Test Switches
Trainer:
Enables easy, reliable, and quick test with currents and voltages to verify correct A/D and calculation. Interrupts the TRIP and CLOSE commands to the circuit breaker Visual- and electrical indication of test position Pre-assembled connection to the portable test set Design and connection matches all digital protection devices
The right test switch for application to every protection device Feeder protection with starpoint inside the test switch Feeder protection with open star point in the test switch Test switch for transformer differential protection Test switch design with additional contacts and functions
Test
X2
1 2 3 4
X2
Test Switch with Open Starpoint in the Current Measuring Circuit (Operation) Prfschalter mit aufgelstem Sternpunkt im Strommekreis (Betrieb)
L1 L2 L3
X2
L1
To other protect. relays
L2 L3 N
Zu weiteren Schutzgerten
Test Switch with Open Starpoint in the Current Measuring Prfschalter mit Circuit (Test) aufgelstem Sternpunkt im Strommekreis (Test)
L1 L2 L3
L1 L2
To other prot. relays Zu weiteren
Schutzgerten
L3 N
Interruption of TRIP / / EIN bei Prfung mit Prfschalter Unterbrechung AUS CLOSE During Test via Test Switch
indication Protective relay Trip Trip Trip
Operation
CB Close
Test indication
Lock-Out Function
The TIRP command contact remains closed - the CB closing circuit remains open until reset It is used to: - output the TRIP command continuously - disable the CLOSE command Only upon acknowledgement is the latched command reset. Latching takes place: - in the SW of the protection device ( SIPROTEC 4) - via separated lock-out relays which are mechanically linked. Reset: electrically or hand reset
s
LOCK-OUT RELAY Lock Out Relais
L+
1 L+
CB LS EIN Close
Reset
Reset
R S
L-
Close
Kontakte dargestellt Contacts shown at bei Stellung Reset reset position
CB LS Trip AUS
LS CB EIN Close
Trip-circuit Supervision
The trip circuit is monitored as to: - Presence of the control voltage - Interruption in the wiring - Interruption in the trip coil of the CB Supervision takes place: - in the protection device via BI ( advantage of self-monitoring and oscillographic record with time stamp) - with separated special monitoring relays The trip-circuit supervision is possible for phase-selective tripping and / or three-phase tripping
Trip-circuit Supervision in the Protection Device zwei Binreingngen Auslsekreisberwachung im Schutzgert mit with Two Binary Inputs
L+
VCTRL USt
~2 m A
SIPROTEC
L+
VCTRL USt
SIPROTEC
protection AUS TRIP Schutz
BI1 BE1
BI1 BE1
BI2 BE2
BI2 BE2
indication Meldung
Meldung indication
HIKO1 Aux.
HIKO2 Aux.
Cont.2
LS CB
Cont.1
CBTC LSS
Aux. HIKO1
Trip AUS
L-
VCTRL USt
SIPROTEC
BI1 BE1
indication Meldung
indication Meldung
R
Close EIN Aux. HIKO1 Cont.1 CB LS Close EIN Trip AUS Aux. HIKO2 Cont.2
Trip AUS
R
Aux. HIKO2 Cont.2
LSS CBTC
LS CB AUS Trip
CBTC LSS
L-
L-
indication Meldung
LS CB EIN Close L-