Вы находитесь на странице: 1из 2

.: EXIDE :.

APPLICATION & PRODUCTS STAND BY

http://www.exide4u.com/exide/JSP/masters/apnpro/inva_tubular.htm

Welcome to Exide Industries Limited, India...

May 1, 2012

Home

Contact us

Sitemap

OUR CORPORATE WEBSITE

GENERAL

Corporate Overview Manufacturing Accreditations Financials Social Responsibility News & Views Battery Recycling
INDUSTRIAL

You are here: Home > Industrial > Application & Products > Stand By > Inverter

Technology Application & Products Battery Sizing Post An Enquiry Battery Servicing Locate a Dealer Contact Us FAQs
EXIDE4U

Inverter

Inva Tubular

Back to Product

My Exide Employee CRM e-learning

Features Ironclad Tubular Technology Electrolyte level indicator High Acid volume per ampere hour Deep cycle design Advantages Very long life User friendly Acid volume per ampere hour is 30% more than that of ordinary tubular batteries. It acts as a coolant and also ensures very low maintenance Suited for use in areas of frequent power cuts (800 to 1000 cycles of deep discharge as against 300/400 cycles of other batteries) Application The next generation Tubular battery designed specially for withstand long and frequent powercuts. It is the ultimate Inverter battery. Technical Specification Can withstand overcharge better Occupies less floor space, totally new look Less pollution, environment friendly Resistance to abuse Tower type design Common Side Venting Conforms to IS 13369-1992

Ensures consistent quality

Model

at 270C when discharged at C20 up to 1.75 vpc (1.280 sp. gr)

Capacity

Dimension (+/-3mm)

Weight (Kg +/-5%)

Volume of Electrolyte (1.220 Sp. Gr) Liters

Initial charge Minimum AH input (AH)

Initial Charge of Constant Current (A) Start (upto 2.36 vpc) Finish (upto 2.75 vpc)

Constant Potential Limiting Current (Amps)

Trickle Charge (Current in mA)

Length

Width

Height*

Dry

Filied

Min.

Max.

1 of 2

5/1/2012 7:06 PM

.: EXIDE :. APPLICATION & PRODUCTS STAND BY

http://www.exide4u.com/exide/JSP/masters/apnpro/inva_tubular.htm

IT 400 110 Ah IT 500 150 Ah IT 550 165 Ah IT 650 200 Ah 500 187 430 45.00 72.00 21.60 720 19.2 9.6 40 160 640 500 187 430 35.80 60.80 20.00 610 16 8 34 135 540 500 187 430 33.80 60.05 23.80 540 14.4 7.2 30 120 480 506 220 257 29.10 43.35 11.40 450 12 6 25 100 400

Higher Discharge Rates (Optional)

Hours

10

IT400

100

83

72

50

IT500 Capacity Ah IT550

120

100

86

60

135

112

97

68

IT650

160

133

115

88

Initial Charging Information 1. 2. 3. 4. Filling in Specific Gravity Rest Period Minimum Ah input 1.220 +/ - 0.005 at 27 C 10-12 hrs 450 Ah for IT400, 540 Ah for IT500, 610 Ah for IT550 and 720 Ah for IT 650

In order to reduce the charging time, the following routine may be adopted. For IT400, the initial charging current may be 12A upto 2.36vpc followed By 6A upto 2.75 vpc. For IT500, the initial charging current may be 14.4A upto 2.36vpc followed By 7.2A upto 2.75 vpc. For IT550, the initial charging current may be 16A upto 2.36vpc followed By 8A upto 2.75 vpc. For IT 650 , the initial charging current may be 19.2A Up to 2.36vpc followed by 9.6A upto 2.75vpc. However in both cases, minimum Ah to be given. Under the circumstances, Battery temperature should not exceed 50C. In case the temperature exceeds 50C Adequate rest to be given till the electrolyte temp. comes to ambient temp. and charging to be continued.

5.

Conditions of fully charged 3 consecutive hourly readings of specific gravity and voltage become constant. Top of charge voltage will e around 16.2V 16.5V. All cells should gas freely. Minimum Ah has been given.

6.

Specified gravity of fully charged condition

1.250 +/ - 0.005 at 27

Normal Recharging Instruction Recharging through Inverter at constant potential mode of 14.4V with limited current as specified. After battery potential matches 14.4V, the battery should continue in trickle charge made at constant potential of 13.8V. Statutory Notice All batteries contain lead, which is harmful for humans and environment. As per statutory requirements, the used battery must be returned to the authorized dealer, manufacturer or at the designated collection centres. Back to Product

2006 Exide Industries Limited.

Powered by WDC

2 of 2

5/1/2012 7:06 PM