ELECTRICAL MACHINES
Learning Outcomes
At the end of the lecture, student should to: Understand the principle and the nature of 3 phase transformer. transformer. Perform an analysis on 3 phase transformers which their principles are basic to the understanding of electrical machines. machines
Introduction
A 3 transformer is essentially 3 single phase transformer wound on a common core. core. The geometry of the core is such that the fluxes of the phases share common paths as a result, the volume of iron in 3 transformer is less than the volume of iron of 3 single phase transformer of the same rating. rating. reduced Hence, the cost is reduced. any phase of a 3 transformer behaves exactly like a single phase transformer. In 3 transformer, the primary and secondary windings can be connected either in Y or . The possible connection are: Primary Secondary Y Y Y Y
Transformer Construction
3 Single Phase Transformer
R Y B Np1 Ns1
Used a lot in older transformer adv:- each unit in the bank can be replaced individually
Np3 Ns3
Transformer Construction
3 Transformer wound a single three legged iron core
Np1 Np2 Np3
more preferred in practice adv:- lighter, smaller, cheaper, slightly more efficient iron core must be laminated : to reduce eddy current loss iron must be made of soft iron : to reduce hysteresis loss cooling the transformer :- use fan or heat sink
Ns1
Ns2
Ns2
soft iron must be add with 3-5% silicon :- to increase the saturation flux in the iron * The amount of silicon must not too high otherwise the iron will be brittle clamp the lamination :- to reduce the humming noise
IL2 V1 V2
A'
VL1 B
C
I2
B' C'
N C
N C
N A A
I1 =
IL1 3
R01 X01
V1 = VL1
aV 2 = aVL2
VL1
VL2
B'
A'
B'
C'
I1 = I L1
R01 X01
VL1 V1 = 3
VL2 aYYV 2 = a 3
IL2
A'
I1 VL2
B'
C'
N C
N C
N A
I1 = IL1
R01 X01
VL1 V1 = 3
aYV2 = 3aVL2
VL1
V1
VL2 B
B'
N C
N C
N A
I1
I L1 = 3
R01 X01
V1 = VL1
a VL2 aYV 2 = 3 3
Voc Im Xm
Ic
Rc
Pi (Voc ) = 3 Rc
Poc Voc
Ic
Pi 3
Voc Im Xm
Rc
(V )
oc
Xm Xm =
(Voc )
Xm
3Voc I oc
(Voc )2
Rc
Poc
2
Rc =
V 3 oc 3 = Pi
Ic Voc
Pi 3
Voc Im Xm
Rc
(V )
oc
Xm Xm =
(Voc )
Xm
3Voc I oc
(Voc )2
Rc
Z magnetism = 3Z magnetismY
Psc 3
Vsmall
Irated Vsmall
Req
Xeq
(I )
sc
X eq =
Vsc sin sc
(I )
sc
3Vsc I sc
2
X eq
Pcu
Z eq = 3Z eq Y
Psc Pcu i ) Psc = = 3 3 Vsc ii ) Vsc = 3 iii ) Isc = I sc Pcu ( Isc ) Req = 3 Pcu Req = 3( Isc ) 2
2
Irated Vsmall
Req
Xeq
(I )
sc
(I )
sc
3Vsc I sc
2
X eq
X eq
Pcu
The following are the test result for a 500kVA 6600/415V Y- 3 Transformer. Vsc = 100V Voc = 415V Ioc = 10A Isc = 75.76A Poc = 2000W Psc = 4000W
Calculate the Rc, Xm, Req and Xeq of the transformer referred to high voltage side. Voltage Regulation and Efficiency if power factor is 0.8 lagging. [65.3k, 18.91k, 0.23, 0.73, 1.24%, 98.52%] 65. 18.91k 23 73 24% 98.52%
AutoAuto-Transformer
Auto-Transformer is a transformer with only one winding. winding. That means, the primary and secondary windings are not electrically isolated form each other In other words, other. the primary and the secondary of autotransformer are physically connected. connected. The theory is almost the same as two winding transformer. transformer.
StepStep-down Autotransformer
StepStep-up Autotransformer
VL = V1 VH = V1 + V2
2. Current Rating IL
IH V2
b I2 I1 V1 c
VH
VATW I1 = V1 VATW I2 = V2 I Rated autotrans ; I Rated at high voltage side , I H = I 2 I Rated at low voltage side , I L = I H + I1
VL
VH a= VL
Given, Plosses and power factor, Pout = p. f kVAautotrans Know that, Pin = Plosses + Pout Pin Plosses Pout 100% = 100% = Pin Pin Plosses 100% = 1 Pin
AutoAuto-Transformer (Example)
1.
A single phase, 100kVA, 2000/200V two-winding transformer is connected as an autotransformer as shown in Figure 1 such that 2000V is obtained at secondary. The portion ab is the 200V winding, and the portion bc is the 2000V winding. Compute the kVA rating as an autotransformer. Also calculate the efficiency for a given losses of 2800W at 0.866 lagging power factor.
IH V2
IL
b I2 I1 V1 c Figure 1
VH
VL
AutoAuto-Transformer (Example)
ii.
The secondary winding is as part of primary winding. Hence, autotransformer eliminates the need for a separate secondary winding winding. As a results, autotransformers are always smaller, lighter, and cheaper cheaper. Absence of electrically isolation is a serious drawbacks in some applications
Drawback
i.
In electronic power supplies, there is always a need to isolate the output from the input and to reduce the weight and cost of unit. The objective are best achieved by using a relatively high frequency compared to normal frequency of 50Hz / 60Hz.
Questions ???