grilles and registers Application Guidelines

Introduction
Application Guide
It is the intent of this section to give some basic application guidelines for the use of supply and return grilles and registers in a simple non-technical manner. the information presented here is based on Prices laboratory results as well as commonly accepted industry practices supported by AsHrAE (American society of Heating, refrigeration and Air Conditioning Engineers). these application guidelines are designed to enhance your ability to use the performance data in this catalog to select an air outlet that will create an air pattern in the occupied space conducive to the comfort of the occupant. Figure 1. Model 510 single deflection supply

Figure . Model 520 double deflection supply

Grille Type & Application

Double Deflection Supply A grille or register consisting of two sets of adjustable blades oriented perpendicular to each other to allow control of the air pattern in both horizontal and vertical planes. While both sets of blades have an affect on the air pattern, the front or outward most set has the most influence. the front blades should be horizontal if control of rise and drop is primary (i.e. free space or high sidewall) or vertical if spread and throw are the largest concerns. double deflection outlets are the most flexible type of grille or register. (see Figure 2) Example Model 520 or 22. Eggcrate Return A grille or register with a cubical grid core to be used for return or exhaust where maximum free area is desired and see through is not a concern. typically used in ceiling applications where see-through sight lines are minimized to directly below the grille. (see Figure 3) Example Model 80 series.

Figure 5. Model 530 Louvered return

Perforated Return this grille utilizes a symmetrically perforated sheetmetal core for free areas of approximately 50%. It is typically used in ceiling applications where see through and blending with the mounting surface are of prime concerns. (see Figure 4) Example Model 10 series.

Louvered Returns these grilles and registers utilize a core of parallel fixed blades set at a deflection, usually 45 degrees from horizontal, to provide a return or exhaust unit with minimum see through. the most common application is sidewall with blade deflection upward in high applications and down in lower applications. this type of outlet usually has a slightly higher sound and pressure drop than either the eggcrate or perforated. (see Figure 5). Example Model 530 or 630.

Copyright E.H. Price Limited 2007.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

D-9

grILLEs And rEgIstErs

Single Deflection Supply A grille or register with a single set of adjustable blades which controls the air pattern in only one direction depending on blade orientation. Horizontal blades control rise and drop of the airstream. For example, to prevent unwanted drop in a free space (no ceiling) application or blow warm air down in a high sidewall application. Vertically oriented blades control the spread of the air pattern and would be used where throw, not drop, is a prime concern. these would be the most economical type of outlet. (see Figure 1) Example Model 510 or 21.

Figure 3. 80 series Aluminum Egg Crate return

Figure 4. 10 series Perforated return

grilles and registers Application Guidelines

Performance Data Interpretation


the grilles and registers, as stated in the corresponding performance notes, have been tested to AsHrAE 70-2006 "Method of testing for rating the Performance of Air Outlets and Inlets". the following is an explanation of the conditions under which the performance data is derived and some suggestions on how to apply the data to different conditions. Throw the throw data indicated in the grilles and registers section is the maximum distance in feet from a supply grille that a predetermined air velocity (terminal velocity) can be measured under the conditions outlined by the test codes. these conditions are: grille to be sidewall mounted 9" below the ceiling (to generate surface effect Air distribution Engineering guide, section Eg. supply air is to be isothermal. the supply register throw data in this section is to terminal velocities of 150 fpm, 100 fpm and 50 fpm for air patterns of 0, 22 1 /2 and 45 degree horizontal spread (see Fig.3) the isovel diagrams shown in Figure 3 are based on actual test results. they illustrate the relationship of horizontal spread to throw for a typical selection of a high sidewall supply outlet. typical isovels to terminal velocities of 150 fpm (Vt = 150), 100 fpm (Vt = 100) and 50 fpm (Vt = 50) are illustrated, with a variety of horizontal spread settings. note that the outer envelope represents the Vt = 100 isovel, and the dark colored area represents the Vt = 150 isovel. Corrections for Location In the event a supply outlet is mounted in a location where its throw will not be affected by surface effect (i.e. more than 2 ft. (610) from a wall or ceiling parallel to the airflow), a good approximation is to multiply the catalog throw by 0.70. this is due to the fact that the air flow without surface effect is exposed to room air on its complete boundary. It tends to lose momentum faster and drop sooner for this reason. to combat the potential draft problems caused by premature drop, it is advisable to put an upward deflection of 15-20 degrees on supply units without the benefit of surface effect (i.e. free space). spreading the air pattern horizontally also has the effect of reducing undesired drop. Figures 4 through 6 show the effect mounting location and blade deflection have on a typical grille. You will also note that for a given CFM the lower the core velocity the more resulting drop. Figure 3.

grILLEs And rEgIstErs

D-10

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright E.H. Price Limited 2007.

grilles and registers Application Guidelines

Throw and Drop from Sidewall Outlets


Fig. 4. Deflection: Vertical 0 Up, Horizontal 0

Mounted 2 4 ft. below Ceiling Fig. 5. Deflection: Vertical 0, Horizontal 0

no Ceiling

Mounted Within 1 ft. of Ceiling Fig. 6. Deflection: Vertical 0, Horizontal 45

no Ceiling

Mounted Within 1.5 ft. of Ceiling


Notes 1. Throw and drop values are based on 50 fpm terminal velocity. 2. Data is based on tests with 20F cooling temperature differential in space with no boundary walls. 3. Data is based on Model 21 and 22 cores.

no Ceiling

4. Small circle in white area of each chart shows comparative performances of one size of grille at 300 cfm and 600 fpm outlet velocity. 5. Deflection settings and resulting patterns are shown in Product Catalog. 6. Shaded area to right of each chart indicates noise level above 30 NC.
All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright E.H. Price Limited 2007.

D-11

grILLEs And rEgIstErs

grilles and registers Application Guidelines

Throw cont'd, Sound


Supply Air Temperature Buoyancy also has an influence on throw which must be considered. Cold supply air (approximately 20 F t) has the effect of reducing horizontal throw 30% while increasing vertical downward throw by 30% from catalog data. Warm supply air (approximately 20F t) will increase horizontal throw approximately 30% while reducing vertical downward throw by 30%. For further discussion on installation conditions and their effect on throw and air pattern, see Air distribution Engineering guide, section Eg. Summary of Throw Guidelines 1. Multiply catalog throw by 0.70 for free space installation. 2. the lower core velocity for a given CFM the more resulting drop (core velocity > 300 fpm recommended). 3. supply air / room air temperature differential 20 F t cooling - multiply horizontal throw by .70 Multiply vertical down throw by 1.30 20 F t heating - multiply horizontal throw by 1.30 Multiply vertical down throw by .70 Sound the nC data presented is derived from AsHrAE and IsO test standards. In all cases the rating is for a single outlet with accessories as indicated in the performance notes (i.e. in most cases outlets are tested with dampers). When tested with integral dampers, the dampers are in the 100% open position. supply units with adjustable vanes are rated at zero degree deflection with corrections for 221/2 and 45 degrees. nOtE: For typical application design nC levels see Air distribution Engineering guide, section Eg. NC Corrections Multiple Outlets In the event that more than one outlet is serving areas of 400 to 600 sq Ft or less, the additive effects of the multiple sound sources must be considered. For example, if two outlets of equal nC are within close proximity, the result is an increase of 3 to the nC level (see example). If the outlets have different nC levels, the increase to the higher nC is inversed to the difference between the two nCs (see example) so that a difference of 10 dB results in no correction, i.e. use the higher nC. see Fig.7 for the appropriate correction based on the nC differential of outlets. Example 1: two 12 x 6 520 series registers supplying 390 cfm each in a space < 600 Ft.2 rated nC = 30 each Oversized Outlets NC In the event an outlet is selected which exceeds the sizes and capacities of the catalog performance data, nC levels may be approximated by treating the unit as multiple outlets of equal size and capacities. In this way the nC levels of these smaller multiple outlets may be attained from the catalog data and used to derive the oversized units sound level. Example 3: A series 22 supply register size 60" x 48" supplying 11,250 CFM. treat this as three units 60" x 16" each delivering 3750 CFM @ nC 25 per the previously discussed multiple outlet corrections. Example : three 12 x 4 530 series registers exhausting 130 cfm each in a space < 600 Ft.2 rated nC = 24 each

grILLEs And rEgIstErs

30

30

4

4

4

33
Example 3:

7 (24 + 3*)

5

5

5

9 (27 + 2**)

8

30

* Equal sound sources ** resulting adder for 3 dB difference between sound sources (ref. Figure 7)

Figure 7

D-1

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright E.H. Price Limited 2007.

Perforated Face 10 Series


Product Information
Model Grille steel Core Construction Aluminum Core Construction stainless steel Construction 10 10A 10SS Perforated Face Return

grILLEs And rEgIstErs

Application: Mid to high capacity return with core free area of approximately 50%. Perforated core blends unobtrusively with most interior design conditions. Ideally suited for ceiling mounted return applications. Construction: Available in steel or aluminum core con struction. (Aluminum core recommended for high humidity applications.) Extruded aluminum borders for clean, crisp detailing. Core 3/16" (5) holes on 1/4" (6) centers staggered 60. Mounting frames available to accent grille border and protect wall surface during grille removal. For Firerated applications please see d40. Mounting / Finish Options Border Style surface sidewall Mount 11/4" (32) Flat (standard) tBar LayIn 1" (25) tee Optional Mounting Frame For F Border (SW) Fastening Countersunk screwholes c/w ovalhead screws no screwholes

F Border (LI) Lay-In

Module Size Nom. Size = Mod. Size - 2" (51) Nom. - 13/16" (21) 11/8" (28)

1" (25)

Perforated Face Face Opening = D - 11/2" (38) Mod. Size - 5/16" (8)

11/4" (32)

1/4" (6)

F (SW) F (LI) D A

F Border (SW) Sidewall

Nom. Size Nom. - 13/16" (21)


1/4" (6)

11/8" (28)

Perforated Face Face Opening = D - 11/2" (38) Nom. + 111/16" (43) Optional D Mounting Frame

Finish White Powder Coat B12 For optional and special finishes see color matrix. Available Sizes Minimum 6" x 4" (152 x 102) Maximum* 48" x 24" (1219 x 610)

11/4" (32)

Use with F Border (SW) Only

* One piece For oversize grille construction, see page d110d111.

1] 2] 3] 4] 5] 6] 7]

Product Selection Checklist


select Unit size based on desired performance characteristics. select Outlet type by model number (Core style). select Border style according to installation requirements (F is standard). select Module size if tB Border selected. (note: Maximum duct size = module size2" (50)) select Mounting frame if desired. select Fastening type (A is standard, n/a with tB Border). select Finish. Example: 24" x 12" / 10 / SW / A / B12 24" x 24" / 10A / TB /0/ B12 Application Recommendations: surface Mount F Border, A Fastening. tBar LayIn LI Border, Fastening n/a
Copyright E.H. Price Limited 2007.

Product Information Index Performance data ...............................d41 Available Borders / Frames ...... d82 d84 Available Fastenings................. d82 d84 Accessory dampers .............. d107 d109 suggested specification ................ d172

D-39

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Perforated Face 10, 10FF Series

Performance Data
Core Area Sq. Ft. 0.15 0.18 0.22 0.26 0.30 0.34 0.39 0.46 0.52 0.60 0.69 0.81 0.90 1.07 1.18 1.34 1.6 1.8 2.08 2.45 2.78 3.11 3.61 4.29 4.65 5.58 6.25 Core Velocity Velocity Pressure Negative SP CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC CFM NC 200 0.002 0.019 30 36 44 52 60 68 78 92 104 120 138 162 180 214 236 268 320 360 416 490 556 622 722 858 930 1116 1250 300 0.006 0.043 45 54 66 78 90 102 117 138 156 180 207 243 270 321 354 402 480 540 624 735 834 933 1083 1287 1395 1674 1875 400 0.010 0.076 60 72 88 104 120 136 156 184 208 240 276 324 360 428 472 536 640 720 832 980 1112 1244 1444 1716 1860 2232 2500 NC 20 500 600 0.016 0.022 0.118 0.171 75 90 20 25 90 108 20 25 110 132 20 25 130 156 20 25 150 180 20 25 170 204 20 25 195 234 20 25 230 276 20 25 260 312 20 25 300 360 20 25 345 414 20 25 405 486 20 25 450 540 20 25 535 642 20 25 590 708 20 25 670 804 20 25 800 960 20 25 900 1080 20 25 1040 1248 20 25 1225 1470 20 25 1390 1668 20 25 1555 1866 20 25 1805 2166 20 25 2145 2574 20 25 2325 2790 20 25 2790 3348 20 25 3125 3750 20 25 NC 20 NC 30 700 800 0.031 0.040 0.232 0.303 105 120 29 33 126 144 29 33 154 176 29 33 182 208 29 33 210 240 29 33 238 272 29 33 273 312 29 33 322 368 29 33 364 416 29 33 420 480 29 33 483 552 29 33 567 648 29 33 630 720 29 33 749 856 29 33 826 944 29 33 938 1072 29 33 1120 1280 29 33 1260 1440 29 33 1456 1664 29 33 1715 1960 29 33 1946 2224 29 33 2177 2488 29 33 2527 2888 29 33 3003 3432 29 33 3255 3720 29 33 3906 4468 29 33 4375 5000 29 33 NC 30 900 0.050 0.384 135 36 162 36 198 36 234 36 270 36 306 36 351 36 414 36 468 36 540 36 621 36 729 36 810 36 963 36 1062 36 1206 36 1440 36 1620 36 1872 36 2205 36 2502 36 2799 36 3249 36 3861 36 4185 36 5022 36 5625 36 1000 0.062 0.474 150 39 180 39 220 39 260 39 300 39 340 39 390 39 460 39 520 39 600 39 690 39 810 39 900 39 1070 39 1180 39 1340 39 1600 39 1800 39 2080 39 2450 39 2780 39 3110 39 3610 39 4290 39 4650 39 5580 39 6250 39

Nominal Size 6 x 5 7 x 4 6 x 6 7 x 5 8 x 4 7 x 6 10 x 4 6 x 6 10 x 5 12 x 4 14 x 4 10 x 6 12 x 5 16 x 4 8 x 8 12 x 6 14 x 5 18 x 4 20 x 4 14 x 6 16 x 5 10 x 8 24 x 4 16 x 6 18 x 5 28 x 4 18 x 6 20 x 5 12 x 8 30 x 4 20 x 6 24 x 5 14 x 8 36 x 4 22 x 6 28 x 5 16 x 8 40 x 4 26 x 6 30 x 5 18 x 8 48 x 4 30 x 6 36 x 5 18 x 10 34 x 6 20 x 10 24 x 8 16 x 12 60 x 4 36 x 6 48 x 5 18 x 12 72 x 4 24 x 10 30 x 8 22 x 12 60 x 5 36 x 8 48 x 6 30 x 10 72 x 5 40 x 8 60 x 6 36 x 10 72 x 6 32 x 12 48 x 8 26 x 14 36 x 12 26 x 16 30 x 14 24 x 18 60 x 8 40 x 12 48 x 10 36 x 14 72 x 8 48 x 12 60 x 10 36 x 16 48 x 14 32 x 20 36 x 18 28 x 24 72 x 10 36 x 20 48 x 16 30 x 24 72 x 12 48 x 18 60 x 14 36 x 24 72 x 14 48 x 20 60 x 16 30 x 30

10 x 10 12 x 10 14 x 10 16 x 10 12 x 12 14 x 12 14 x 14 16 x 14 18 x 14 16 x 16 24 x 12 20 x 14 30 x 12 24 x 14 24 x 16 20 x 18 22 x 20 30 x 16 26 x 18 30 x 18 24 x 24

18 x 16 20 x 16 18 x 18 24 x 20

Performance Notes 1. Tested in accordance with ASHRAE Standard 70-2006 Method of Testing for Rating the Performance of Air Outlets and Inlets. 2. All pressures are in inches of water.
Copyright E.H. Price Limited 2007.

3. The NC values are based on a room absorption of 10 dB, re 10-12 watts. 4. Blanks () indicate an NC level below 15.

5. Air flow is in cubic feet per minute, cfm. 6. Neg. SP is negative static pressure.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

D-41

grILLEs And rEgIstErs

Optional Borders, Frames and Fastening


Availability Schedule
Grille / Register 510 / 610 / 710 50 / 60 / 70 530 / 630 / 730 535 / 635 / 735 80 / 81 / 8 10 1,  31, 3 60, 70 Border F C STD. STD. STD. STD. STD. STD. STD. STD. STD. TBP/TB* N ED CH** Border / Frame D K T refer to d-74 refer to d-74 refer to d-74 refer to d-74 Fastening A C* STD. STD. STD. STD. STD. STD. STD. STD. STD.

std. = standard Border / Fastening supplied with grille / register * Concealed Fastening not available for tB and CH Borders. ** damper not available for CH border. Outlet Mounted Accessory Opposed Blade Damper D steel Construction DAL Aluminum Construction

grILLEs And rEgIstErs

D-8

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright E.H. Price Limited 2007.

Optional Borders, Frames and Fastening

Dimensioned Details
F Border FD Border / Frame (for 500/600) C Border CK Border / Frame TB Border

1 1/4" (32) flat border for surface mount.

1 1/4" (32) curved border for surface mount. K mounting frame is curved to complement C border.

For T-bar lay-in application. Steel panel is provided when ceiling module is more than 2" (51) over duct size. Note that concealed fastening is not available. 60 / 70 Series uses .730" (18) face.

N Border NT Border / Frame (except 500/600/700)

N Border NT Border / Frame (for 500/600)

ED Border / Frame
GRILLES AND REGISTERS
13

1" (25) narrow low profile border with matching curved mounting frame to satisfy architectural / space conditions.

1" (25) flat border for surface mount.

/16" (21) border for exposed duct. Frame hems the raw edge of the duct providing a neat, clean grille mount. Note the reduced core area of this border. See Performance Notes for correction factors to catalog data.

TBP Panel

Copyright E.H. Price Limited 2007.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

D-83

Optional Borders, Frames and Fastening

Dimensioned Details
CH Border A screw Fastening C Concealed Fastening

Channel border designed for non-ducted applications in t-bar ceilings. It provides structural strength to the grille and is hidden by the ceiling grid.

Counter-sunk screwholes in border type. Factory painted oval head screws supplied.

Permits surface mounting with concealed screw. the bracket attached to the back of the grille screws to a loose bracket which hooks into a hem in the duct.

grILLEs And rEgIstErs

700 F Border FD Border / Frame

700 N Border NT Border / Frame

D-84

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright E.H. Price Limited 2007.

suggested specification Grilles & Registers

Egg Crate Face / Perforated Face / Filter Grilles


Egg Crate Face
80 Return Grille Furnish and install Price model 80 return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall be of aluminum construction, consisting of aluminum 1/2" x 1/2" x 1/2" (13 x 13 x 13) grid (egg crate core) and an extruded aluminum border. the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat). 80D Exhaust Register Furnish and install Price model 80d exhaust registers of the sizes and mounting types indicated on the plans and outlet schedule. registers shall be of aluminum construction, consisting of aluminum 1/2" x 1/2" x 1/2" (13 x 13 x 13) grid (egg crate core) and an extruded aluminum border.the integral volume control damper shall be of the opposed blade type and shall be constructed of heavy gauge cold rolled steel (optional aluminum construction 80dAL).the damper shall be operable from the register face.the damper shall be coated steel (mill finish aluminum 80dAL). the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat). 81 Return Grille Furnish and install Price model 81 return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall be of aluminum construction, consisting of two aluminum x x (13 x 13 x 13) grids (egg crate core) stacked to make a x x 1 (13 x 13 x 25) core and an extruded aluminum border.the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat). Options optional core 1 piece x x 1 (13 x 13 x 25) aluminum grid (egg crate) 81D Exhaust Register Furnish and install Price model 81d exhaust registers of the sizes and mounting types indicated on the plans and outlet schedule. registers shall be of aluminum construction, consisting of two aluminum " x " x " (13 x 13 x 13) grids (egg crate core) stacked to make a x x 1 (13 x 13 x 25) core and an extruded aluminum border. the integral volume control damper shall be of the opposed blade type and shall be constructed of cold rolled steel (optional aluminum construction 81dAL).the damper shall be operable from the register face.the damper shall be coated steel (mill finish aluminum 81dAL). the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat). 8 Return Grille Furnish and install Price model 82 return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall be of aluminum construction, consisting of aluminum 1" x 1" x 1" (25 x 25 x 25) grid (egg crate) core and an extruded aluminum border.the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat). 8D Exhaust Register Furnish and install Price model 82 exhaust registers of the sizes and mounting types indicated on the plans and outlet schedule. registers shall be of aluminum construction, consisting of aluminum 1" x 1" x 1" (25 x 25 x 25) grid (egg crate) core and an extruded aluminum border. the integral volume control damper shall be of the opposed blade type and shall be constructed of cold rolled steel (optional aluminum construction 82dAL).the damper shall be operable from the register face.the damper shall be coated steel (mill finish aluminum 82dAL).the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat). 535FF / 635FF / 735FF Filter Return Grille Furnish and install Price model (535FF steel / 635FF aluminum / 735FF stainless steel) filter return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall be 45 degree deflection fixed louver type with blades spaced 1/2" (13) on center. the blades shall run parallel to the (long / short) dimension of the grille.the border shall be mounted to the filter frame with 1/4 turn quick release fasteners (and a hinge-tab mechanism on type 530FF). the mounting frame shall accept a standard 1" (25) filter media. the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat).

Filter Grilles - Egg Crate


80FF Filter Return Grilles Furnish and install Price model 80FF filter return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall consist of aluminum 1/2" x 1/2" x 1/2" (13 x 13 x 13) grid (egg crate) core and a formed steel border and filter frame. A hinge-tab mechanism allows hinging or removal of the grille from the filter frame to ease cleaning of the grille. the mounting frame is designed to accept a standard 1" (25) or 2" (51) filter media. Unit is to be complete with 1/4 turn quick release fasteners. the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat).

grILLEs And rEgIstErs

Perforated Face
10 Return Grille Furnish and install Price model (10 steel/ 10A aluminum) return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall consist of a perforated core with 3/16" (5) holes on 1/4" (6) centers staggered 60 degrees and an extruded aluminum border. the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat).

Filter Grilles - Perforated


10FF Filter Return Grille Furnish and install Price model 10FF filter return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall consist of a perforated steel core with 3/16" (5) holes on 1/4" (6) centers staggered 60 degrees and a formed steel border and filter frame. A hinge-tab mechanism allows hinging or removal of the grille from the filter frame to ease cleaning of the grille. the mounting frame is designed to accept a standard 1" (25) or 2" (51) filter media. Unit is to be complete with 1/4 turn quick release fasteners. the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat).

Filter Grilles - Louvered


530FF / 630FF / 730FF Filter Return Grille Furnish and install Price model (530FF steel / 630FF aluminum) filter return grilles of the sizes and mounting types indicated on the plans and outlet schedule. grilles shall be 45 degree deflection fixed louver type with blades spaced 3/4" (19) on center. the blades shall run parallel to the (long / short) dimension of the grille. the border shall be mounted to the filter frame with 1/ 4 turn quick release fasteners (and a hinge-tab mechanism on type 530FF). the mounting frame shall accept a standard 1" (25) filter media. the grille shall be finished in (B12 White Powder Coat / B15 Aluminum Powder Coat).

D-17

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright E.H. Price Limited 2007.