Oil Immersed Transformer

INTEGRATION OF POWER SYSTEM

)Contents
Oil-immersed Distribution Transformer
(1) Features

(2)Specifications & Characteristic (3)The outline dimension oil quantity &total weight (4)Sue of Bushing Terminal (5)Accemries of Standard and Option parts
(6) Connecting Duct, Terminal & Foundation Biits

Energy Efficiency & Environmental Protection Transformer


(1 ) Preface (2) Features

(3)Total owning cost


(4) Characteristic

(5)The outline dimension oil quantity &total weight


(6) Size of bushing Terminal

(7) Dimension of connecting Duct (8)Accessories Main Domestic Customers Main Export Customers

Oil-Immersed Distribution Transfomer


I

Energy Savlng T e design and produciion goal of Shihlin oil-Immersed distrlbutton t W n m W Is to r e d w fhe h power losses and to provide economlcai and energy-efliclency Joluttons to customer.

Extraordinary corrugated heat slnk Shihlln oil-immersed distrlbunon transformer has a hlgh performance conugded tank thd has the followlng benefits: (1) Excellent heat dUpatlon ablltly shall be obtained. (2) T e weldlng path cut in half to reduce possible oll h leak. (3)An Excellent extendable straln abliHy (2) Unique heat sl k deslgn for more efflclency in heat n disslpatlon.
B

.',?,DyQ

r,;l" 9

., <,

01 1FIOW
,,

.. . ~. . . . .
,;

Remarkable fully sealed structure

Shihlin oil-Immersed dlstrlbutlon transformer use good quality moisture-proof gasket to provide tlght sealing completely between the top cover and tank to keep the insulation oil tlghted from outside alr then a good insuiotlon abliHy of oll could be run in good condmon.

(, s; , ; E?4k! ,?;t;i,~d$l,
,

:.;j;$; .& ;" .: I

.* ;
:

,.I

Simplified device to operation


-)

Grounding operation i simplified by well designed s grounding terminal structure

, :

, .,,

. .,.?,, ,,,

Easy installation
The long-hole type foundation screw design provides better workability

I
-

(2) Speclflcatlons & Characterlstlc

A,Toierance refer to I C 60076 E B.Ratlng Current Calculation Total Loss less than 6% Single phase Transformer Load loss (Copper loss) less man 10% (kvA)x1000 Rated Cunent = No Load Loss (Iron l a ) less than 10% R d e d Voltage(V) No Load Curreni Voltage Regulation mree Phase Transformers Noise (kVA~looo
Rated Current =

J3xRated VoltageM

(3) T e outline dlmenslon, d quan h


pree Phase 11.4kV1220VTransformers (150-2000WA)I

Standard W FOunddOn sOnS Bushllyl Dlstance & 0 1 Net 1 DlStanCe Height (I)
M

(WA)

Fb.
K

OutllneDlm

Outline
DlmeMlOnS

Wz

1 W
1200 810 247 150 0 1 14x28 115 11k:.240 240 170 685 1WO 1340 1260 760

zs

xs ~

XH

xl YH

X D Y

200 Flp.1 820 1340 810 247 150 500 450

lMXI Rg.1 1370 2120 1210 3M 323 700 8W

18

2WO Rg,l 1480 2250 1310 300 323 7W 800 18r

[Three Phase 1 1.4kV1380Y-220VTransformers (150-3000kVA)l

H ~ I ~ /

);s Fig. 1

Fig. 2

Standard Type phase Cap. Ref, (mm) Outline Dimensions (mm) Dlstance d (mm) Founddlon Boils Bushing Distance

Duct T p ye

(kVA) Fig.

oil
(I)

Net Welght

ofline Dimen~ions X D

(mm)

~ e t Terminc Weigh Dlm

& Height

ZS

ZH ZL XS YS

XH XL YH

YL

(kg)

2000 Fig.1 1480 2250 1310 300 323 700 800 2500 Fig.2 2350 1680 1365 300 323 700 800 3000 Fig.2 2440 1765 1565 300 323 800 800

18x36 18x36 18x36

160 160 240 180 1290 I 6 0 160 240 180 1000 160 160 240 180 1290

4300 4700 5750

1600 2250 1820 4450 2500 1680 1875 4900 2600 1765 2075 5950

H3

Fig
L1: L1: Fig -

Fig Ll'

Free Phase 22.8kVI380Y-220V Transformers (1 50-3000WA)l

x 7 .

Flg. 1

U U
Fig 2

Standard Type

hrct Type
Net

phase

Cop. Ref.
(MIA) Flg.

lmml Oufllne-l D
Y
V

lmml lmm) Founddlon noits Bushing Distance 011 ~lstance d &W~ht


XH XL YH
(I)

lmml Ovtline ~imensions


Y

Net Weigh

TelllliMl
Dim

Weight

ZS ZH A XS YS

YL

Ikg1 X D
6 0 760 1010 1320 1460 2330 29W 3750 45W 5350 tQYl

Ikgl
730 835

W s.v
Fb L6 Fb L7 -

150 Ag1 6M) 1180

BPQ 3271W800450 14x28 110 120290 180 170


14x28 l a 8 14x28 14x28 18x36 18x36 18x36 18x96 18x96 18x96 110 120 290 180 200 120 120 290 140 275 120 120 290 140 370 120 120 290 140 400 160 160 290 180 660 160 160 290 180 795 160 160 290 180 1025 160 160 290 180 1230 160 160 290 180 1245 160 160 290 180 1430

W0 11801460
WO 1280 1460

2W A g l 770 1280 863 327 150 590 450 3W A g l 8 W 1200 893 327150600550 400 Ag 1 730 1360 1023 327 163 MXl 550
5a) R g l 930 13601023327173600550

10001200 1495 1085 lDOO 1360 1625 1400 12001360 1625 1550 13001770 1820 2450 1300 1910 1870 3WO 1600 2120 1870 39W 1600 2250 1970 4650 2400 1905 2125 5550 2600 1885 2225 6250

L?

La Fg L9 i
LIO Fig Fig L10 Fig

7M) Flgl 10M)1770116d346237700800 1000 Flgl 1150 1910 1219 346 237 700 800 15a) F b l 1410 2120 1214 346 293 700 800

2WO Flgl 1480 2250 1314 346 323 700 800


2500 Flp2 2280 1905 1465 346 323 700 800 3WO Flg2 2480 1885 1565 346 293 800 800

H3

Ll 1
L12 Flg

L13 Ftl Fb L14

(4) Size of Bashing Terminal


[HV Terminal] (CrampType)

,,

,: ., r,

J &
Fig. HI

m
Fig. H3

[LV Terminal] (CrampType)

I
b7 rn

(BUS-BAR Type)
2- 4 14 hole

rn m

.
Fig. L3 Fig. L4

Fig. L2

Flg. L5

2- B 14 hole

z(qqTLOl4(700A) Fig. 18 TL238(3300A) Fig. L12

2- B l4hole

TL008(250A) Fig. L6

TL040(1100A) Fig. L9
. ..

TL091(1650A) Fig. L10

TL053(2300A) Fig. L1 1

Fig. L13

. . ,, > . ..

TL214(4800A) Fig. L14

TL068(1000A) Fig. L15

(5) Accessories
Slngle Phase
hie% Phose

10

Name ~ b i e

Hand H M

mng LUG
SemnSeoJe
Fwnddon Botk

MI L6ve4 Gauge

Olmemwmeter Gauge

'- Tap W e (22.8W lmlde Use)


N O b w G w T q ) Chonper

[I 1.4W OM& Use) MI lmmorlwiw Gauge

.............. .............. ............. .............. .............. . .... . ..... .....


I I

15

75
I

150
I

600

15
I

75
I

150
t

250
I

600
I

100025CC
I l

I I O O O I

50

100

500

750

10

50

100

200

500

750

2MX) 3000

0 . .

0.. 0 0

I+"-1
-lug

0 0

mng lug WLVI

Standard DUCT

Shl(le Elephant DUCT

O O

O O

C C

0 0

0 0

0 0

0 0

0 0

[Dlrnenslon of duct]

12kV Connedng duct

. , . , ".-' 4 ..+?
':'
'

. . ,.. .
,

3..

[Earth Terminal]
Apply to 1.3Q 3-5OOkVA

ME SCREW
7

$ hole

/4014X28L

HOLE

4.018X36L

HOLE

Energy Efficiency& Environmental Protection Transformer


( 1 ) Preface
The government is persistentty promoting the "Energy Saving" policy as Taiwan belongs to a high energy cost area.To comply the policy.Shihiin Electric & Engineering Corporation has introduced the "Energy Efficiency & environmental protection Transformer".a distribution transformer with "super low loss" and product not only can help customer save energy but also can greatly reduce "super hlgh efficiency".This the operation cost.ii Is no doubt the best product an customer can select,

350WA Energy Efflc-

& Environmental ProtectionTransfmr

] Features

,. ..
:.

:'.

.
/
;

:;:

'.

1 I

A.Energ/ saving reallzatlon T e lron core I made of high pmeablltiy slllcon steel sheets (that are also called the "HI-B Core")to h s greatly reduce lron loss (no-loadloss). Improvements have been made on coil structure to reduce copper loss (loadloss) sharpb B reduclng copper and Iron losses,the purpose of "energy saving" y Iked. Please refer to Flgure 1-3 [Losses Comparison Flgure) B.Spacesavlng realization Since the losses Incurred durlng operdlon have been Iessened,the ske of radiator In the transformer can be relatively cut down.Consequenth/ the space required for Installotion of this speclal transformer can be reduced by some 5%-15% In comporlson with other Shlhlln general type transformers. c.n~n*tiy cost saving reaikatlon Due to the sharp decrease In total losses (by as much as 40%-55%),a huge cut on annual electrlctiy cost con be achieved. Short Investment return period can be expxted (2-5 years approximately).

loo

Fig.1 Total Loss

Flg.2 Load

+ Norm01
FQ.3 No-Load Loss

C-MkVA)

+ E.5.E.P

(3)Total owning cost


1 .Transformer operation cost (The calculation of transformer operation cost should consider not only the purchasing price but also the factors such as efficiency,load factor,electricity consumption and interest. The operation cost should be calculated based on compound interest.Theformula i shown as below: s C=A(1+ i ) " + I : { [We+p,'cux L.F~]) 2 X 30 X k)(l +i)"-"' I ; X 4 C: T e Nth year operation cost of the transformer (thousand) h A: Cost in purchasingthe tronsformer (thousclnd) We: Iron loss (No-loadloss) (kW) Wcu: Copper loss (Load loss) (kW) L.F:Average load factor (calculatedat 0.85) N: T e number of years that the tronsformer has been operating h n: T e number of months that the transformer has been operating h K: Average electricity cost per kWH (calculated at NTS2.5) i: Annual interest rate (calculatedat 7.0%),Monthiyinterest rate (calculatedat 7.0%/12) 2.The 3 P 60Hz 1000kVA 11.4kVl220Vtransformer used as an example.Pleoserefer to Figure 5 for its operdion cost. 3.Refer to Figure 6 for the saving of annual electricity cost. [based on NTS2.51kWH)
16,WO 14.000
Fig5, Operation Cost

?I 2.000 a
6

10,000 4,000 2,000 0 0

: 6,000 :

5
+ Normal

10 Year
6 E.S.E.P

1 5

2 "

Capacity(kVA1

L.F100%

* L.F 80%

CNS L.F 5Wb

(4) Chafacterlstlc

1000
1250

1.3
1.1

1.320

8.5bO
10,910

w,',.'
in*.,

9,880

99.M

1.10

4.0 6.5

1,540

3 O 60Hz 22.8kV I 2 2 0 V Or 380Y-220V


EMclency (%I

Full Loss DN)

(5) T e Outllne dirnensbn, OII Quantlty &total Weight h

SlaIXk,d~.1!,3
CapoCitV Ik'JA)
X

Duct TVpe

Fig.

lmm)
Ovtllne Dlmenslw
Y ZS ZH ZL

1 -

.
YS

Founddon W. h ' .
.':. ! ;

,,

1mm1
~Bushlng Pltch

Imm)
0 1 Weight 1

11)
M

m1

Ounlne D- s ln X D Y a D

W. e ,

.,

(kg)

d ' X H

XL

YH

1250

Flg 3 1345 1720 1365 308 323

7W

800

18&.

;=60

240 2 W

740

3310

1500 1720 1876

9420

standard T v w

Duct TvDe

. ,

1 td6 1260 860 247 155 500

MY) 14x28

141, 140

240 140 245

1030

8W

1260 I310

1090

..

Ug.l 865 1385 965 247 168 MY) MY) 14x28 140 140 240 140 565

1590

1WO 1385 1415

1670

KyI

Ug,3 1626 1720 1366 308 298 800

800 18x36 160 160 240 200 815

3680

1800 1720 1875

3810

l w i '"Ag.3

2010 1940 1565 308 323 800

8 W 18x36 2 W 200 240 2 W 1350 6240 22W


k ,

1940 2075

6400

sane a8 standardhansfm~r.

m o
I
XQO

standard l y p

Duct Type
lmm) Burning pitch
Wht

CapocW
Ik'JAVA)

lmm) Outl~ne Dimensions


X Y ZS ZH ZL

lmm)
Foundation mch
XS
YS
6W

~ XD

(mm) 1 ~ Y

Webht

(1)
d

(@I

XH

XL

YH

ZD

I@)

150

Flgl 565 13251060 327 155 WO

14x28 160 1

4W
500

W . 1 795 1450 1115 327 178 600


Hp. l 815 1450 1215 327 242

600
600 800

14x28 160 I60 2W

140 475

1720 1990 28W

WO

1460 1715

1810 2090

600 700

14x28 160 I60 290 140 520 18x36 160 160 290 140 770

1WO 1460 1815 lW0 1710 2075

600

Fig. 2 895 1710 1415 350 242

2900

The ske of duct type translmerexcepilhosebelng bbe1ed.hW e snvt a standard transformer. s


-

'. P

(6) Size of bushing terminal


1.H.V terminal

130~1
Fig. A

2.L.V terminal

jtQ-&
m

m m

p Si

(50Wl Fig. C

zg fF-$y)
t ! +

Si

?a

! @

!O i@
I

2. $ i4bbsrFz~ !

(7OWl
Fig. D

(11rn)
Fig. E

(1m)
Fig. F

(23004

(33WA)
Fig. H

Fie. G

(4oCQA) Fig. K

(48034)
Fig. L

3. Terminal select for three phase transformer

Main Export Customers

Main Domestic Customers

Head Offce Export Sales Dept Heavy Electric Factory

16F. No 88, Sec.6, Chung Shan N. Rd., Taipei, 11 1 Taiwan T. +886~2-2834-2662 F. +886-2-2836-6187
T. 18x6~2-2832-1556