DESCRIPTION
The 8 Channel EDIO Module is specially designed to
expand the Input and Output capability of the Det-
Tronics Eagle Quantum Premier™ System.
VIBRATION—
FEATURES FM 3260-2000 (clause 4.9).
1.2 2 90-1189
1.42 2.5
(3.6) (6.4)
1 6 1 6 1 6 1 6
5.02
(12.7)
4.6
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 (11.7)
4.6
A B C A B C A B C A B C A B C A B C A B C A B C (11.7) A B C A B C A B C A B C A B C A B C A B C A B C
5.35
5.35 1.66 (13.6) 1.9
A2288 (13.6) (4.2) (4.8)
1.2 3 90-1189
SIGNALING OUTPUT, TYPES— INSTALLATION
Configurable for device applications:
– Continuous All electrical connections are made to the field wiring
– 60 beats per minute connectors furnished with the module. Refer to
– 120 beats per minute Figure 2 for identification of module wiring terminals.
– Temporal Pattern.
Note: All eight channels are synchronized when Connector P1, Terminals 1 to 6
programmed as a signaling output. 24 Vdc Power Input
Connect the module power supply to terminals 1 and
SUPERVISED OUTPUT RATING— Releasing Type 2. If additional terminals are required for powering
other devices, these devices should be connected to
MAXIMUM OUTPUT CURRENT (Per Channel)— terminals 4 and 5. Shields are to be connected to
2 amperes at 30 Vdc maximum. terminals 3 and 6 — chassis (earth) ground terminals.
Automatic short circuit protection provided. Terminals are rated for 10 amperes. Use both sets of
Instantaneous short circuit current < 15 amperes. input terminals in parallel if total output current can
exceed 10 amperes.
SUPERVISORY CURRENT (Per Channel)—
Monitored at 1.3 mA ±0.2 mA. Connector P2, Terminals 1 to 6
LON/SLC Signaling Circuit Terminals
RESPONSE TIME— Be sure to observe polarity when wiring the LON/SLC.
Output actuates in <0.15 second after acknowledging shield connection — terminals 3 and 6.
an alarm command message. 1 — "A" side of signaling circuit for COM 1
2 — "B" side of signaling circuit for COM 1
RELEASING OUTPUT, TYPES— 4 — "A" side of signaling circuit for COM 2
Configurable for device applications: 5 — "B" side of signaling circuit for COM 2
– Continuous
– Timed. Connector P3, Terminals 1 to 12
Terminals A,B & C
For Class A wiring on outputs, configure adjacent Channels 1 to 4 Input / Output Terminals
channels for Class A wiring and connect both channels Refer to individual wiring configurations for terminal
to single output device(s). descriptions. Only channel 1 is shown in each
diagram. The information is typical for channels 2-8.
EQ3730EDIO
COMMON C 24
IN–/OUT+ B 23 CHANNEL 8
SHLD 6 COM 2 SHLD + SUPPLY A 22
LON FROM CLASS A
B 5 COM 2 B
PREVIOUS DEVICE CHANNEL 7
A 4 COM 2 A COMMON C 21
1.2 4 90-1189
Connector P4, Terminals 13 to 24 COMMON C 3
Terminals A, B & C
Channels 5 to 8 Input / Output Terminals
Refer to individual wiring configurations for terminal IN– / OUT+ B 2
descriptions. Only channel 1 is shown in each
diagram. The information is typical for channels 2-8. + SUPPLY A 1
C2090
EOL
The input to the EDIO consists of one or more RESISTOR
10 K Ω
normally open or normally closed switches. An EOL IN– / OUT+ B 2
resistor is not required.
+ SUPPLY A 1
C2091
+ SUPPLY A 1
Supervised Input Open and Short Circuit Supervision B2291
Connect external system wiring to the appropriate Figure 5—Supervised Input Configuration – Class A, Style D
terminals on the terminal block. For Class B, Style C
wiring, see Figure 6. For Class A, Style E wiring, see
Figure 7. Note that two channels are used for one COMMON C 3
INLINE
circuit. RESISTOR EOL
3.3 K Ω RESISTOR
10 K Ω
ohm, 1/4 watt resistor in series with each switch. Figure 6—Supervised Input Configuration (Opens and Shorts) –
Class B, Style C
NOTE
If using more than one switch, the first active
condition (switch closed) must be latched. Any COMMON C 6
The initiating device circuit(s) for use with the deluge and EOL
RESISTOR
pre-action system configuration must use Class A wiring 10 K Ω
or be wired within 20 feet and in conduit from the EDIO. IN– / OUT+ B 2
See Table 2 for a list of FM Approved solenoids for
+ SUPPLY A 1
deluge and pre-action applications. B2292
1.2 5 90-1189
Two-Wire Smoke Detectors
IMPORTANT
No more than 15 devices can be connected per
channel.
IN IN IN
+ SUPPLY A 1 L1 -R L1 -R L1 -R
EOL
RESISTOR
5KΩ
L1 L2 L1 L2 L1 L2
OUT OUT OUT
A2283
IN–/OUT+ B 2
+ SUPPLY A 1
1 2 1 2 1 2
EOL
RESISTOR
3 3 5KΩ 3
7 6 7 6 7 6
A2284
IN–/OUT+ B 2
Unsupervised Output
Connect external system wiring to the appropriate
COMMON C 3
terminals on the terminal block. See Figure 10.
1.2 6 90-1189
Supervised Output—
Notification Supervised for Open & Short Circuits COMMON C 3
Connect external system wiring to the appropriate
EOL
terminals on the terminal block. For Class B, Style Y RESISTOR
10 K Ω
wiring, refer to Figure 11.
IN– / OUT+ B 2
The output of the EDIO module supervises the Figure 11—Supervised Output Configuration (Notification)—
notification circuit by reversing the polarity of the Class B, Style Y
monitoring circuit. Polarity must be observed when
connecting the notification device. It is essential to
utilize a notification device approved for fire alarm COMMON C 6
COMMON C 3
No connection should be made to “+ Supply”
EOL
terminal. RESISTOR
10 K Ω
IN– / OUT+ B 2
Each output channel is individually activated for
response pattern: + SUPPLY A 1
A2285
Supervised Output—
IN– / OUT+ B 2
Agent Release
Connect external system wiring to the appropriate + SUPPLY A 1 NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
TO BE INSTALLED ON THE FIELD DEVICE.
terminals on the terminal block. For Class B wiring, CIRCUIT PROTECTION IS PROVIDED
WITHIN THE DCIO MODULE.
refer to Figure 13.
Figure 13—Supervised Output Configuration (Agent Release)
For Class A wiring, refer to Figure 14. Note that two
channels are used for one output circuit. Trouble
indication is provided for any open wire and the
COMMON C 6
output can still be activated with a single open wire.
+ SUPPLY A 4
No connection should be made to “+ Supply”
terminal. COMMON C 3
The output of the EDIO module supervises the NOTE: SHUNT/FLYBACK DIODES DO
NOT NEED TO BE INSTALLED
releasing circuit via the coil of the releasing solenoid. ON THE FIELD DEVICE.
CIRCUIT PROTECTION IS
IN– / OUT+ B 2
It is essential to utilize a releasing device approved PROVIDED WITHIN THE
DCIO MODULE.
for use with this output module. This type of output + SUPPLY A 1
does not require the use of EOL resistors or diodes to A2286
1.2 7 90-1189
The output can be configured for latching, ORDERING INFORMATION
continuous, supervisory, trouble or timed response.
When ordering, please specify:
To ensure adequate operating voltage for the output
EQ3730EDIO 8 Channel Enhanced Discrete
device, the maximum wiring length from the power
Input/Output Module
source to the output device must not exceed the
values shown in Table 1 for automatic release
Options Panel Mount
applications. (For solenoids, this wire length includes
DIN Rail Mount
both the wiring from the power supply to the EDIO
EOL Resistors
module and the wiring from the module to the
Inline Resistors
solenoid.)
For additional information or for assistance in
NOTE
designing a system to meet the needs of a specific
Squibs are not compatible with this output. If
application, please contact:
squib actuation is required, use EQ2500ARM
release module.
Detector Electronics Corporation
6901 West 110th Street
Supervised Output for Deluge and Pre-action
Minneapolis, Minnesota 55438 USA
To ensure proper operating voltage, the input voltage
Operator: (952) 941-5665 or (800) 765-FIRE
to the EDIO must be in the range from 21 to 30 vdc
Customer Service: (952) 946-6491
and the maximum wiring length must not exceed the
Fax: (952) 829-8750
values shown in Table 2 for deluge and pre-action
Web site: www.det-tronics.com
applications. Per FM Approval requirements, the
E-mail: detronics@detronics.com
secondary power must provide capacity for a 90 hour
minimum standby operation followed by a minimum of
10 minutes of releasing and alarm operation. The Table 1—Maximum Wire Length for Releasing Applications
initiating device circuit(s) for use with the deluge
and pre-action system configuration must use Device Maximum Wire Length in Feet
Class A wiring or be wired in conduit within 20 feet
12 AWG 14 AWG 16 AWG 18 AWG
from the EDIO.
890181* 150 100 60
899175* 150 100 60
895630-000* 150 100 60
897494* 190 120 75
486500-001* 1500 1000 600 400
31-199932-004* 150 100 60
2 Amp Load 190 120 75
*Fenwal Solenoid
Table 2—Maximum Wire Length for FM Approved Solenoids for Deluge and Pre-Action Applications
STE
RED BY UL AN
D
Detector Electronics Corporation
GI B
RE
SI
RM
IR M
FI
ST S
E RE D F
I
T E ED
I
R
N
O
82
6
.A
230 25
5 • N O.
http://www.det-tronics.com • E-mail: detronics@detronics.com Specifications subject to change without notice.