TECHNICAL SUPPORT North America Tel: (888) Mircom5 (888) 647-2665 International Tel: (905) 647-2665 Canada - Head Office 25 Interchange Way, Vaughan, Ontario, L4K 5W3 Tel: (905) 660-4655, Fax: (905) 660-4113 USA 4575 Witmer Industrial Estates, Niagara Falls, NY 14305 Tel Toll Free: (888) 660-4655, Fax Toll Free: (888) 660-4113 Website: www.mircom.com
Warning
CAUTION: Do not use looped wire under terminal L2. Break wire run to provide supervision of connections.
Technical Data
Detector model # Detector type MHD-65-135, MHD-65-200 Heat Rate-of-Rise/Fixed Temperature 933V dc 17mA at 9V, 52mA at 24V 0mA 4050A at 9V, 4555A at 24V MHD-65-135 MHD-65-200 Control panel Test method Installation temperature Ordinary (135F/57C) Intermediate (200F/93C) UL/ULC Listed Compatible Control Panel Magnet or hair dryer Minimum 32F (0C) Maximum at least 20F (11C) below rating Magnet or Gemini 501 Minimum 32F (0C) Maximum 158F (70C) Magnet or Gemini 501 Minimum 32F (0C) Maximum 140F (60C) MID-65I Ionization 933V dc 17mA at 9V, 52mA at 24V 0mA 4050A at 9V, 4555A at 24V N/A MPD-65P Photoelectric 933V dc 17mA at 9V, 52mA at 24V 0mA 4050A at 9V, 4555A at 24V N/A
Remote LED
Working voltage Maximum alarm current Surge current Supervisory current Heat element rating
L1 IN
L1 IN
L1 IN
L1OUT
SHIELD
L1OUT L2
SHIELD
L1OUT End-of-line
device
L2
SHIELD
L2
Remote LED
L1 IN
L1 IN
L1OUT L2
SHIELD
L1OUT L2
End-of-line device
SHIELD
L2
Place the magnet near the detector on the OPPOSITE side of the LED.
Fig 2. Wiring diagram of MIR-65 Series zone with common remote indicator
LED
The above instructions cover the following base model: MSB-65B 6 E-Z Fit base