CVMk2 Modular power analyzer


System composed by measuring module and screen Communications between measuring module and the screen its done via RS-485 Universal mounting: Panel mounted 144x144, 96x96, and round The module measure can be installed in DIN rail and the screen in the panel Slim line screen (only 22 mm deep) Universal power supply available in Plus type. Modular system up to 3 expansion modules

Ethernet system protocol


Modbus RTU Modbus TCP

RS-485 or RS-232 system protocol


Modbus RTU

Measure
Harmonics measuring up to the 50 th in current and voltage. Option for measuring in Low and Medium Voltage systems. Varied Measuring range permitted (110, 520, 866 Vph-ph)) Double scale kW / MW Current reading using external transformers .../5A or /1A (insulated inputs, according to type). Recording of max and minimum dates

Power quality analyzer


Calculation of the harmonic distortion of voltage and current Calculation of THD using the fundamental or RMS Even and odd THD calculation Decomposition until 50 harmonic. Calculation of icker according to IEC 61000-4-15 standard Calculation of imbalance and asymmetry according to IEC 61000-4-30 norm Summary of the state of the quality of network

Communications
ETHERNET Modbus TCP/RTU, and Modbus TCP/IP RS-485 with Modbus RTU, Modbus TCP, Metasys N2 Compatible with the Power Studio / Scada system RS-485 communications MODBUS - RTU Up to 3 expansion communications channels

Display fearutes
Incorrect connection detection. Internal clock for setting and for 12 hourly tariffs (TOU). System of visualization by menus Direct access to the measurement screens, setup, etc. Access to summary of the system by function key in any screen (PT, CT, registry, etc.). Menus in different languages Big LCD display Allows selection of default page

Expansion modules and functions


CVM-K2 modules, 8 Inputs / 4 Ouputs, relays and 8 Inputs / 8 Outputs Applications using outputs Static output for AC or DC Associate an output to electric variable, AC or DC. Possibility of functions AND and OR. Energy impulses outputs Remote Activation via software.

Communications (2 ports)

Valid for .../ 5 A and .../1 A

Leakage / Neutral current

Harmonic decomposition up to the 50st (V, A)

Memory expansion slot

Three-phase 50...60 Hz

Disturbance detection

THD Measuring (V, A)

Insulated inputs (ITF)

Class (Power, energy)

Multitarariff (9 tariffs)

Analogue outputs

Analogue inputs

Digital inputs

Relay output

Wave form

Protocol

Type

Code

COMPACT EQUIPMENTS (M-CVMk2 + Display) 0,5 0,2 RS-485 RS-485 MEASUREMENT EQUIPMENTS 0,5 0,2 RS-485 RS-485 Modbus/RTU Modbus/RTU M-CVMk2-ITF-405 M-CVMk2-ITF-402 M54410 M54412 Modbus/RTU Modbus/RTU CVMk2-ITF-405 CVMk2-ITF-402 M54400 M54402

PARAMETERS
Phase-neutral voltage Phase-phase voltage Current Frequency Active power Inductive reactive powera Capacitive reactive power Apparent power Power factor cos Power demand Neutral current Earth leakage current Harmonic decomposition, U and I (50th) Harmonic Measuring in voltage Harmonic measuring in current kWh (consumed and generated)(*) kvarh L (consumed and generated)(*) kvarh C (consumed and generated)(*) kVAh (consumed and generated)(*) Flicker (*) For every tariff and total and much more...

UNIT
V V A Hz kW kvar L kvar C kVA PF cos Pd IN If

L1

L2

L3

III

optional

% THD - V % THD - A Wh varh varh VAh Wa , Pst, Plt

FEATURES
Power supply circuit (*) Consumption Frequency Measuring circuit Rated voltage Frequency Voltage circuit consumption Rated current Permanent overload Class Power Energy 0,5 % ( 1 digits) / 0,2 % ( 1 digits) 0,5 % ( 1 digits) / 0,2 % ( 1 digits) 300 V ac (phase-neutral)/ 520 V ac (phase-phase) 45...65 Hz 0,9 VA .../5 A / .../1 A 1,2 In 85 ... 265 V ac 5 VA (without display & expansion cards) 50 / 60 Hz Assembly features Connection Type of casing Protection: assembled equipment (front) unassembled equipment (side) Dimensions Weight Environmental conditions Operating temperature Humidity Safety -10 ... +50 C 5 ... 95 % (without condensation) Category III-300 V AC. 520 V AC. EN 61010. Electrical shock protection by double insulation class II IEC 664, VDE 0110, IEC 801, UL 94, IEC 348, IEC 571-1, EN 61010-1, EN 50081-1, EN 50082-1 IEC 61000-4-30 Class B Pluggable board Self extinguishing V0 plastic IP 54 IP 31 144 x 144 mm 0,6 kg

(*) Other power supplies and measurings on request (please see price list).

Standards

Accessories

5A

Converters (see M.5)

Management software (see M.9)

Measuring transformer (see M.7)

Vial Sant Jordi s/n 08232 Viladecavalls Barcelona (Spain) Tel. (+34) 93 745 29 00 Fax: (+34) 93 745 29 14 e-mail: central@circutor.es web: www.circutor.com

CIRCUTOR reserves the right to change the content of this catalogue without prior warning. CIRCUTOR does not assume any responsibility for any damage caused to persons or materials due to improper or unsuitable use of its equipment.

Desing: Comunication CIRCUTOR, SA

Вам также может понравиться