Analysis as per seismic forces acting in horizontal direction and vertical force acting in upward direction:Load combinations considered

for design are as per CL. 9.3 of ACI-318 as follows:1. 0.9 D + 1.4 E 2. 1.2 D + 1.4 E By engineering judgement 0.9D + 1.4E is considered as this is critical for anchor bolt design. Actual unfactored Load type Laod factor Design factored forces forces 297000 Dead load = 330000 kg * 0.9 kg *The values considered in this document are taken as Fv = 198000 kg * 1.4 277200 kg per the document submitted by you. Fh = 198000 kg * 1.4 277200 kg Mx = 42428760 kg-m * 1.4 59400264 kg-m Mz = 4794240 kg-m * 1.4 6711936 kg-m Zxx = Zzz= 39192 cm * 40 8.17 (M36) cm2
2 3 3 52335.8 cm * Number of anchor bolts =

Effective area of anchor bolt = Considering 30% reduction of eff. Area of anchor bolt= Net vertical load = Maximum tension force =

( As per table 7 of IS-1367 for M36 bolt )

cm 5.61 ( As per clause D.1 of ACI-318 ) 297000 277200 = 19800 kg 19800 - 59400264 6711936 40 * 5.61 39192 52335.8 2 kg / cm = 1555.6 = 85.52 kN / bolt 392020 1746.97 7840.00 0.70 kg kg / cm2 kg / cm
2

Maximum shear force = Shear stress per anchor bolt = Allowable tensile stress on bolt = Strength reduction factor for anchor bolt in tension= Allowable shear stress on bolt = Strength reduction factor for anchor bolt in shear= Combined check =

( As per table 3 of IS-1367 for M36 bolt ) ( As per Cl D.4.5 of ACI-318 )

kg / cm2 5255.00 ( As pre Cl 6.2 of IS-12427 : 2001 ) 0.65 ( As per Cl D.4.5 of ACI-318 ) 1555.60 + 1746.97 = 0.79 < 1.2 ( OK as per D.7.3 of ACI-318 )

5488.00

3415.75

Embedded length of anchor bolt (hef) = 460 mm After this , the concrete capacity has to be checked for the anchor bolt's tensile force as per Appendix-D of ACI-318. Note : M25 grade of concrete is considered and edge distance of 500mm is considered for design. Accordingly, following checks has to be performed by considering strength load combinations:1. Concrete breakout check in tension ( refer CL. D.5.2 for group of anchor bolts )

Ca1 = 500 mm ; S1 = 108 mm (3d ) Anc = (500+108+690)*(690+690)


2 = 1791240 mm Anco= (690+108+690)*(690+690) 2 = 2053440 mm

= 1.0

( refer Cl. D.5.2.4 )

( refer Cl . D.5.2.5 ) = 0.92

1.25

Cac = 2.5 hef =

0.434783

Kc = 10 for cast in anchor bolts = 1 (Cl. 8.6.2 ACI 318 ) fc = 25 Nb = 493295 = 0.65 Ncbg = 215153.6 N Ncbg= 139.8498 kN > ( 2 * 85.52 )= 171.0476 kN ( Not OK ) Number of 12 dia rebars required to transfer balance of tension force = (171-140)/(3.14*6*6*0.9*415) = 1 Accordingly, provide extra steel reinforcement of 12 tor @ 200 mm c/c. 2. Concrete pullout check in tension. ( refer CL. D.5.3 ) (for one anchor bolt ) Where, ( refer Cl. 5.3.6 )

Abrg = Np = = Npn =

2 561 mm

112200

0.65 157080 N = 102.102 kN (Hence OK ) 3. Side face blowout strength of anchor bolt in tension This check is not requried if edge distance of 500mm is provided. As per Cl D.5.4.1 of ACI-318, this check is not required, if hef < 2.5 Ca1. 4. Concrete breakout check in shear ( refer CL. D.6.2 for group of anchor bolts )