Вы находитесь на странице: 1из 101

W3000

TECHNICAL MANUAL
C0240111-01-06-GB

Replaces C0240111-10-05-GB

GB
The information contained in this document may be modified without prior notice. No part of this document may be reproduced and/or disclosed to third parties or competitors.

CLIMAVENETA S.p.A Via Sarson, 57C 36061 Bassano del Grappa(VI)-ITALY Tel. (+39) 0424 509 500 Fax. (+39) 0424 509 509 www.climaveneta.it info@climaveneta.it
HTU UTH HTU UTH

January 2006

C0240111-01-06-GB

Summary
1 2 3 USER INTERFACE................................................................................................................3 MENU STRUCTURE ..............................................................................................................4 SETTING THE CONNECTIONS..............................................................................................6 3.1 3.2 3.3 3.4 4 5 Available hardware ............................................................................................................ 6 Connecting more than one unit............................................................................................ 9 Additional connections ..................................................................................................... 13 Configuring the terminals ................................................................................................. 14

SWITCHING THE UNIT ON AND OFF ................................................................................. 21 USER PROGRAMMING ....................................................................................................... 23 5.1) SETTING THE OPERATING MODE ...................................................................................... 23 5.2) USER MENU................................................................................................................... 25 5.2.1 ) ADJUSTMENT ............................................................................................................. 25 5.2.2 ) RECOVERY................................................................................................................. 31 5.3) SETPOINT MENU ............................................................................................................ 33 5.4) CLOCK MENU................................................................................................................. 33

MANUFACTURER PROGRAMMING ..................................................................................... 34 6.1) FREECOOLING ............................................................................................................... 35 6.2) CONDENSATION ............................................................................................................ 36

ALARMS............................................................................................................................ 38

ANNEX 1A : TABLE OF W3000 MASKS ..................................................................................... 43 ANNEX 1B : TABLE OF W3000 BASE MASKS ............................................................................. 66 ANNEX 1C : PARAMETERS TABLE ............................................................................................. 70 ANNEX 2 : INPUT/OUTPUT TABLE .......................................................................................... 77 L HARDWARE: ................................................................................................................... 77 XL HARDWARE: ................................................................................................................. 82 B HARDWARE (for hermetic compressors).............................................................................. 85 EXPANSIONS ....................................................................................................................... 87

This means that it can only work on cards supplied by Climaveneta and not on cards purchased from other dealers.

Notice: The W3000 controller software is protected by a digital signature.

C0240111-01-06-GB

USER INTERFACE

There are three types of user interface:

W3000

W3000 compact

W3000 base

Depending on the type of user interface installed, there are more or less keys available for controlling the unit and for accessing system information: Key
W3000, W3000 base W3000 compact

Description [MENU key]: accesses the main menu. [UP key]: moves around the masks and sets control parameter values [DOWN key]: moves around the masks and sets control parameter values [ENTER key]: confirms entered data. [ESC key]: goes back one level in the mask tree if you are in the header masks, or returns to the unit controller. [ALARM key]: displays the alarms and resets normal operating conditions. [SETPOINT key]: directly accesses the setpoint menu. [ON/OFF key]: switches the machine on and off.

-----

For each compressor, the following LED's are also located on the W3000 user interface: Symbol Colour Green Red Green Green Green Green Green Description If the LED shines steady the compressor is on, if it flashes the compressor is demanded The compressor is blocked by a compressor or circuit alarm The compressor is in the chiller mode The circuit is in the freecooling mode The compressor is in the heat pump mode If the LED shines steady the circuit is in the recovery mode, if it flashes there is a recovery alarm If the LED shines steady the circuit is in the defrost mode, if it flashes it is in the drip mode

C0240111-01-06-GB

MENU STRUCTURE
Power On

The tree structures for moving around the various menus are shown below.
Menu Tasto key Men
Tasto Setpoint Setpoint key

Alarm Tasto key Alarm

Termoregolatore Thermoregulator

Esc / Esc Selezione Unit menu Men unit selection / Esc Selezione Setpoint menu Men setpoint selection / Esc Selezione I/O menu Men I/O selection / Esc Selezione Clock menu Men orologio selection / Esc Selezione User menu Men utente selection / Esc Selezione Manufacturer Men costruttore menu selection / Esc / Esc / Password User utente Password Esc Password Factory costruttore Password Esc Esc / Esc / Esc / Esc /

Alarm Alarm Men menu

Unit menu Men unit

Setpoint menu Men setpoint

I/O menu Men I/O

Men orologio Clock menu

User utente Men menu

Manufacturer Men costruttore menu

Figure 2.1: menu tree for W3000-W3000 compact


Power On

Menu Tasto key Men

Setpoint Tasto key Setpoint

Alarm Tasto key Alarm

Thermoregulator Termoregolatore

Esc /

Visual. Termoreg. Thermoregulator

Display

Esc / Esc Selezione Unit menu Men unit selection / Esc Selezione Setpoint menu Men setpoint selection / Esc Selezione I/O menu Men I/O selection / Esc Selezione Clock menu Men orologio selection / Esc Selezione User menu Men utente selection / Esc Selezione Manufacturer Men costruttore menu selection / Esc / Esc / Password User utente Password Esc Password Factory costruttore Password Esc Esc / Esc / Esc / Esc /

Alarm Alarm Men menu

Esc /

DisplayAlarm Visual. alarm

Unit menu Men unit

Esc /

Display unit Visual. unit

Men setpoint Setpoint menu

Esc /

Displaysetpoint Visual. setpoint

I/O menu Men I/O

Esc /

DisplayI/O Visual. I/O

Men orologio Clock menu

Esc /

Display clock Visual. orologio

User utente Men menu

Esc /

Display user Visual. utente

Manufacturer Men costruttore menu

Esc /

Display Visual. costruttore manufacturer

Figure 2.2: menu tree for W3000 base

C0240111-01-06-GB

The menus are briefly described below: The Unit Menu contains information such as temperature, pressure and circuit states. The Setpoint menu is used to set the setpoints for the various available functions. The I/O menu shows the status of the digital inputs and values read from the analogue inputs. It also shows the status of the digital outputs and the voltage supplied to the analogue outputs. If expansions are necessary (depending on the configuration parameters), the inputs and outputs of the latter are also shown. The Clock menu, if the clock card is present, is used to set and display the date and time. Parameters relative to user programming of the unit can be displayed and set in the User menu. The Manufacturer menu is used to display and set critical system parameters.

C0240111-01-06-GB

SETTING THE CONNECTIONS

Set the hardware connections before switching on the unit. The inputs/outputs table explaining the functions of the various connectors on the unit is contained in [annex 2] at the end of this manual.

3.1 Available hardware


UNIT B

UNIT M

C0240111-01-06-GB

UNIT L

UNIT XL

C0240111-01-06-GB

EXPANSION E

W3000

C0240111-01-06-GB

3.2 Connecting more than one unit


Caution: perform the following operations before touching the cards in order to prevent electrostatic discharge: wear the bracelet (connected to the earth circuit) and the heel strap the card should be closed inside an antistatic bag protecting it from electrostatic discharge: remove it from the bag and place it on the light-blue mat with the yellow edge or on the dark-blue mat. You can now work on the card. Several intercommunicating cards can be connected together on units L or XL. There are two connection types: base-expansion on the expansion serial line and master-slave on the plan serial line. The mixed connection is a combination of the other two. Details are shown below. 3.2.1 BASE-EXPANSION CONNECTION In the base-expansion connection, the entire intelligence of the unit resides in the base. The connected expansions are exclusively used as additional I/O. The cards must be connected together with a threewire shielded cable connected from terminal J23 of the base to terminal J3 of expansion E or to terminal J11 of expansion M (see figure 3.1).

Figure 3.1: base-expansion connection The expansions must be given a specific address depending on the type of chiller and the enabled functions:

C0240111-01-06-GB

EXPANSIONS FOR HERMETIC COMPRESSORS: Additional function Recovery enable Recovery enable Freecooling enable HP relay enable Low temperature control enable Low pressure transducer enable Number of compressors for circuit 3 or 4 Function, chiller type Chiller with heat recovery Multi-use Heat pump with total heat recovery Freecooling chiller Chiller with HP relay Low temperature chiller Any chiller with hermetic compressors where low pressure monitoring is required Chiller with 3 or 4 hermetic compressors per circuit Expansion address 1 2 Expansion type E M

EXPANSIONS FOR SEMI-HERMETIC COMPRESSORS: Additional function Recovery enable Recovery enable Freecooling enable HP relay enable Setpoint variation enable Recovery setpoint variation enable Secondary setpoint enable Number of evaporators 0 Number of compressors per circuit 2 At least one pump enable Heat pump Recovery enable Freecooling enable HP relay enable Low temperature control enable 2 evaporators Function, chiller type Chiller with heat recovery Multi-use Heat pump with total heat recovery Freecooling chiller Chiller with HP relay Unit with setpoint or secondary setpoint enable Condensing units Unit with 2 alternative compressors per circuit Chiller with pumps on card Heat pump chiller Chiller with heat recovery Freecooling chiller Chiller with HP relay Low temperature chiller Chiller with more than one evaporator Expansion address 1 2 Expansion type E M

EXPANSIONS FOR CENTRIFUGE COMPRESSORS: Additional function Setpoint variation enable Secondary setpoint enable Function, chiller type Unit with setpoint or secondary setpoint enable Expansion address 3 Expansion type E

10

C0240111-01-06-GB

3.2.2 MASTER-SLAVE CONNECTION Intelligence is distributed instead in the masterslave connections. Suppose we have a unit with 4 cooling circuits: the master card manages circuits 1 and 2 while the slave card manages circuits 3 and 4. In this case, the additional card is not simply an input/output expansion, but is fully involved managing part of the unit. The card software is the same and identifies its functions depending on the card address: the one with address 1 will be the master and will communicate with the card with address 11 (master address plus 10). Pay special attention to card addresses for this reason. Connect the cards together with a 3-wire shielded cable connected between terminals J11 of the cards, as shown in figure 3.2.

Figure 3.2: master-slave connection

11

C0240111-01-06-GB

3.2.3 MIXED CONNECTION: The mixed connection is used in units with 3/4 cooling circuits where an increase in inputs/outputs is required. The master card manages circuits 1 and 2 while the slave card manages circuits 3 and 4. Additionally, depending on the required functions or the type of machine, cards used simply as expansions can be connected. The expansions will be connected to both the master and the slave if the required inputs/outputs are circuit functions (recovery valves, freecooling,). They will only be connected to the master if they are machine functions (pumps, external air temperature,). Figure 3.3 shows the connections between the cards and the expansions: a 3-wire shielded cable connects terminals J11 of the master and slave cards, and a 3-wire shielded cable connects terminals J23 of the master and/or slave cards with terminal J3 or J11 of expansions E or M.

Figure 3.3: mixed connection

12

C0240111-01-06-GB

3.3 Additional connections


In this case set the card address with the following dip-switches:
ON DIP ON DIP

Cards L,XL

Cards E

Table of possible combinations: (0 = off, 1= on) Address 0 1 2 3 4 5 1 0 1 0 1 0 1 2 0 0 1 1 0 0 3 0 0 0 0 1 1 4 0 0 0 0 0 0

13

C0240111-01-06-GB

3.4 Configuring the terminals


The first operation to perform when a network is started up for the first time or a card is replaced, is to perform the procedure for terminal configuration. This cannot be achieved with the basic W3000 keypad. In this case, configure the terminals using the W3000 or W3000 compact keypad and then connect the W3000 basic display. Before starting, it is advisable to check that each card and each terminal has been identified with the correct address established when the network was designed. It is important to remember that as the set address is only read by the boards during startup, it is best to perform a global reset of all the devices if a mistake is made when configuring the addresses (more than one card with the same address). Reset the network by disconnecting all the devices from the power supply . The configuration procedure can be activated from any terminal (keypad), which may also be connected temporarily only to perform configuration operations and removed upon completion. The operations to perform are described in the following paragraphs.

3.4.1 SETTING THE KEYPAD ADDRESS


After connecting the keypad to the device, perform the following procedure: 1) Press [UP], [DOWN] and [ENTER] together and hold down until the mask shown to the side appears. Press [ENTER] to move the cursor to Display address setting. Press [UP] and [DOWN] to set the required keypad address (e.g.: 21 ).

Display address Setting..........:00 I/O Card address: Display address Setting..........:21 I/O Card address:--

2)

3)

This mask means that the address of the keypad has been set.

Display address changed

4)

If an empty mask or a mask showing NO LINK appears after pressing [ESC], it means that the keypad is not communicating with any card. Either the card must be addressed or the plan network must be configured.

NO LINK

N.B.: This is a timed procedure; if the parameters are not set within a few seconds, the display turns off. In this case, the operation must be repeated.

14

C0240111-01-06-GB

3.4.2 SETTING CARD ADDRESSES


The card address is set by the software using the keypad. Proceed as follows: 1 Make sure the keypad address is set to 0 ( see para 3.4.1).

Display address Setting..........:00 I/O Card address:

Disconnect the card from the power supply (turn off the general switch). Power the card by pressing [ALARM] and [UP] together; hold the keys down until the mask shown to the side appears. Set the required address (e.g.: 1 ) To do this, press [UP] or [DOWN]; press [ENTER] to confirm. An empty mask appears because the address of the keyboard is 0 and that of the board is (as shown in the example) 1; the two devices cannot communicate. In any case, card address 1 has been set. Now perform NETWORK CONFIGURATION to allow the card to communicate with its keypad

pLan address: 0 UP: increase DOWN: decrease ENTER: save & exit pLan address: 1 UP: increase DOWN: decrease ENTER: save & exit

15

C0240111-01-06-GB

3.4.3 CONFIGURING THE PLAN NETWORK CONFIGURING THE PLAN NETWORK (local):

For each unit with an on-board keyboard, perform the following procedure to create a locale plan network: 0 Make sure the card has been addressed (see para 3.4.2).

Press [UP], [DOWN] and [ENTER] together and hold down until the mask shown to the side appears. Set the required address for the keypad (e.g.: 21 )

pLan address: 1 UP: increase DOWN: decrease ENTER: save & exit Display address Setting..........:00 I/O Card address: Display address Setting..........:21 I/O Card address:--

Display address Press [ENTER] to display the address of the cards in pLan (in this Setting..........:21 case 1 ). N.B.: If there is more than one card, press [UP] or [DOWN] to choose I/O Card address:01 which card to configure.
Press [ENTER] to configure the terminals; press [ENTER] to confirm

Terminal config Press ENTER To continue

P:01 Adr Priv/Shared Trm1 None -Trm2 None -Trm3 None -- Ok?No Configure keyboard 21 (previously set) as Pr=private (usually the one P:01 Adr Priv/Shared Trm1 21 Pr on the unit). (Sp=printer, or Sh=shared) Trm2 None -Trm3 None -- Ok?No P:01 Adr Priv/Shared The remote keypad must also be configured. Simply define the Trm1 21 Pr keypad addressed with 32 (even if not present) as Sh. Trm2 32 Sh Trm3 None -- Ok?No To save the settings and exit the configuration procedure, move the P:01 Adr Priv/Shared cursor to No, change it to Yes and press [ENTER]. To exit without Trm1 21 Pr saving the settings, wait 30 seconds without touching the keypad. Trm2 32 Sh Trm3 None -- Ok?Yes ##################### The following mask may appear. If no expansions are connected, expansion simply press [ESC] to show the main display menu. connection #####################

In this mask, the [ENTER] key moves the cursor from one field to another and the [UP] or [DOWN] keys change the values. P:01 means that the card with address 1 is being configured.

To connect several units together and remote control them, thereby forming a plan network (global), a remote keypad controlling all the units is required. The remote keypad cannot be used with a W3000 basic keypad. If a W3000 basic keypad is installed on the machine, replace it with a 3000 compact.

16

C0240111-01-06-GB

CONFIGURING THE PLAN NETWORK (global):

It is easy to install a PLAN network (global). Just a few but essential operations are required. If just one of these is not performed correctly, the entire system will not work. The remote keypad will work problem-free if the following operations are performed one after the other. 1 2 3 4 5 6 7 8 9 11 Set the on-board machine card and keypad addresses (see configuring the local plan network) Check the chillers work correctly without being connected to the network. Disconnect the power supply from the chillers Connect all the chillers to the network except for the remote keypad. Power the chillers. Check that all the networked devices work correctly Connect the remote keypad to one of the units Make sure the remote keypad address is set to 32. Make sure that the devices outside the chillers are correctly configured. Connect the remote keyboard. If any faults occur, check the configuration of the terminals to make sure that no two devices have the same address. Disconnect the machine keyboard and connect the remote keypad to the J10 connector. Follow the procedure for addressing the keyboard (see para 3.4.1). If the power unit for the remote keypad is fitted (see below: remote keypad from 200 up to 500 metres), make sure the remote keypad is powered. Disconnect connector J10 from the last board and connect it to connector A of the T shunt. Connect connector J10 on the last board to connector B of the T shunt. Connect connectors J11 together. Do not connect the remote keyboard. This creates a plan network comprising more than one chiller. Leaving the network cable disconnected. configure the terminals on each card and keypad (J11 connector)

10

Wait a few seconds until network communication has stabilised. If there is global network comprising just W3000 chillers, the W3000-compact can be used as a remote keyboard. After configuring the various units (each with a different address in order not to generate conflicts in the global network), connect the remote keyboard and repeat the procedure. In this case, the various machines of the network are switched by pressing [ESC] and [UP] together. If the plan network does not comprise just W3000 chillers, a 16-key keypad must be used. In this case, press [UNIT] to switch between one card and another. In this case, however, the terminals must be given a special configuration as the 16-key keypad is only recognised on terminal 3. The terminal configuration procedure remains the same up to point 6 of paragraph 3.4.5, after which: The remote keypad can be configured even if the plan network doe not P:01 Adr Priv/Shared Pr comprise just W3000 chillers. Simply define the keypad addressed with Trm1 21 Trm2 None -32 (N.B.: on terminal 3) as Sh, i.e.: shared. To save the settings and exit the configuration procedure, move the cursor to No, change it to Yes and press [ENTER]. To exit without saving the settings, wait 30 seconds without touching the keypad.

Trm3 P:01 Trm1 Trm2 Trm3

32 Sh Ok?No Adr Priv/Shared 21 Pr None -32 Sh Ok?Yes

17

C0240111-01-06-GB

CONNECTING THE REMOTE KEYPAD: T SHUNT: Let us analyse a vital component for connecting several units in a network: the T shunt. This is a shunt with phone connectors (called A,B,C in figure 3.4b). CONFIGURATION: For our purposes, configure terminals J14 and J15 (see Figure 3.4b). There are several pins in each terminal. Short pins 1 and 2 with a jumper.

Figure 3.4a: photo of a T shunt

Screw terminal 0 1 2 3 4 5 6

Function Earth (sheath of shielded cable) +VRL=30V GND Rx+/Tx+ Rx+/Tx+ GND +VRL=30V

Figure 3.4b: wiring diagram of a T shunt

Figure 3.4c: terminal card of a T shunt T

REMOTE KEYPAD UP TO 200 metres:

To connect a remote keypad, two T shunt cards must be used, one near the controller and the other near the remote keypad, configured as indicated above. The T shunt cards must be connected together by terminals. 1. If the remote keypad monitors just one unit, proceed as follows: Disconnect the connector J10 connecting the keypad on the unit with the card, and connect it to connector A of the T shunt (see figure 3.5). Connect connector J10 on the card to connector B of the T shunt. The correct configuration is shown in figure 3.5:

18

C0240111-01-06-GB

SHIELDED TWISTED

Figure 3.5 : connecting the remote keypad (for distances less than 200 metres) 2. If a remote keypad monitors more than one unit, the above configuration may only be used for the last card in the network (the nearest to the remote keypad).

REMOTE KEYPAD FROM 200 metres UP TO 500 metres N.B.: The remote keypad cannot be installed more than 500 m away. If the remote keypad must be installed over 200 metres away from the plan network, a power unit must be installed near the remote keypad. The only difference between this and a remote keypad up to 200 metres is that the power unit must be to terminals 1 and 2 of the T shunt (the one near the remote keypad) The connection diagram is:

19

C0240111-01-06-GB

SHIELDED TWISTED

Figure 3.6: connecting the remote keypad (for distances between 200 and 500 metres)

20

C0240111-01-06-GB

SWITCHING THE UNIT ON AND OFF


Caution: connect the unit to the power supply at least 8 hours before starting it; if this is not done, the guarantee will become null and void.

After making connections (see chapter 3) there are different procedures for starting or stopping the unit: using the user interface keys or selecting from the display. The following procedures have a priority. In the event of conflicts between different settings, the following priorities apply: - highest priority: - lowest priority: on/off on/off on/off on/off from from from from keypad on/off from parameter digital input time bands protocol

using the [ON/OFF] key :


The unit can only be switched off in the W3000 and W3000 base versions. Proceed as follows: SWITCHING ON: press the [ON-OFF] key. SWITCHING OFF: press the [ON-OFF] key. In the W3000, the message Com. : ON appears on the display In the W3000 base, the message On appears on the display with the LED on, or OFF with the LED off.

using the On/Off parameter:


Only in the W3000 and W3000 compact. The Com: On/Off parameter can be displayed on the user interface. Off means that the unit is switched off while On means that the unit is switched on. Proceed as follows: SWITCHING ON: Move to the On/Off parameter by pressing [Enter] and then press [Up] or [Down] until On appears. Press [Enter] again to confirm. If On continues to be displayed it means that the unit has been switched on. SWITCHING OFF: Move to the On/Off parameter and change to Off using the same procedure used to switch the unit on. Press [Enter] again to confirm. If Off continues to be displayed it means that the unit has been switched on.

using the On/Off from digital input command:


Only if the digital input is present (or an additional button on the user interface). Check that the On/Off enable from digital input parameter in the user menu is set to Yes. When the contact is open the unit is Off, when the contact is closed the unit is On. Proceed as follows: SWITCHING ON: Close the remote On/Off contact. The On from digital input message appears in the main mask to show that the unit has been switched on. SWITCHING OFF: Open the remote On/Off contact. The Off from digital input message appears in the main mask to show that the unit has been switched off. In the W3000 base the following procedure is used: press [MENU] / select the User menu using the [UP] or [DOWN] keys / press [ENTER] to access the menu / press enter to type in the password / press [UP] or [DOWN] to choose the password and [ENTER] to confirm / use the [UP] or [DOWN] keys to choose the dI 0 (Enable from digital input) mask / press [ENTER] to view

21

C0240111-01-06-GB

the current setting of the parameter (Y or N) / press [ENTER] to modify the parameter (the display flashes) / press [UP] or [DOWN] to select one of the two alternatives. Press the digital input button on the panel to switch the unit on and off.

using time bands:


Only in the W3000 and W3000 compact and if the clock card is present. Make sure that the Clock card not installed mask does not appear in the clock menu . Check that the Time bands enable parameter in the user menu is set to Yes. SWITCHING ON: Set the required switching on time in the clock menu. The unit switches on when the set time is reached. The On from time bands message appears in the main mask to show that the unit has been switched on. NB.: The unit does not switch on if it is set to Off from keypad or Off from digital input. SWITCHING OFF: Set the required switching off time in the clock menu. The unit switches off when the set time is reached. The Off from time bands message appears in the main mask to show that the unit has been switched off.

using the supervision protocol:


Only if the serial card is fitted. Check that the Supervisor enable and On/Off enable from supervisor parameters in the user menu are set to Yes. Proceed as follows: SWITCHING ON: Send the switching on command from the protocol. The On from supervisor message appears in the main mask to show that the unit has been switched on. NB.: The unit does not switch on if it is set to Off from keypad or Off from digital input. SWITCHING OFF: Send the switching off command from the protocol. The Off from supervisor message appears in the main mask to show that the unit has been switched off. In the W3000 base the following procedure is used: press [MENU] / select the User menu using the [UP] or [DOWN] keys / press [ENTER] to access the menu / press enter to type in the password / press [UP] or [DOWN] to choose the password and [ENTER] to confirm / use the [UP] or [DOWN] keys to choose the SPr (Enable from supervisor) mask / press [ENTER] to view the current setting / press [ENTER] to see the display flashing / press [UP] or [DOWN] to modify the setting and press [ENTER] to confirm.

22

C0240111-01-06-GB

USER PROGRAMMING

The following settings can be modified using the interface.

5.1) SETTING THE OPERATING MODE


Caution: Do not switch from the summer to winter mode unless the inlet temperature is above 15C. Do not switch from the winter to summer mode unless the inlet water temperature is below 30C.

There are various ways of setting the operating mode of the unit. The set operating mode may be any one of the following, as long as they are compatible with the unit: Operating mode W3000 base Chiller ch chiller+rec heatpump hp summer ch summer ch+rec summer rec recovery summer auto winter hp winter rec winter auto auto Description

Chiller Chiller plus recovery Heat pump Chiller in summer mode Chiller plus recovery in summer mode Recovery in summer mode Recovery only Automatic in summer mode Heat pump in winter mode Recovery in winter mode Automatic in winter mode Automatic

The following procedures have a priority: in the event of conflicts between opposing settings the following priorities apply: - highest priority: - lowest priority: change through parameter sum/win from digital input ch/ch+rec from digital input change through protocol

Using the parameter:


Make sure the unit is Off. Access the setpoint menu and display the Operating mode parameter. Move to the Operating mode parameter by pressing [Enter] and modify the parameter by pressing [Up] or [Down]. Press [Enter] again to confirm. If the set message continues to be displayed it means that operating mode has been changed. In the W3000 base the key sequence is: switch off the unit using the [ON/OFF] key / press the [setpoint] key / select MODE with the [UP] or [DOWN] keys / press [Enter] / press [Enter]. At this point the cursor flashes. Press the [UP] or [DOWN] keys to select either ch= chiller or hp= heat pump. Press [Enter] to confirm.

Using the Sum/Winter from digital input command:


Only for heat pump units and only if the digital input is present. Check that the Sum/Win enable from digital input parameter in the user menu is set to Yes. When the contact is open the unit is in the winter mode, when the contact is closed the unit is in the summer mode. Switching the digital input switches the unit off, changes the operating mode and switches the unit on again.

23

C0240111-01-06-GB

In the W3000 base access the user menu / select DI S by pressing the [UP or DOWN] key/ press [Enter] to view the current setting / press [Enter] to see the current setting flashing and change it using the [UP or DOWN] key / press [Enter] to confirm the new setting.

Using the recovery from digital input command:


Only for chiller plus recovery units and only if the digital input is present. This mode is not present in the W3000 base. Proceed as follows: check that the Recovery control enable from digital input parameter in the Recovery menu is set to Yes. When the contact is open the unit is in the chiller+rec mode, when the contact is closed the unit is in the chiller mode. Switching the digital input switches the unit off, changes the operating mode and switches the unit on again.

Using the supervision protocol:


Only applicable if the serial card is fitted. Check that the Supervisor enable and Enable operating mode from supervisor parameters in the user menu are set to Yes. Make sure the unit is Off. Send the change operating mode command from the protocol. The operating mode only changes if the unit is switched off. In the W3000 base press [ON/OFF] to switch the unit off. Access the user menu / press [UP] or [DOWN] to select SV M/ press [Enter] to view the set mode / press [Enter] to see the setting flashing / press [UP] or [DOWN] to modify the setting / press [Enter] to confirm the new setting. Send the change operating mode command from the protocol. The operating mode only changes if the unit is switched off.

24

C0240111-01-06-GB

5.2) USER MENU


The user menu is used to display and set important operating, adjustment, setpoint and recovery parameters. The physical principles lying at the heart of some special functions are described below.

5.2.1 ) ADJUSTMENT
Depending on the type of hardware and the type of compressor used, a choice may be made (for inlet or outlet temperature) between STEP and QUICK MIND adjustment. N.B.: some functions, such as setting the compressor type and modulating adjustment, can only be set from the manufacturer menu. XL Hardware Hermetic compressor

Other Hardware
Step adjustment (inlet only) Quick Mind adjustment (outlet only)

Alternative compressor Screw compressor

Step adjustment (inlet only) Quick Mind adjustment (outlet only) Step adjustment (inlet only) Quick Mind adjustment (outlet only) Modulating adjustment (Quick mind for outlet required)

Centrifuge compressor

Proportional step adjustment for inlet and integral for outlet

Table 5.3: adjustment types depending on the type of hardware and the type of compressor The various adjustment methods are shown in detail below.

STEP INLET ADJUSTMENT METHOD:

The procedure for accessing step inlet adjustment is shown in the parameters annex. The step inlet adjustment type and adjustment band can be set from the relative parameters in the user menu. Some examples of step adjustment for the input variable (inlet temperature) are shown below. Figures 5.1 and 5.2 show the graphs of the variable controlled according to the power delivered by the machine for two typical cases.

25

C0240111-01-06-GB

summer ( n steps=2 ) P out

T in proportional band

Figure 5.1: Tin is the inlet variable, Pout is the percentage of delivered power (summer). = Set + proportional band/2

Winter (n steps = 2) Pout

Tin

proportional band
Figure 5.2: Tin is the inlet variable, Pout is the percentage of delivered power (winter). = Set + proportional band/2 Table 5.1 and 5.2 show some typical values for the parameters in question. The theoretical maximum and minimum outlet temperature values refer to operation at nominal flow rates ( with a thermal head at the evaporator of 5 C and sufficient water in the system to ensure a litre / KW ratio equal to or greater than 11). N steps 2 4 Setpoint (C) 9.5 7 Proportional band (C) 2.5 5 Theoretical min. outlet T 5.7 5.7 Theoretical max. outlet T 10.8 8.3

Table 5.1: normally used setpoint and proportional band values according to the number of steps (summer).

26

C0240111-01-06-GB

N steps 2 4

Setpoint (C) 42.5 45

Proportional band (C) 2.5 5

Theoretical min. outlet T 41.2 43.7

Theoretical max. outlet T 46.3 46.3

Table 5.2: normally used setpoint and proportional band values according to the number of steps (winter).

QUICK MIND ADJUSTMENT METHOD:

QUICK MIND adjustment is not available on chillers with recovery or freecooling or multi-purpose. QUICK MIND adjustment is currently only possible on outlet water temperature. Users only need set the required setpoint as the other parameters are adapted to the system by the Quick Mind algorithm. The values normally used are: Chiller SETPOINT 7 C Heat pump SETPOINT 45 C QUICK MIND is a self-adapting algorithm for adjusting the temperature of the water treated by a chiller. Figure 5.3 shows how this adjustment is made:
SUMMER ESTATE

Disattivazione compressori Compressors deactivated ZONA NEUTRA DEAD AREA

Attivazione compressori Compressors activated Tin/Tout

Setpoint

INVERNO WINTER

Attivazione compressori Compressors activated


DEAD AREA ZONA NEUTRA

Compressors deactivated Disattivazione compressori

Tin/Tout

Setpoint

Figure 5.3: QUICK MIND adjustment model (summer and winter) The setpoint remains within a dead area. If the temperature also remains within this area, no change is made to the number of active compressors. When the temperature leaves the dead area following a change in system load, the compressors are either activated or deactivated in order to return the temperature to the dead area. The amplitude of the dead area depends on the dynamic characteristics of the system and, in particular, on the amount of water it contains and the load. The self-adapting algorithm is able to measure system dynamics and calculate the minimum dead area in order to respect compressor activation times and the maximum number of start-ups per hour. Both return and delivery temperatures can be adjusted. Special functions are also present which reduce the number of compressor start-ups in the event of very low loads or start-ups of units with significantly higher or lower temperatures than the setpoint.

27

C0240111-01-06-GB

2 compressors Litres/kW 10.5 3.2 out 2 compressors Litres/kW 10.5 3.0 out 4 compressors Litres/kW 10.5 1.8 out 4 compressors Litres/kW 10.5 1.8 out

with maximum permitted number 9.5 8.5 7.5 3.2 3.4 3.4 with maximum permitted number 9.5 8.5 7.5 3.0 3.0 3.2 with maximum permitted number 9.5 8.5 7.5 1.8 1.8 1.8 with maximum permitted number 9.5 8.5 7.5 1.8 1.8 1.8

of start-ups per 6.5 5.5 3.6 3.8 of start-ups per 6.5 5.5 3.2 3.4 of start-ups per 6.5 5.5 1.8 1.9 of start-ups per 6.5 5.5 1.8 1.9

hour 8 4.5 4.0 hour 12 4.5 3.6 hour 8 4.5 2.0 hour 12 4.5 2.0

3.5 4.4 3.5 3.8 3.5 2.3 3.5 2.3

2.5 5.2 2.5 4.3 2.5 2.7 2.5 2.7

Table 5.3: maximum theoretical delivery temperature range at constant part load (depending on the quantity of water contained in the system) An example of real data acquired during operation with the Quick Mind adjuster on the delivery side is shown below. Reference is made to figure 5.4.

Fase di avviamento controllato Adattamento zona neutra Temperatura uscita evaporatore Temperatura ingresso evaporatore 1 compressore attivo 2 compressori attivi

= = = = = =

Controlled starting phase Adaptation to dead area Outlet temperature of evaporator Inlet temperature of evaporator 1 compressor active 2 compressors active

Figure 5.4: example of real data with quick-mind outlet adjustment (x-axis: time in [s]; y-axis: Tout in [C] ). This is an example of start-up with a very high initial temperature compared with the setpoint (7C). About 10 seconds after data acquisition began, one compressor switches on. The second compressor does not switch on immediately as the algorithm which handles start-up checks if one compressor is enough to return delivery temperature to the setpoint and avoid unnecessary start-ups. As the delivery temperature is still at 12 C after about 200 seconds, the second compressor is also switched on, otherwise it would take too long to reach setpoint. Following the controlled starting phase, the delivery temperature falls until it enters the dead area. The algorithm (at t= 350 s) begins to adapt the amplitude of the dead area in order to respect compressor safety times. As can be seen, the dead area is later reduced (t= 780 s, 950 s) to the absolute minimum amplitude which allows safety times to be respected. It can also be seen that the compressors are

28

C0240111-01-06-GB

activated and deactivated when the outlet temperature reaches the upper or lower limits of the dead area. The example shows that outlet temperature varies by about 3.5 C during regular operation.

ADJUSTMENT METHOD FOR CENTRIFUGE COMPRESSORS:

The W3000 controller can manage units with centrifuge compressors. The units are combination-adjusted (steps and continuously), with steps for activating the compressors. Some diagrams outlining how this works are shown below. Suppose we have a single compressor unit (figure 5.5).
Absorbed P o te n z a power a s s o rb ita [kW]] [K w

M ax

M in P o te n z a power ric h ierequestl s ta d e te rm o re g o la to re [%] [% ]

Thermoregulator

s e t p o in t (0 % )

% a c c e n s io n e % compressor c o switch-on re m p re s s o

SSetppoint + B a n d a e t o in t + Prop. p ro p o rz io n(100%) 0 % ) band a le (1 0

Figure 5.5: adjustment for a single-compressor unit. Min=theoretical minimum electrical power absorbed by a compressor, Max=theoretical maximum electrical power absorbed by a compressor Let us take a close look at how the compressor is activated (figure 5.6). When the system return temperature lies in zone A (figure 5.6a) or less than the setpoint, the compressor is off. The amplitude of zone A normally coincides with the temperature difference at the evaporator with the compressor running at minimum power. When the return temperature exceeds zone A (figure 5.6b), the compressor is switched on and then switches off if the temperature falls below the setpoint. If the return temperature lies in zone B (figure 5.6c), the power of the compressor is modulated according to system requirements.
set point + proportional band Tin [C]

set point + proportional band

Tin [C]

start compressor 1 set point

A
t [min]

start com pressor 1 set point

A
t [m in]

ON

ON

OFF

OFF

Figure 5.6 a)

Figure 5.6 b)

29

C0240111-01-06-GB

s e t p o in t + p r o p o r t io n a l b a n d

T in [ C ]

B
s ta rt c o m p re s s o r 1 s e t p o in t t [m in ] O N

O FF P a s s [K w ] m ax

m in

Figure 5.6 c)

Suppose we have a unit with more than one compressor (figure 5.7).

Potenza Absorbed assorbita power [Kw] [Kw]

Max

2x Min Min

set point (0%)

% % % accensione % accensione compressor 1 compressor 2 compressore 1 compressore 2switch-on switch-on

Set point + Banda Set point + prop. band (100 %) proporzionale (100 %)

Potenza Thermoregulator power richiesta [%] Request del termoregolatore [%]

Figure 5.7: adjustment for a two-compressor unit. Min=theoretical minimum electrical power absorbed by a compressor, Max=theoretical maximum electrical power absorbed by a compressor. Let us take a close look at how the compressor is activated (figure 5.8). The amplitude of zone A coincides with the temperature difference at the evaporator, with all the compressors running at minimum power. Zone A is the sum of the zones of each single compressor (A1+A2+). When the temperature lies in one of the An zones, the power of the active compressors is modulated according to system requirements. When moving from an An zone to the one just above it, the active compressors are taken to minimum power while waiting for the next one to be switched on. After that, they continue to be modulated in the new zone. When moving from an An zone to the one just below it, one of the compressors is switched off while the others are kept at a minimum.

30

C0240111-01-06-GB

sSee tt p o o n n t p i it + + p d p r r n o b i nd b a n r oa op t ioo p a l r z ao n a l e

T in

[ C ]

srt t sos 2 s t a t a r2 c o m p r eps r e r s o r e c o m s t t c 1o s t a tra r 1 ocm pm ep s o rs s r e o r sre


s e t p o in t m a x P a s s [K w ]

A 2 A A 1
t [m in ]

C o m p r.1

m in

m a x

P a s s

[K w ]

C o m p r.2 m in

Figure 5.8: adjustment for a two-compressor unit

CONTINUOUS ADJUSTMENT METHOD FOR SCREW COMPRESSORS (modulating adjustment)

In screw compressors, modulating adjustment requires Quick mind outlet adjustment. Modulating adjustment is only available on Bitzer screw compressors. Reference is made to figure 5.9. The setpoint remains within a dead area. If the temperature also remains within this zone, no change is made to the number of active compressors or their load percentages (position of modulating chamber). When the temperature rises above zone B following a change in the system load, the compressors are activated in order to return the temperature to the dead area. Inside zone B, compressor power is modulated to return the temperature to the dead area (DA).

Tout [C]

B(increase) (incremento)
set point

ZN DA

t [min]

C (decremento) (decrease)

Figure 5.9: adjustment for screw compressors When the temperature falls below zone C following a change in the system load, the compressors are either deactivated in order to return the temperature to the dead area. Inside zone C, compressor power is modulated to return the temperature to the dead area (DA). The amplitude of the dead area depends on the dynamic characteristics of the system and, in particular, on the amount of water it contains and the load. The self-adapting algorithm is able to measure system dynamics and calculate the minimum dead area in order to respect compressor activation times and the maximum number of start-ups per hour.

5.2.2 ) RECOVERY
The user menu can be used to set certain recovery parameters, such as the recovery adjustment band and the recovery setpoint.

31

C0240111-01-06-GB

100% 75%

50% 25%

Banda regolazione recupero Recovery adjustment band Setpoint Recovery recupero setpoint

T.Rec [C]

Figure 5.10: recovery function of a 4-circuit unit

32

C0240111-01-06-GB

5.3) SETPOINT MENU


Different setpoints can be set depending on the available operating modes (chiller, heat pump and recovery). Secondary setpoint values can also be set for chiller and heat pump operation (only if the digital input is fitted and the secondary setpoint function is enabled in the user menu).

5.4) CLOCK MENU


The clock menu is not enabled in the W3000 base. After enabling time bands from the enable time bands parameter in the user menu, time bands can be set and specific operating modes and different setpoints can be set according to requirements. Several time bands (up to 10) of different types (A, B, C and D) can be set during the day. Figure 5.11 shows an example: the beginning of the first time band is set at 00:00 and the end of the tenth time band is set at 23:59; the end of one time band determines the beginning of the following one. To use a smaller number of bands, set the time a band ends to the same time it begins, and that band will be ignored. Summer and winter setpoints and unit On/Off switching can be set for each time band. If the unit is switched Off, it will remain in the Off from time bands mode.

Adjustment Unit off

Figure 5.11: example of setting time bands

33

C0240111-01-06-GB

MANUFACTURER PROGRAMMING

The manufacturer menu is not present in the W3000 base. For the other user interfaces, instead, access the manufacturer menu by pressing [Menu] / selecting the manufacturer menu by pressing [UP] / entering the password. The tree diagram of the manufacturer menu is shown in figure 6.1.
S e le z io n e Manufacturer M e n c o s tru tto re Menu selection E sc / M Manufacturerumenu e n c o s tr tto re / Esc

Configurationnmenu S e le z io e M e n c selectionr a z i o n e o n f ig u
/

E sc /

M e n c o n f i g u menu n e Configuration r a z io

Esc

Global io n e S e le z menu M e n g lo b a le selection


/

E sc /

Global menu M e n g lo b a le

Esc

Functions menu S e le z io n e M e nselection io n i fu n z

E sc /

M Functions menu i e n f u n z io n

Esc

Pumps io n e S e le z menu M en pom pe selection


/

E sc /

M en pom pe Pumps menu

Esc

Compressorsnmenu S e le z io e M e n selectione s s o r i com pr


/

E sc /

Compressors menu M e n c o m p re s s o ri

Esc

Valves io n e S e le z menu M e n v a l v o le selection


/

E sc /

Valves a lv o M e n v menule

Esc

Recovery menu S e le z io n e M e n selectionp e r o re c u


/

E sc /

M Recovery menu o e n re c u p e r

E sc

Condensation menu S e l e z io n e M e n c o n d e n s a z io n e selection


/

E sc /

Condensation a z io M e n c o n d e n smenu n e

E sc

Freecooling n e S e l e z io menu M e n selection o lin g fre e c o


/

E sc /

Freecooling o o li n M e n f r e e c menu g

E sc

Defrosting menu S e l e z io n e M e n selectionm e n t o s b r in a


/

E sc /

Defrosting menu M e n s b rin a m e n to

E sc

Alarms menu S e l e z io n e M e n s ic u re z z e selection


/

E sc /

M e Alarms menu z e n s ic u r e z

Esc

Calibration menu S e le z io n e M e nselectiont u r a ta ra


/

Esc /

Calibration menu M e n ta ra tu ra

Esc

Assistance menu S e le z io n e M e n selection e n z a a s s is t


/

Esc /

Assistance menu M e n a s s is t e n z a

Esc

Initialisation n e S e le z io menu M e n i nselection a z io n e i z i a liz z


/

Esc /

M e n Initialisation menu n e in iz ia liz z a z io

Figure 6.1 : manufacturer menu tree diagram Some important parameters that can be set from the manufacturer menu are shown below.

34

C0240111-01-06-GB

6.1) FREECOOLING
The freecooling function is applied to the efficient production of cold water by using external air. The operating principle is illustrated in figure 6.2.

air FREECOOLING COIL EVAPORATOR

3-way valve water


Figure 6.2: block diagram of the freecooling activation circuit If the external water is cold, the valve closes and the water passes through the coil which cool the water by the water-air heat exchange achieved thanks to the internal fans. If, instead, the air is hot, there is no point in it passing through the coil and all the water is cooled with the evaporator compressors. Further details of the valve and fan adjustment system are shown in figures 6.3.

% v a lv e a p e rtu re 100%

- O n / O f f v a lv e - M o d u la tin g v a lv e

T e x t. D e lta

T fc o o l.

Figure 6.3a: valve operation


- O n /O ff v a lv e - M o d u la tin g v a lv e

% v a lv e a p e rtu re

100% T . in

D iff. O ffs e t

C h ille r s e tp o in t

Figure 6.3b: freecooling low temperature control (to prevent the coil from freezing)

35

C0240111-01-06-GB

step n

Step speed adjustm ent

% dem and

T. in D ynam ic setpoint Dynam ic freecooling band Chiller setpoint

Figure 6.3c: fan adjustment in the step mode (example with 8 fans)
Continuous speed adjustment % demand

100%

T. in Dynamic setpoint Dynamic freecooling band Chiller setpoint

Figure 6.3d: fan adjustment in the continuous mode

6.2) CONDENSATION
Condensation adjustment depends on how the fans are turned on. Various condensation adjustment types in the chiller operating mode are shown below. The fans may be turned on using the on/off system ( step) in which the fans are turned on progressively one after the other (figure 6.4a) or mutually excluded (figure 6.4b). Fans switched on in parallel but that increase fan speed (depending on pressure) are illustrated in figure 6.4c).

Active steps

Continuous step adjustment

Step4 on

Step3 on
Set Point differential Set Point

Step2 on
Set Point differential Set Point

Step1 on
Set Point differential Set Point

Set Point differential

Set Point

Pressure

Figure 6.4a: continuous step condensation adjustment

36

C0240111-01-06-GB

Active steps
Step1 on 1

Step adjustment
Step2 on Step3 on Step4 on

Set Point differential

Set Point

Set Point differential

Set Point

Set Point differential

Set Point

Set Point differential

Set Point

Pressure

Figure 6.4b: step condensation adjustment


Condensation Continuous adjustment
100% max speed % Condensation without Off adjustment min speed % Condensation with Off adjustment Set Point diff. Off

Set Point

Set Point + differential

Pressure

Figure 6.4c: continuous condensation adjustment

37

C0240111-01-06-GB

ALARMS

Press the [ALARM] key once to enter the alarms menu and view the alarm message along with its code. If there is more than one alarm, scroll the menu using the [UP] and [DOWN] keys. In the W3000 base, NO A is displayed if there is no alarm, otherwise the alarm code appears. Press any other key to exit from this menu. The only thing the user can to is to reset the alarm. To reset the alarm press the [ALARM] key again and hold it down until the message No Alarm Active (for W3000 or W3000 compact) or No A (for W3000 base) appears. If the message does not appear it means that one or more alarm conditions are still active.

alarms table
ALARM DESCRIPTION details Faulty phase connection. Totally shuts down the unit (only displayed if the input that detects it is fitted) In units with hardware that does not distinguish between flow switch and thermal protection, this alarm trips when the pump motor overheats or if there is no flow to the evaporator. The alarm automatically resets if there is no flow but must be manually reset (on the pump) if the pump has overheated. Only displayed if the digital input is separate from the evaporator pump thermal protection. No flow to evaporator. Enabled only in the heat pump mode. Low water temperature at evaporator inlet. Enabled only in the chiller mode. High water temperature at evaporator inlet. Low water temperature at evaporator outlet. Also specifies (except for W3000 base) which evaporator (if more than one) is involved in the alarm condition. Only displayed if the relative input is present (see I/O menu). Unit stops due to an external signal. The evaporator outlet temperature changes too quickly and creates a low water level in the system. The temperature difference between the evaporator inlet and outlet is too high and creates a low water flow from the pump The temperature difference between the evaporator inlet and outlet is too low and creates a high water flow from the pump No water flow to the condenser. No water flow to the recuperator. Maintenance hours limit exceeded (in units with just 1 pump, pump 1 is the evaporator pump) Pump 2 maintenance hours limit exceeded (in units with more than one pump). Low water temperature at condenser outlet. Except for W3000 base, it also specifies which condenser (if more than one) is involved in the alarm condition. Risk of freezing on recuperator exchanger. Pump 1 overheated (in units with just 1 pump, pump 1 = evaporator pump) Pump 2 overheated (in units with more than one pump). Condenser pump overheated Recuperator pump overheated RESET A

002

Phase sequence

003

Evaporator flow switch

005 006

Low inlet temperature High inlet temperature Evaporator antifreeze No enable signal Low water charge Low water flow High water flow Condenser flow switch Recuperator flow switch Pump 1 maintenance Pump 2 maintenance Condenser antifreeze Recuperator antifreeze Pump 1 thermal protection Pump 2 thermal protection Condenser pump thermal protection Recuperator pump thermal protection

S-A S-A M M S M S A A S S M A M M M M

010

014 021

022

023 045 046 051 052

075 076 081 082 085 086

38

C0240111-01-06-GB

087

Glycol pump thermal protection

Glycol pump overheated (in units with freecooling). Master expansion 1 unlinked. Apart from W3000 base, the word master appears in units with 3 or 4 circuits. as above, for expansion 2 as above, for expansion 3 as above, for expansion 4 as above, for expansion 5 Slave expansion 1 unlinked. as above, for expansion 2 as above, for expansion 3 as above, for expansion 4 as above, for expansion 5 No oil on compressor 1 due to low compressor oil level or pressure as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 delivery temperature is higher than a preset limit. as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 Compressor 1 motor overheated or any another fault as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8

S/A

091 092 093 094 095 101 102 103 104 105 111 112 113 114 115 116 117 118 121 122 123 124 131 132 133 134 135 136 137 138 141 142 143 144 145 146 147 148 151 152 153 154 155 156 157 158 171 172 173 174 175 176 177 178 211 212 213

Expansion 1 no-link Expansion 2 no-link Expansion 3 no-link Expansion 4 no-link Expansion 5 no-link Expansion 1 slave no-link Expansion 2 slave no-link Expansion 3 slave no-link Expansion 4 slave no-link Expansion 5 slave no-link Compressor oil 1 Compressor oil 2 Compressor oil 3 Compressor oil 4 Compressor oil 5 Compressor oil 6 Compressor oil 7 Compressor oil 8 High outlet temperature compressor 1 High outlet temperature compressor 2 High outlet temperature compressor 3 High outlet temperature compressor 4 Compressor 1 fault Compressor 2 fault Compressor 3 fault Compressor 4 fault Compressor 5 fault Compressor 6 fault Compressor 7 fault Compressor 8 fault Compressor 1 offline Compressor 2 offline Compressor 3 offline Compressor 4 offline Compressor 5 offline Compressor 6 offline Compressor 7 offline Compressor 8 offline Compressor 1 maintenance Compressor 2 maintenance Compressor 3 maintenance Compressor 4 maintenance Compressor 5 maintenance Compressor 6 maintenance Compressor 7 maintenance Compressor 8 maintenance Compressor 1 start-up timeout Compressor 2 start-up timeout Compressor 3 start-up timeout Compressor 4 start-up timeout Compressor 5 start-up timeout Compressor 6 start-up timeout Compressor 7 start-up timeout Compressor 8 start-up timeout Circuit 1 high pressure Circuit 2 high pressure Circuit 3 high pressure

S S S S S S S S S S M M M M M M M M M M M M M - A/M M - A/M M - A/M M - A/M M - A/M M - A/M M - A/M M - A/M S S S S S S S S S S S S S S S S A/M A/M A/M A/M A/M A/M A/M A/M M M M

Maintenance hours limit exceeded on compressor 1 as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 did not start within the set timeout as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 High pressure on cooling circuit 1 as above, for circuit 2 as above, for circuit 3

39

C0240111-01-06-GB

214 221 222 223 224 231 232 233 234 241 242 243 244 251 252 253 254 261 262 263 264 271 272 273 274 301 302 303 304 305 306 307 308 311 312 313 314 315 316 317 318 321 322 323 324 325 326 327 328 331 332 333 334 335 336 337 338 341 342 343

Circuit 4 high pressure Circuit 1 fan thermal protection Circuit 2 fan thermal protection Circuit 3 fan thermal protection Circuit 4 fan thermal protection Circuit 1 low pressure Circuit 2 low pressure Circuit 3 low pressure Circuit 4 low pressure Transducer 1 high pressure Transducer 2 high pressure Transducer 3 high pressure Transducer 4 high pressure Circuit 1 start-up timeout Circuit 2 start-up timeout Circuit 3 start-up timeout Circuit 4 start-up timeout Freon leakage in circuit 1 Freon leakage in circuit 2 Freon leakage in circuit 3 Freon leakage in circuit 4 Finned coil in circuit 1 Finned coil in circuit 2 Finned coil in circuit 3 Finned coil in circuit 4 Compressor 1 inverter temperature Compressor 2 inverter temperature Compressor 3 inverter temperature Compressor 4 inverter temperature Compressor 5 inverter temperature Compressor 6 inverter temperature Compressor 7 inverter temperature Compressor 8 inverter temperature Compressor 1 discharge temperature Compressor 2 discharge temperature Compressor 3 discharge temperature Compressor 4 discharge temperature Compressor 5 discharge temperature Compressor 6 discharge temperature Compressor 7 discharge temperature Compressor 8 discharge temperature Compressor 1 low pressure Compressor 2 low pressure Compressor 3 low pressure Compressor 4 low pressure Compressor 5 low pressure Compressor 6 low pressure Compressor 7 low pressure Compressor 8 low pressure Compressor 1 high pressure Compressor 2 high pressure Compressor 3 high pressure Compressor 4 high pressure Compressor 5 high pressure Compressor 6 high pressure Compressor 7 high pressure Compressor 8 high pressure Compressor 1 input current Compressor 2 input current Compressor 3 input current

as above, for circuit 4 One of the condensation fans in circuit 1 overheated and stopped. as above, for circuit 2 as above, for circuit 3 as above, for circuit 4 Low pressure detected by the transducer/pressure switch on circuit 1 as above, for circuit 2 as above, for circuit 3 as above, for circuit 4 High pressure detected by the transducer/pressure switch on cooling circuit 1 as above, for circuit 2 as above, for circuit 3 as above, for circuit 4 Possible start-up attempt with no Freon in circuit 1. as above, for circuit 2 as above, for circuit 3 as above, for circuit 4 Possible Freon leakage in circuit 1 as the Startup timeout alarm has continued for at least 8 hours. as above, for circuit 2 as above, for circuit 3 as above, for circuit 4 Circuit 1 condensation coil obstructed as above, for circuit 2 as above, for circuit 3 as above, for circuit 4 Compressor 1 inverter overheated as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 discharge overtemperature as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 suction pressure under min. as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 compression pressure over max. as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 current input over max. as above, for compressor 2 as above, for compressor 3

M M M M M A/M A/M A/M A/M M M M M A A A A S S S S A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M

40

C0240111-01-06-GB

344 345 346 347 348 351 352 353 354 355 356 357 358 361 362 363 364 365 366 367 368 371 372 373 374 375 376 377 378 381 382 383 384 385 386 387 388 391 392 393 394 395 396 397 398 400 401 402 403 404 405 406 407 408 409 411 412 413 414 421 422 423 424 425

Compressor 4 input current Compressor 5 input current Compressor 6 input current Compressor 7 input current Compressor 8 input current Compressor 1 rotor temperature Compressor 2 rotor temperature Compressor 3 rotor temperature Compressor 4 rotor temperature Compressor 5 rotor temperature Compressor 6 rotor temperature Compressor 7 rotor temperature Compressor 8 rotor temperature Compressor 1 compression ratio Compressor 2 compression ratio Compressor 3 compression ratio Compressor 4 compression ratio Compressor 5 compression ratio Compressor 6 compression ratio Compressor 7 compression ratio Compressor 8 compression ratio Compressor 1 bearings Compressor 2 bearings Compressor 3 bearings Compressor 4 bearings Compressor 5 bearings Compressor 6 bearings Compressor 7 bearings Compressor 8 bearings Compressor 1 SCR temperature Compressor 2 SCR temperature Compressor 3 SCR temperature Compressor 4 SCR temperature Compressor 5 SCR temperature Compressor 6 SCR temperature Compressor 7 SCR temperature Compressor 8 SCR temperature Compressor 1 block Compressor 2 block Compressor 3 block Compressor 4 block Compressor 5 block Compressor 6 block Compressor 7 block Compressor 8 block Probe 10 err Probe 1 err Probe 2 err Probe 3 err Probe 4 err Probe 5 err Probe 6 err Probe 7 err Probe 8 err Probe 9 err Exp 1 Probe 1 err Exp 1 Probe 2 err Exp 1 Probe 3 err Exp 1 Probe 4 err Exp 2 Probe 1 err Exp 2 Probe 2 err Exp 2 Probe 3 err Exp 2 Probe 4 err Exp 2 Probe 5 err

as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 rotor temperature over max. as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 compression ratio over max. as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 bearings faulty as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 SCR temperature over max. as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Compressor 1 blocked as above, for compressor 2 as above, for compressor 3 as above, for compressor 4 as above, for compressor 5 as above, for compressor 6 as above, for compressor 7 as above, for compressor 8 Probe 10 error. Values read by probe 10 out of range. analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above Probe 1, expansion 1 fault analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above

A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A/M A A A A A A A A A A A A A A A A A A A

41

C0240111-01-06-GB

426 427 428 431 432 433 434 451 452 453 454 500 501 502 503 504 505 506 507 508 509 511 512 513 514 521 522 523 524 525 526 527 528 531 532 533 534 551 552 553 554

Exp 2 Probe 6 err Exp 2 Probe 7 err Exp 2 Probe 8 err Exp 3 Probe 1 err Exp 3 Probe 2 err Exp 3 Probe 3 err Exp 3 Probe 4 err Exp 5 Probe 1 err Exp 5 Probe 2 err Exp 5 Probe 3 err Exp 5 Probe 4 err Probe 10 err slave Probe 1 err slave Probe 2 err slave Probe 3 err slave Probe 4 err slave Probe 5 err slave Probe 6 err slave Probe 7 err slave Probe 8 err slave Probe 9 err slave Exp 1 Probe 1 err slave Exp 1 Probe 2 err slave Exp 1 Probe 3 err slave Exp 1 Probe 4 err slave Exp 2 Probe 1 err slave Exp 2 Probe 2 err slave Exp 2 Probe 3 err slave Exp 2 Probe 4 err slave Exp 2 Probe 5 err slave Exp 2 Probe 6 err slave Exp 2 Probe 7 err slave Exp 2 Probe 8 err slave Exp 3 Probe 1 err slave Exp 3 Probe 2 err slave Exp 3 Probe 3 err slave Exp 3 Probe 4 err slave Exp 5 Probe 1 err slave Exp 5 Probe 2 err slave Exp 5 Probe 3 err slave Exp 5 Probe 4 err slave

analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above Slave probe 10 faulty - only in units with more than 2 circuits analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above Probe 1, expansion 1, connected to slave faulty analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above analogue, as above

A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A

Key to RESET column:


= Manual reset alarm (if the condition that generated the alarm is eliminated, the alarm must be reset by hand) A = Automatic reset alarm (if the condition that generated the alarm is eliminated, the alarm is reset automatically) A/M = Automatic reset alarm for the first three cut-ins, after which manual S = Signal on display (but does not set the cumulative alarms which stops the machine) S-A = Automatic reset signal (that does not stop the machine) or alarm. The mode is selected from a parameter M - A/M = Manual reset alarm (in hermetic, alternative and screw compressors), automatic for the first three cut-ins, after which manual (in centrifuge compressors) M

42

C0240111-01-06-GB

ANNEX 1a : TABLE OF W3000 MASKS


Press [UP] or [DOWN] to move from one mask to another inside the same menu. Press [ENTER] to access the parameter, press [UP] or [DOWN] to change the value of the parameter.

Mask Com. : ON AL152 Mode : chiller Status: ON keybd. LIMIT ID:011 U:01

Therm. Req. Act. Cool. 042 050 % Rec. 040 050 % Pump time 010s Temp. In. Out. Evap. 12.5 07.0C Rec. 35.6 40.5C Cond. 38.0 42.5C Temp. In. Out. Evap. 12.5 07.0C Evap1 07.2C Evap2 06.9C Temp. In. Out. Cond. 24.3 22.4C Cond.1 22.3C Cond.2 22.4C

Description Main display mask. Shows operating mode and status. The unit can be switched on and off with the On/Off command: press "Enter" to move to "Com. :", select the command using the "Up" or "Down" keys and press "Enter" again to confirm. Also displays the following messages: ALxxx: alarm active, Sxxx: signal active, "U:xx" : unit configuration address, "ID:xxx" : unit supervisor address, Symbols describing unit status also appear. Shows the request of the controller and the operating percentage of the unit for cool/heat and recovery (if possible). Also shows pump time. Shows the inlet and outlet water temperature. (evaporator, recuperator and condenser are only displayed if they are fitted). (if 2 evaporators are fitted) Displays inlet and outlet temperatures of the evaporator or condenser (depending on whether the unit is in the summer or winter mode) and the outlet temperature of the two evaporators. (if 2 condensers are fitted) Displays inlet and outlet temperatures of the evaporator or condenser (depending on whether the unit is in the summer or winter mode) and the outlet temperature of the two condensers. Access mask to user configuration submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Para n

Config.
Unit: Type : chiller Compressors : Type : hermetic Circuits: N : 2

Mask for setting the type of unit and compressors.

01.01 01.02

Sets the number of circuits in the unit 01.03 Sets the number of compressors per circuit and the number of separation stages per compressor. Sets the type of condensation (for evaporating units set none). For water-cooled units, select the number of condensers. For water-cooled heat pumps set the type of circuit reversal (water-side or freon-side reversal). Selects the type of ventilation used, only for air-cooled units. 01.09 Selects the type of evaporation and the number of evaporators. (For evaporating units set the number of evaporators to 0) Sets the number of evaporating banks, only for evaporating units. 01.12 Sets the type of refrigerant used. 01.13 Enables recovery. Recovery is enabled automatically in the polyvalent units.

N compressors per circuit : N sep. stages per compressor : Condensation type : water N : 2 Reversal : water Fan Type : axial

2 0

01.04 01.05 01.06 01.07 01.08

Evaporation type : water N : 1 Evaporating banks: N : 1

01.10 01.11

Refrigerant: Type : R407c

Recovery: Enabled: Y

01.14

43

C0240111-01-06-GB

Freecooling: Enabled: Y

Enables freecooling control. 01.15 Access mask to user global parameters submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu. Sets a new password. ATTENTION: THE PASSWORD ENTERED IN THIS FIELD IS THE ONLY ONE THAT ALLOWS ACCESS TO THE MANUFACTURER MENU!! This mask contains the reference information of the software [Code] and of the reference user manual [Man.]. The closed padlock symbol shows that the card is provided with its propriety software; two padlocks appear on units with 3 or 4 circuits Access mask to functions submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Global.
Enter another manufacturer password W 3000 Cod. CA 10.00 GB Man. C0240011-12-05

0000

Functions
Setpoint offset Summer N Winter N Summer offset Set ext. air 45.0C Delta 05.0C Max var. set 06.0C Min. summer setpoint offset limit 07.0C Winter offset Set ext. air -05.0C Delta 05.0C Max var. set 05.0C Max. winter setpoint offset limit 45.0C HP relays Enable Y

Enables setpoint offset in summer and winter modes.

05.01 05.02 05.03 05.04 05.05 05.06

Enables setting of external air temperature setpoint for activating summer setpoint offset and defining the temperature delta at which the maximum (positive) setpoint variation takes place. Minimum summer setpoint limit with setpoint offset activated.

Enables setting of external air temperature setpoint for activating winter setpoint offset (but also in the recovery mode) and defining the temperature delta at which the maximum (negative) setpoint variation takes place. Maximum winter setpoint limit with setpoint offset activated.

05.07 05.08 05.09 05.10

Enables the HP relays. 05.11 Sets the upper setpoint and differential and the lower setpoint and differential for controlling the HP relays. 05.12 05.13 05.14 05.15 05.16

Upper Upper Lower Lower

set diff. set diff.

10.0 05.0 09.5 00.5

bar bar bar bar N

Subcooling Enable

Enables subcooling. This function is only enabled in units with recovery mode. Sets the delay before subcooling adjustment commences and the delay in the subcooling relay. Sets the upper and lower sub cooling setpoint.

Subcooling Adjustment start delay 060 s Relay delay 030 s Subcooling Upper s. 04.0 C Lower set 03.0 C High temp. pressure switch control Enabled: N High temp. pressure switch control Setpoint: 23.5 bar Diff: 02.0 bar Pumpdown Disabled

05.17 05.18 05.19 05.20

Enables setting of the pressure switch control of high temperatures by separating active circuit power

05.21

Enables the setpoint and differential for the pressure switch control of high temperatures

05.22 05.23

Enables or disables pumpdown. Selects the type of pumpdown to perform, pumpdown during shutdown or cyclical pumpdown.

05.24

44

C0240111-01-06-GB

Pumpdown Setpoint Max. time 02.5bar 03s

Cyclical pumpdown Cycle time 030min

Sets end pumpdown setpoint and pumpdown timeout. The pumpdown procedure is interrupted - when low pressure falls below the setpoint (if there are transducers on the low pressure section) - when the low pressure switch trips (if there are no transducers) - after the timeout (if the procedure is not interrupted by pressure) Sets the cyclical pumpdown time. A pumpdown is performed each time the set time elapses. The time is reset every time a mode change occurs.

05.25 05.26

05.27

Pumpdown Chiller Y Heatpump N Ch+Rec N Win rec N Sum rec N => 01

Pumps
Evaporator pumps configuration: N Pumps Enable recuperator pumps: N 2

Sets the modes in which pumpdown is performed (both cyclical and shutdown). Depending on the type of unit, a smaller or larger number of available modes appear. Pumpdown can be selected in the chiller mode and not in the chiller plus recovery mode, for example. Access mask to pumps submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

05.28

Sets the n of pumps in the unit.

07.01 07.02

Enables the pump on the recuperator. 07.03 Enables the pump on the condenser. 07.04 Enables control of the secondary circuit pump and sets the flow switch bypass time during starting and stopping. Defines (threshold), in the automatic mode, the number of days of continuous operation after which a pump is stopped and the other one started. Max. diff. defines the maximum difference in hours between the two pumps over which the threshold value for the pump with less hours is doubled in order to balance pump hours more rapidly. Only appears for units with two pumps. When enabled, this function activates the pumps for the set impulse time after a period of activity reaches the threshold value. Only appears for units with two pumps. Access mask to compressor submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu. 07.05 07.06 07.07 07.08 07.09 07.10 07.11 07.12

Enable condenser pump: N

Sec. pump control Enable: Y Fs bypass ON 015s Fs bypass OFF 120s Pump changeover after long activity: Threshold 0007 days Max diff. 0060 days Long inactivity: Test pumps Y Threshold 1500 days Impulse 10 s

Compressor
Enable continuous modulation Y

Enables continuous modulation of screw compressors. 09.01 Minimum switch-off time of a compressor. (Only visible in the step adjustment mode)

Min compressor stop time 0060 s Min. del. btw starts diff. compr. 0010 s Min. del. btw starts same compr. 0360 s Max. compr. starts per hour 08 Min. compr. start time 060 s Force at low ext.t. Enable N Set point -05.0 C Diff. 01.0 C Force sep. time Enable Y Max. time: 1200s Force time: 120s Period for power maintenance impulse 010 s

09.02 Antipeak time to prevent overcurrents at start-up due to simultaneous demand. Delay which limits the number of compressor start-ups per hour. (Only visible in the step adjustment mode) Maximum permitted number of compressor starts per hour. Minimum switch-on time of a compressor. (Only visible in the quick mind adjustment mode) Only for screw compressors. Enables 100% screw compressor forcing of in the winter mode with low external temperatures. Enables maximum separation time control for screw compressors. Sets the maximum time and full override time of the compressor. Sets the period for the power maintenance impulse. 09.13

09.03 09.04 09.05 09.06 09.07 09.08 09.09 09.10 09.11 09.12

45

C0240111-01-06-GB

Power incr. impulse: Period: 020 s Min. dur.: 01.5 s Max. dur.: 03.0 s Power decr. impulse: Period: 001 s Min. dur.: 01.5 s Max. dur.: 03.0 s Compressor start time: 30 s

Sets the period and duration of the power increase impulse.

09.14 09.15 09.16 09.17 09.18 09.19 09.20

Sets the period and duration of the power decrease impulse.

Sets the start-up time of the compressor, that, is, the time the compressor remains in the no-load start mode before it starts adjusting.

Min. time sep. stages active: 10 s Time compressor oil valve active 10 s Model: Bitzer

Sets the minimum time the separation stages remain active. 09.21 Sets the time the compressor oil valve remains active. Sets the compressor model. 09.23 Enables the economiser and sets the start delay.

09.22

Economiser: Enable Y Start delay 120 s Economiser disable: Set point 15.0 bar Diff. 2.0 bar Compressor discharge temperature control Enabled: Y Compressor discharge temperature control Setpoint 115.0 C Diff. 10.0 C Compressor modulation Minimum: 040 % Maximum: 091 % Start revs: 01500 rpm Compressor start time: 030 s Number of bypass valves 1

09.24 09.25 09.26 09.27

Sets the setpoint and differential for disabling the economiser.

Enables compressor discharge temperature control for liquid injection. 09.28 Sets the setpoint and differential for liquid injection.

09.29 09.30 09.31 09.32 09.33 09.34

Sets minimum and maximum values for centrifugal compressor modulation.

Sets the number of revs for calculating opening of the liquid line solenoid valve. Sets minimum revs timeout during start-up . Sets the number of bypass valves (N.B.: controlled by the board and not by external timers)

09.35

Start compression 2.2 Start bypass delay 015 s Power request increase Integral T. 002 sec Minimum Var. 001 % Power request decrease Integral T. 002 sec Minimum Var. 001 % Centrifuge Comp. off: on: Comp. 1 000% 040% Comp. 2 000% 040% Centrifuge Comp. off: on: Comp. 3 000% 040% Comp. 4 000% 040% Centrifuge Comp. off: on: Comp. 5 000% 040% Comp. 6 000% 040%

Sets the compression ratio for calculating opening of the liquid line solenoid valve. Sets the bypass solenoid valve closing delay. Sets the integral time and minimum variation for increasing the power request.

09.36 09.37 09.38 09.39 09.40 09.41 09.42 09.43 09.44 09.45 09.46 09.47 09.48 09.49 09.50 09.51 09.52 09.53

Sets the integral time and minimum variation for decreasing the power request.

Sets the enable and disable percentage for each centrifuge compressor.

Sets the enable and disable percentage for each centrifuge compressor.

Sets the enable and disable percentage for each centrifuge compressor.

46

C0240111-01-06-GB

Centrifuge Comp. off: on: Comp. 7 000% 040% Comp. 8 000% 040%

Sets the enable and disable percentage for each centrifuge compressor.

09.54 09.55 09.56 09.57

Valves
Status configuration S0 => off Valves: CCCCCCCCCC => 00

Access mask to valves submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Status editor mask. Configures the valves (A=valve open, C=valve closed) in each status (S0,S1, S12). Valve configuration is automatically converted. It is also possible to directly set the coded information, the state of the valves is automatically decoded and memorised.

Sets the valve release time. Valve release time: V1: 000 s V2: 000 s V3: 000 s V4: 000 s V5: 000 s Sets the valve release time. Valve release time: V6: 000 s V7: 000 s V8: 000 s V9: 000 s V10:000 s C1: off valve:CCCCCCCCCC C2: off valve:CCCCCCCCCC C3: off valve:CCCCCCCCCC C4: off valve:CCCCCCCCCC

13.01 13.02 13.03 13.04 13.05 13.06 13.07 13.08 13.09 13.10 13.11 13.12 13.13 13.14 13.15 13.16 13.17 13.18 13.19 13.20 13.21 13.22 13.23

Visualises the status of the circuits and the valves of the circuit.

Visualises the status of the circuits and the valves of the circuit.

Recovery
Winter priority: N

Access mask to recovery submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Sets recovery priority in winter. 15.01 Enables recovery control from a remote contact. 15.02 Defines the pressure setpoint and differential at which the recovery mode is forced to chiller. Enables override to the chiller mode from the chiller plus recovery mode. Sets the cycle time of this function, that is, the maximum time in the chiller plus recovery mode. The time is reset every time a mode change occurs. (NB.: pumpdown is also considered a mode change and therefore the cyclical pumpdown function in the Ch+rec mode is inconsistent with cyclical override, the function will be performed with the lowest cycle time.) Changing mode to Chiller+Rec. On, requires the Chiller On mode. This mask sets the Chiller On mode timeout before passing to the Chiller+Rec On mode. Access mask to condensation submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Enable remote recovery control: N Chiller override fm recovery pressure Setpoint 23.5 bar Diff. 5.0 bar Cyclical override to chiller from ch+rec Enable Y Cycle time 060min

15.03 15.04

15.05 15.06

Override time in chiller before passing to ch+rec 120

15.07

Condens.
Condensation control Enable : Y Type : Step Cont. N steps : 4

Enables condensation control, the type and number of steps.

17.01 17.02 17.03

47

C0240111-01-06-GB

Condensation control Type: Separate Mod.: Linear Condensation control Valve logic: direct Condensation control Precond. enable Y Precond. time 10 s Precond. perc. 100 % Enable max. override Chiller cond. NO Setpoint 23.0 bar Diff. 3.0 bar Enable max. override Heat pump evap. NO Set point 01.0 bar Diff. 5.0 bar Condensation control Chiller step1 Setpoint 15.0 bar Diff. 3.0 bar Condensation control Chiller step2 Setpoint 16.5 bar Diff. 3.0 bar Condensation control Chiller step3 Setpoint 18.0 bar Diff. 3.0 bar Condensation control Chiller step4 Setpoint 19.0 bar Diff. 2.0 bar Evaporation control HeatPump step1 Set point 08.0 bar Diff. 1.0 bar Evaporation control HeatPump step2 Set point 05.0 bar Diff. 1.4 bar Evaporation control HeatPump step3 Set point 02.2 bar Diff. 0.8 bar Evaporation control HeatPump step4 Set point 01.0 bar Diff. 0.5 bar Cont. cond. control Chiller Set point 14.0 bar Diff. 05.0 bar Cont. evap. control HeatPump Set point 06.0 bar Diff. 01.0 bar Cont. condensation control Lim. max. 100 % Lim. min. 030 % Cont. condensation control Min. lim. Adjustment off: Y Diff. 01.0 bar

Selects between individual and contemporary condensation. Also sets linear fan operation. Selects the type of valve for condensation in water-cooled chillers.

17.04 17.05

17.06 Enables pre-condensation (pre-ventilation), sets the duration and defines a value at which the fans (or condensation valve) run during this phase. Enables 100% forced condensation in the chiller mode and establishes the setpoint. 17.07 17.08 17.09 17.10 17.11 17.12 17.13 17.14 17.15 17.16 17.17 17.18 17.19 17.20 17.21 17.22 17.23 17.24 17.25 17.26 17.27 17.28 17.29 17.30 17.31 17.32 17.33 17.34 17.35 17.36 17.37 17.38 17.39

Enables 100% forced condensation in the heat pump mode and establishes the setpoint.

Sets step 1 in the chiller mode (only displayed if step condensation is set).

Sets step 2 in the chiller mode (only displayed if step condensation is set).

Sets step 3 in the chiller mode (only displayed if step condensation is set).

Sets step 4 in the chiller mode (only displayed if step condensation is set).

Sets step 1 in the heat pump mode (only displayed if step condensation is set).

Sets step 2 in the heat pump mode (only displayed if step condensation is set).

Sets step 3 in the heat pump mode (only displayed if step condensation is set).

Sets step 4 in the heat pump mode (only displayed if step condensation is set).

Sets the setpoint and differential for continuous condensation adjustment in the chiller mode. Sets the setpoint and differential for continuous condensation adjustment in the heat pump mode. Sets maximum and minimum condensation with continuous adjustment. This is fan speed or condensation valve opening. Enables the fans or the condensation valve when the minimum condensation limit is reached with continuous adjustment. The set condensation minimum may remain enabled or adjustment can be turned off when pressure falls below the condensation setpoint of the differential value. Access mask to freecooling submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Freecool.
Freecooling Delta 02.0 C Offset -09.0 C Diff. 01.0 C

Sets the freecooling adjustment parameters. The delta, the offset and the differential for freecooling adjustment are set here.

19.01 19.02 19.03

48

C0240111-01-06-GB

Direct valve Fans hysteresis 00.3 C delay 020 s

Selects the type of control for the freecooling valve, direct or reverse. Also sets the hysteresis of each fan and the start/stop delay for each fan. Access mask to defrost submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

19.04 19.05 19.06

Defrost
Standard Defrost Config. Defrost parameters: Start Stop 03.0 bar 14.0 bar

Sets 3 defrost types: Standard, defrosting at fixed intervals, Timer Tuning, defrosting at dynamic intervals, Timer Tuning + Auto Tuning, defrosting at dynamic intervals, also analysing evaporation pressure values. Defines the pressure setpoints for start and stop defrost.

21.01

21.02 21.03 21.04 21.05 21.06 21.07 21.08

Defrost parameters: Delay 01800 s Max. time 00300 s Drip time 120 s Timer tuning defrost Ref. time 120 s Lower band 030 s Upper band 060 s Timer tuning defrost maximum delay modulation perc. 20 Maximum defrosts per hour 3

Sets defrost time parameters. Delay: cumulative time measured before the defrost procedure starts. Max. time: maximum duration of defrost procedure. Drip time: duration of coil dripping Sets certain timer tuning defrost parameters. Nominal defrost reference time, Lower band for increasing waiting time, Upper band for decreasing waiting time. Sets the maximum current defrost delay variation percentage.

21.09 Sets the maximum number of defrosts in an hour. If this value is exceeded, the finned coil alarm appears. (only for auto tuning) Maximum rate of change in the difference between external temperature and evaporation temperature. If exceeded, it activates the defrost procedure after the bypass time. The calculation is updated every "calculation interval". (only for auto tuning) Maximum difference between external temperature and evaporation temperature for reducing defrost delay. (only for auto tuning) Safety offset on maximum difference between external temperature and evaporation temperature for reducing defrost delay. Percentage of delay reduction by the Auto Tuning Defrost component. (only for auto tuning) Time during which defrost start is disabled by circuit start. If the difference is greater than the set threshold, when the start defrost delay expires, defrosting begins. (solo per auto tuning) Minimum derived evaporation pressure for reducing the defrost delay. Minimum permitted evaporation pressure in heatpump. If the pressure falls below this value, defrosting is forced. Evaporation pressure values at which the circuit with more than one hermetic compressor per circuit is "separated" to return the operating point within limits. Evaporation pressure value at which compressor "separation" terminates. Enables the Free-Defrost algorithm and sets the minimum external temperature for operation. Access mask to alarms submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

21.10

Ext t.-Evap. t. calc. interval. 300s Max. diff. between ext t.-evap. t.3.0C Ext t.-evap. t. difference threshold for changing defrost delay 15.0C Threshold offset Start var. 2.0C Reduction factor 5 Circuit start bypass 120 s Start variation delay 600 s Minimum derived evaporation pressure -00.1 bar/m Forced defrosting with low pressure Enabled N Threshold 1.0 bar Minimum operative heatpump pressure Separate 1.2 bar restore 1.6 bar Enable Free Defrost N Minimum external pressure 04.0C

21.11 21.12

21.13

21.14 21.15

21.16 21.17

21.18

21.19 21.20 21.21 21.22 21.23 21.24

Alarms
High pressure from transducers alarm: Setpoint 28.0 bar Diff. 07.0 bar

Sets the setpoint and differential for activating the high pressure from transducers alarm.

23.01 23.02

49

C0240111-01-06-GB

Low press. alarm N resets 3 Start bypass 120 s

Low pressure alarm from transducers: Setpoint 01.6 bar Diff. 00.9 bar Low pressure alarm low air temp. Enabled Y Start timeout 120 s Low pressure alarm low air temp. Setpoint 0.1 bar Diff. 0.5 bar Compressor alarms N trips 3

Sets the parameters for activating the low pressure alarm. Number of times the alarm has triggered in the previous hour and been reset automatically within the set period, the next time the alarm triggers it must be reset manually. Alarm by-pass time before the motor starts. Sets the setpoint and differential for activating and resetting the low pressure alarms (only if the low pressure transducers are configured) Enables external air temperature control for activating the low pressure alarm and sets the start timeout. Sets the setpoint and differential for activating and resetting the low pressure alarms with control on external air temperature Sets the maximum number of automatic reset compressor fault alarms in the arc of an hour, after which the compressor fault alarm must be reset manually. (only for centrifugal compressors) The compressor is switched off for a set time when the unit is powered. It must be set to 360 secs only for BRISTOL compressors Sets the setpoint and differential for activating the high compressor discharge temperature alarm. Sets the compressor oil alarm delay

23.03 23.04

23.05 23.06 23.07 23.08 23.09 23.10

23.11

Compressor thermal protection alarm: Bypass time 0010 s Compressor discharge temperature alarm Setpoint 125.0C Diff. 10.0C Compressor oil alarm: Start delay 120 s Running delay 010 s Evap. antifreeze alarm: Setpoint 04.0 C Diff. 04.0 C Evap. antifreeze heating element: Setpoint 04.0 C Diff. 04.0 C Cond. antifreeze alarm: Setpoint 04.0 C Diff. 04.0 C Recup. antifreeze heater: Setpoint 04.0 C Diff. 04.0 C Flow switch alarm N trips 3

23.12

23.13 23.14 23.15 23.16 23.17 23.18 23.19 23.20 23.21 23.22 23.23 23.24

Sets the setpoint and differential for activating the evaporator anti-freeze alarm.

Sets the setpoint and differential for activating the evaporator anti-freeze heating element.

Sets the setpoint and differential for activating the condenser anti-freeze alarm.

Sets the setpoint and differential for activating the recuperator anti-freeze heater.

Evaporator flow switch alarm: Start delay 010 s Running delay 001 s Recuperator flow switch alarm: Start delay 010 s Running delay 001 s

Condenser flow switch alarm: Start delay 010 s Running delay 001 s Low water flow alarm: max. delta 08.0 C delay 010 s Maximum pump operating time in alarm mode 015 s

Sets the maximum number of automatic reset flow switch fault alarms in the arc of an hour, after which the flow switch fault alarm must be reset manually. The flow switch alarm is always automatically reset until the maximum pump low-water operation time has elapsed. The pump then turns off and the flow switch alarm must be manually reset. Configuration parameters for evaporator flow switch alarm. Start delay: minimum time during which the flow must remain constant before the compressors start running. Running delay: minimum time before the flow switch triggers with the compressors running. Configuration parameters for recuperator flow switch alarm. Start delay: minimum time during which the flow must remain constant before the compressors start running. Running delay: minimum time before the flow switch triggers with the compressors running. Configuration parameters for condenser flow switch alarm. Start delay: minimum time during which the flow must remain constant before the compressors start running. Running delay: minimum time before the flow switch triggers with the compressors running. Sets the setpoint and delay for triggering the low water flow alarm.

23.25

23.26 23.27

23.28 23.29

23.30 23.31

23.32 23.33

Maximum operating time of pumps with a low volume/flow of water in the system. Following alarms requiring the pump to start (antifreeze alarm, low flow rate alarm, evaporator flow switch alarm) the pump is kept running in order to recover flow/volume.

23.34

50

C0240111-01-06-GB

High/Low temp. unit inlet Type: signal Delay: 030 s Inlet water high temp. signal: setpoint 00.0 C Inlet water low temp. signal: setpoint 00.0 C

Chooses whether, with high/low inlet water temperature, the unit must continue to work (giving a signal) or stop the compressors to prevent them from suffering damage (automatic reset alarm). Sets the delay before activating the high inlet water temperature (summer mode) / low temperature inlet water (winter mode) alarm/signal. Sets the setpoint for activating the high inlet water temperature alarm/signal. (When operating in the chiller mode) Sets the setpoint for activating the low inlet water temperature alarm/signal. (When operating in the chiller mode) Access mask to calibration submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

23.35 23.36

23.37

23.38

Calibration
Configuration of compressor discharge temperature probes: NTC 0-150C Probe enable: External temp. Probe enable: Y

Mask only visible in screw compressors that allow the type of discharge temperature probe used to be selected. Probe enable mask for enabling the external air temperature probe or condenser inlet probe (Only visible where applicable) Probe enable mask for enabling high and low pressure transducers.

25.01

25.02 25.03 25.04 25.05 25.06 25.07 25.08 25.09 27.01 27.02 27.03 27.04 27.05 27.06 27.07 27.08 27.09 27.10 27.11 27.12 27.13 27.14 27.21 27.22 27.23 27.24 27.25 27.26

Pressure Y Low pressure Y High pressure transducers Start Scale 00.0bar End Scale 30.0bar Low pressure transducers Start Scale 00.0bar End Scale 16.0bar Master calibration offset Value B1: 0.0bar 07.3bar B2: 0.0C 12.3C Master calibration offset Value B3: 0.0C 12.3C B4: 0.0C 12.3C Master calibration offset Value B5: 0.0C 12.3C B6: 0.0C 07.3bar Master calibration offset Value B7: 0.0C 05.3C B8: Master calibration offset Value B9: 0.0C 00.0C B10: Master calibr. exp1 offset Value B1: 0.0C 35.6C B2: 0.0C 40.5C Master calibr. exp1 offset Value B3: 0.0C 37.2C B4: 0.0C 37.2C Master calibr. exp2 offset Value B1: 0.0bar 04.2bar B2: 0.0bar 03.9bar Master calibr. exp2 offset Value B3: 0.0C 35.6C B4: 0.0C 40.5C Master calibr. exp2 offset Value B5: 0.0C 22.3C B6: 0.0C 24.2C

Mask for configuring the high pressure transducers.

Mask for configuring the low pressure transducers.

Modifies the probe offsets. (Only present if required by the type of machine configured). The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 1. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 1. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits.

51

C0240111-01-06-GB

Master calibr. exp2 offset Value B7: 0.0C 22.4C B8: Master calibr. exp3 offset Value B1: 0.0C 05.3C B2: 0.0C 00.0C Master calibr. exp3 offset Value B3: 0.0C 00.0C B4: 0.0C 00.0C Master calibr. exp5 offset Value B1: 0.0C 00.0C B2: 0.0C 00.0C Master calibr. exp5 offset Value B3: 0.0C 00.0C B4: 0.0C 00.0C Slave calibration offset Value B1: 0.0bar 07.3bar B2: 0.0C 12.3C Slave calibration offset Value B3: 0.0C 12.3C B4: 0.0C 12.3C Slave calibration offset Value B5: 0.0C 12.3C B6: 0.0C 07.3bar Slave calibration offset Value B7: 0.0C 05.3C B8: Slave calibration offset Value B9: 0.0C 00.0C B10: Slave calibr. exp1 offset Value B1: 0.0C 35.6C B2: 0.0C 40.5C Slave calibr. exp1 offset Value B3: 0.0C 37.2C B4: 0.0C 37.2C Slave calibr. exp2 offset Value B1: 0.0bar 04.2bar B2: 0.0bar 03.9bar Slave calibr. exp2 offset Value B3: 0.0C 35.6C B4: 0.0C 40.5C Slave calibr. exp2 offset Value B5: 0.0C 22.3C B6: 0.0C 24.2C Slave calibr. exp2 offset Value B7: 0.0C 22.4C B8: Slave calibr. exp3 offset Value B1: 0.0C 05.3C B2: 0.0C 00.0C Slave calibr. exp3 offset Value B3: 0.0C 00.0C B4: 0.0C 00.0C Slave calibr. exp5 offset Value B1: 0.0C 00.0C B2: 0.0C 00.0C

Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 3. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 3. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 5. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets of expansion 5. (Only present if required by the type of machine configured) The word "master" only appears on units with more than 2 circuits. Modifies the probe offsets. (Only present if required by the type of machine configured).

27.27 27.28 27.31 27.32 27.33 27.34 27.51 27.52 27.53 27.54 31.01 31.02 31.03 31.04 31.05 31.06 31.07 31.08 31.09 31.10 31.11 31.12 31.13 31.14 31.21 31.22 31.23 31.24 31.25 31.26 31.27 31.28 31.31 31.32 31.33 31.34 31.51 31.52

Modifies the probe offsets. (Only present if required by the type of machine configured)

Modifies the probe offsets. (Only present if required by the type of machine configured)

Modifies the probe offsets. (Only present if required by the type of machine configured)

Modifies the probe offsets. (Only present if required by the type of machine configured)

Modifies the probe offsets of expansion 1. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 1. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 2. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 3. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 3. (Only present if required by the type of machine configured) Modifies the probe offsets of expansion 5. (Only present if required by the type of machine configured)

52

C0240111-01-06-GB

Slave calibr. exp5 offset Value B3: 0.0C 00.0C B4: 0.0C 00.0C

Modifies the probe offsets of expansion 5. (Only present if required by the type of machine configured) Access mask to assistance submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

31.53 31.54

Service
Hour counter Pump: Threshold 012x1000 Reset N 000000 Hour counter Pump 2: Threshold 012x1000 Reset N 000000 Hour counter Compressor 1: Threshold 010x1000 Reset N 000000 Hour counter Compressor 2: Threshold 010x1000 Reset N 000000 Hour counter Compressor 3: Threshold 010x1000 Reset N 000000 Hour counter Compressor 4: Threshold 010x1000 Reset N 000000 Hour counter Compressor 5: Threshold 010x1000 Reset N 000000 Hour counter Compressor 6: Threshold 010x1000 Reset N 000000 Hour counter Compressor 7: Threshold 010x1000 Reset N 000000 Hour counter Compressor 8: Threshold 010x1000 Reset N 000000

Sets the threshold for programmed maintenance on the evaporator pump. 35.01 Sets the threshold for programmed maintenance on pump 2. (this may be pump 2 of the evaporator or the pump on the secondary circuit in the water/water units or the recuperator pump, depending on unit configuration) Sets the threshold for programmed maintenance.

35.02 35.03 35.11 35.12 35.04 35.13 35.14 35.05 35.15 35.16 35.06 35.17 35.18 35.07 35.19 35.20 35.08 35.21 35.22 35.09 35.23 35.24 35.10 35.25 35.26

Sets the threshold for programmed maintenance.

Sets the threshold for programmed maintenance.

Sets the threshold for programmed maintenance.

Sets the threshold for programmed maintenance.

Sets the threshold for programmed maintenance.

Sets the threshold for programmed maintenance.

Sets the threshold for programmed maintenance.

Default
Reset chiller to default values N Load configuration N

Access mask to initialisation menu. Press "Up" or "Down" to scroll the other mask and "Esc" to return to the submenu. The mask is not displayed when the chiller is ON. This restores the default values. Deletes the memory and installs "logical" values. The chiller must then be programmed with the parameter set during factory testing. Loads parameters from file. The unit is configured with factory settings. NB: Run default before Load configuration. Access mask to user menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

User
Step adjustment type

IN INLET Start-up mode standard

Chooses between step adjustment and Quick Mind adjustment. Also defines on which temperature probe the adjustment is made. If the unit has more than one evaporator or step adjustment is set, adjustment can only be made on the inlet probe. Chooses between standard or rapid start-up (only displayed in the Quick Mind adjustment mode) Sets the percentage inside the dead area around the setpoint in which the compressor is not modulated. (only for modulating screw compressors)

39.01 39.02

39.03

Amplitude of stable zone: 023 %

39.04

53

C0240111-01-06-GB

Input adjustment: Type PROPORTIONAL

Defines the type of adjustment. (only visible in the step inlet adjustment mode) 39.05 Sets integration time and correction limit (displayed in the step inlet adjustment mode with proportional + integral adjustment type) Maximum and minimum setpoint values that can be set with inlet adjustment N.B.: For low temperature units, the minimum value that can be set for the low limit is equal to the antifreeze setpoint +2C (also check the value set for forced shut-down in the Quick Mind adjustment mode). Maximum and minimum setpoint values that can be set with outlet adjustment N.B.: For low temperature units, the minimum value that can be set for the low limit is equal to the antifreeze setpoint +2C (also check the value set for forced shut-down in the Quick Mind adjustment mode). Maximum and minimum setpoint values that can be set with inlet adjustment (only visible if the heat pump configuration is set) Maximum and minimum setpoint values that can be set with outlet adjustment (only visible if the heat pump configuration is set) Maximum and minimum recovery setpoints. (only visible if recovery is configured)

Integral time: 0600 s Integral correction limit: 005 % Setpoint limits chiller: Low 11.0 C High 20.0 C Setpoint limits chiller: Low 06.0 C High 18.0 C Setpoint limits heat pump: Low 30.0 C High 44.0 C Setpoint limits heat pump: Low 30.0 C High 48.0 C Setpoint limits recovery: Low 30.0 C High 50.0 C Forced shutdown Summer Winter 04.5 C 52.0 C

39.06 39.07 39.08 39.09 39.10 39.11 39.12 39.13 39.14 39.15 39.16 39.17 39.18 39.19 39.20 39.21 39.22

Temp. adjustment band 02.5 C Recovery adjustment band 03.0 C Secondary setpoint Enable N

(Only in the Quick Mind adjustment mode) Forces the compressors to shut down if: Tout summer < summer minimum or Tout winter > winter maximum Sets the temperature and recovery adjustment band.

Enables selection of the main or secondary setpoint via an external contact (only displayed on compatible units). Enables setpoint variation through an external input which can be configured at 4-20mA or 0-10V. Maximum and minimum variation limits can also be set. If time bands have been enabled the external setpoint cannot be enabled (only displayed on compatible units). For units with alternative or screw compressors only a 4-20 mA variation can be selected. Enables recovery setpoint variation through an external input which can be configured at 4-20mA or 0-10V. Maximum and minimum variation limits can also be set. If time bands have been enabled the external setpoint cannot be enabled (only displayed on compatible units). For units with alternative or screw compressors only a 4-20 mA variation can be selected. (Only displayed if more than one pump is set) Selects whether to use both pumps through hourly rotation (FIFO if they have the same number of operating hours) or override pump 1 or pump 2. Defines the delay between pump start-up and compressor start-up after the unit has been switched on. Defines pump shutdown delay after the unit has been switched off. Enables limitation of the power delivered by the unit.

39.23 39.24 39.25 39.26 39.27 39.28 39.29 39.30 39.31 39.32

External setpoint Enabled 4-20 mA Min. 00.0 C Max. 06.0 C Ext. rec setpoint Enabled 4-20 mA Min. 00.0 C Max. 06.0 C Pump config. Type of use: automatic Min. delay between pump start-up and compressor start-up 060 s Pump shutdown delay 060 s Compressor enable Enable Y

39.33

39.34

39.35 Sets the maximum percentage of power delivered by the unit in the summer, winter (in heat pump units) and recovery (in compatible units where possible) modes. Allows the on/off status of the unit to be selected from external enables. Also performs summer/winter switching in heat pump units. Activates/deactivates time bands. The time bands cannot be activated if the external setpoint is enabled. 39.36 39.37 39.38 39.39 39.40

Compressor enable Summer 050 % Winter 050 % Recovery 050 % En. from dig. inp.: On/Off: N Summer/Winter: N Time bands enable: Disabled

39.41

54

C0240111-01-06-GB

Serial line configuration: Supervision En. from superv.: On/Off: N Operating mode: N Superv. setting Modbus protocol Speed 9600 baud ID 011 Select language: English Select language W 3000 Code CA 10.00 GB Man. C0240001-12-05 Enter another user password 0000

Allows the devices connected to the serial interface card to be enabled and selected ( "0"=disabled, "1"= supervision, "2"= sequencer). N.B.: the Service software does not need to be enabled. Allows the on/off status of the unit to be selected from a supervision system. Also performs operating mode switching (to modify the latter, the unit must be switched off). Defines the connection parameters with the supervisor: protocol type, communication speed and unit identification number. Selects the required language; Select language flashes on the last line in all the available languages. Once a language has been selected, the programme automatically switches to the first mask of the display menu. N.B.: Up to three languages are present on the card: Italian, English and another language. This mask contains the reference information of the software [Code] and of the reference user manual [Man.]. The closed padlock symbol shows that the card is provided with its propriety software; two padlocks appear on units with 3 or 4 circuits Personalises the password by defining one that will replace the default password.

39.42

39.43 39.44 39.45 39.46 39.47

39.48

Clock
Clock card not installed Clock configuration: Date Time 01/01/04 08:00 Time bands not enabled. See user menu Advanced daily time band programming: Weekly timetable Monday type A Tuesday type A Wednesday type A Weekly timetable Thursday type A Friday type A Saturday disabled Weekly timetable Sunday disabled

Access mask to clock menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Mask showing that the clock card is missing or damaged.

Current date and time settings.

Indicates that the time bands are set correctly but not enabled. To enable them, consult the user menu. Advanced time band programming manages two different daily time bands, type A and type B; each type can be personalised and each is independent from the other. Only the A-type time band is used in the standard programming mode. Weekly timetable setting.

51.01 51.02 51.03 51.04 51.05 51.06 51.07 51.08

Weekly timetable setting.

Weekly timetable setting.

Time Time Sp S Sp R

band 1A Off 00:00 / 07:00 08.0C W 40.0C 40.0C

Setting band A, first daily time band.

Time Time Sp S Sp R

band 2A Adj. 07:00 / 12:00 07.0C W 45.0C 45.0C

Setting band A, second daily time band.

Time Time Sp S Sp R

band 3A Off 12:00 / 13:30 08.0C W 40.0C 40.0C

Setting band A, third daily time band.

53.01 53.02 53.03 53.04 53.05 53.06 53.07 53.08 53.09 53.10 53.11 53.12 53.13 53.14 53.15 53.16 53.17 53.18

55

C0240111-01-06-GB

Time Time Sp S Sp R

band 4A Adj. 13:30 / 19:30 07.0C W 45.0C 45.0C

Setting band A, fourth daily time band.

Time Time Sp S Sp R

band 5A Off 19:30 / 19:30 08.0C W 40.0C 40.0C

Setting band A, fifth daily time band.

Time Time Sp S Sp R

band 6A Off 19:30 / 19:30 08.0C W 40.0C 40.0C

Setting band A, sixth daily time band.

Time Time Sp S Sp R

band 7A Off 19:30 / 19:30 08.0C W 40.0C 40.0C

Setting band A, seventh daily time band.

Time Time Sp S Sp R

band 8A Off 19:30 / 19:30 08.0C W 40.0C 40.0C

Setting band A, eighth daily time band.

Time Time Sp S Sp R

band 9A Off 19:30 / 19:30 08.0C W 40.0C 40.0C

Setting band A, ninth daily time band.

Time Time Sp S Sp R Time Time Sp S Sp R

band 10A Off 19:30 / 19:30 08.0C W 40.0C 40.0C band 1B Off 00:00 / 06:30 09.0C W 40.0C 40.0C

Setting band A, tenth daily time band.

First daily time band setting.

Time Time Sp S Sp R

band 2B Off 00:00 / 06:30 09.0C W 40.0C 40.0C

Second daily time band setting.

Time Time Sp S Sp R

band 3B Adj. 06:30 / 19:30 07.0C W 45.0C 45.0C

Third daily time band setting.

Time Time Sp S Sp R

band 4B Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Fourth daily time band setting.

Time Time Sp S Sp R

band 5B Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band B, fifth daily time band.

53.19 53.20 53.21 53.22 53.23 53.24 53.25 53.26 53.27 53.28 53.29 53.30 53.31 53.32 53.33 53.34 53.35 53.36 53.37 53.38 53.39 53.40 53.41 53.42 53.43 53.44 53.45 53.46 53.47 53.48 53.49 53.50 53.51 53.52 53.53 53.54 53.55 53.56 53.57 53.58 55.01 55.02 55.03 55.04 55.05 55.06 55.07 55.08 55.09 55.10 55.11 55.12 55.13 55.14 55.15 55.16 55.17 55.18 55.19 55.20 55.21 55.22 55.23 55.24 55.25 55.26 55.27 55.28 55.29 55.30

56

C0240111-01-06-GB

Time Time Sp S Sp R

band 6B Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band B, sixth daily time band.

Time Time Sp S Sp R

band 7B Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band B, seventh daily time band.

Time Time Sp S Sp R

band 8B Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band B, eighth daily time band.

Time Time Sp S Sp R

band 9B Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band B, ninth daily time band.

Time Time Sp S Sp R Time Time Sp S Sp R

band 10A Off 19:30 / 19:30 09.0C W 40.0C 40.0C band 1C Off 00:00 / 06:30 09.0C W 40.0C 40.0C

Setting band B, tenth daily time band.

Setting band C, first daily time band.

Time Time Sp S Sp R

band 2C Off 00:00 / 06:30 09.0C W 40.0C 40.0C

Setting band C, second daily time band.

Time Time Sp S Sp R

band 3C Adj. 06:30 / 19:30 07.0C W 45.0C 45.0C

Setting band C, third daily time band.

Time Time Sp S Sp R

band 4C Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band C, fourth daily time band.

Time Time Sp S Sp R

band 5C Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band C, fifth daily time band.

Time Time Sp S Sp R

band 6C Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band C, sixth daily time band.

Time Time Sp S Sp R

band 7C Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band C, seventh daily time band.

55.31 55.32 55.33 55.34 55.35 55.36 55.37 55.38 55.39 55.40 55.41 55.42 55.43 55.44 55.45 55.46 55.47 55.48 55.49 55.50 55.51 55.52 55.53 55.54 55.55 55.56 55.57 55.58 57.01 57.02 57.03 57.04 57.05 57.06 57.07 57.08 57.09 57.10 57.11 57.12 57.13 57.14 57.15 57.16 57.17 57.18 57.19 57.20 57.21 57.22 57.23 57.24 57.25 57.26 57.27 57.28 57.29 57.30 57.31 57.32 57.33 57.34 57.35 57.36 57.37 57.38 57.39 57.40 57.41 57.42

57

C0240111-01-06-GB

Time Time Sp S Sp R

band 8C Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band C, eighth daily time band.

Time Time Sp S Sp R

band 9C Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band C, ninth daily time band.

Time Time Sp S Sp R Time Time Sp S Sp R

band 10C Off 19:30 / 19:30 09.0C W 40.0C 40.0C band 1D Off 00:00 / 06:30 09.0C W 40.0C 40.0C

Setting band C, tenth daily time band.

Setting band D, first daily time band.

Time Time Sp S Sp R

band 2D Off 00:00 / 06:30 09.0C W 40.0C 40.0C

Setting band D, second daily time band.

Time Time Sp S Sp R

band 3D Adj. 06:30 / 19:30 07.0C W 45.0C 45.0C

Setting band D, third daily time band.

Time Time Sp S Sp R

band 4D Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band D, fourth daily time band.

Time Time Sp S Sp R

band 5D Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band D, fifth daily time band.

Time Time Sp S Sp R

band 6D Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band D, sixth daily time band.

Time Time Sp S Sp R

band 7D Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band D, seventh daily time band.

Time Time Sp S Sp R

band 8D Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band D, eighth daily time band.

Time Time Sp S Sp R

band 9D Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band D, ninth daily time band.

Time Time Sp S Sp R

band 10D Off 19:30 / 19:30 09.0C W 40.0C 40.0C

Setting band D, tenth daily time band.

57.43 57.44 57.45 57.46 57.47 57.48 57.49 57.50 57.51 57.52 57.53 57.54 57.55 57.56 57.57 57.58 59.01 59.02 59.03 59.04 59.05 59.06 59.07 59.08 59.09 59.10 59.11 59.12 59.13 59.14 59.15 59.16 59.17 59.18 59.19 59.20 59.21 59.22 59.23 59.24 59.25 59.26 59.27 59.28 59.29 59.30 59.31 59.32 59.33 59.34 59.35 59.36 59.37 59.38 59.39 59.40 59.41 59.42 59.43 59.44 59.45 59.46 59.47 59.48 59.49 59.50 59.51 59.52 59.53 59.54 59.55 59.56 59.57 59.58

58

C0240111-01-06-GB

In/Out
Dig.In. master 12345 67890 12345 CCCCC CCCCC CCCCC CCC

Access mask to In/Out menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Dig.Out. master 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. master N Value 1 07.3 bar 2 12.3 C An. In. master N Value 3 12.3 C 4 12.3 C An. In. master N Value 5 12.3 C 6 07.3 bar An. In. master N Value 7 05.3 C 8 00.0 An. In. master N Value 9 00.0 C 10 A An. Out. master N Value 1 00.0 V 2 00.0 V An. Out. master N Value 3 00.0 V 4 00.0 V An. Out. master N Value 5 00.0 V 6 00.0 V Masters required Exp.1: Y Exp.2: N Exp.3: Y Exp.4: N Exp.5: N Masters on-line Exp.1: Y Exp.2: N Exp.3: Y Exp.4: N Exp.5: N Dig.In. master exp1 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. master exp1 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. master exp1 N Value 1 35.6 C 2 40.5 C An. In. master exp1 N Value 3 37.2 C 4 37.2 C Dig.In. master exp2 12345 67890 12345 CCCCC CCCCC CCCCC CCC

Displays the state of the digital inputs and specifies their state. C: Contact closed O: Contact open The number of inputs displayed depends on the type of unit. (the figures on the second row are for reference purposes) Master is only specified on units with 3 or 4 circuits. Displays the state of the digital outputs and specifies their state. C: Contact closed O: Contact open The number of outputs displayed depends on the type of unit. (the figures on the second row are for reference purposes) Master is only specified on units with 3 or 4 circuits. Display of analogue inputs 1 and 2. Master is only specified on units with 3 or 4 circuits. Display of analogue inputs 3 and 4. Master is only specified on units with 3 or 4 circuits. Display of analogue inputs 5 and 6. Master is only specified on units with 3 or 4 circuits. Display of analogue inputs 7 and 8. Master is only specified on units with 3 or 4 circuits. Display of analogue inputs 9 and 10. Master is only specified on units with 3 or 4 circuits. Voltage applied to analogue outputs 1 and 2. Master is only specified on units with 3 or 4 circuits. Voltage applied to analogue outputs 3 and 4. Master is only specified on units with 3 or 4 circuits. Voltage applied to analogue outputs 5 and 6. Master is only specified on units with 3 or 4 circuits. Mask indicating the address for the expansion boards. This changes depending on the parameter settings. Master is only specified on units with 3 or 4 circuits. Mask for checking connection with the expansion boards. N means that there is no link with the expansion indicated in the address. Master is only specified on units with 3 or 4 circuits. Displays the state of the digital inputs of expansion 1 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays the state of the digital outputs of expansion 1 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 1 and 2 of expansion 1 (if present). Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 3 and 4 of expansion 1 (if present). Master is only specified on units with 3 or 4 circuits. Displays the state of the digital inputs of expansion 2 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits.

59

C0240111-01-06-GB

Dig.Out. master exp2 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. master exp2 N Value 1 04.2 bar 2 03.9 bar An. In. master exp2 N Value 3 35.6 C 4 40.5 C An. In. master exp2 N Value 5 22.3 C 6 24.2 C An. In. master exp2 N Value 7 22.4 C 8 - C Dig.In. master exp3 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. master exp3 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. master exp3 N Value 1 06.0 C 2 00.0 C An. In. master exp3 N Value 3 00.0 C 4 00.0 C An. Out. master exp3 N Value 1 00.0 V Dig.In. master exp4 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. master exp4 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. master exp4 N Value 1 A 2 A An. In. master exp4 N Value 3 A 4 A Dig.In. master exp5 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. master exp5 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. master exp5 N Value 1 00.0 C 2 00.0 C An. In. master exp5 N Value 3 00.0 C 4 00.0 C

Displays the state of the digital outputs of expansion 2 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 1 and 2 of expansion 2 (if present). Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 3 and 4 of expansion 2 (if present). Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 5 and 6 of expansion 2 (if present). Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 7 and 8 of expansion 2 (if present). Master is only specified on units with 3 or 4 circuits. Displays the state of the digital inputs of expansion 3 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays the state of the digital outputs of expansion 3 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 1 and 2 of expansion 3 (if present). Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 3 and 4 of expansion 3 (if present). Master is only specified on units with 3 or 4 circuits. Voltage applied to analogue output 1 of expansion 3 (if present). Master is only specified on units with 3 or 4 circuits. Displays the state of the digital inputs of expansion 4 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays the state of the digital outputs of expansion 4 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 1 and 2 of expansion 4 (if present). Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 3 and 4 of expansion 4 (if present). Master is only specified on units with 3 or 4 circuits. Displays the state of the digital inputs of expansion 5 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays the state of the digital outputs of expansion 5 (if present) and specifies their state. C: Contact closed O: Contact open Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 1 and 2 of expansion 5 (if present). Master is only specified on units with 3 or 4 circuits. Displays analogue inputs 3 and 4 of expansion 5 (if present). Master is only specified on units with 3 or 4 circuits.

60

C0240111-01-06-GB

Dig.In. slave 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. slave 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. slave N Value 1 07.3 bar 2 12.3 C An. In. slave N Value 3 12.3 C 4 12.3 C An. In. slave N Value 5 12.3 C 6 07.3 bar An. In. slave N Value 7 05.3 C 8 00.0 An. In. slave N Value 9 00.0 C 10 A An. Out. slave N Value 1 00.0 V 2 00.0 V An. Out. slave N Value 3 00.0 V 4 00.0 V An. Out. slave N Value 5 00.0 V 6 00.0 V Slaves required Exp.1: Y Exp.2: N Exp.3: Y Exp.4: N Exp.5: N Slaves on-line Exp.1: Y Exp.2: N Exp.3: Y Exp.4: N Exp.5: N Dig.In. slave exp1 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. slave exp1 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. slave exp1 N Value 1 35.6 C 2 40.5 C An. In. slave exp1 N Value 3 37.2 C 4 37.2 C Dig.In. slave exp2 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. slave exp2 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. slave exp2 N Value 1 04.2 bar 2 03.9 bar

Displays the state of the digital inputs and specifies their state. C: Contact closed O: Contact open The number of inputs displayed depends on the type of unit. (the figures on the second row are for reference purposes) Displays the state of the digital outputs and specifies their state. C: Contact closed O: Contact open The number of outputs displayed depends on the type of unit. (the figures on the second row are for reference purposes) Display of analogue inputs 1 and 2.

Display of analogue inputs 3 and 4.

Display of analogue inputs 5 and 6.

Display of analogue inputs 7 and 8.

Display of analogue inputs 9 and 10.

Voltage applied to analogue outputs 1 and 2.

Voltage applied to analogue outputs 3 and 4.

Voltage applied to analogue outputs 5 and 6.

Mask indicating the address for the slave expansion boards. This changes depending on the parameter settings. Master is only specified on units with 3 or 4 circuits. Mask for checking connection with the slave expansion boards. N means that there is no link with the expansion indicated in the address. Master is only specified on units with 3 or 4 circuits. Displays the state of the digital inputs of expansion 1 (if present) and specifies their state. C: Contact closed O: Contact open Displays the state of the digital outputs of expansion 1 (if present) and specifies their state. C: Contact closed O: Contact open Displays analogue inputs 1 and 2 of expansion 1 (if present).

Displays analogue inputs 3 and 4 of expansion 1 (if present).

Displays the state of the digital inputs of expansion 2 (if present) and specifies their state. C: Contact closed O: Contact open Displays the state of the digital outputs of expansion 2 (if present) and specifies their state. C: Contact closed O: Contact open Displays analogue inputs 1 and 2 of expansion 2 (if present).

61

C0240111-01-06-GB

An. In. slave exp2 N Value 3 35.6 C 4 40.5 C An. In. slave exp2 N Value 5 22.3 C 6 24.2 C An. In. slave exp2 N Value 7 22.4 C 8 - C Dig.In. slave exp3 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. slave exp3 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. slave exp3 N Value 1 06.0 C 2 00.0 C An. In. slave exp3 N Value 3 00.0 C 4 00.0 C An. Out. slave exp3 N Value 1 00.0 V Dig.In. slave exp4 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. slave exp4 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. slave exp4 N Value 1 A 2 A An. In. slave exp4 N Value 3 A 4 A Dig.In. slave exp5 12345 67890 12345 CCCCC CCCCC CCCCC CCC Dig.Out. slave exp5 12345 67890 12345 AAAAA AAAAA AAAAA AAAAA AAAAA AAAA An. In. slave exp5 N Value 1 00.0 C 2 00.0 C An. In. slave exp5 N Value 3 00.0 C 4 00.0 C

Displays analogue inputs 3 and 4 of expansion 2 (if present).

Displays analogue inputs 5 and 6 of expansion 2 (if present).

Displays analogue inputs 7 and 8 of expansion 2 (if present).

Displays the state of the digital inputs of expansion 3 (if present) and specifies their state. C: Contact closed O: Contact open Displays the state of the digital outputs of expansion 3 (if present) and specifies their state. C: Contact closed O: Contact open Displays analogue inputs 1 and 2 of expansion 3 (if present).

Displays analogue inputs 3 and 4 of expansion 3 (if present).

Voltage applied to analogue output 1 of expansion 3 (if present).

Displays the state of the digital inputs of expansion 4 (if present) and specifies their state. C: Contact closed O: Contact open Displays the state of the digital outputs of expansion 4 (if present) and specifies their state. C: Contact closed O: Contact open Displays analogue inputs 1 and 2 of expansion 4 (if present).

Displays analogue inputs 3 and 4 of expansion 4 (if present).

Displays the state of the digital inputs of expansion 5 (if present) and specifies their state. C: Contact closed O: Contact open Displays the state of the digital outputs of expansion 5 (if present) and specifies their state. C: Contact closed O: Contact open Displays analogue inputs 1 and 2 of expansion 5 (if present).

Displays analogue inputs 3 and 4 of expansion 5 (if present).

Setpoint
Unit type: chiller Operating mode: chiller Active Setpoint: Main Recovery

Access mask to setpoint menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Mask for displaying the unit type and setting the operating mode. 43.01 Displays the current setpoint. If the letter R appears in the top right-hand corner, the active setpoint is the secondary one.

07.0 C 42.5 C

62

C0240111-01-06-GB

Chiller setpoint 07.0 C Heatpump setpoint 42.5 C Chiller setpoint 11.0 C Heatpump setpoint 45.0 C Secondary chiller setpoint 07.0 C Secondary heatpump setpoint 45.0 C Recovery setpoint 42.5 C

Sets the chiller and heat pump setpoint for inlet adjustment.

43.02 43.03 43.04 43.05 43.06 43.07 43.08

Sets the chiller and heat pump setpoint for outlet adjustment.

Sets the secondary setpoint (only displayed if the secondary setpoint is enabled).

Sets the recovery setpoint (only displayed if recovery is enabled). 43.09 Access mask to unit menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.

Unit
Temp. In. Evap. 12.5 Rec. 35.6 Cond. 38.0 Temp. In. Evap. 12.5 Evap1 Evap2 Temp. In. Cond. 24.3 Cond.1 Cond.2 Temp. External air Freecooling Circ1 07.3 04.2 Off Circ3 07.3 04.2 Off Circ1 07.3 00.0 00.0 Circ3 07.3 00.0 00.0 Out. 07.0C 40.5C 42.5C Out. 07.0C 07.2C 06.9C Out. 22.4C 22.3C 22.4C 05.3C 06.0C Circ2 07.3bar 03.9bar Off Circ4 07.3bar 03.9bar Off Circ2 07.3 C 00.0 C 00.0 C Circ4 07.3 C 00.0 C 00.0 C

Displays inlet and outlet temperatures of the evaporator, recuperator and condenser (where fitted). (if 2 evaporators are fitted) Displays inlet and outlet temperatures of the evaporator or condenser (depending on whether the unit is in the summer or winter mode) and the outlet temperature of the two evaporators. (if 2 condensers are fitted) Displays inlet and outlet temperatures of the evaporator or condenser (depending on whether the unit is in the summer or winter mode) and the outlet temperature of the two condensers. Displays temperature or external air or freecooling. (if probes are fitted)

hp lp st hp lp st tc tl sub tc tl sub

Displays high and low pressure values (if transducers are fitted) and codifies the operating mode of circuits 1 and 2. Displays high and low pressure values (if transducers are fitted) and codifies the operating mode of circuits 3 and 4. (in chiller units with recovery) Displays pressure converted into temperature values, temperature of the liquid and calculated subcooling values of circuits 1 and 2. (in chiller units with recovery) Displays pressure converted into temperature values, temperature of the liquid and calculated subcooling values of circuits 3 and 4. Displays, for timer tuning defrost, the variation range in the defrost delay according to external temperature. Also displays the maximum duration of the free defrost procedure according to external temperature. Displays the defrost delay calculated by the timer tuning defrost algorithm.

Timer tuning defrost Range 1200 - 03600 s Free Defrost 0370 s Circ1 Circ2 Time 02700 02700 s Timer tuning defrost Circ3 Circ4 Time 02700 02700 s Timer tuning Circ1 Time 0188 Max 0290 Free Defrost Circ3 Time 0188 Max 0290 Free Defrost Circ1 defr N Delay 0904 T.def 0000 defrost Circ2 0125 s 0270 s Circ4 0125 s 0270 s Circ2 N 0000 s 0028 s

Displays the defrost delay calculated by the timer tuning defrost algorithm.

Displays the free defrost enable time and the maximum procedure time according to the length of the delay. Displays the free defrost enable time and the maximum procedure time according to the length of the delay. Displays the defrosting status of circuits 1 and 2, the delay before defrosting starts and the time taken to defrost.

63

C0240111-01-06-GB

Circ3 Circ4 defr N N Delay 0904 0000 s T.def 0000 0028 s Discharge time Comp.1 105.3C Comp.2 098.4C Discharge time Comp.3 105.3C Comp.4 098.4C Analogue outputs: Cond. 1 adj.:000 % Cond. 2 adj.:000 % Analogue outputs: Cond.3 adj.:000 % Cond.4 adj.:000 % Analogue outputs: --- % --- % Analogue outputs: 3 Freecooling :000 % --- % Analogue outputs: Cond. 3 adj.:000 % Cond. 4 adj.:000 % Analogue outputs: --- % --- % Analogue outputs: --- % --- % Analogue outputs: 3 Freecooling :000 %

Displays the defrosting status of circuits 3 and 4, the delay before defrosting starts and the time taken to defrost. Displays the discharge temperature (if probes are present) of compressors 1 and 2.

Displays the discharge temperature (if probes are present) of compressors 3 and 4.

Displays analogue outputs 1 and 2. Shows the percentage of demand of the devices connected to it (for non-linear devices correspondence with supplied voltage V does not apply). Compares Cond.1-2 adj. with single or dual ventilation adjustment. Displays analogue outputs 3 and 4.

Displays analogue outputs 5 and 6.

Displays analogue outputs 1 and 2 of expansion 3.

Displays analogue outputs 1 and 2 of the slave card. Shows the percentage of demand of the devices connected to it (for non-linear devices correspondence with supplied voltage V does not apply). Compares Cond. 3-4 adj. with single or dual ventilation adjustment. Displays analogue outputs 3 and 4 of the slave.

Displays analogue outputs 5 and 6 of the slave.

Displays analogue outputs 1 and 2 of slave expansion 3.

Hour counter Pump 1 000000 Pump 2 000000 Compr. hour counter Av. hrs 000000 C1 000000 C2 000000 C3 000000 C4 000000 Compr. hour counter C5 000000 C7 000000 C6 000000 C8 000000 Work Req 078 << 082 Act 082% 32450rpm CR 02.82 Work Req 075 << 080 Act 080% 29500rpm CR 02.84 Work Req 076 << 082 Act 082% 33600rpm CR 02.86 Work Req 078 << 081 Act 081% 30250rpm CR 02.83 Work Req 078 << 083 Act 083% 32400rpm CR 02.94

Displays the operating hours of the circulation pump (pump 2 appears only if two pumps are enabled). Displays average compressor hours. Displays the operating hours of compressors 1, 2, 3 and 4. Displays the operating hours of compressors 5, 6, 7 and 8 (if fitted).

Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered. Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered. Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered. Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered. Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered.

64

C0240111-01-06-GB

Work Req 077 << 082 Act 082% 30850rpm CR 02.88 Work Req 075 << 081 Act 081% 28650rpm CR 02.96 Work Req 074 << 080 Act 080% 29860rpm CR 03.00 Enable circuits Circ1: Y Circ2: Y Circ3: N Circ4: N Enable compressors C1:Y C2:Y C3:Y C4:Y C5:Y C6:Y C7:Y C8:Y

Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered. Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered. Displays the operating status of the centrifugal compressors, the request and effective activation, the rpm and the percentage delivered. Selects/deselects circuits. 47.01 47.02 47.03 47.04 47.05 47.06 47.07 47.08 47.09 47.10 47.11 47.12

Selects/deselects compressors.

W 3000 Cod. CA 10.00 GB

This mask contains the reference information of the software [Code]. The closed padlock symbol shows that the card is provided with its propriety software; two padlocks appear on units with 3 or 4 circuits

65

C0240111-01-06-GB

ANNEX 1b : TABLE OF W3000 base MASKS


DISPLAY MASK

Unit menu selection / Setpoint menu selection / I/O menu selection /

/ ESC / ESC

Unit menu

Setpoint menu / / Display menu

/ ESC

I/O menu

ESC

Clock menu selection / User menu selection /

/ ESC
User password

Clock menu

User menu /

ESC / ESC
Manufacturer menu

Manufacturer menu selection

Alarm menu

The figure shows the menu layout. Access to the menu is indicated on the display by a dot at the end of the menu name. In the following table of masks, level 1 is attributed to the menu, level 2 to the menu parameter, level three to the parameter value. To shift from one level to another press [ENTER] to go up or [ESC] to go down. To change the value of a parameter press [ENTER]: the display flashes and the new value can be entered using [UP or DOWN].
Mask
level1 | level2 | level3

Description Main display mask. Indicates the state of the unit ("ON", "OFF"). The submask displays the operating mode of the unit "CH"=Chiller, "HP"= Heat Pump The submask displays the operating status of the unit "ON K"= on from keypad, "ON D"= on from digital input, "ON B"= on from time bands, "ON S"= on from supervisor, "OFFA"= off from alarm, "OFFS"= off from supervisor, "OFFB"= off from time bands, "OFFD"= off from digital input, "OFFK"= off from keypad, "OFF"= off The submask displays the percentage of power requested by the thermoregulator value ranging from 0 to 100 The submask displays the percentage of power delivered by the thermoregulator value ranging from 0 to 100 The submask displays the time remaining before the pump is switched on/off. If the time decreases the unit is in the switching on/off phase. The time is expressed in seconds. The submask displays the inlet temperature of the evaporator temperature expressed in degrees centigrade The submask displays the outlet temperature of evaporator 1 temperature expressed in degrees centigrade (If 2 evaporators are present). The submask displays the outlet temperature of evaporator 2 temperature expressed in degrees centigrade The submask displays the inlet temperature of the condenser temperature expressed in degrees centigrade

Para

OFF

>MODE > > CH >ST > > ON H >REQ > > 50 >ACT > > 50 >PUMP > > 60 >EVIN > > >EVO1 > > >EVO2 > > >CDIN > > 12.5 07.2 06.9 24.3

66

C0240111-01-06-GB

MAN

>CDO1 > > 22.3 >CDO2 > > 22.4 >SALI > > >DALI > > >SR I > > >DR I > > >PASS > > 04.0 04.0 04.0 04.0 0

USER

>REG > > STEP >FLOU > > IN >GO > > STD >PROP > > P >LL S > > 0 >HL S > > >LL S > > >HL S > > >LL U > > >HL U > > >LL U > > >HL U > > >OFFS 0 0 0 0 0 0 0

The submask displays the outlet temperature of condenser 1 temperature expressed in degrees centigrade (If 2 condensers are present). The submask displays the outlet temperature of condenser 2 temperature expressed in degrees centigrade The manufacturer menu is not available on this keypad Evaporator antifreeze alarm setpoint temperature expressed in degrees centigrade Evaporator antifreeze alarm differential temperature expressed in degrees centigrade Evaporator antifreeze heating element setpoint temperature expressed in degrees centigrade Evaporator antifreeze heating element differential temperature expressed in degrees centigrade The submask is used to set the Manufacturer Password 0 to 9999 User menu The submask is used to set the adjustment type. (Switch off the unit before changing this setting!!!). "STEP"= steps, "QM"= quick mind The submask is used to set the adjustment flow type. "IN"= inlet flow, "OUT"= outlet type (only visible in the Quick Mind adjustment mode). The submask is used to choose between two types of start-up "STD"= standard, "FAST"= fast (Enable the "step adjustment" parameter first). The submask is used to set step adjustment. "P"=proportional adjustment, "P+I"=proportional + integrative adjustment The submask is used to set the lower limit of the chiller setpoint with inlet adjustment expressed in degrees centigrade The submask is used to set the upper limit of the chiller setpoint with inlet adjustment expressed in degrees centigrade The submask is used to set the lower limit of the chiller setpoint with outlet adjustment expressed in degrees centigrade The submask is used to set the upper limit of the chiller setpoint with outlet adjustment expressed in degrees centigrade The submask is used to set the lower limit of the heat pump setpoint with inlet adjustment expressed in degrees centigrade The submask is used to set the upper limit of the heat pump setpoint with inlet adjustment expressed in degrees centigrade The submask is used to set the lower limit of the heat pump setpoint with outlet adjustment expressed in degrees centigrade The submask is used to set the upper limit of the heat pump setpoint with outlet adjustment expressed in degrees centigrade (Only in the quick mind adjustment mode). The submask is used to set the forced shutdown temperature in summer expressed in degrees centigrade (Only in the quick mind adjustment mode). The submask is used to set the forced shutdown temperature in winter expressed in degrees centigrade (Only visible in the step adjustment mode). The submask is used to set the temperature adjustment band expressed in degrees centigrade The submask is used to enable setpoint variation with an analogue signal "N"= disabled, "Y"= enabled The submask is used to set the setpoint variation signal type. "0-10"= 0-10 V, "4-20"= 4-20 mA The submask is used to set the minimum variation, corresponding to the minimum signal expressed in degrees centigrade The submask is used to set the maximum variation, corresponding to the maximum signal expressed in degrees centigrade (if 2 pumps are present on the evaporator). The submask is used to set the pump control type. "AUTO"= automatic, "PMP1"= pump 1 only, "PMP2"= pump 2 only The submask is used to set the minimum pump operation time when the unit is switched on time expressed in seconds The submask is used to set the minimum pump switch-off time when the unit is switched off time expressed in seconds The submask is used to enable power limiting

23.17 23.18 23.19 23.20

39.01 39.02

39.03 39.05 39.08 39.09 39.10 39.11 39.12 39.13 39.14 39.15 39.16

> > 4.5 >OFFU > > 42.5 >BAND > > >SETV > > >SETT > > >SETL > > >SETH > > >P PR 0 N 4 20 0 6.0

39.19

39.20

39.21 39.24 39.25 39.26 39.27

> > AUTO >P ON > > 60 >P OF > > 60 >PURL

39.32 39.33 39.34

67

C0240111-01-06-GB

> > N >PURS > > 50 >PURU > >DI > >DI O S > 0 > N N N N MODB

> > >BAND > > >SER > > >PROT > > >BAUD

> > 1200 >ID > >SV > >SV O M > 0 > N

CLH I/O

> > N >PASS > > 0 >NONE >DI A > > CCCC >DI B > > CCCC >DI C > > CCCC >DI D > > CCC >DO A > > CAAA >DO B > > CAAA >DO C > > AAAA >AI > >AI > >AI > >AI > >AI > >AI > >AI 1 2 3 4 5 6 7 > 18.1 > 17.9 > 25.3 > 30.2 > 24.5 > 24.5

"N"=disabled, "Y"=enabled (If the "power limiting" parameter is enabled). The submask is used to set the power limitation percentage in the summer mode value expressed in percent (If the "power limiting" parameter is enabled). The submask is used to set the power limitation percentage in the winter mode value expressed in percent The submask is used to set the digital input for switching on/off the unit "N"= disabled, "Y"= enabled (Only if the "operating mode" parameter is set on the heat pump). The submask is used to enable the digital input for summer/winter "N"= disabled, "Y"= enabled The submask can be used to enable time bands "N"= disabled, "Y"= enabled The submask is used to enable the supervisor "N"= disabled, "Y"= enabled (If the "supervisor" is enabled). The submask is used to set the communication protocol. "MODB"= modbus, "LON"= lonWorks, "STD"=standard Carel (If the "supervisor" is enabled). The submask is used to set the speed of communication expressed in bauds Possible values: "1200"-"2400"-"9600"-"19,2"=19200 (If the "supervisor" is enabled). The submask is used to set the identification n for communicating in the supervisor network address (If the "supervisor" is enabled). The submask is used to set on/off from the supervisor "N"= disabled, "Y"= enabled (If the "supervisor" is enabled). The submask is used to enable the operating mode as supervisor "N"= disabled, "Y"= enabled The submask is used to set the user Password 0 to 9999 Clock menu, not available on this keypad Input/output menu Displays digital input 1:4 C=closed, A=open. XXXX=[input1][input2][input3][input4] Displays digital input 5:8 C=closed, A=open. XXXX=[input5][input6][input7][input8] Displays digital input 09:12:00 C=closed, A=open. XXXX=[input9][input10][input11][input12] Displays digital input 13:15 C=closed, A=open. XXX-=[input13][input14][input15] Displays digital output 1:4 C=closed, A=open. XXXX=[output1][output2][output3][output4] Displays digital output 5:8 C=closed, A=open. XXXX=[output5][output6][output7][output8] Displays digital output 9:12 C=closed, A=open. XXXX=[output9][output10][output11][output12] Displays analogue input 1 value Displays analogue input 2 value Displays analogue input 3 value Displays analogue input 4 value Displays analogue input 5 value Displays analogue input 6 value Displays analogue input 7

39.35

39.36

39.37 39.39

39.40 39.41 39.42 39.45

39.46

39.47 39.43

39.44

68

C0240111-01-06-GB

SETP

> >AI > >AO > >AO >

8 3 4

> 0 > 0 > 70 > 80

>MODE > > CH >ACT > > 50 >SUM > >SUM > > 9.5 >UIN > > 0 >UIN > 11.0

value Displays analogue input 8 value Displays analogue output 3 value expressed in Volts Displays analogue output 4 value expressed in Volts Setpoint menu The submask is used to set the operating mode (this depends on the machine type set in the manufacturer menu using the W3000-compact keypad) "CH"= Chiller, "HP"= heat pump The submask displays the percentage of active power of the thermoregulator value ranging from 0 to 100 (If the FLOW parameter in the user menu is set to inlet). The submask is used to set the summer setpoint with inlet adjustment expressed in degrees centigrade (If the FLOW parameter in the user menu is set to outlet). The submask is used to set the summer setpoint with outlet adjustment expressed in degrees centigrade (If the FLOW parameter in the user menu is set to inlet). The submask is used to set the winter setpoint with inlet adjustment expressed in degrees centigrade (If the FLOW parameter in the user menu is set to outlet). The submask is used to set the winter setpoint with outlet adjustment expressed in degrees centigrade Unit menu Displays evaporator inlet temperature Displays evaporator 1 outlet temperature (If evaporator 2 is present). Displays evaporator 2 outlet temperature (If condenser is present). Displays condenser inlet temperature (If condenser is present). Displays condenser 1 outlet temperature (If condenser 2 is present). Displays condenser 2 outlet temperature (If the temperature probe is present and if it is enabled in the manufacturer menu). Displays external temperature expressed in degrees centigrade Displays circuit 1 high pressure high pressure value Displays circuit 2 high pressure high pressure value Displays value of analogue output 3 value expressed in percent Displays value of analogue output 4 value expressed in percent Displays compressor 1 operating hours expressed in thousands e.g.: "1"=1000 hours Displays compressor 1 operating hours expressed in units e.g.: "50"=50 hours Displays compressor 2 operating hours expressed in thousands e.g.: "1"=1000 hours Displays compressor 2 operating hours expressed in units e.g.: "50"=50 hours Enables compressor 1 "N"=deselected, "Y"= selected Enables compressor 2 "N"=deselected, "Y"= selected Software release Software revision Alarms menu : no alarm active

43.01

43.02 43.03

43.05

43.04

UNIT

> >EVIN >EVO1 >EVO2 >CDIN >CDO1 >CDO2 >EHT

> 0

43.06

NO A

> > >HP1 > > >HP2 > > >AO 3 > > >AO 4 > > >HH 1 > > >LH 1 > > >HH 2 > > >LH 2 > > >SEL1 > > >SEL2 > > >CA07 > >

0 0 0 0 0 1 50 1 50 Y Y r.00

47.05 47.06

69

C0240111-01-06-GB

ANNEX 1c : PARAMETERS TABLE


N.par. 01.01 01.02 01.03 01.04 01.05 01.06 01.07 01.08 01.09 01.10 01.11 01.12 01.13 01.14 01.15 05.01 05.02 05.03 05.04 05.05 05.06 05.07 05.08 05.09 05.10 05.11 05.12 05.13 05.14 05.15 05.16 05.17 05.18 05.19 05.20 05.21 05.22 05.23 05.24 05.25 05.26 05.27 05.28 07.01 07.02 07.03 07.04 07.05 07.06 07.07 07.08 07.09 07.10 07.11 07.12 09.01 09.02 09.03 Description of parameter Type of unit (0:chiller - 1:heat pump - 2:multi-use) Type of compressors (0:Centrifuge - 1:hermetic - 2:semi-hermetic - 3:screw) N circuits N compressors per circuit N separation stages per compressor Condensation type (0:none - 1:air - 2:water) N condensers Reversal side for chiller-heat pump (0:water - 1:freon ) Fan type (0:axial - 1:centrifuge) Evaporation type (0:none - 1:water - 2:flooded - 3:air) N evaporators N evaporating banks Freon type (0: R22 - 1: R134a - 2: R404a 3: R407c - 4: R410a 5: R507c - 6: R290 - 7: R600 - 8: R600a - 9: R717 - 10: R744) Recovery enable (0:disabled - 1:enabled) Freecooling enable (0:disabled- 1:enabled) Enable summer setpoint offset Enable winter setpoint offset Setpoint offset of summer setpoint Summer setpoint offset differential Maximum variation for summer setpoint offset Minimum limit for summer setpoint offset Setpoint offset of winter setpoint Winter setpoint offset differential Maximum variation for winter setpoint offset Minimum limit for winter setpoint offset Hp relays enable (0:disabled - 1: enabled) Upper setpoint Upper differential Lower setpoint Lower differential Subcooling enable (0:disabled - 1:enabled) Start delay for subcooling adjustment Activation delay for subcooling relay Upper setpoint for opening/closing subcooling valves Lower setpoint for opening/closing subcooling valves Enable pressure switch high temperature control Pressure switch high temperature control setpoint Pressure switch high temperature control differential Pumpdown type (0:enabled - 1:during shutdown - 2:cyclical - 3:during shutdown and cyclical) End pumpdown setpoint Maximum pumpdown time Timeout for performing cyclical pumpdown Configure pumpdown start modes Number of pumps on the evaporator Type of rotation of pumps on evaporator (not used) Recuperator pump enable (0:disabled - 1: enabled) Condenser pump enable (0:disabled - 1: enabled) Secondary circuit pump control enable for water/water units (0:disabled - 1: enabled) Flow switch alarm bypass time when starting pump on secondary circuit Flow switch alarm bypass time when stopping pump on secondary circuit Maximum acceptable continuous operating time of a pump before rotation is forced Maximum difference in days between the two pumps before the 'Threshold' value of the pump is doubled Pump override enable during a long period of inactivity (0:No - 1:Yes) Threshold time for long period of inactivity Duration of pump override for long period of inactivity Continuous modulation enable of screw compressors (0:disabled 1:enabled) Minimum compressor shut-down time (with step adjustment) Minimum delay between start-ups of different compressors (with input step Default 0 1 2 1 0 1 1 0 0 1 1 2 3 0 0 0 0 45.0 5.0 6.0 7.0 -5.0 5.0 5.0 45.0 0 10.0 5.0 9.5 0.5 0 60 30 4.0 3.0 0 23.5 2.0 0 2.5 3 30 0 1 2 0 0 0 15 120 7 60 1 30 10 0 60 10 U.M. C C C C C C C C bar bar bar bar s s C C bar bar bar s min s s dd dd dd s s s 1 1 500 500 10 10 1 1 1 1 120 120 1500 9999 1500 999 Min. 0 P 99.25 1 1 0 0 1 0 1 0 1 0 Max. P 99.01 P 99.02 P 99.03 P 99.04 P 99.05 2 2 1 P 99.31 P 99.06 P 01.03 10

0.0 0.0 0.0 P 99.09 -30.0 0.0 0.0 26.0 0.0 0.0 0.0 0.0 0 0 0.0 0.0 P 25.06 0.0 0 0.1 3 1 0 0 1

60.0 20.0 20.0 23.0 0.0 20.0 20.0 70.0 P 25.07 10.0 P 05.12 10.0 120 120 20.0 20.0 P 25.07 5.0 3 7.0 60 999 31 P 99.24 2

70

C0240111-01-06-GB

N.par. 09.04 09.05 09.06 09.07 09.08 09.09 09.10 09.11 09.12 09.13 09.14 09.15 09.16 09.17 09.18 09.19 09.20 09.21 09.22 09.23 09.24 09.25 09.26 09.27 09.28 09.29 09.30 09.31 09.32 09.33 09.34 09.35 09.36 09.37 09.38 09.39 09.40 09.41 09.42 09.43 09.44 09.45 09.46 09.47 09.48 09.49 09.50 09.51 09.52 09.53 09.54 09.55 09.56 09.57 13.01 13.02 13.03 13.04 13.05 13.06 13.07

Description of parameter adjustment) Minimum time between start-ups of the same compressor (with step adjustment) Maximum number of compressor starts per hour (with Quick Mind adjustment) Minimum compressor start-up time (with Quick Mind adjustment) Enables 100% screw compressor forcing (0:disabled - 1:enabled) Minimum separation mode temperature setpoint Separation re-activation differential Enables screw compressor maximum separation time control (0:disabled 1:enabled) Maximum separation time before 100% screw compressor forcing 100% forcing time following maximum separation time control Period for power maintenance impulse Period for power increase impulse Minimum duration of power increase impulse Maximum duration of power increase impulse Period for power decrease impulse Minimum duration of power decrease impulse Maximum duration of power decrease impulse No-load start time Minimum time the separation stages remain active Time the compressor oil valve remains active Compressor model (0:Bitzer - 1:Hitachi - 2:Fu-Sheng) Economiser enable (0:disabled - 1:enabled) Economiser start delay after compressor starts Setpoint for disabling the economiser Differential for disabling the economiser Enable compressor discharge temperature control, liquid injection (0:disabled - 1:enabled) Setpoint for enabling discharge temperature control Differential for disabling discharge temperature control Minimum percentage for modulating centrifuge compressors Maximum percentage for modulating centrifuge compressors Number of revs for compressor start (for units with shall and tube evaporator) Start-up time for centrifuge compressors Number of bypass valves for centrifugal compressors Compression ration required to open the liquid line solenoid Bypass valve closing timeout upon compressor start-up Integral time for power increase Minimum variation for power increase Integral time for power decrease Minimum variation for power decrease Off percentage for centrifugal compressor 1 On percentage for centrifugal compressor 1 Off percentage for centrifugal compressor 2 On percentage for centrifugal compressor 2 Off percentage for centrifugal compressor 3 On percentage for centrifugal compressor 3 Off percentage for centrifugal compressor 4 On percentage for centrifugal compressor 4 Off percentage for centrifugal compressor 5 On percentage for centrifugal compressor 5 Off percentage for centrifugal compressor 6 On percentage for centrifugal compressor 6 Off percentage for centrifugal compressor 7 On percentage for centrifugal compressor 7 Off percentage for centrifugal compressor 8 On percentage for centrifugal compressor 8 Valve configuration in status 0 Valve configuration in status 1 Valve configuration in status 2 Valve configuration in status 3 Valve configuration in status 4 Valve configuration in status 5 Valve configuration in status 6

Default 360 8 60 0 -5.0 1.0 0 1200 120 600 10 1.0 5.0 10 1.0 5.0 30 10 10 0 0 120 15.0 2.0 1 115.0 10.0 10 90 3500 20 1 2.2 20 5 1 5 1 0 40 0 40 0 40 0 40 0 40 0 40 0 40 0 40 0 2 3 0 0 3 2

U.M. s s C C s s s s s s s s s s s s s bar bar C C % % rpmx10 s s s % s % % % % % % % % % % % % % % % % % -

Min. 1 1 1 -30.0 0.5

Max. 900 12 500 0.0 10.0

1 1 0 0 0.0 0.0 1 0.0 0.0 1 1 1 0 1 10.0 0.1

7200 300 999 999 99.9 99.9 999 99.9 99.9 60 60 60 2 500 P 25.07 9.9

70.0 2.0 0 P 09.31 100 0 0 1.0 15 1 0 1 0 0 P 09.42 0 P 09.44 0 P 09.46 0 P 09.48 0 P 09.50 0 P 09.52 0 P 09.54 0 P 09.56 0 0 0 0 0 0 0

P 23.13 25.0 P 09.32 100 6000 300 1 4.0 120 120 100 120 100 P 09.43 100 P 09.45 100 P 09.47 100 P 09.49 100 P 09.51 100 P 09.53 100 P 09.55 100 P 09.57 100 99 99 99 99 99 99 99

71

C0240111-01-06-GB

N.par. 13.08 13.09 13.10 13.11 13.12 13.13 13.14 13.15 13.16 13.17 13.18 13.19 13.20 13.21 13.22 13.23 15.01 15.02 15.03 15.04 15.05 15.06 15.07 17.01 17.02 17.03 17.04 17.05 17.06 17.07 17.08 17.09 17.10 17.11 17.12 17.13 17.14 17.15 17.16 17.17 17.18 17.19 17.20 17.21 17.22 17.23 17.24 17.25 17.26 17.27 17.28 17.29 17.30 17.31 17.32 17.33 17.34 17.35 17.36 17.37 17.38 17.39 19.01

Description of parameter Valve configuration in status 7 Valve configuration in status 8 Valve configuration in status 9 Valve configuration in status 10 Valve configuration in status 11 Valve configuration in status 12 Valve 1 release time Valve 2 release time Valve 3 release time Valve 4 release time Valve 5 release time Valve 6 release time Valve 7 release time Valve 8 release time Valve 9 release time Valve 10 release time Recovery priority in winter (0:disabled - 1:enabled) Remote recovery control enable (0:disabled - 1:enabled) Pressure setpoint for forcing chiller status from recovery Pressure differential for forcing chiller status from recovery Enables cyclical forcing from chiller plus heat recovery mode to chiller mode Maximum time in chiller plus heat recovery mode before forcing to chiller mode Minimum time in chiller mode before forcing to chiller plus heat recovery mode Enable condensation control (0:No - 1:Yes) Type of condensation adjustment (0:Step. Cont - 1:Step - 2:Continuous) N condensation steps Type of condensation control (0:Separate - 1:Individual - 2:Dual) Linear operation model (0:Standard - 1:Linear) Condensation valve logic (0:direct - 1:reverse) Enable pre-condensation (0:No - 1:Yes) Pre-condensation time Pre-condensation percentage Enable maximum condensation override in the chiller mode (0:No - 1:Yes) Maximum condensation override setpoint in the chiller mode Maximum condensation override differential in the chiller mode Enable maximum condensation override in the heat pump mode (0:No 1:Yes) Maximum condensation override setpoint in the heat pump mode Maximum condensation override differential in the heat pump mode Step 1 set point in chiller mode Step 1 differential in chiller mode Step 2 set point in chiller mode Step 2 differential in chiller mode Step 3 setpoint in chiller mode Step 3 differential in chiller mode Step 4 set point in chiller mode Step 4 differential in chiller mode Step 1 setpoint in heat pump mode Step 1 differential in heat pump mode Step 2 setpoint in heat pump mode Step 2 differential in heat pump mode Step 3 setpoint in heat pump mode Step 3 differential in heat pump mode Step 4 setpoint in heat pump mode Step 4 differential in heat pump mode Continuous adjustment setpoint in the chiller mode Continuous adjustment differential in the chiller mode Continuous adjustment setpoint in the heat pump mode Continuous adjustment differential in the heat pump mode Maximum condensation limit in continuous adjustment Minimum condensation limit in continuous adjustment Adjustment under the minimum condensation limit (0:adjustment always1:adjustment Off) Condensation adjustment off differential Temperature difference for activating freecooling

Default 0 0 3 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 23.5 5.0 0 60 120 1 2 3 0 1 0 1 10 100 0 23.0 3.0 0 1.0 0.5 15.0 3.0 16.5 3.0 18.0 3.0 19.0 2.0 8.0 1.0 5.0 1.4 2.2 0.8 1.0 0.5 14.0 5.0 6.0 1.0 100 30 1 1.0 1.0

U.M. s s s s s s s s s s bar bar s s s % bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar % % bar C

Min. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Max. 99 99 99 99 99 99 999 999 999 999 999 999 999 999 999 999

10.0 0.1 1 40 0 1 0 0

P 25.07 9.9 999 500 2 P 99.23 P 99.26 2

0 50 10.0 0.1

30 100 P 25.07 5.0

0.5 0.1 0.5 0.1 0.5 0.1 0.5 0.1 0.5 0.1 0.5 0.1 0.5 0.1 0.5 0.1 0.5 0.1 5.0 0.1 0.5 0.1 P 17.37 0

15.0 5.0 P 25.07 5.0 P 25.07 5.0 P 25.07 5.0 P 25.07 5.0 15.0 5.0 15.0 5.0 15.0 5.0 15.0 5.0 P 25.07 15.0 15.0 15.0 100 P 17.36

0.0 1.0

5.0 5.0

72

C0240111-01-06-GB

N.par. 19.02 19.03 19.04 19.05 19.06 21.01 21.02 21.03 21.04 21.05 21.06 21.07 21.08 21.09 21.10 21.11 21.12 21.13 21.14 21.15 21.16 21.17 21.18 21.19 21.20 21.21 21.22 21.23 21.24 23.01 23.02 23.03 23.04 23.05 23.06 23.07 23.08 23.09 23.10 23.11 23.12 23.13 23.14 23.15 23.16 23.17 23.18 23.19 23.20 23.21 23.22 23.23 23.24 23.25 23.26 23.27 23.28 23.29 23.30 23.31 23.32 23.33

Description of parameter Temperature offset for deactivating freecooling Temperature delta for deactivating freecooling Type of freecooling valve control (0:direct - 1:reverse) Hysteresis temperature of individual fans Start/stop delay for each fan Defrost type (0:standard - 1:Timer Tuning - 2:Timer Tuning + Auto Tuning) Start defrost setpoint Stop defrost setpoint Defrost activation delay Maximum defrost time Drip time Defrost delay increase differential Defrost delay decrease differential Defrost delay increase/decrease percentage Maximum number of defrosts per hour Calculation interval of the difference between external temperature and evaporation temperature Maximum difference between external temperature and evaporation temperature Temperature threshold for changing defrost delay Variation threshold offset Reduction factor in defrost delay Bypass time from start of circuits for calculating the reduction in the defrost delay Start variation delay Minimum derived evaporation pressure Forced defrosting with low pressure (0:disabled - 1:enabled) Forced defrosting pressure threshold Minimum heatpump operating pressure for separating hermetic compressors Restore pressure for separating the hermetic compressors Free defrost enable (0:disabled - 1:enabled) Minimum external temperature for free defrost operation High pressure from transducers alarm High pressure from transducers alarm differential N of low pressure alarm automatic resets Duration of low pressure alarm Low pressure alarm setpoint Low pressure alarm differential Enable low pressure control with low external air temperature (0:No - 1:Yes) Start-up time for low pressure control with low external air temperature Low pressure setpoint with low external air temperature Low pressure differential with low external air temperature N of centrifugal compressor alarm automatic resets Bypass time of compressor thermal protection alarm Setpoint for activating the high compressor discharge temperature alarm Differential for deactivating the high compressor discharge temperature alarm Compressor oil alarm delay after starting Compressor oil alarm delay during running Evaporator antifreeze alarm setpoint Evaporator antifreeze alarm differential Evaporator antifreeze heating element setpoint Evaporator antifreeze heating element differential Condenser antifreeze alarm setpoint Condenser antifreeze alarm differential Recuperator antifreeze heating element setpoint Recuperator antifreeze heating element differential N of flow switch alarm automatic resets Evaporator flow switch start-up delay Evaporator flow switch running delay Recuperator flow switch start-up delay Recuperator flow meter running delay Condenser flow meter start-up delay Condenser flow meter running delay Low water flow alarm setpoint Low water flow alarm delay

Default -9.0 1.0 0 0.3 20 0 3.0 14.0 1800 300 120 60 180 20 3 300 3.0 15.0 2.0 5 120 600 -0.1 0 1.0 1.2 1.6 0 4.0 28.0 7.0 3 120 1.6 0.9 0 120 0.1 0.5 3 10 125.0 10.0 120 10 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3 10 1 10 1 10 1 8.0 30

U.M. C C C s bar bar s s s s s s s C C C % s s bar/m bar bar bar C bar bar s bar bar s bar bar s C C s s C C C C C C C C s s s s s s C s

Min. -10.0 0.1 0.0 1 0 0.0 P 21.02 60 10 0 0 1 0 1 10 0.1 12.0 0.5 0 0 0 -10.0 P 23.05 P 23.05 P 21.21 -10.0 0.0 0.0 0 0 0.1 0.1 10 0.1 0.1 0 0 70.0 2.0 1 1 -30.0 1.0 P 23.17 1.0 -30.0 1.0 -30.0 1.0 0 1 1 1 1 1 1 3.0 P 23.26

Max. P 99.21 P 99.22 1.0 500 2 P 21.03 P 25.07 3600 500 500 P 99.27 P 99.28 100 9 600 9.9 20.0 9.9 99 999 999 10.0 9.9 9.9 9.9 10.0 P 25.07 30.0 5 500 9.9 4.0 P 23.04 P 23.05 4.0 5 360 125.0 25.0 120 120 5.0 10.0 5.0 10.0 5.0 10.0 5.0 10.0 9 120 20 120 20 120 20 10.0 30

73

C0240111-01-06-GB

N.par. 23.34 23.35 23.36 23.37 23.38 25.01 25.02 25.03 25.04 25.05 25.06 25.07 25.08 25.09 27.01 27.02 27.03 27.04 27.05 27.06 27.07 27.08 27.09 27.10 27.11 27.12 27.13 27.14 27.21 27.22 27.23 27.24 27.25 27.26 27.27 27.28 27.31 27.32 27.33 27.34 27.51 27.52 27.53 27.54 31.01 31.02 31.03 31.04 31.05 31.06 31.07 31.08 31.09 31.10 31.11 31.12 31.13 31.14 31.21 31.22 31.23 31.24 31.25 31.26 31.27 31.28

Description of parameter Maximum pump operation time in alarm mode High/low inlet temperature (0:signal - 1:alarm) High/low inlet temperature alarm delay High inlet water temperature alarm setpoint Low inlet water temperature alarm setpoint Type of compressor discharge temperature probe (0:NTC 0-150V, 1:PT1000 ) Condenser inlet temperature probe enable (0:disabled - 1:enabled) External air temperature probe enable (0:disabled - 1:enabled) Pressure transducers enable (0:disabled - 1: enabled) Low pressure transducers enable (0:disabled - 1: enabled) Start scale value of high pressure transducers End scale value of high pressure transducers Start scale value of low pressure transducers End scale value of low pressure transducers Probe 1 calibration Probe 2 calibration Probe 3 calibration Probe 4 calibration Probe 5 calibration Probe 6 calibration Probe 7 calibration Probe 8 calibration Probe 9 calibration Probe 10 calibration Expansion 1 Probe 1 calibration Expansion 1 Probe 2 calibration Expansion 1 Probe 3 calibration Expansion 1 Probe 4 calibration Expansion 2 Probe 1 calibration Expansion 2 Probe 2 calibration Expansion 2 Probe 3 calibration Expansion 2 Probe 4 calibration Expansion 2 Probe 5 calibration Expansion 2 Probe 6 calibration Expansion 2 Probe 7 calibration Expansion 2 Probe 8 calibration Expansion 3 Probe 1 calibration Expansion 3 Probe 2 calibration Expansion 3 Probe 3 calibration Expansion 3 Probe 4 calibration Expansion 5 Probe 1 calibration Expansion 5 Probe 2 calibration Expansion 5 Probe 3 calibration Expansion 5 Probe 4 calibration Slave Probe 1 calibration Slave Probe 2 calibration Slave Probe 3 calibration Slave Probe 4 calibration Slave Probe 5 calibration Slave Probe 6 calibration Slave Probe 7 calibration Slave Probe 8 calibration Slave Probe 9 calibration Slave Probe 10 calibration Expansion 1 Slave Probe 1 calibration Expansion 1 Slave Probe 2 calibration Expansion 1 Slave Probe 3 calibration Expansion 1 Slave Probe 4 calibration Expansion 2 Slave Probe 1 calibration Expansion 2 Slave Probe 2 calibration Expansion 2 Slave Probe 3 calibration Expansion 2 Slave Probe 4 calibration Expansion 2 Slave Probe 5 calibration Expansion 2 Slave Probe 6 calibration Expansion 2 Slave Probe 7 calibration Expansion 2 Slave Probe 8 calibration

Default 15 0 30 30.0 15.0 1 0 0 0 0 0.0 30.0 0.0 30.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

U.M. s s C C bar bar bar bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar

Min. 15 1 P 99.12 15.0

Max. 999 999 40.0 P 99.13

0.0 P 25.06 0.0 P 25.08 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9

P 25.07 42.0 P 25.09 30.0 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9

74

C0240111-01-06-GB

N.par. 31.31 31.32 31.33 31.34 31.51 31.52 31.53 31.54 35.01 35.02 35.03 35.04 35.05 35.06 35.07 35.08 35.09 35.10 35.11 35.12 35.13 35.14 35.15 35.16 35.17 35.18 35.19 35.20 35.21 35.22 35.23 35.24 35.25 35.26 39.01 39.02 39.03 39.04 39.05 39.06 39.07 39.08 39.09 39.10 39.11 39.12 39.13 39.14 39.15 39.16 39.17 39.18 39.19 39.20 39.21 39.22 39.23 39.24 39.25 39.26 39.27 39.28 39.29 39.30 39.31 39.32

Description of parameter Expansion 3 Slave Probe 1 calibration Expansion 3 Slave Probe 2 calibration Expansion 3 Slave Probe 3 calibration Expansion 3 Slave Probe 4 calibration Expansion 5 Slave Probe 1 calibration Expansion 5 Slave Probe 2 calibration Expansion 5 Slave Probe 3 calibration Expansion 5 Slave Probe 4 calibration Evaporator pump hour counter threshold Pump 2 hour counter threshold Compressor 1 hour counter threshold Compressor 2 hour counter threshold Compressor 3 hour counter threshold Compressor 4 hour counter threshold Compressor 5 hour counter threshold Compressor 6 hour counter threshold Compressor 7 hour counter threshold Compressor 8 hour counter threshold Compressor 1 hours (thousands) Compressor 1 hours (units) Compressor 2 hours (thousands) Compressor 2 hours (units) Compressor 3 hours (thousands) Compressor 3 hours (units) Compressor 4 hours (thousands) Compressor 4 hours (units) Compressor 5 hours (thousands) Compressor 5 hours (units) Compressor 6 hours (thousands) Compressor 6 hours (units) Compressor 7 hours (thousands) Compressor 7 hours (units) Compressor 8 hours (thousands) Compressor 8 hours (units) Adjustment type (0:step - 1:Quick Mind) Adjustment control type (0:inlet - 1:outlet) Start-up mode (0:standard - 1:rapid) Percentage inside the dead area in which the compressor is not modulated (modulating screw compressors) Step adjustment type (0: proportional - 1: proportional + integrative) Inlet adjustment integral time Integral correction limit Minimum chiller setpoint (in the Quick Mind inlet adjustment mode) Minimum chiller setpoint (in the step inlet adjustment mode) Maximum chiller setpoint (with inlet adjustment) Minimum chiller setpoint (with outlet adjustment) Maximum chiller setpoint (with outlet adjustment) Minimum heat pump setpoint (with inlet adjustment) Maximum heat pump setpoint (with inlet adjustment) Minimum heat pump setpoint (with outlet adjustment) Maximum heat pump setpoint (with outlet adjustment) Minimum recovery setpoint Maximum recovery setpoint Forced summer shutdown Forced winter shutdown Temperature adjustment band (with step adjustment) Recovery adjustment band Enable secondary setpoint (0:No - 1:Yes) Enable external setpoint variation (0:No - 1:Yes) External setpoint variation type (0:4-20 mA - 1:0-10 V) Minimum external setpoint Maximum external setpoint Enable external recovery setpoint variation (0:No - 1:Yes) External recovery setpoint variation type (0:4-20 mA - 1:0-10 V) Minimum external recovery setpoint Maximum external recovery setpoint Evaporator pump operating mode (0:automatic - 1:pump 1 only - 2:pump 2

Default 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 12 12 10 10 10 10 10 10 10 10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 35 0 90 20 11.0 6.0 20.0 6.0 18.0 30.0 44.0 30.0 48.0 30.0 50.0 4.5 52.0 2.5 5.0 0 0 0 0.0 6.0 0 0 0.0 6.0 0

U.M. C/bar C/bar C/bar C/bar C/bar C/bar C/bar C/bar h x 1000 h x 1000 h x 1000 h x 1000 h x 1000 h x 1000 h x 1000 h x 1000 h x 1000 h x 1000 h x 1000 h h x 1000 h h x 1000 h h x 1000 h h x 1000 h h x 1000 h h x 1000 h h x 1000 h % s % C C C C C C C C C C C C C C C C C C C -

Min. -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 -9.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Max. 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999 999

0 0 1 P 99.09 P 99.09 P 99.10 P 99.09 P 43.05 26.0 P 43.04 30.0 P 43.06 30.0 P 39.17 P 23.17 P 99.14 2.0 2.0

100 600 100 P 43.02 P 43.03 P 99.29 P 43.05 P 99.30 P 43.04 70.0 P 43.06 70.0 P 39.18 70.0 P 99.11 75.0 10.0 10.0

0.0 0.0

10.0 10.0

0.0 0.0 0

10.0 10.0 2

75

C0240111-01-06-GB

N.par. 39.33 39.34 39.35 39.36 39.37 39.38 39.39 39.40 39.41 39.42 39.43 39.44 39.45 39.46 39.47 39.48 43.01 43.02 43.03 43.04 43.05 43.06 43.07 43.08 43.09 47.01 47.02 47.03 47.04 47.05 47.06 47.07 47.08 47.09 47.10 47.11 47.12

Description of parameter only) Minimum delay between pump start-up and compressor start-up Pump shutdown delay Enable power limitation (0:No - 1:Yes) Power limitation in summer mode (%) Power limitation in winter mode (%) Power limitation in recovery mode (%) On/off enable from digital input (0:No - 1:Yes) Summer/winter enable from digital input (0:No - 1:Yes) Time bands enable (0:deactivated - 1:activated) Serial line configuration (0:Disabled - 1:Supervision - 2:Sequencer 3:Manager 3000) On/off enable from supervisor (0:No - 1:Yes) Enable operating mode modification from supervisor (0:No - 1:Yes) Set communication protocol with supervisor (1:Standard - 2:ModBus 3:LonWorks - 4:Trend - 5:Bacnet) Speed of communication with supervisor setting (0:1200 baud - 1:2400 baud - 2:4800 baud - 3:9600 baud - 4:19200 baud) Set unit identification number with supervisor Language (0:Italian - 1:English - 2:Extra language) Setting the operating mode Summer setpoint with Quick Mind inlet adjustment Summer setpoint with step inlet adjustment Winter setpoint with step inlet adjustment Summer setpoint with outlet adjustment Winter setpoint with outlet adjustment Secondary summer setpoint Secondary winter setpoint Recovery setpoint Enable circuit 1 Enable circuit 2 Enable circuit 3 Enable circuit 4 Enable compressor 1 Enable compressor 2 Enable compressor 3 Enable compressor 4 Enable compressor 5 Enable compressor 6 Enable compressor 7 Enable compressor 8

Default 60 60 0 50 50 50 0 0 0 0 0 0 2 3 11 0 0 11.0 9.5 42.5 7.0 45.0 7.0 45.0 42.5 1 1 1 1 1 1 1 1 1 1 1 1

U.M. s s % % % C C C C C C C C -

Min. 1 10 0 0 0

Max. 500 500 100 100 100

1 0 1 0 P 99.07 P 39.08 P 39.09 P 39.13 P 39.11 P 39.15 P 99.11 P 99.13 P 39.17

5 4 200 2 P 99.08 P 39.10 P 39.10 P 39.14 P 39.12 P 39.16 P 99.12 P 99.14 P 39.18

76

C0240111-01-06-GB

99.01 99.02 99.03 99.04 99.05 99.06 99.07 99.08 99.09 99.10 99.11 99.12 99.13 99.14 99.15 99.16 99.17 99.18 99.19 99.20 99.21 99.22 99.23 99.24 99.25 99.26 99.27 99.28 99.29 99.30 99.31

Maximum settable limit for configuring the machine type (depends on the type of hardware) Maximum settable limit for choosing the compressor type Maximum limit for the number of circuits (depends on the type of hardware) Maximum limit for the number of compressors (depends on the type of hardware) Maximum limit for the number of steps per compressor (depends on the type of hardware) Maximum limit for the number of evaporators (depends on the type of hardware) Minimum settable limit for the operating mode (depends on the parameter settings and the type of hardware) Maximum settable limit for the operating mode (depends on the parameter settings and the type of hardware) Minimum settable value for the minimum chiller setpoint (equal to anti-freeze setpoint + 2C) Maximum settable limit for the minimum chiller setpoint Minimum chiller setpoint limit (depends on the adjustment type) Maximum chiller setpoint limit (depends on the adjustment type) Minimum heat pump setpoint limit (depends on the adjustment type) Maximum heat pump setpoint limit (depends on the adjustment type) Minimum recovery setpoint Maximum recovery setpoint Maximum number of available languages Enable limit for advanced time bands Minimum settable value for controlling time bands (depends on parameter settings) Maximum settable value for controlling time bands (depends on parameter settings) Negated value of parameter: Temperature delta for deactivating freecooling Negated value of parameter: Temperature offset for deactivating freecooling Maximum number of ventilation steps available on the card Maximum number of pumps available on the card Compressor types that can be used by the card Possible ventilation type, depends on the number of cooling circuits Reference time calculated by the system according to weather conditions and the unit operating mode Maximum upper Timer-Tuning-Defrost band limit. This is the result of (maximum defrost time)-(reference time calculated by the system according to weather conditions and the unit operating mode) Maximum settable summer setpoint limit with inlet adjustment of: high inlet temperature alarm setpoint - 7C Maximum settable summer setpoint limit with outlet adjustment of: high outlet temperature alarm setpoint - 12C Maximum number of evaporators that can be configured on the board

C0240111-01-06-GB

ANNEX 2 : INPUT/OUTPUT TABLE


L HARDWARE: a ) for hermetic compressors:
WATER-AIR UNIT with L axial fans
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor 3 thermal protection Compressor 4 thermal protection Circuit 1 fan thermal protection Circuit 2 fan thermal protection Evaporator flow switch Remote on/off Pump 1 thermal protection Pump 2 thermal protection Circuit 1 high pressure switch Circuit 2 high pressure switch Phase sequence General enable Compressors enable Remote Summer/Winter Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Evap. 1 outlet water temperature Evap. 2 outlet water temperature Circuit 2 high pressure transducer External air temperature Setpoint variation (4-20mA 0.0-10V) Dual setpoint Digital outputs Circuit 1 cycle reversal valve Circuit 2 cycle reversal valve Solenoid valve 1 Solenoid valve 2 Pump 1 Pump 2 Compressor 1 Compressor 2 Ventilation step 1 circuit 1 Ventilation step 2 circuit 1 Ventilation step 3 circuit 1 Evaporator antifreeze heating element General alarms cumulative Compressor 3 Compressor 4 Ventilation step 1 circuit 2 Ventilation step 2 circuit 2 Ventilation step 3 circuit 2

WATER-AIR UNIT with L centrifuge fans


ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor 3 thermal protection Compressor 4 thermal protection Fans thermal relay Evaporator flow switch Remote on/off Pump 1 thermal protection Pump 2 thermal protection Circuit 1 high pressure switch Circuit 2 high pressure switch Phase sequence General enable Compressors enable Remote Summer/Winter Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Evap. 1 outlet water temperature Evap. 2 outlet water temperature Circuit 2 high pressure transducer External air temperature Setpoint variation (4-20mA 0.0-10V) Dual setpoint Digital outputs Circuit 1 cycle reversal valve Circuit 2 cycle reversal valve Solenoid valve 1 Solenoid valve 2 Pump 1 Pump 2 Compressor 1 Compressor 2 Main ventilation step

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Evaporator antifreeze heating element General alarms cumulative Compressor 3 Compressor 4 Ventilation step 1 Ventilation step 2 Ventilation step 3

Analogue outputs Y1 Circuit 1 speed adjustment Y2 Circuit 2 speed adjustment Y3 Y4 Y5

Analogue outputs Y1 Speed adjustment Y2 Y3 Y4 Y5

77

C0240111-01-06-GB

Y6

Y6

L WATER-WATER UNIT
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor 3 thermal protection Compressor 4 thermal protection

L CONDENSING UNIT
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor 3 thermal protection Compressor 4 thermal protection Circuit 1 fan thermal protection Circuit 2 fan thermal protection Remote on/off

Evaporator flow switch Remote on/off Pump 1 thermal protection Pump 2 thermal protection Circuit 1 high pressure switch Circuit 2 high pressure switch Phase sequence General enable Compressors enable Remote Summer/Winter Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Evap. 1 outlet water temperature Evap. 2 outlet water temperature Circuit 2 high pressure transducer Outlet 2 water temp. / cond. inlet Setpoint variation (4-20mA 0.0-10V) Condenser outlet water temperature Dual setpoint Digital outputs Cycle reversal valve Solenoid valve 1 Solenoid valve 2 Pump 1 Pump 2 Compressor 1 Compressor 2

Circuit 1 high pressure switch Circuit 2 high pressure switch Phase sequence

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

Analogue inputs Circuit 1 high pressure transducer

Step 1 Step 2 Circuit 2 high pressure transducer

Step 3 Step 4 Digital outputs

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Evaporator antifreeze heating element General alarms cumulative Compressor 3 Compressor 4

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Solenoid valve 1 Solenoid valve 2

Compressor 1 Compressor 2 Ventilation step 1 circuit 1 Ventilation step 2 circuit 1 Ventilation step 3 circuit 1 General alarms cumulative Compressor 3 Compressor 4 Ventilation step 1 circuit 2 Ventilation step 2 circuit 2 Ventilation step 3 circuit 2

Analogue outputs Y1 Condensation adjustment Y2 Y3 Y4 Y5 Y6

Analogue outputs Y1 Circuit 1 speed adjustment Y2 Circuit 2 speed adjustment Y3 Y4 Y5 Y6

78

C0240111-01-06-GB

L EVAPORATING UNIT
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor 3 thermal protection Compressor 4 thermal protection Circuit 1 fan thermal protection Circuit 2 fan thermal protection Evaporator flow switch Remote on/off Pump 1 thermal protection Pump 2 thermal protection Circuit 1 high pressure switch Circuit 2 high pressure switch Phase sequence General enable Compressors enable

Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 Evap. outlet water temperature (blend) Evaporator inlet water temperature Evap. 1 outlet water temperature Evap. 2 outlet water temperature

Setpoint variation (4-20mA 0.0-10V) Dual setpoint Digital outputs

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Solenoid valve 1 Solenoid valve 2 Pump 1 Pump 2 Compressor 1 Compressor 2

Evaporator antifreeze heating element General alarms cumulative Compressor 3 Compressor 4

Analogue outputs Y1 Y2 Y3 Y4 Y5 Y6

79

C0240111-01-06-GB

b ) for centrifuge compressors:


WATER-AIR UNIT with L axial fans
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18

WATER-AIR UNIT with L centrifuge fans


Digital inputs

Circuit 1 fan thermal protection Circuit 2 fan thermal protection Evaporator flow switch Remote on/off Pump 1 thermal switch Pump 2 thermal switch Circuit 1 high pressure switch

Circuit 1 fan thermal protection Circuit 2 fan thermal protection Evaporator flow switch Remote on/off Pump 1 thermal switch Pump 2 thermal switch Circuit 1 high pressure switch

Circuit 2 high pressure switch


Compressors enable

Circuit 2 high pressure switch


Compressors enable

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Evap. outlet water temperature 1 Evap. outlet water temperature 2 Circuit 2 high pressure transducer External air temp./ 2 cond. out / cond. in Setpoint variation (4-20mA 0.0-10V)

Condenser outlet temperature Dual setpoint


Digital outputs Ventilation step 4 circuit 1 Ventilation step 4 circuit 2 Solenoid valve 1 Solenoid valve 2 Pump 1 Pump 2 Compressor 1 Compressor 2 Ventilation step 1 circuit 1 Ventilation step 2 circuit 1 Ventilation step 3 circuit 1 Evaporator antifreeze heating element General alarms cumulative Compressor 3 Compressor 4 Ventilation step 1 circuit 2 Ventilation step 2 circuit 2 Ventilation step 3 circuit 2

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Evap. outlet water temperature 1 Evap. outlet water temperature 2 Circuit 2 high pressure transducer External air temp./ 2 cond. out / cond. in Setpoint variation (4-20mA 0.0-10V)

Condenser outlet temperature Dual setpoint


Digital outputs Ventilation step 4 circuit 1 Ventilation step 4 circuit 2 Solenoid valve 1 Solenoid valve 2 Pump 1 Pump 2 Compressor 1 Compressor 2 Main ventilation step

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Evaporator antifreeze heating element General alarms cumulative Compressor 3 Compressor 4 Ventilation step 1 circuit 2 Ventilation step 2 circuit 2 Ventilation step 3 circuit 2

Analogue outputs Y1 Circuit 1 speed adjustment Y2 Circuit 2 speed adjustment Y3 Y4 Y5 Y6

Analogue outputs Y1 Circuit 1 speed adjustment Y2 Y3 Y4 Y5 Y6

80

C0240111-01-06-GB

L WATER-WATER UNIT L
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18

Evaporator flow switch Remote on/off Pump 1 thermal switch Pump 2 thermal switch Circuit 1 high pressure switch Circuit 2 high pressure switch

Compressors enable

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Evap. outlet water temperature 1 Evap. outlet water temperature 2 Circuit 2 high pressure transducer External air temp./ 2 cond. out / cond. in Setpoint variation (4-20mA 0.0-10V) Condenser outlet temperature Dual setpoint Digital outputs Ventilation step 4 circuit 1 Ventilation step 4 circuit 2 Solenoid valve 1 Solenoid valve 2 Pump 1 Pump 2 Compressor 1 Compressor 2

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Evaporator antifreeze heating element General alarms cumulative Compressor 3 Compressor 4

Analogue outputs Y1 Condensation adjustment Y2 Y3 Y4 Y5 Y6

81

C0240111-01-06-GB

XL HARDWARE:
WATER-AIR UNIT with XL axial fans
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor oil 1 Compressor oil 2 Circuit 1 fan thermal protection Circuit 2 fan thermal protection Evaporator flow switch Remote on/off Phase sequence Compressors enable Circuit 1 high pressure switch Circuit 2 high pressure switch Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Discharge temperature compressor 1 Discharge temperature compressor 2 Circuit 2 high pressure transducer Circuit 1 low pressure transducer Circuit 2 low pressure transducer Digital outputs Compressor 1 start 1 Compressor 1 start 2 Separation stage 1 compressor 1 Compressor 2 start 1 Compressor 2 start 2 Separation stage 1 compressor 2 Oil valve comp. 1/ Compressor 3 start 1 Oil valve comp. 2/ Compressor 3 start 2 Liquid injection 1 / Compressor 4 start 1 Liquid injection 2 / Compressor 4 start 2 Economiser compressor 1 Evaporator antifreeze heating element General alarms cumulative Solenoid valve 1 Solenoid valve 2 Economiser compressor 2 Ventilation step 1 circuit 1 Ventilation step 2 circuit 1 Ventilation step 3 circuit 1 Ventilation step 4 circuit 1 Ventilation step 1 circuit 2 Ventilation step 2 circuit 2 Ventilation step 3 circuit 2 Ventilation step 4 circuit 2 Compressor 1 no-load starting Compressor 2 no-load starting Separation stage 2 compressor 1 Separation stage 2 compressor 2 Drip tray resistor

WATER-AIR UNIT with XL centrifuge fans


ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor oil 1 Compressor oil 2 Fans thermal relay Evaporator flow switch Remote on/off Phase sequence Compressors enable Circuit 1 high pressure switch Circuit 2 high pressure switch Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Discharge temperature compressor 1 Discharge temperature compressor 2 Circuit 2 high pressure transducer Circuit 1 low pressure transducer Circuit 2 low pressure transducer Digital outputs Compressor 1 start 1 Compressor 1 start 2 Separation stage 1 compressor 1 Compressor 2 start 1 Compressor 2 start 2 Separation stage 1 compressor 2 Oil valve comp. 1/ Compressor 3 start 1 Oil valve comp. 2/ Compressor 3 start 2 Liquid injection 1 / Compressor 4 start 1 Liquid injection 2 / Compressor 4 start 2 Economiser compressor 1 Evaporator antifreeze heating element General alarms cumulative Solenoid valve 1 Solenoid valve 2 Economiser compressor 2 Main ventilation step

B1 B2 B3 B4 B5 B6 B7 B8

B1 B2 B3 B4 B5 B6 B7 B8

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29

Ventilation step 1 circuit 2 Ventilation step 2 circuit 2 Ventilation step 3 circuit 2 Ventilation step 4 circuit 2 Compressor 1 no-load starting Compressor 2 no-load starting Separation stage 2 compressor 1 Separation stage 2 compressor 2 Drip tray resistor

Analogue outputs Y1 Circuit 1 speed adjustment Y2 Circuit 2 speed adjustment Y3 Y4

Analogue outputs Y1 Speed adjustment Y2 Y3 Y4

82

C0240111-01-06-GB

XL WATER-WATER UNIT
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor oil 1 Compressor oil 2

XL CONDENSING UNIT
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor oil 1 Compressor oil 2 Circuit 1 fan thermal protection Circuit 2 fan thermal protection Remote on/off Phase sequence Compressors enable Circuit 1 high pressure switch Circuit 2 high pressure switch Analogue inputs Circuit 1 high pressure transducer

Evaporator flow switch Remote on/off Phase sequence Compressors enable Circuit 1 high pressure switch Circuit 2 high pressure switch Analogue inputs Circuit 1 high pressure transducer Evap. outlet water temperature (blend) Evaporator inlet water temperature Discharge temperature compressor 1 Discharge temperature compressor 2 Circuit 2 high pressure transducer Circuit 1 low pressure transducer Circuit 2 low pressure transducer Digital outputs Compressor 1 start 1 Compressor 1 start 2 Separation stage 1 compressor 1 Compressor 2 start 1 Compressor 2 start 2 Separation stage 1 compressor 2 Oil valve comp. 1/ Compressor 3 start 1 Oil valve comp. 2/ Compressor 3 start 2 Liquid injection 1 / Compressor 4 start 1 Liquid injection 2 / Compressor 4 start 2 Economiser compressor 1 Evaporator antifreeze heating element General alarms cumulative Solenoid valve 1 Solenoid valve 2 Economiser compressor 2

B1 B2 B3 B4 B5 B6 B7 B8

B1 B2 B3 B4 B5 B6 B7 B8

Discharge temperature compressor 1 Discharge temperature compressor 2 Circuit 2 high pressure transducer Circuit 1 low pressure transducer Circuit 2 low pressure transducer Digital outputs Compressor 1 start 1 Compressor 1 start 2 Separation stage 1 compressor 1 Compressor 2 start 1 Compressor 2 start 2 Separation stage 1 compressor 2 Oil valve comp. 1/ Compressor 3 start 1 Oil valve comp. 2/ Compressor 3 start 2 Liquid injection 1 / Compressor 4 start 1 Liquid injection 2 / Compressor 4 start 2 Economiser compressor 1 General alarms cumulative Solenoid valve 1 Solenoid valve 2 Economiser compressor 2 Ventilation step 1 circuit 1 Ventilation step 2 circuit 1 Ventilation step 3 circuit 1 Ventilation step 4 circuit 1 Ventilation step 1 circuit 2 Ventilation step 2 circuit 2 Ventilation step 3 circuit 2 Ventilation step 4 circuit 2 Compressor 1 no-load starting Compressor 2 no-load starting Separation stage 2 compressor 1 Separation stage 2 compressor 2

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29

Compressor 1 no-load starting Compressor 2 no-load starting Separation stage 2 compressor 1 Separation stage 2 compressor 2

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29

Analogue outputs Y1 Condensation adjustment Y2 Y3 Y4

Analogue outputs Y1 Circuit 1 speed adjustment Y2 Circuit 2 speed adjustment Y3 Y4

83

C0240111-01-06-GB

XL EVAPORATING UNIT
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Digital inputs Circuit 1 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Circuit 2 low pressure switch Compressor oil 1 Compressor oil 2 Circuit 1 fan thermal protection Circuit 2 fan thermal protection Evaporator flow switch Remote on/off Phase sequence Compressors enable Circuit 1 high pressure switch Circuit 2 high pressure switch Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Evap. outlet water temperature (blend) Evaporator inlet water temperature Discharge temperature compressor 1 Discharge temperature compressor 2

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29

Digital outputs Compressor 1 start 1 Compressor 1 start 2 Separation stage 1 compressor 1 Compressor 2 start 1 Compressor 2 start 2 Separation stage 1 compressor 2 Oil valve comp. 1/ Compressor 3 start 1 Oil valve comp. 2/ Compressor 3 start 2 Liquid injection 1 / Compressor 4 start 1 Liquid injection 2 / Compressor 4 start 2 Economiser compressor 1 Evaporator antifreeze heating element General alarms cumulative Solenoid valve 1 Solenoid valve 2 Economiser compressor 2

Compressor 1 no-load starting Compressor 2 no-load starting Separation stage 2 compressor 1 Separation stage 2 compressor 2

Analogue outputs Y1 Y2 Y3 Y4

84

C0240111-01-06-GB

B HARDWARE (for hermetic compressors)


Water/air chiller with B axial fans
Digital inputs Circuit 1 high pressure switch Circuit 2 high pressure switch Remote on/off Remote Summer/Winter Evaporator flow switch Circuit 1 low pressure switch Circuit 2 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Pump 1 thermal protection Fans thermal relay Phase sequence General enable Pump 2 thermal protection Compressors enable Analogue inputs Circuit 1 high pressure transducer Circuit 2 high pressure transducer Evaporator inlet water temperature Evaporator outlet 1 water temperature Evaporator outlet 2 water temperature External temperature Setpoint variation (4-20mA) Digital outputs Evaporator antifreeze heating element Circuit 1 cycle reversal valve Circuit 2 cycle reversal valve Pump 1 Compressor 1 Compressor 2 General alarms cumulative Pump 2 Ventilation step 1 Ventilation step 2 Ventilation step 3

Water/air chiller with B centrifuge fans


Digital inputs Circuit 1 high pressure switch Circuit 2 high pressure switch Remote on/off Remote Summer/Winter Evaporator flow switch Circuit 1 low pressure switch Circuit 2 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Pump 1 thermal protection Fans thermal relay Phase sequence General enable Pump 2 thermal protection Compressors enable Analogue inputs Circuit 1 high pressure transducer Circuit 2 high pressure transducer Evaporator inlet water temperature Evaporator outlet 1 water temperature Evaporator outlet 2 water temperature External temperature Setpoint variation (4-20mA) Digital outputs Evaporator antifreeze heating element Circuit 1 cycle reversal valve Circuit 2 cycle reversal valve Main fan step Pump 1 Compressor 1 Compressor 2 General alarms cumulative Pump 2 Ventilation step 1 Ventilation step 2 Ventilation step 3

ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15

ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15

B1 B2 B3 B4 B5 B6 B7 B8

B1 B2 B3 B4 B5 B6 B7 B8

NC1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12

NC1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12

Analogue outputs Y1 Circuit 1 speed adjustment (PWM) Y2 Circuit 2 speed adjustment (PWM)

Analogue outputs Y1 Speed adjustment (PwM) Y2

85

C0240111-01-06-GB

B WATER-WATER UNIT
ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 Digital inputs Circuit 1 high pressure switch Circuit 2 high pressure switch Remote on/off Remote Summer/Winter Evaporator flow switch Circuit 1 low pressure switch Circuit 2 low pressure switch Compressor 1 thermal protection Compressor 2 thermal protection Pump 1 thermal protection Phase sequence General enable Pump 2 thermal protection Compressors enable Analogue inputs Circuit 1 high pressure transducer Circuit 2 high pressure transducer Evaporator inlet water temperature Evaporator outlet 1 water temperature Evaporator outlet 2 water temperature Condenser outlet water temperature Outlet 2 water temp. / cond. inlet Setpoint variation (4-20mA) Digital outputs Evaporator antifreeze heating element Cycle reversal valve

B1 B2 B3 B4 B5 B6 B7 B8

NC1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12

Pump 1 Compressor 1 Compressor 2 General alarms cumulative Pump 2

Analogue outputs Y1 Condensation adjustment (PUM) Y2

86

C0240111-01-06-GB

EXPANSIONS a) for hermetic compressors


E expansion for chiller with recovery.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 Digital outputs Recovery valve circuit 1 Recovery valve circuit 2 Expansion "E" address 1 Digital inputs Recovery flow switch Recovery remote enable

ID1 ID2 ID3 ID4

Analogue inputs Circuit 1 liquid temperature Circuit 2 liquid temperature Recovery inlet temperature Recovery outlet temperature Digital outputs Subcooling circuit 1-1 Subcooling circuit 1-2 Subcooling circuit 2-1 Subcooling circuit 2-2 Analogue outputs

B1 B2 B3 B4

NO1 NO2 NO3 NO4

Y1

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Analogue outputs Y1 Y2 Y3 Y4 Y5 Y6

87

C0240111-01-06-GB

M expansion for hermetic compressors. Air-cooled polyvalent units and heat pumps with total recovery.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Expansion "M" address 2 Digital inputs Recovery flow switch ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14

Not used Analogue inputs

Analogue inputs Circuit 1 low pressure transducer Circuit 2 low pressure transducer Recovery inlet temperature Recovery outlet temperature

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 Digital outputs Not used Not used

B1 B2 B3 B4 B5 B6 B7 B8

Digital outputs V V V V V 1-1 1-2 1-3 1-4 1-5 NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 Analogue outputs Y1 Y2 Y3 Y4

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

V V V V V

2-1 2-2 2-3 2-4 2-5

Analogue outputs Y1 Y2 Y3 Y4 Y5 Y6

88

C0240111-01-06-GB

M expansion for hermetic compressors. Water-cooled polyvalent units and heat pumps with total recovery.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 Digital outputs Not used Not used Expansion "M" address 2 Digital inputs Recovery flow switch Condenser flow switch Condenser pump thermal protection ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14

Analogue inputs Circuit 1 low pressure transducer Circuit 2 low pressure transducer Recovery inlet temperature Recovery outlet temperature Condenser inlet temperature (if 2 cond.)

B1 B2 B3 B4 B5 B6 B7 B8

Digital outputs V V V V V 1-1 1-2 1-3 1-4 1-5 NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Condenser pump V 2-1 V 2-2 V 2-3 V 2-4 V 2-5

Analogue outputs Y1 Y2 Y3 Y4

Analogue outputs Y1 Y2 Y3 Y4 Y5 Y6

89

C0240111-01-06-GB

E expansion for hermetic compressors. Chiller with freecooling.


Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 Digital outputs Freecooling valve Off Freecooling valve On Expansion "E" address 3 Digital inputs Glycol pump thermal protection

ID1 ID2 ID3 ID4

Analogue inputs Circuit 1 low pressure transducer Circuit 2 low pressure transducer Freecooling inlet temperature

B1 B2 B3 B4

Hp Hp Hp Hp

Digital outputs relay circuit 1-1 relay circuit 1-2 relay circuit 2-1 relay circuit 2-2

NO1 NO2 NO3 NO4

Analogue outputs Freecooling modulating valve

Y1

NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18

Analogue outputs Y1 Y2 Y3 Y4 Y5 Y6

90

C0240111-01-06-GB

E expansion for hermetic compressors. Units with more than 4 compressors.


Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 Analogue outputs Y1 Y2 Y3 Y4 Y5 Y6 Expansion "E" address 4 Digital inputs Compressor 5 thermal protection Compressor 6 thermal protection Compressor 7 thermal protection Compressor 8 thermal protection Analogue inputs Step Step Step Step 5 6 7 8 B1 B2 B3 B4

ID1 ID2 ID3 ID4

Digital outputs Compressor 5 Compressor 6 Compressor 7 Compressor 8 Analogue outputs

NO1 NO2 NO3 NO4

Y1

91

C0240111-01-06-GB

b) for semi-hermetic compressors


E expansions for chillers with heat pumps or two pumps.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Analogue outputs Y1 Y2 Y3 Y4 Expansion "E" address 5 Digital inputs Remote Summer/Winter Pump 1 thermal protection Pump 2 thermal protection Analogue inputs Evap. 1 outlet water temperature Evap. 2 outlet water temperature External temp. / Cond. 2 outlet water temp. Condenser outlet water temperature Digital outputs Rev. cycle valve 1/recovery 1/freecooling OFF Rev. cycle valve 2/recovery 2/freecooling ON Pump 1 Pump 2 Analogue outputs Y1

ID1 ID2 ID3 ID4

B1 B2 B3 B4

NO1 NO2 NO3 NO4

92

C0240111-01-06-GB

E expansions for chillers with setpoint variation or secondary setpoint.


Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Analogue outputs Y1 Y2 Y3 Y4 Expansion "E" address 3 Digital inputs Glycol pump thermal protection Dual setpoint

ID1 ID2 ID3 ID4

Analogue inputs Setpoint variation (4-20mA) Recovery setpoint variation (4-20mA) Freecooling inlet temperature

B1 B2 B3 B4

Hp Hp Hp Hp

Digital outputs relay circuit 1-1 relay circuit 1-2 relay circuit 2-1 relay circuit 2-2

NO1 NO2 NO3 NO4

Analogue outputs Freecooling modulating valve

Y1

93

C0240111-01-06-GB

E expansions for chillers with recovery.


Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Analogue outputs Y1 Y2 Y3 Y4 Expansion "E" address 1 Digital inputs Recovery flow switch Recovery remote enable

ID1 ID2 ID3 ID4

Analogue inputs Circuit 1 liquid temperature Circuit 2 liquid temperature Recovery inlet temperature Recovery outlet temperature Digital outputs Subcooling circuit 1-1 Subcooling circuit 1-2 Subcooling circuit 2-1 Subcooling circuit 2-2 Analogue outputs

B1 B2 B3 B4

NO1 NO2 NO3 NO4

Y1

Expansion "E" address 5 Digital inputs Remote Summer/Winter Pump 1 thermal protection Pump 2 thermal protection Analogue inputs Evap. 1 outlet water temperature Evap. 2 outlet water temperature External temp. / Cond. 2 outlet water temp. Condenser outlet water temperature Digital outputs Rev. cycle valve 1/recovery 1/freecooling OFF Rev. cycle valve 2/recovery 2/freecooling ON Pump 1 Pump 2 Analogue outputs

ID1 ID2 ID3 ID4

B1 B2 B3 B4

NO1 NO2 NO3 NO4

Y1

94

C0240111-01-06-GB

M expansion for semi-hermetic compressors. Air-cooled polyvalent units and heat pumps with total recovery.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Analogue outputs Y1 Y2 Y3 Y4 V V V V V 1-1 1-2 1-3 1-4 1-5 Expansion "M" address 2 Digital inputs Recovery flow switch ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14

Analogue inputs Evap. 1 outlet water temperature Evap. 2 outlet water temperature Recovery inlet temperature Recovery outlet temperature

B1 B2 B3 B4 B5 B6 B7 B8

Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 Analogue outputs Y1 Y2 Y3 Y4

V V V V V

2-1 2-2 2-3 2-4 2-5

95

C0240111-01-06-GB

M expansion for semi-hermetic compressors. Water-cooled polyvalent units and heat pumps with total recovery.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Analogue outputs Y1 Y2 Y3 Y4 V V V V V 1-1 1-2 1-3 1-4 1-5 Expansion "M" address 2 Digital inputs Recovery flow switch Condenser flow switch Condenser pump thermal protection ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14

Analogue inputs Evap. 1 outlet water temperature Evap. 2 outlet water temperature Recovery inlet temperature Recovery outlet temperature Condenser inlet temperature (if 2 cond.) Condenser outlet water temp. Condenser 2 outlet water temp.

B1 B2 B3 B4 B5 B6 B7 B8

Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13

Condenser pump V 2-1 V 2-2 V 2-3 V 2-4 V 2-5

Analogue outputs Y1 Y2 Y3 Y4

96

C0240111-01-06-GB

E expansions for semi-hermetic compressors. Chiller with freecooling.


Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Analogue outputs Y1 Y2 Y3 Y4 Expansion "E" address 3 Digital inputs Glycol pump thermal protection Dual setpoint

ID1 ID2 ID3 ID4

Analogue inputs Setpoint variation (4-20mA) Recovery setpoint variation (4-20mA) Freecooling inlet temperature

B1 B2 B3 B4

Hp Hp Hp Hp

Digital outputs relay circuit 1-1 relay circuit 1-2 relay circuit 2-1 relay circuit 2-2

NO1 NO2 NO3 NO4

Analogue outputs Freecooling modulating valve

Y1

Expansion "E" address 5 Digital inputs Remote Summer/Winter Pump 1 thermal protection Pump 2 thermal protection Analogue inputs Evap. 1 outlet water temperature Evap. 2 outlet water temperature External temp. / Cond. 2 outlet water temp. Condenser outlet water temperature Digital outputs Rev. cycle valve 1/recovery 1/freecooling OFF Rev. cycle valve 2/recovery 2/freecooling ON Pump 1 Pump 2 Analogue outputs

ID1 ID2 ID3 ID4

B1 B2 B3 B4

NO1 NO2 NO3 NO4

Y1

97

C0240111-01-06-GB

E expansions for semi-hermetic compressors. Condensing unit or for alternative compressors. Unit with four compressors on two circuits.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Analogue outputs Y1 Y2 Y3 Y4 Expansion "E" address 4 Digital inputs Compressor 3 thermal protection Compressor 4 thermal protection Compressor oil 3 Compressor oil 4 Analogue inputs Step Step Step Step 1 2 3 4 B1 B2 B3 B4 ID1 ID2 ID3 ID4

Digital outputs Separation stage 1 compressor Separation stage 2 compressor Separation stage 1 compressor Separation stage 2 compressor Analogue outputs

3 3 4 4

NO1 NO2 NO3 NO4

Y1

98

C0240111-01-06-GB

b ) for centrifuge compressors:


Expansion E Chiller with bypass valves.
Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 ID18 Analogue inputs B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 Analogue outputs Y1 Y2 Y3 Y4 Y5 Y6 Expansion "E" address 2 Digital inputs ID1 ID2 ID3 ID4 Analogue inputs B1 B2 B3 B4 Digital outputs Compressor 5 Compressor 6 Injection 5 Injection 6 Analogue outputs Y1 Expansion "E" address 1 Digital inputs ID1 ID2 ID3 ID4 Analogue inputs B1 B2 B3 B4 Digital outputs Injection 1 Injection 2 Injection 3 Injection 4 Analogue outputs Y1

NO1 NO2 NO3 NO4

NO1 NO2 NO3 NO4

99

C0240111-01-06-GB

SYMBOLS The following symbols are used in the W3000 and W3000 compact masks. Symbol Off Ch nr Ch Ch+R Hp nr Hp R nr R Pd Defr Drip Bands Fcool Limit Description Unit/circuit off Chiller circuit not demanded by thermoregulator Chiller circuit demanded by thermoregulator Chiller circuit plus recovery demanded by thermoregulator Heat pump circuit not demanded by thermoregulator Heat pump circuit demanded by thermoregulator Recovery only circuit not demanded by thermoregulator Recovery only circuit demanded by thermoregulator Circuit in pump-down mode Circuit in defrost mode Circuit in drip mode Time bands active Unit in free-cooling mode Power limit active (demand limit)

CA10

100

Вам также может понравиться