Вы находитесь на странице: 1из 3

SUSPENSION TOWER :: DIRN.

TYPE OF LOAD RELIABILITY Climatic Load Condition : I 100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind. Climatic Load Condition : II 36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind. Normal Condition SECURITY Broken Wire Condition Normal Condition SAFETY Broken Wire Condition

WIND TRANS. TENSION

Nil Component of Tensions at 320C + Nil Wind

Nil Component of Tensions for 50% conductor tension and 100% of ground wire tension at 320C + Nil Wind (i) Weight of all Components.

Nil Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all components. Design Weight Span : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.

Nil Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all components. Design Weight Span : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.

VERT.

(i) Weight of all components. Design Weight Span : 100% (ii) Weight of Structure.

(i) Weight of all components. Design Weight Span : 100% (ii) Weight of Structure.

Design Weight Span : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure.

WIND LONG. TENSION Nil Nil 50% of conductor tension and 100% of Ground Wire tension at 320C + Nil Wind

Nil

Per Sub Conductor 1000Kg and Ground Wire 500Kg

TENSION TOWER :: TYPE OF DIRN. LOAD

RELIABILITY Climatic Load Condition : I Climatic Load Condition : II Normal Condition Climatic Load Climatic Load Condition : I Condition : II 100% Wind on Structure and all other components.

SECURITY Broken Wire Condition Climatic Load Climatic Load Condition : I Condition : II Wind Span as : Broken condition : 60% Intact condition : 100% 100% Wind on 36% Wind on Structure and all Structure and all other components. other components. Component of Tensions at 320C + 100% Wind. Component of Tensions at 40C + 36% Wind Normal Condition

SAFETY Broken Wire Condition

WIND TRANS.

100% Wind on Structure and all other components.

36% Wind on Structure and all other components.

36% Wind on Structure and all other components.

Nil

Nil

TENSION

Component of Tensions at 320C + 100% Wind.

Component of Tensions at 40C + 36% Wind.

Component of Tensions at 320C + 100% Wind.

Component of Tensions at 40C + 36% Wind

Component of Tensions at 320C + Nil Wind

Load Case 23 : Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all Strings. Design Weight Span :

(i) Weight of all Strings. VERT. Design Weight Span : 100% (ii) Weight of Structure.

(i) Weight of all Strings . Design Weight Span : 100% (ii) Weight of Structure.

(i) Weight of all Strings. Design Weight Span : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. 100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind. 36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind

(i) 2 * Weight of Strings. Design Weight Span : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.

Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.

WIND LONG. TENSION Nil Nil

Nil for tension tower

2 times 50% sagging tension of conductors under stringing and 1.5 times for conductors already stringed at 320C + Nil Wind

`DEAD END TOWER ::

DIRN.

TYPE OF LOAD

RELIABILITY Climatic Load Condition : I Climatic Load Condition : II Normal Condition Climatic Load Condition : I 100% Wind on Structure and all other components.

SECURITY

SAFETY

Climatic Load Condition : II 36% Wind on Structure and all other components.

Broken Wire Condition Wind Span as : Broken condition : 60% Intact condition : 100% 100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind. 36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind

Normal Condition

Broken Wire Condition

WIND TRANS.

100% Wind on Structure and all other components.

36% Wind on Structure and all other components.

Nil

Nil

TENSION

Component of Tensions at 320C + 100% Wind.

Component of Tensions at 40C + 36% Wind.

Component of Tensions at 320C + 100% Wind.

Component of Tensions at 40C + 36% Wind

Component of Tensions at 320C + Nil Wind

Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all Strings Design Weight Span as : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.

VERT.

(i) Weight of all Strings. Design Weight Span : 100% (ii) Weight of Structure.

(i) Weight of Strings etc. Design Weight Span : 100% (ii) Weight of Structure.

(i) Weight of all Strings etc. Design Weight Span as : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure.

(i) 2 * Weight of all Strings Design Weight Span : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.

WIND LONG. TENSION

100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind.

36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind

100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind.

36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind Nil Tensions at 320C + No Wind Nil