ENGINEERING CONSULTANTS GROUP

Max. Leakage The fan coil units control valves shall be pressure independent type that contains two valves: the self regulating pressure reducing valve and the control valve that works with equal percentage. When the differential pressure increases, the pressure reducing valve closes and ensures a constant pressure over the control valve. This is to ensure constant flow at the range of 5% at a differential pressure of 30-350

- Damper Actuators: Damper actuators shall be of the direct coupled type for either modulating or two or three position control. Actuators shall stroke by a rotating motion of a reversible overload-proof synchronous VDC as required motor. Control voltages shall be either 24 VAC or by the application. All actuators shall have a hand operating facility and position indication marked 0-10 indicating 0-100%. On modulating types the direction of operation and stroke limitation shall be adjustable without mechanical changes in the linkage. Modulating and two position types shall be with spring return type, the spring return time shall not be more than 3 seconds. - Variable speed drive unit: Adjustable frequency drive unit, each approved and suitable for installation of the scheduled motors. Ensure that as compatible. drives and motors are approved by respective
The adjustable frequency totally digital drive shall be of the pulse width modulated PWM type utilizing insulated gate bipolar transistors in the inverter section of the drive and shall have the following minimum specifications: Suitable for use with standard of high efficiency 380 volt, 3 phase, 50 Hz motors.

IF' 43 wall or floor mounted enclosure.

- 380 volt 3 phase, 50 Hz input power supply and volt, phase 0.5 to 120 Hz output. No transmitters shall be used on either the input or output of the adjustable frequency controller. - Input transient protection by line reactors line filters as required harmonic distortion to 3% at each VSD input. Total harmonic distortion value shall be calculated according to the actual selection by the manufacturers of drivers. Complete with an incoming, horsepower rated, non-automatic circuit breaker with an operating mechanism which is door interlocked and lockable in the open position. Input line fuses whose characteristics are coordinated with the drive's electronic protection circuits so as not to blow under normal output faults such as over-current, short circuit and ground fault.

Automatic C Cairo Festival City - Festival Center

1137)

Section 15950 Page

ENGINEERING CONSULTANTS GROW

Line over and under voltage protection, phase loss protection and phase unbalance protection. Inherent short circuit protection for line to line and line to ground faults. If either of these faults should occur in the output of the drive, the drive shall safely shut down without damaging any power circuit devices. Controllers utilizing fuses or isolation transformers to provide this protection shall not be acceptable.

- Electronic instantaneous over-current protection.


Current limit, of the high performance inner current loop type, adjustable between and 110% of rated output. Independent adjustment shall be provided for both motoring and regenerating operating modes.

- A continuous duty service factor of 100% of rated output current with overload protection rating of 150% for one minute. - Minimum efficiency of 98% at maximum load and speed. - Minimum line side displacement power factor of 0.98 at all speeds.
Maximum ambient temperature of Maximum relative humidity of 95% non-condensing.

- Maximum altitude of

m for rated output. to 50 Hz. to

Adjustable minimum motor frequency of

Adjustable maximum motor frequency of to 50 Hz. Separately adjustable acceleration and deceleration ramps from 1800 seconds to 100% speed).

- Controller internal over temperature protection. - Motor protection including electronic motor stall protection to trip the drive off should a motor overload or stall condition occurs.
Automatic restart after an inverter fault trop; the drive shall attempt to restart automatically three times with lock out after the third attempt if a restart has not occurred this feature can be defeated if auto restart is not required.

- Rotating motor restart feature; this feature will allow a motor unit which has been shut down or has fault tripped but is still rotating to be restarted without first stopping the motor unit. The drive shall restart the motor at the speed at which it is rotating and then reaccelerate to the speed called for by the speed reference signal.
Capable of running without a motor connected for setup and testing.

- Capable of accepting the opening of a remote motor disconnects while running without causing damage to the drive. - Auto restart after power outage (provided that run enable is maintained).

Automatic C Cairo Festival City Festival Center

1137)

Section 15950 Page of 22

ENGINEERING CONSULTANTSGROW

- Three frequency reject points to prevent the pump from operating a


resonant speed; both the center frequency and the bandwidth shall be adjustable.

- Thermistor relay for all motors. If the relay operates due to a motor over
temperature condition, the drive controller shall shut down and illuminate a door mounted (motor over-temp) pilot light.

30 cycle ride through.

- Provide automatic1 manual signal follower for a 4-20


reference.

and 0-10 VDC

Input current limiting fuses to suit short circuit capacity of equipment; fuse characteristics shall be coordinated with drive's electronic protection circuits so as to not low under normal output faults such as over-current, short circuit or ground fault; refer to motor schedules. Complete with an incoming uon-automatic circuit breaker or disconnect with operation mechanism, which is door interlocked and pad-lockable in open position.

- Energy metering system


Energy metering system comprises a flow meter, two-paired temperature sensors and metering unit. The selection of flow meter and temperature sensors shall be based on high quality for sensitivity and accuracy. Temperature measurements to be made with dual slope principle - 4 wires technique. The maximum divergence within the pair to be Flow meter to be fitted with de-bouncing filters to prevent double counting. Metering system shall be required by the engineer. with all necessary accessories as

Metering system should be capable of interfacing to the building management system. The Building management system should monitor the following variables: 1. Supply and return temperature 2. Water flow 3. Heat consumption All controls and magnetic actuated control valves shall have a five year guarantee. 2.4.2

Principle of Control System: Controls shall be built up of modular microprocessor based DDC control units. The DDC system must be and ensure the automatic operation of the electrical and
Control
Section 15950 Page 14 of 22