Technical Information TI 189F/24/ae

Ultrasonic Measurement prosonic FDU 80 to 86


Sensors for non-contact, continuous measurement of level and flow. Suitable for use in explosion hazardsous areas.
FDU 80 FDU 81 FDU 82

FDU 83

FDU 84

FDU 85

FDU 80F / 81F with slip-on flange FDU 86

Applications The Prosonic FDU is a series of ultrasonic sensors with different measuring ranges for continous, non-contact measurement of level and flow in liquids and solids. FDU 80, 80 F Liquids: 16 ft (5 m) Solids: 6.5 ft (2 m) FDU 81, 81 F Liquids: 32 ft (10 m) Solids: 16 ft (5 m) FDU 82 Liquids: 65 ft (20 m) Solids: 32 ft (10 m) FDU 83 Liquids: 82 ft (25 m) Solids: 49 ft (15 m) FDU 84 Solids: 82 ft (25 m) FDU 85 Solids: 147 ft (45 m) FDU 86 Solids: 230 ft (70 m)

Features and benefits Complete sensor program for non-contact, continuous measurement of level and flow For use in flumes, weirs, tanks and silos Insensitive to dirt and build-up Optional integrated heating for protection against ice build-up on sensor Wide range of mountings using flanges or external threads (with slip-on flange for flush mounting of sensor) Weather resistant and safe against submersion, NEMA 6P (IP 68)

The Power of Know How

Measuring system

Measuring system The complete measuring system consists of: The Prosonic FDU 80, 80 F, 81, 81 F, 82, 83, 84, 85, or 86 ultrasonic sensor the Prosonic FMU 860 transmitter; FMU 860 single channel for level measurement, FMU 861 single channel for flow or level measurement, or FMU 862 dual channel version The FDU 86 sensor can be used with any FMU transmitter with software version 2.2 or newer.

Sensor accessories Accessories are available to adapt the FDU sensors to special application conditions (refer to Accessories, page 12): Alignment unit FAU 40 for sensor positioning All-weather protective cover Mounting frame Wall bracket Slip-flanges, FAU 80, for FDU 80/81 sensors External temperature sensor, FMT 131 Separate power supply unit for heated sensors

FMU Transmitter

FMU Transmitter

FMU Transmitter

FDU with FAU 40 Alignment unit

FDU sensor FDU 80F with FAU 80 flange


FDU Sensor

Separate maximum limit switch

FDU sensor in flumes or weirs

FDU sensors in tanks or silos

Prosonic transmitters have an input for connection of a separate limit switch

Function

The emitter in the sensor is excited electrically and sends an ultrasonic pulse in the direction of the surface of the product, which partially reflects the pulse. This echo is detected by the sensor which converts the pulse into an electrical signal. The time between transmission and reception of the pulse is directly proportional to the distance between the sensor and the product surface. This distance is determined by the velocity of sound (c) and the run time (t) using the following formula: D= ct 2

Blocking distance Due to the ringing time of the sensor, there is a zone immediately below the sensor in which returing echoes cannot be detected. This distance, called the Blocking Distance (BD) determines the minimum distance between the sensor diaphragm and the maximum material level. If the minimum distance is not maintained, the level will not be measured correctly.

BD

FMU

E F

Operating principle of FDU ultrasonic sensors BD = Blocking Distance D = Distance from sensor to material surface L = Height in vessel (Level) F = Maximum level (100%) E = Zero point of measurement (0%, Empty)

Planning recommendations

Maximum measuring ranges The correct sensor for your application depends on the process and ambient conditions. When selecting the sensor, take into account that the maximum measuring range of the sensor is determined by the attenuation of the ultrasonic pulse in air as well as by the reflecting characteristics of the product surface. Both the level of background noise (e.g., when filling) and the mounting point can also affect measurement.

Application requirements Optimum conditions in tanks or silos are achieved if: The lower edge of the sensor is below the vessel top The detection zone does not include any internal fixtures or the filling curtain The surface of solid materials is hard and coarse-grained Operation is under normal atmospheric pressure The vessel is not being filled during measurement Less than optimum conditions reduce the accuracy and measuring range ot the sensors.
Factors Temperature difference between sensor and surface of material: Up to 68F (20C) Up to 104F (40C) Up to 176F (80C) Up to 302F (150C) Filling curtain: Outside detection zone Small amounts in detection zone Large amounts in detection zone Dust: None Low amounts High amounts Surface of solid: Hard, coarse (e.g. grit) Soft (peat, dust covered clinker) Surface of liquid: Calm Ripples Strong turblence (agitator blades) Foam: Contact Endress+Hauser Sensor installation: Lower edge free in vessel On collar, lower edge slanted depending on diameter/length ratio On collar, lower dege horizontal depending on diameter/length ratio Attenuation (dB)

Calculating the range The diagram below shows ideal attenuation curves for the FDU sensors: Check the factors affecting your measurement in the table at right Add up the attenuation values Take this sum and find the point where it intersects with the range limit of the sensor you are using. This gives the maximum range of that sensor.

0 5 to 10 10 to 20 20 to 30 0 5 to 10 10 to 40 0 5 5 to 20 40 40 to 60 0 5 to 10 10 to 20

0 10 to 20 20 to 40

Example for calculating range (liquid)


Temperature difference in tank: 104F Small amounts of fill stream in detection Liquid surface strongly turbulent Sum of attenuation values 10 dB 10 dB 20 dB 40 dB

230 150 130

FDU 86

FDU 85

Measuring Range (ft.)

Under above conditions, the range of an FDU 81 is approximately 23 feet (7 m).

100

FDU 83
60

FDU 82

32
23 16

FDU 81/81F FDU 80/80F


20 40 60 80 100 110

0 0

Attenuation (dB)

Installation

Detection limits and interference signals For best performance and maximum range, the selected sensor should be positioned vertically at the top of the vessel. It should be in a location that maximizes its returned echo signal and minimizes vessel obstructions in its line of sight. Although an individual sensor has a constant, definable output beam, the more important consideration is the line of sight echo. Minimizing vessel obstructions in the line of sight is accomplished by considering the geometry of both the vessel and the resulting reflected echoes. Accuracy A constant temperature and sound velocity within the measuring path enable a high degree of accuracy to be achieved. The effects of large temperature variations within the measuring path and changing gas mixtures must be calculated and the Prosonic transmitter programmed accordingly. With liquids having a high partial pressure, the gas composition must be determined to see if it remains constant.

On vessels with coned bottoms or dished (round) tops, positioning the sensor away from the vessel center is recommended to eliminate echo travel paths not related to level. Maximizing the returned level echo is generally accomplished by avoiding sensor mounts that either sight into the fill stream or position the sensor so that a large part of its output beam is lost into the vessel wall.

Estimation of the detection limits Edges, internal fixtures, etc. within the sound cone are of greatest importance in the first third of the range as the beam energy is highly concentrated. The energy in the last third of the range is distributed over a larger area, so that internal structures and edges are not as critical

r = tan

a 2

Sensor

Liquids

L
16 ft (5 m) 32 ft (10 m) 65 ft (20 m) 82 ft (25 m) Solids 6.6 ft (2 m) 16 ft (15 m) 32 ft (10 m) 49 ft (15 m) 82 ft (25 m) 147 ft (45 m) 230 ft (70 m)

r
1.1(0.35 m) 2.3 ft (0.69 m) 4.6 ft (1.4 m) 2.8 ft (0.87 m) 0.46 ft (0.14 m) 1.1 ft (0.35 m) 2.3 ft (0.7 m) 1.7 ft (0.52 m 3.6 ft (1.1 m) 6.2 ft (1.9 m) 11.8 ft (3.6 m)

FDU 80, 80F FDU 81, 81F FDU 82 FDU 83 FDU 80 FDU 81 FDU 82 FDU 83 FDU 84 FDU 85 FDU 86

8 8 8 4 8 8 8 4 5 5 6

Guidelines when mounting Check that the maximum level height does not come within the blocking distance of the sensor. If possible, the face of the sensor should be parallel to the surface of the product. The PE or PTFE coating on the sensor diaphragm (FDU 84, 85, and 86) is an integral part of the measuring system and must not be damaged during installation. Do not damage the funnel of the FDU 86 sensor when mounting The connecting cable of the FDU sensor is not designed as a support. Do not use as a suspension wire. For dust explosion areas, the cable must be mounted inside conduit. Local regulations for explosive atmoshperes caused by dust must be observed. All local and national codes or guidelines must be observed when used in explosion hazardous areas. Mounting in vessels Install the sensor so that its lower edge projects into the vessel. Position the sensor so that neither the filling curtain nor any internal fittings, e.g. an additional limit switch, are within the detection zone. The sensor must be positioned at the center of the outflow funnel so that an echo is received when the silo is empty. Accurate positioning of the sensor can be simplified using the FAU 40 sensor alignment unit. The sensor cable is not designed as a mounting or supporting cable. Do not use as a supension wire. If the sensor is to be installed in tanks containing very aggressive material, check that the chemical and corrosion resistance of the sensor materials meet these requirements.

Correct installation: Mount as far as possible from vessel wall, the material inlet, and internal fixtures. The center of the outflow funnel reflects an echo which is received by the sensor when the vessel is empty. Incorrect installation: The detection zone includes the filling curtain. The echo is reflected to one side when the vessel is empty.

FDU 84 mounted on girder or angle bracket

FDU 84 with FAU 40 alignment unit

Hazardous area

Nonhazardous area

1 pipe Conduit seal 1 threaded sleeve


FDU 84 with a 1 sleeve welded to a grating

Conduit seal

Sensor mounted on a 1 pipe in combustible dust areas (for FM, Class II)

Flush mounting with FAU 80 slip-on flange The FDU 80 F and 81 F sensors can be flush mounted using an FAU 80 slip-on flange.
FDU 80F / 81F Slip-on flange, 3 ANSI Class 150 7.5 (190.5) 3.19 (81)

PPS flanges should only be used in pressures up to 21 psia (1.5 bar), stainless steel flanges up to 58 psia (4 bar).

0.94 (23.9) Part No. FAU 80 - AAP, polypropylene FAU 80 - AAJ, 317 SS
FDU 80F / 81F Slip-on flange, 4 ANSI Class 150 5.12 (130) 3.19 (81)

3.83 (97.5)

0.59 (15)

0.94 (23.9) 2.99 (76) 9.00 (228.6)

Part No. FAU 80 - AHP, polypropylene FAU 80 - AHJ, 317 SS

Slip-on flanges are also available for DIN and JIS standards, please consult factory.

Mounting on mounting pipe or nozzle The sensor should be mounted on a pipe only when the maximum level comes within the blocking distance. No build-up of material should form inside the pipe Select a pipe diameter as large as possible (see figure). If there is a possibility of build-up inside the pipe, the pipe diameter should be significantly larger.

The inner surface of the nozzle should be as smooth as possible (no edges or welding seams). When mounting in the open, the pipe should be insulated as the temperature inside the pipe can differ significantly from that inside the vessel. For other nozzles, fixed target target suppression must be used.

D Heat isolation

Inner Edge 45 x .08" (2 mm)

FDU 80F FDU 81F Mounted with FAU 80 3 or 4 flange


D 3.15 (80 mm) 3.15 (80 mm) 3.94 (100 mm) 5.91 (150 mm) 7.87 (200 mm) 9.84 (250 mm) 11.8 (300 mm)

Sensor FDU 80, 81 FDU 80F, 81F FDU 80F, 81F FDU 82 FDU 83 FDU 84, 85 FDU 86

L
< 9.8 (250 mm) < 9.8 (250 mm) < 11.8 (300 mm) < 11.8 (300 mm) < 15.7 (400 mm) < 19.7 (500 mm) < 23.6 (600 mm)

Mounting above flumes To achieve the highest accuracy, the sensor should be situated immediately above the high water level (100%) plus the blocking distance (BD). The sensor must always be mounted perpendicular to the surface of the water and be above the center of the flume.

The appropriate mounting distances with respect to the flume are to be maintained (refer to Prosonic operating manual, BA 100F). When mounted in the open, the sensor must be protected from direct sunlight by using a protective cover, so that temperature compensation works correctly. Refer to Accessories for an all weather protection cover.

BD 1 x b0 BD (Blocking Distance) FDU 80: 12 (300 mm) Hmax. Type QV 308 b0 31.5 (800 mm) be 12.6 (320 mm) Hmax 23.6 (600 mm)

b0

be

Example of flow measurement with Khafagi-Venturi flume, QV 308 type.

Other examples of mounting the sensor over flumes with accessories from Endress+Hauser are shown below.

Mounting unit with wall bracket and cantilever

Mounting unit can be swivelled so that the sensor can be positioned over the center of the flume

Mounting unit with mounting frame and cantilever

Electrical connection

Connecting the FDU sensors The sensors are supplied with a fixed cable (18 AWG) for attachment to the FMU 86x transmitter, and are available in the following lengths: 16 ft (5 m), 32 ft (10 m), 49 ft (15 m), 65 ft (20 m), 82 ft (25 m) and 98 ft (30 m) Cables can be connected directly to the FMU transmitter or to a connection box. Additional cable, up to 981 ft (3oo m) is required for connection to the FMU transmitter from the connection box. Additional cable specifications: 6 per core Maximum 60 nF Two-wire with shield (6 max. for braided shield) NOTE: Connection box and cable not supplied with unit. The shielding serves as a return cable. Do not ground shield and wire to the transmitter without any electrical break. If the connection box is to be installed in explosion hazardous areas, then all local and national guidelines must be followed.
FDU 80, 80F 81, 81F, 82 Use terminal box for cables up to 980 ft (300 m)

These measures ensure that the sensors correspond to industrial (NAMUR) and European EMC Standards EN 50 081-1 for interference emission and EN 50 0822 for interference immunity. For general information on EMC (test methods, installation hints) see TI 241F/00/en. Ultrasonic sensors with heating The FDU 80 and FDU 81 can be supplied with heating units. The connecting terminals for the heated units are delivered with the sensor and are connected in the FMU transmitter connection compartment. External power supply for heated units, 24 VDC, for each heated sensor, 250 mA, 8W. Wire size and maximum length are shown in the chart below
Wire size AWG 20 AWG 18 AWG 17 max. L 490 ft 817 ft 981 ft (150 m) (250 m) (300 m)

Color code BK Black RD Red YE Yellow BN Brown BU Blue GNYE Green/Yellow

FDU 80, 81 with heating Grounding BN BU BK YE RD

BK

YE

RD

Grounding

Use terminal box for cables up to 980 ft (300 m)

Sensor extension cable: FDU 80, 80F, 81, 81F, 82 Order No. 938278-0120 FDU 83, 84, 85 Order No. 938278-1021 FDU 86 Order No. 52000261

80 81 82

FMU 860/861/862 Channel 1

Power supply

80 81 82

FMU 860/861/862 Channel 1 FMU 862 Channel 2

90 91 92

FMU 862 Channel 2

90 91 92

FDU 80, 80F, 81, 81F, 82

FDU 80, 81 with heating system

FDU 83, 84, 85, 86

FDU 83, 84, 85, 86

GNYE BK YE RD

Use terminal box for cables up to 980 ft (300 m)

GNYE BK YE RD

Use terminal box for cables up to 980 ft (300 m)

Grounding

Grounding

Shielding The shielding acts as feedback and must exhibit electrical continuity between sensor and transmitter

80 81 82

FMU 860/861/862 Channel 1

80 81 82

FMU 860/861/862 Channel 1

90 91 92

FMU 862 Channel 2

90 91 92

FMU 862 Channel 2

FDU 83, 84, 85, 86 (ground to FMU)

FDU 83, 84, 85, 86 (ground via connection box)

Technical data
General information
Manufacturer Instrument Designation Application Endress+Hauser Ultrasonic sensor Prosonic FDU 80, 80F, 81, 81F, 82, 83, 84, 85, 86 Non-contact continuous level measurement in liquids and solids Ultrasonic echo level measurement, time-of-flight Ultrasonic sensor for various measuring ranges for connection to FMU 860, 861, or 862 ultrasonic transmitter, as standard with integrated temperature sensor and mounting accessories, FDU 80/81 with optional heating. FDU 86 sensor can be selected and operated by all FMU transmitters with software version 2.2 and newer. FDU 80 to 86, sensors with connecting cable, mounted via threaded boss on sensor collar. FDU 80F/81F, flush-mounted sensor with connecting cable mounted via slip-on flange. Analog voltages Level or flow, determined by the distance from the sensor (membrane) to the product surface FDU 80 FDU 80 F FDU 81 FDU 81 F FDU 82 FDU 83 FDU 84 FDU 85 FDU 86 Blocking distance FDU 80, 80 F FDU 81, 81 F FDU 82 FDU 83, FDU 84, 85 FDU 86 FDU 80, 80 F FDU 81, 81 F FDU 82 FDU 83 FDU 84 FDU 85 FDU 86 inliquids 16 ft (5 m) 16 ft (5 m) 32 ft (10 m) 32 ft (10 m) 65 ft (20 m) 82 ft (25 m) 1.0 ft (0.3 m) 1.6 ft (0.5 m) 2.6 ft (0.8 m) 3.3 ft (1.0 m) 2.6 ft (0.8 m) 5.2 ft (1.6 m) 58 44 29 30 21 17 11 kHz kHz kHz kHz kHz kHz kHz in solids 6.5 ft (2 m) 16 ft (5 m) 32 ft (10 m) 49 ft (15 m) 82 ft (25 m) 147 ft (45 m) 230 ft (70 m)

Operation and system design

Measuring principle Modularity

Construction

Signal transmission

Input

Measured variables Measuring ranges

Operating frequency (at 74F)

Pulse frequency Attenuation

Dependent on measuring range, 1 Hz to 10 Hz Due to conditions, determining the detection limits with a 3 dB beam angle, refer to chart on bottom of page 4 FMU 860, 1-channel instrument for level measurement FMU 861, 1-channel instrument for flow measruement FMU 862, 2-channel instrument for flow or level measurement Vertical to the surface of the material FDU 80 FDU 80 F FDU 81 FDU 81 F FDU 82, 83, 84, 85 FDU 86 -40 to +140F (-40 to +60C) -40 to +203F (-40 to +95C) -40 to +176F (-40 to +80C) -40 to +203F (-40 to +95C) -40 to +176F (-40 to +80C) -40 to +302F (-40 to +150C)

Output

Transmitters

Installation Process conditions

Mounting position Ambient temperature

Relative humidity Protection Electromagnetic compatibility

FDU 80, 80F, 81, 81F, 82, 83, 85, 86: 100% FDU 84, 100%, max. 140F (60C); max. 95%, 176F (80C) NEMA 6P (IP 68), tested by immersing to 1 m for 24 hours Emitted interference to EN 61326, Class B equipment; immunity to interference resistance to EN 61326; Annex A (industry sector)

General operating conditions

Temperature at sensor FDU 80 FDU 80 F ***** FDU 81 **** FDU 81 F ***** FDU 82, 83, 84, 85 FDU 86 * ** *** **** ***** -4 to +140F (-20 to +60C) * -40 to +203F (-40 to +95C) -4 to +176F (-20 to +80C) -40 to +203F (-40 to +95C) -4 to +176F (-20 to +80C) -40 to +302F (-40 to +150C)

With limited data -40 to +140F (-40 to +60C) -40 to +203F (-40 to +95C) -40 to +176F (-40 to +80C) -40 to +203F (-40 to +95C) -40 to +176F (-40 to +80C) -35 to +284F (-40 to +140C) ** -40 to +284F (-40 to +140C) ***

May be used at high temperatures but only after contacting Endress+Hauser Limits apply as stated in Certificates E, J (see order codes) Limits apply as stated in Certificates P, Q, S, T (see order codes) With heating, -4 to +140F (-20 to + 60C) CIP cleaning at 203F (95C), sterilization for 30 min. at 275F (135C)
FDU 80, 81 Weight: FDU 80, 1.2 lbs (0.55 kg) FDU 81, 1.3 lbs (0.6 kg) FDU 82 Weight: 2.6 lbs (1.2 kg)

Mechanical construction

FDU 80F, 81F (flush-mounted) Weight: FDU 80F, 1.1 lbs (0.5 kg) FDU 81F, 1.2 lbs (0.55 kg)

0.79 (20)

1.16" (29.5)

1.16" (29.5)

4.68 (119) 3.15 (80) 3.82" (97)

0.12 (3)

4.80" (122)

5.20" (132)

2.76 (70)

3.86" (98)

FDU 83 Weight: 6.8 lbs (3.1 kg)

FDU 84 Weight: 10.3 lbs (4.7 kg)

1.18 (30)

1.18 (30) 5.35" (136)

5.47" (139)

7.44" (189)

9.41 (239)

FDU 85 Weight: 10.9 lbs (5.0 kg)

FDU 86 Weight: 10.9 lbs (5.0 kg)

1.16" (29.5) 6.10" (155)

1.18" (30)

9.61" (244)

17.7" (450)

7.79" (198)

10

Materials

Housing

FDU 80, 81, 82: PP-GF FDU 80F, 81F: ETFE FDU 83, 84: PA * FDU 85, 86: UP * A 304 SS cover around the PA housing enables the units to be used in Zone 10 FDU 80, 81, 82: FDU 80F, 81F: FDU 83, 84: FDU 85, 86: FDU 83: FDU 84: FDU 85 FDU 86 * PP-GF ETFE 304 SS or aluminum UP 316 Ti SS 316 Ti SS / PE * Al / PE ** Al / PTFE *** 1 NPT, G 1A 1 NPT, G 1A 1 NPT, G 1A 1 NPT, G 1A

Mounting thread

Diaphragm

0.02 (0.5 mm) 316 Ti SS with a 0.16 (4 mm) closed-pore PE cover, facing process material ** 0.04 (1 mm) aluminum with a 0.19 (5 mm) closed-pore PE cover, facing process material *** Aluminum diaphragm coated with PTFE Diaphragm seal Connecting cable FDU 80 to 85: FDU 86: EPDM Silicon PVC PUR Silicon

FDU 80, 80F, 81, 81F, 82: FDU 83, 84, 85: FDU 86:

Mounting accessories

Alignment unit: 304 SS flange, galvanized steel pipe Slip-on flange: PP (max. 22 psi) or 304 SS (> 22 psi) Via FMU 860, 861, or 862 Prosonic transmitters By attaching the CE mark, Endress+Hauser confirms that the instrument fulfills all the requirements of the relevant EC directives FDU 80, 80F, 81, 81F, 82: Class I, II, III; Div. 1, 2; Grps. A-G FDU 83, 84, 85: Class II, Div. 1, Grps. E-G FDU 86: Class I, II, III; Div. 1, 2; Grps. A-G, ambient temperature -40 to +284F (-40 to +140C). Class I, II, III; Div. 1, 2; Grps. A-G, ambient temperature -40 to +176F (-40 to +80C) FDU 80, 80F, 81, 81F, 82: Class I, Div. 1, Grps. A-D FDU 83, 84, 85: Class II, Div. 1, Grps. E-G FDU 86: Class II, III; Div. 1, Grps. E-G, ambient temperature -40 to +284F (-40 to +140C). Class II, III; Div. 1, Grps. E-G, ambient temperature -40 to +176F (-40 to +80C) FDU 80, 80F, 81, 81F, 82: ATEX II 2G EEx m II T5 (T6 for FDU 80) FDU 83, 84, 85: BVS/DMT (Dust-Ex) Zone 10/ATEX II 1/2 D FDU 86: DMT Dust-Ex ATEX II 1/2D, -40 to +140C. DMT Dust-Ex ATEX II 1/2D, -40 to +80C. DMT Gas-Ex ATEX II 2 G, -35 to +140C

Power supply CE mark

Certificates and approvals


FM

CSA

ATEX

11

Accessories

Mounting frame Mounting frame with 1 pipe for installing the cantilever and Prosonic FMU. 28 (700 mm), galvanized steel Order No. 919791-0000 28 (700 mm), 304 SS Order No. 919791-0001 55 (1400 mm), galvanized steel Order No. 919791-0002 55 (1400 mm), 304 SS Order No. 919791-0003
1.77 (45) 0.26 (6.5)

0.51 (13)

3.94 (100)

2.17 (55)

0.98 (25)

0.13 (3.2) 1.33 (33.7) 0.79 (20)

2.36 (60) 27.6 / 55 (700 / 1400) 0.16 (4) 2.99 (76) 7.87 (200)

3.94 (100)

5.12 (130)

3.94 (100) 5.91 (150)

Cantilever (for mounting frame) For mounting Prosonic sensors FDU 80 and 81 over open channels. 20 (500 mm), galvanized steel Order No. 919790-0000 20 (500 mm) 304 SS Order No. 919790-0001 39 (1000 mm), galvanized steel Order No. 919790-0002 39 (1000 mm), 304 SS Order No. 919790-0003

0.79 (20)

0.79 (20) D

1.38 (35)

1.97 (50)

3.94 (100)

M8

0.98 (25) 1.38 (35)

L
2.95 (75) 2.95 (75) 3.94 (100) C 4.13 (105) B

1.38 (35)

0.87 (22)

For separate temperature sensor

0.26 (6.5)

0.59 (15)

39 42 29 (1000) (1085) (750) 19 23 10 (500) (585) (250)

0.12 12 (3) (300) 0.08 8 (2) (200)

Wall bracket Wall bracket for mounting cantilever to wall. Galvanized steel Order No. 919792-0000 304 SS Order No. 919792-0001

0.26 (6.5) 7.09 (180)

0.20 (5)

0.13 (3.2) 1.33 (33.7) ~ 8.38 (213)

0.98 (25)

0.51 (13)

4.33 (110)

5.91 (150)

~ 3.46 (88)

4.33 (110) 5.91 (150)

12

All-weather protective cover For Prosonic sensors FDU 80 and 81 Material, PP-GF Order No. 919793-0000 The measurement point designation is fixed to the protective cover. Break off mounting eyes on the sensor at the preformed positions before installing in the protective cover.

1.34 (34)

3.94 (100)

3.86 (98)

Power supply unit for sensor heating for FDU 80 and FDU 81 24 VDC power unit for sensor heating, NEMA 4X (IP 66) protective housing. Material: PT/ABS Order No. 215095-0002 External temperature sensor FMT 131 Used with heated sensor or when temperature is not being measured in the sensor. Housing: POM, NEMA 4 (IP 65) Sensor (NTC): 316Ti SS Mounting thread: G 1/2 A Two-wire shielded cable, maximum 25 per wire. Standard version: FMT 131-R7, not certified, without cable.
2.64 (67)

1 FMT 131 1

Certificates J Cenelec EEX m II T5 Q FM Class I, Div. 1, Grps. A-D R Standard Cable length 1 16 ft (5 m) 7 Without cable 8 Variable length, 20 ft (6 m) to 100 ft (30 m), specify in feet (m)

FMU 860 / 861 / 862 / 867


70 71 YEGN

4.33 (110)

BK YE

SW 27

0.98 (25) 4.72 (120)

EX

G 1/2A ISO 228

EX

0.39 (10)

BK YE YEGN

FMT 131

Temperature sensor protective sleeve Thread-on sensor protector for the FMT 131 sensor. Material: 316Ti SS Order No. 942046-0000

G 1/2 SW 27 0.47 (12)

0.86 (21.8) 4.33 (110)

13

FAU 40 alignment unit For easy mounting and positioning of the FDU sensor (refer to TI 179F/00/en).
3/4" NPT PG 11

15 pivot

Sealant here 13 AF hex screw for lateral adjustment

Two 4 AF allen screws for height adjustment 0.39" (10) Ground pin

O-ring

19.7" (500)

2.76" (70)

Maximum height adjustment, 14.2" (360)

1" NPT

G1A Seal inserted when used in combustible dusts (Germany) applications.

Ordering information FDU 80 1

4 FDU 80 F 1

Certificate R Nonhazardous areas J ATEX II 2G EEx m II T6 Q FM, Class I, II, III; Div. 1, 2; Grps A-G U CSA general purpose S CSA, Class I, Div. 1, Grps. A-D Proces connection G G1B threaded, PP-GF N 1 NPT threaded, PP-GF Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length Heater A Heater not selected B Heater, 24 VDC

Certificate R Nonhazardous areas J ATEX II 2G EEx m II T6 Q FM, Class I, II, III; Div. 1, 2; Grps A-G U CSA general purpose S CSA, Class I, Div. 1, Grps. A-D Proces connection G G1B threaded, ETFE N 1 NPT threaded, ETFE F 1 NPT threaded, ETFE, 3-A Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length

14

1 FDU 81 1

4 FDU 81 F 1

Certificate R Nonhazardous areas J ATEX II 2G EEx m II T5 Q FM, Class I, II, III; Div. 1, 2; Grps A-G U CSA general purpose S CSA, Class I, Div. 1, Grps. A-D Proces connection G G1B threaded, PP-GF N 1 NPT threaded, PP-GF Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length Heater A Heater not selected B Heater, 24 VDC

Certificate R Nonhazardous areas J ATEX II 2G EEx m II T5 Q FM, Class I, II, III; Div. 1, 2; Grps A-G U CSA general purpose S CSA, Class I, Div. 1, Grps. A-D Proces connection G G1B threaded, ETFE N 1 NPT threaded, ETFE F 1 NPT threaded, ETFE, 3-A Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length

1 FDU 82 1

3 FDU 83 1

Certificate R Nonhazardous areas J ATEX II 2G EEx m II T5 Q FM, Class I, II, III; Div. 1, 2; Grps A-G U CSA general purpose S CSA, Class I, Div. 1, Grps. A-D Proces connection G G1B threaded, PP-GF N 1 NPT threaded, PP-GF Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length

Certificate R Nonhazardous areas E ATEX II 1/2D P FM, Class II, Div. 1, Grps E-G T CSA, Class II, Div. 1, Grps. E-G U CSA general purpose Proces connection G G1A threaded, aluminum N 1 NPT threaded, aluminum S G1A threaded, 304 SS V 1 NPT threaded, 304 SS Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length

15

1 FDU 84 1

3 FDU 85 1

3 FDU 86 1

Certificate R Nonhazardous areas E ATEX II 1/2D P FM, Class II, Div. 1, Grps E-G T CSA, Class II, Div. 1, Grps. E-G U CSA general purpose Proces connection G G1A threaded, aluminum N 1 NPT threaded, aluminum S G1A threaded, 304 SS V 1 NPT threaded, 304 SS Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length

Certificate R Nonhazardous areas E ATEX II 1/2D P FM, Class II, Div. 1, Grps E-G T CSA, Class II, Div. 1, Grps. E-G U CSA general purpose Proces connection G G1A threaded, UP N 1 NPT threaded, UP Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length

Certificate R Nonhazardous areas E ATEX II 1/2D, -40 to +284F F ATEX II 1/2D, -40 to +176F J ATEX II 2G EEx m II T6 P FM, Class I, II, III; Div. 1, Grps A-G, HT, -40 to +284F K FM, Class I, II, III; Div. 1, Grps A-G, -40 to +176F T CSA, Class II, III; Div. 1, Grps. E-G, HT, -40 to +284F L CSA, Class II, III; Div. 1, Grps. E-G, -40 to +176F U CSA general purpose Proces connection G G1B threaded, UP N 1 NPT, UP S G1A threaded, 304 SS V 1 NPT threaded, 304 SS Cable length 1 With 16 ft (5 m) extension cable 2 With 32 ft (10 m) extension cable 3 With 49 ft (15 m) extension cable 4 With 65 ft (20 m) extension cable 5 With 82 ft (25 m) extension cable 6 With 98 ft (30 m) extension cable 8 Extension cable, meters (priced per meter) specify length A Extension cable, feet (priced per foot) specify length

For application and selection assistance, in the U.S. call 888-ENDRESS For total support of your installed base, 24 hours a day, in the U.S. call 800-642-8737 Visit us on our web site, www.us.endress.com
United States Endress+Hauser, Inc. 2350 Endress Place Greenwood, IN 46143 Phone: (317) 535-7138 888-ENDRESS FAX: (317) 535-8498 Canada Endress+Hauser Canada Ltd. 1440 Grahams Lane Unit 1, Burlington ON, L7S 1W3 Phone: (905) 681-9292 800-668-3199 FAX: (905) 681-9444 Mexico Endress+Hauser Paseo del Pedregal No. 610 Col. Jardines del Pedregal 01900, Mexico D.F. Mexico Phone: (525) 568-2405 FAX: (525) 568-7459

Endress+Hauser
The Power of Know How

TI 189F/24/ae/05.03 2003 Endress+Hauser, Inc.