Вы находитесь на странице: 1из 2

GB

Technical Data
T216D201B01 issue 05/2007

a-eberle

Tap Position Interface


Type: REG-SK
* * * * 1 ... 29 tap positions into BCD wall-mounting case design with DIN-rail adapter with connection cable for 1.5 m

Function
The tap position interface REG-SK converts the tap position of a contact row from a transformer with on-load tap-changer into a BCD signal. The installation near a contact row reduces the number of connection cables to the voltage regulator system from 29 to 7. An external supply voltage is connected to the middle contact of the contact row. Switching contacts transfer the signal to the REG-SK which will then be converted into a BCD code by a diode matrix . The outputs of the tap position interface can be connected directly to the BCD inputs of the voltage regulator REG-D or any other device. All inputs are protected against malfunction. 29 switching positions are converted into BCD code control cable with a small number of cores is used cable length between REG-SK and the voltage regulator system REGSysTM can be up to 100 m wide external auxiliary voltage range with suitable adapters for DIN-rail mounting (TS35) and G-rail mounting (TS32)

Output
load impedance on BCD output internal voltage drop diode reverse voltage input capacity output capacity Insulation Coordinates protective class overvoltage category pollution grade nominal circuit voltage test voltage

5 k 1 V + I2 x 450 400 V DC 0.010 F / 500 V DC 1 F / 250 V DC

I II 2 DC/AC 150 V 820 V

Temperature operation / storage, transport -10 ...+70C / -20 ...80C

Mechanical Data
5 mm

Please note: A protective earth conductor is necessary when operating with voltages > 50V.

Input: 1 out of n (only one contact closed) tap position 1 tap position 2 " tap position 10 tap position 11 " tap position 29

20 0 0 0 0 1

10 0 0 1 1 0

Output: BCD - code 8 4 0 0 0 0 0 0 1 0 0 0

72 mm
2 0 1 0 0 0 1 1 0 0 1 1

Inputs rated voltage U1 with switch closed

18 ... 150 V AC/DC

84 mm

Technical Data

REG - SK
BCD - Converter: 1...29 18...150V AC/DC
111.9003.04

BCD

a-eberle 11 mm

68.4 mm
A. Eberle GmbH & Co. KG

Technical Data
Contact Assignments REG-SK
(colours of cables according to DIN 47100)
D-Sub colour of cable PIN (F1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 white brown green yellow grey pink blue red black violet grey/pink red/blue white/green brown/green white/yellow yellow/brown white/grey grey/brown white/pink pink/brown white/blue brown/blue white/red brown/red white/black brown/black grey/green yellow/grey pink/green yellow/pink green/blue yellow/blue green/red yellow/red green/black yellow/black grey/blue

REG-SK
design: connector protection
2 4 6 8 10 12 14 16 18 20 22 24 26 28 1 4 10 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 2 8 20

function
GND tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position BCD BCD BCD GND tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position tap position BCD BCD BCD

weight DIN-rail adapter

wall-mounting case PVC, grey 68x84x56 mm (BxHxT) 1 plug: F1, 37 pins IP40 case with plugged D-Sub connector, connection cable included < 1 kg screwed TS 35 DIN-rail for 7.5 mm height TS 35 DIN-rail for 15 mm height TS 32 G-rail

Standards
IEC 1010 / EN 61010 (VDE 0411) EN 61326-1/A1 IEC 529 DIN 47100

Order Details
Characteristics
tap-position interface, wall-mounting design (adapter for DIN-rail i.e. G-rail) for contact row of the motor drive, cable for 1.5 m included. Input: 1..29 tap positions Output: BCD

Code
REG-SK

Application: REG-SK connected to REG-D


tap-changer of transformer
1 out of 29 tap position 1 2

REG-SK
decoder 1 out of n --> BCD tap position 1 2

e.g. REG-D

cable length L, core cross section < 100m < 40m 1.5mm 1.0mm2
indication of tap-changer position BCD 1 2 4 8 10 BCD 20 or Vz(-) GND F1/ 16 F1/ 35 F1/ 17 F1/ 36 F1/ 18 F1/ 37 F1/ 1 F1/ 19 BCD 1 BCD 2 BCD 4 BCD 8 BCD 10 BCD 20 i.e. Vz BCD GND input binary input 50V
2

25 26 27 28 29 U+

25 26 27 28 29

REG-SK is preferably installed near a tap-changer which reduces the control cables from up to 29 down to 7 cables.

19" rack
U+ GND

cable length

e-mail: info@a-eberle.de

A. Eberle GmbH & Co. KG


2

http://www.a-eberle.de

Aalener Str. 30/32 * D-90441 Nrnberg * Tel.: +49 (0)911 / 62 81 08-0 * Fax: +49 (0)911 / 62 81 08 96
A. Eberle GmbH & Co. KG

Вам также может понравиться