Академический Документы
Профессиональный Документы
Культура Документы
Copyright Materials
Copyright 2009 by the American Society of Heating, Refrigerating and Air-Conditioning g g g Airg Engineers (ASHRAE). All rights reserved. No part of this presentation may be reproduced without written permission from ASHRAE, nor may any part of this presentation be reproduced, stored in a retrieval system or transmitted in any form or by any means (electronic, photocopying, recording or other) without written permission from ASHRAE.
3
What Standard 189.1 is not: - not a design guide - not a rating system
Even if not adopted by your local authorities, this Standard is an indication of future industry trends
55 (current version)
Adapt
Section 2 - Purpose
The purpose of this standard is to provide minimum requirements for the siting, design, q siting, g g construction, and plans for operation of high performance, green buildings to: (a) balance environmental responsibility, resource efficiency, occupant comfort and well being, and community sensitivity, and being comm nit sensiti it (b) support the goal of development that
meets the needs of the present without compromising the ability of future generations
to meet their own needs. needs. needs. .
total site to be impervious - Prescriptive] l b Prescriptive] - Urban heat island [shaded or higher solar reflective index materials]
- Light pollution limitations
11
12
13
14
15
Metering of water source(s) and primary water use systems above threshold use rate
16
17
YES
3 cycles for water
NO
5 cycles for water
Exception: Maximum blowdown concentration of 1,500 mg/l total dissolved solids or 150 mg/l silica
19
Energy Chapter 7
Year
23
24
25
26
28
29
30
32
Climate Zones
33
Corresponding International
34
(7 4 2) 7.4.2)
Climate zone 3
36
37
38
39
7.4.3 HVAC
90.1 (current version) ) 90.1 (current version) (
General Concept: Based on Standard 90.1, but modify to gain improved energy performance over code minimum standards
7.4.3 HVAC
Brief mention of modifications to Std. 90.1
- 7 4 3 1 Minimum equipment efficiency 7.4.3.1 Either use equipment with efficiencies of: - EPAct baseline more on-site renewable and on-
peak load reduction, OR - Higher efficiency levels Greater of the efficiency per Energy Star (if applicable) or Tables C 1-15. pp ) 1Includes new definition of chiller efficiency formula from ARI Standard test conditions
41
7.4.3 HVAC
7.4.3.2 Lowers occupancy threshold for demanddemand-controlled ventilation (DCV)
90.1 (current version) 90.1 (current version)
Standard 90.1-2007: 40 people/100 m 90 1 2007: and area >50 m 25 people/ 100 m m If with CO2 sensors, install per 8.3.1.2.3 p Note: Type of DCV used is not specified in Std. 189.1
42
7.4.3 HVAC
7.4.3.3 Duct sealing level A everywhere 7.4.3.4 Expanded economizer Standard 90.1 90 1 requirement
- Rooftop units <5 tons: two stage (first stage economizer then second stage adds mechanical) - VAV supply air temp reset by at least 5 F (3 C) 5
43
7.4.3 HVAC
More on Economizers
- Li it on total capacity of systems without Limits t t l it f t ith t economizers If reqd, max. capacity without economizer
= 480,000 Btu/h or 140 kW
44
7.4.3 HVAC
7.4.3.4 Expanded economizer reqt
- Exceptions:
Based on IEER part-load efficiency, or full load EER / SEER
Water cooled units with heat transferred with building (water-source heat pumps) and less (waterthan 54,000 Btu/hr (16 kW) capacity
45
7.4.3 HVAC
7.4.3.5 Zone controls for limit on reheat
- Volume reheated re-cooled or remixed not to reheated, reexceed design OA flow rate or 15% of total peak supply p pp y
46
7.4.3 HVAC
7.4.3.7 System controls - 2 stages for DX >65 000 Btu/h (19 kW) >65,000 kW), - Air handling or fan coil units with CHW coils and >5 hp (3.7 kW) motor have il d h (3 7 t h reduced fan speed option 1. of full fan speed 2. Volume of outdoor air per Std. 62.1 p - Single zone, DX units > 110,000 Btu/hr (32 kW) supply fans 2-speed or VSD 247
7.4.3 HVAC
7.4.3.8 Expand energy recovery reqt
- 60% energy recovery effectiveness (enthalpy) - Provisions to bypass to allow air economizing
48
7.4.3 HVAC 7.4.3.9 Kitchen hoods add variable speed (significant impact on energy) 7.4.3.10 and .11 Minimum duct and pipe insulation increased (Tables C-9, C) 10 and 11) 7.4.3.12 Unoccupied hotel/motel >50 guest rooms
49
Reduce peak capacity of the building through demand-limiting or load demandshifting measures ( g (5%) )
50
Egress lighting control, < 0 1 W/ft2 (1 W/m) 0.1 W/m W/ Additional allowed if w/ auto shut-off shut-
52
53
55
56
- (b) Ozone cleaners for outdoor air in building projects located in non-attainment areas for nonozone. (Ozone removal efficiency = 40%, per Std.
62.1 6.2.1.2)
- (c) Filter frames, air cleaner racks, access doors sealed to eliminate bypass pathways yp p y
58
59
Mat M t systems at t t building entrances Envelop acoustical design (sound (sound transmission rating criteria)
60
61
63
Buildings Impact on Atmosphere, Materials and Resources ( 9) ( Mandatory Items Key to ASHRAE:
Construction waste management
- Divert 50% of non-hazardous waste, nondemolition debris (not counting soil, land clearing) - Off-site storage and sorting Offis allowed - Li it on total waste Limit t t l t generated per floor area
64
Buildings Impact on Atmosphere, Materials and Resources ( 9) ( Mandatory Items Key to ASHRAE:
No CFCs; fire suppression systems contain no ozone depleting p g substances (CFCs, HCFCs , Halons) Halons)
Storage, Storage collection of recyclable materials, discarded fluorescent lamps and ballasts
65
66
67
Designate CxA Develop OPR and Basis of Design Design reviews at 50% and final construction documents
Doing full Cx p process also satisfies the Building Acceptance Test requirements
69
70
71
72
2. 3. 3 4.
More Information
Information on ASHRAE standards: www.ashrae.org then follow
Thank you!
Comments, questions, concerns, advice
76