15/30
30/30
30/30
30/30
30/30
30/30
30/30
15/40
40/40
40/40
40/40
30/30
30/30
30/30
40/40
40/40
40/40
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
30/30
C120N 10kA
63
<=40
25/25
25/25
25/25
25/25
25/25
25/25
25/25
C120H 15kA
50
2.5/25
2.5/25
2.5/25
2.5/25
25/25
25/25
25/25
2.5/25
2.5/25
2.5/25
25/25
25/25
25/25
2.5/25
2.5/25
2.5/25
25/25
25/25
25/25
2.5/25
2.5/25
2.5/25
25/25
25/25
25/25
80
2.5/25
25/25
25/25
25/25
2.5/25
25/25
25/25
25/25
100
2.5/25
25/25
25/25
25/25
2.5/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
200
250
63
125
25/25
rating
100
160
250
100
160
250
C60N 6 kA
63
1.2/25
25/25
25/25
1.2/30
30/30
30/30
QOE 10 kA
63
1.2/25
25/25
25/25
1.2/30
30/30
30/30
C60H 10 kA
40
1.2/25
30/30
30/30
1.2/40
50/50
40/40
C60H 10 kA
50-63
1.2/25
30/30
30/30
1.2/40
40/40
40/40
V40H 10kA
40A
1.2/25
30/30
30/30
1.2/40
50/50
40/40
C120N 10kA
<=25
25/25
25/25
25/25
25/25
25/25
25/25
C120H 15kA
32-40
25/25
25/25
25/25
25/25
50-63
2.5/25
25/25
2.5/25
80-100
Upstream
25/25
25/25
25/25
NS160H
NS250H
NS160L
NS250L
70 kA
70 kA
150 kA
150 kA
rating
80
100
125
160
160
200
250
80
NG125H
16
50/50
50/50
50/50
50/50
50/50
50/50
50/50
36kA
125
160
160
20
50/50
50/50
50/50
50/50
50/50
50/50
50/50
25 - 32
50/50
50/50
50/50
50/50
50/50
50/50
50/50
15/100
40
50/50
50/50
50/50
50/50
50/50
50/50
50/50
5/100
50
2.5/50
2.5/50
2.5/50
2.5/50
50/50
50/50
50/50
2.5/100
2.5/50
2.5/50
2.5/50
50/50
50/50
50/50
2.5/50
50/50
50/50
50/50
63
80
58
100
2.5/100 2.5/100
100/100 100/100
AUS010306