INDUSTRIAL

GE Industrial Systems

Catalog/Selection Guide

Record Plus
Current Limiting
Molded Case Circuit Breakers

INTRODUCTION

Breaker Frame Rating

Rated Voltage

Breaker Frame Enclosed Rating

Product Description

Standards

Interruption Capacity

Catalog Number

Standards
Main Standards
UL 489
IEC 947 and Associated EN Sections

Other Global Standards Pending


BS

JIS (Japan)

Bureau Vertitas

KEMA

CCIB (China)

NOM of Shipping

CEI

RINA

CSA (Canada)

UTE

Det Norske Veritas

VDE

Catalog Number Structure


F
Frame Rating
Family

F = Record
Plus

Interruption

(Amperes)

Capacity

C = 100

S = 25kA
V = 35kA
N = 65kA
H = 100 kA
L = 150kA
Y = Switch

TE

050

Voltage
Poles

3 = 3 Poles
32 = 2 poles

Rating

4 = 480V
6 = 600V

Rated
Type

TE = Fixed Thermal
Magnetic

MH = Mag Break,

in 3-pole
envelope

7X-20X

ML = Mag Break,
3X-15X

Current (A)

Connection

003 100

R = Standard,
No Lugs

R1 = Line and Load


Lugs Installed

R2 = Load Lugs Installed


R3 = Line Lugs Installed

www.GEindustrial.com

FC 100 Amp Frame Overview


Interrupting Ratings
Federal Spec C/B Class WC-375B

Type

Ampere No.
Rating Poles

UL Listed Interrupting Ratings rms Symmetrical Amperes (in Thousands)


Max AC/DC Voltage

FCS

15-100

2,3

600Vac, 500Vdc

AC Voltage

IEC Listed Interrupting Ratings,


Icu, Amperes (in Thousands)

DC Voltage

AC Voltage

250 (2p) 500 (3p) 220-240 400-415

DC Voltage

240

480

600

500

250 (2p) 500 (3p)

42

25

18

22

30

36

22

14

22

30

FCV

15-100

2,3

600Vac, 500Vdc

65

35

22

25

35

50

30

18

25

35

FCN

15-100

2,3

600Vac, 500Vdc

150

65

25

30

42

85

50

22

30

42

FCH

15-100

2,3

600Vac, 500Vdc

200

100

35

42

65

100

80

36

42

65

FCL

15-100

2,3

600Vac, 500Vdc

200

150

42

65

80

200

150

50

65

80

Dimensions
E

in

mm

in

mm

in

mm

in

mm

in

mm

in

mm

in

mm

in

mm

FC

3.7

29.1

3.2

81.3

.96

24.4

3.0

76.2

1.0

25.4

6.4

162.6

5.0

127.0

1.0

25.4

Frame

Trip Units
Availability by Interrupting Ratings
Trip Unit Rated Code (see Catalog Number Structure)
Current (A)
Thermal Magnetic
Mag Break

S,N

S,N

15

S,V,N,H,L

S,N

20

S,V,N,H,L

25

S,V,N,H,L

30

S,V,N,H,L

S,N

35

S,V,N,H,L

40

S,V,N,H,L

45

S,V,N,H,L

50

S,V,N,H,L

S,N

60

S,V,N,H,L

70

S,V,N,H,L

80

S,V,N,H,L

90

S,V,N,H,L

100

S,V,N,H,L

S,N

SELECTION AND PRICING

Record Plus, Standard Fixed Thermal Magnetic, 600 Vac, HACR Rated
Ampere Rating

25kA

35kA

65kA

100kA

150kA

15
20
25
30
35
40
45
50
60
70
80
90
100
15
20
25
30
35
40
45
50
60
70
80
90
100
15
20
25
30
35
40
45
50
60
70
80
90
100
15
20
25
30
35
40
45
50
60
70
80
90
100
15
20
25
30
35
40
45
50
60
70
80
90
100

Cat. No.

2-Pole
List Price, GO-135H

FCS326TE015R2
FCS326TE020R2
FCS326TE025R
FCS326TE030R
FCS326TE035R
FCS326TE040R
FCS326TE045R
FCS326TE050R
FCS326TE060R
FCS326TE070R
FCS326TE080R
FCS326TE090R
FCS326TE100R
FCV326TE015R2
FCV326TE020R2
FCV326TE025R
FCV326TE030R
FCV326TE035R
FCV326TE040R
FCV326TE045R
FCV326TE050R
FCV326TE060R
FCV326TE070R
FCV326TE080R
FCV326TE090R
FCV326TE100R
FCN326TE015R2
FCN326TE020R2
FCN326TE025R
FCN326TE030R
FCN326TE035R
FCN326TE040R
FCN326TE045R
FCN326TE050R
FCN326TE060R
FCN326TE070R
FCN326TE080R
FCN326TE090R
FCN326TE100R
FCH326TE015R2
FCH326TE020R2
FCH326TE025R
FCH326TE030R
FCH326TE035R
FCH326TE040R
FCH326TE045R
FCH326TE050R
FCH326TE060R
FCH326TE070R
FCH326TE080R
FCH326TE090R
FCH326TE100R
FCL326TE015R2
FCL326TE020R2
FCL326TE025R
FCL326TE030R
FCL326TE035R
FCL326TE040R
FCL326TE045R
FCL326TE050R
FCL326TE060R
FCL326TE070R
FCL326TE080R
FCL326TE090R
FCL326TE100R

$645.00
645.00
636.00
636.00
636.00
636.00
636.00
636.00
636.00
740.00
740.00
740.00
740.00
705.00
705.00
696.00
696.00
696.00
696.00
696.00
696.00
696.00
821.00
821.00
821.00
821.00
776.00
776.00
757.00
757.00
757.00
757.00
757.00
757.00
757.00
901.00
901.00
901.00
901.00
1202.00
1202.00
1193.00
1193.00
1193.00
1193.00
1193.00
1193.00
1193.00
1488.00
1488.00
1488.00
1488.00
1638.00
1638.00
1629.00
1629.00
1629.00
1629.00
1629.00
1629.00
1629.00
2075.00
2075.00
2075.00
2075.00

Cat. No.

3-Pole
List Price, GO-135H

FCS36TE015R2
FCS36TE020R2
FCS36TE025R
FCS36TE030R
FCS36TE035R
FCS36TE040R
FCS36TE045R
FCS36TE050R
FCS36TE060R
FCS36TE070R
FCS36TE080R
FCS36TE090R
FCS36TE100R
FCV36TE015R2
FCV36TE020R2
FCV36TE025R
FCV36TE030R
FCV36TE035R
FCV36TE040R
FCV36TE045R
FCV36TE050R
FCV36TE060R
FCV36TE070R
FCV36TE080R
FCV36TE090R
FCV36TE100R
FCN36TE015R2
FCN36TE020R2
FCN36TE025R
FCN36TE030R
FCN36TE035R
FCN36TE040R
FCN36TE045R
FCN36TE050R
FCN36TE060R
FCN36TE070R
FCN36TE080R
FCN36TE090R
FCN36TE100R
FCH36TE015R2
FCH36TE020R2
FCH36TE025R
FCH36TE030R
FCH36TE035R
FCH36TE040R
FCH36TE045R
FCH36TE050R
FCH36TE060R
FCH36TE070R
FCH36TE080R
FCH36TE090R
FCH36TE100R
FCL36TE015R2
FCL36TE020R2
FCL36TE025R
FCL36TE030R
FCL36TE035R
FCL36TE040R
FCL36TE045R
FCL36TE050R
FCL36TE060R
FCL36TE070R
FCL36TE080R
FCL36TE090R
FCL36TE100R

Record Plus 15-20 amp circuit breakers come with load lugs factory installed.

$747.00
747.00
738.00
738.00
738.00
738.00
738.00
738.00
738.00
840.00
840.00
840.00
840.00
807.00
807.00
798.00
798.00
798.00
798.00
798.00
798.00
798.00
921.00
921.00
921.00
921.00
868.00
868.00
859.00
859.00
859.00
859.00
859.00
859.00
859.00
1001.00
1001.00
1001.00
1001.00
1304.00
1304.00
1295.00
1295.00
1295.00
1295.00
1295.00
1295.00
1295.00
1588.00
1588.00
1588.00
1588.00
1740.00
1740.00
1731.00
1731.00
1731.00
1731.00
1731.00
1731.00
1731.00
2175.00
2175.00
2175.00
2175.00

Cat. No.

FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK14
FCALK14
FCALK14
FCALK14

FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK14
FCALK14
FCALK14
FCALK14

FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK14
FCALK14
FCALK14
FCALK14

FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK14
FCALK14
FCALK14
FCALK14

FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK13
FCALK14
FCALK14
FCALK14
FCALK14

Lug Kit
List Price, GO-135H

$9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00

9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00

9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00

9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00

9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00

www.GEindustrial.com

Record Plus, MagBreak, 7X-20X Pick Up, 600 Vac


Ampere
Rating

25kA

65kA

Instantaneous
Adj. Range

2-Pole

Lug Kit (3 per kit)

3-Pole

Low

High

Cat. No.

List Price, GO-141H

Cat. No.

List Price, GO-141H

Cat. No.

List Price, GO-141H

21

60

FCS326MH003R1

$554.00

FCS36MH003R1

$656.00

49

140

FCS326MH007R1

554.00

FCS36MH007R1

656.00

15

105

300

FCS326MH015R1

554.00

FCS36MH015R1

656.00

30

210

600

FCS326MH030R

536.00

FCS36MH030R

638.00

FCALK13

$9.00

50

350

1000

FCS326MH050R

536.00

FCS36MH050R

638.00

FCALK13

9.00

21

60

FCN326MH003R1

617.00

FCN36MH003R1

719.00

49

140

FCN326MH007R1

617.00

FCN36MH007R1

719.00

15

105

300

FCN326MH015R1

617.00

FCN36MH015R1

719.00

30

210

600

FCN326MH030R

599.00

FCN36MH030R

701.00

FCALK13

9.00

50

350

1000

FCN326MH050R

599.00

FCN36MH050R

701.00

FCALK13

9.00

Record Plus 3-15 amp circuit breakers come with line and load lugs factory installed.

Record Plus MagBreak, 3X-15X Pick Up, 600 Vac


Ampere
Rating

Instantaneous
Adj. Range

2-Pole

Lug Kit (3 per kit)

3-Pole

Low

High

Cat. No.

List Price, GO-141H

Cat. No.

List Price, GO-141H

Cat. No.

List Price, GO-141H

45

FCS326ML003R1

$481.00

FCS36ML003R1

$599.00

21

105

FCS326ML007R1

481.00

FCS36ML007R1

599.00

15

45

225

FCS326ML015R1

481.00

FCS36ML015R1

599.00

30

90

450

FCS326ML030R

463.00

FCS36ML030R

581.00

FCALK13

$9.00

50

150

750

FCS326ML050R

463.00

FCS36ML050R

581.00

FCALK13

9.00

100

300

1500

FCS326ML100R

549.00

FCS36ML100R

650.00

FCALK14

9.00

45

FCN326ML003R1

554.00

FCN36ML003R1

656.00

21

105

FCN326ML007R1

554.00

FCN36ML007R1

656.00

15

45

225

FCN326ML015R1

554.00

FCN36ML015R1

656.00

30

90

450

FCN326ML030R

536.00

FCN36ML030R

638.00

FCALK13

9.00

50

150

750

FCN326ML050R

536.00

FCN36ML050R

638.00

FCALK13

9.00

100

300

1500

FCN326ML100R

640.00

FCN36ML100R

742.00

FCALK14

9.00

25kA

65kA

Record Plus 3-15 amp circuit breakers come with line and load lugs factory installed.

SELECTION AND PRICING

Record Plus, Non-Automatic Circuit Breaker (Molded Case Switch), 600Vac


2-Pole

Ampere Rating

Cat. No.

3-Pole
List Price, GO-135H

Cat. No.

List Price, GO-135H

Cat. No.

Lug Kit (3 per kit)


List Price, GO-135H

60

FCY206D060R

$345.00

FCY306D060R

$445.00

FCALK13

$9.00

100

FCY206D100R

345.00

FCY306D100R

445.00

FCALK14

9.00

Internal Accessories (supplied with leads attached)


Contacts Auxiliary and Bell Alarm
Normally Open
Accessory

Ratings

Normally Closed

Form C

Cat. No.

List Price,
GO-135H

Cat. No.

List Price,
GO-135H

List Price,
GO-135H

Cat. No.

Aux. Switch Right


Mounted

5A@240Vac,
0.5A@125Vdc

FAS10RW

$149.00

FAS01RW

$149.00

FASH11RW

$295.00

Aux. Switch Left


Mounted

5A@240Vac,
0.5A@125Vdc

FAS10LW

149.00

FAS01LW

149.00

FASH11LW

295.00

Aux. Switch Right


Mounted Gold Contacts

0.5A@30V

FAS11RGW

295.00

Aux. Switch Left


Mounted Gold Contacts

0.5A@30V

FAS11LGW

295.00

Bell Alarm Mechanism

5A@240Vac,
0.5A@125Vdc

FABAM10W

154.00

FABAM01W

154.00

FABAM11W

154.00

Bell Alarm Mechanism


Gold Contacts

0.5A@30V

FABAM11GW

295.00

Releases Shunt Trip and Undervoltage


Shunt Trip

Undervoltage Release

Voltage

Rating (Inrush
Power Consumption

Cat. No.

List Price,
GO-135H

Rating (Inrush
Power Consumption

Cat. No.

List Price,
GO-135H

12V DC
24V AC/DC
48V AC/DC
120V AC
110/130V AC/DC
220/240V AC, 250V DC
400/480V AC

200 mA / 2.4W
100 mA / 3.6W
60 mA / 2.88W
40 mA / 4.8W
40 mA / 4.8W
20 mA / 4.6W
20 mA / 8.4W

FASHTBW
FASHTDW
FASHTFW
FASHTKW
FASHTJW
FASHTNW
FASHTUW

$363.00
363.00
363.00
363.00
363.00
363.00
363.00

50 mA / 1.2W
20 mA / 0.96W
15 mA / 1.8W
15 mA / 1.8W
15 mA / 3.45W
15 mA / 6.3W

FAUVRDW
FAUVRFW
FAUVRKW
FAUVRJW
FAUVRNW
FAUVRUW

$363.00
363.00
363.00
363.00
363.00
363.00

External Accessories
Electrical Operator Motor Drives, Front Mounted

Padlocking Devices

Voltage

Cat. No.

120V AC/125V DC

FCEMF3

List Price, GO-135H


$710.00

220/240V AC, 50/60 Hz

FCEMF6

710.00

24V DC

FCEMFD

710.00

48V DC

FCEMFF

710.00

Description

Cat. No.

List Price, GO-135H

Padlocking Fixed
Toggle

FC1PF

$8.70

Padlocking Euserec
Toggle

FC1PE

32.00

Plug-in Types
Type

Description

Cat. No.

List Price, GO-135H

Base Only

3 Pole - LSL - Horizontal Strap


3 Pole - SLS - Horizontal Strap
3 Pole - LSL - Vertical Strap
3 Pole - SLS - Vertical Strap

FCDDF1
FCDDF2
FCDDF3
FCDDF4

$250.00
250.00
250.00
250.00

Secondary Disconnect

Secondary Disconnect Kit


Secondary Disconnect - Base Part
Secondary Disconnect - Breaker Part

FCDSD
FCDSDP
FCDSDB

185.00
50.00
50.00

Mounting Plate

Mounting Plate

FCDMP

40.00

www.GEindustrial.com

Handles and Handle Accessories


Type

Description

Cat. No.

List Price

GO Schedule

Breaker Mechanism
6 inches for NEMA 1, 3R, 12,13
10 inches for NEMA 1, 3R, 12,13
6 inches for NEMA 4/4X
10 inches for NEMA 4/4X
3 feet
4 feet
5 feet
6 feet
7 feet
8 feet
9 feet
10 feet

FCNBM
FCNHM1
FCNHM2
FCNHM3
FCNHM4
SC3L
SC4L
SC5L
SC6L
SC7L
SC8L
SC9L
SC10L

$96.00
188.00
280.00
258.00
373.00
91.00
108.00
119.00
134.00
148.00
163.00
196.00
211.00

GO-144H
GO-144H
GO-144H
GO-144H
GO-144H
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A

Same as Spectra: 6-inch for NEMA 12/13


Same as Spectra: 10-inch for NEMA 12/13
Same as Spectra: 6-inch for NEMA 4/4X
Same as Spectra: 10-inch for NEMA 4/4X
Operating Mechanism Only
Use with FCNFM
Use with FCNFM
Use with FCNFM
Door Hinged on Left, NEMA 12/13, 2-point Kit
Door Hinged on Left, NEMA 4/4X, 2-point Kit
For Use With TDV1/TDV1X Above
Door Hinged on Right, NEMA 12/13 2-point Kit
Door Hinged on Right, NEMA 4/4X, 2-point Kit
For Use with TDV1L, TDC1LX Above

STDA1
STDA2
STDA1X
STDA2X
FCNFM
TDSR
TDSR
TDS1
TDV1
TDV1X
TDV3
TDV1L
TDV1LX
TDV3L

82.50
94.50
148.00
165.00
67.00
29.50
29.50
29.50
134.00
174.00
29.50
134.00
174.00
29.50

GO-144A
GO-144A
GO-144A
GO-144A
GO-144H
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A
GO-144A

DPDT for STDA Handle on Right


DPDT for STDA Handle on Left

TDAS1L2
TDAS1R2

134.00
134.00

GO-144A
GO-144A

Vertical Mount

FCNRC

65.50

GO-144H

Horizontal Mount

FCNRD

65.50

GO-144H

FCFRDRCK

11.25

GO-144H

SEFRGSK

4.00

GO-144A

Breaker Mechanism
Flange Mounted Handle Mechanism
for Cable Operator

STDA Flange Handle


Operators
Operating Cable

Flange Handle for Variable Depth


Operating Mechanism

STDA Flange
Handles &
Hardware Kits

Auxiliary Contact
Kits

TDR Style Rotary


Handles

Flange Operating Mechanism


Flange Stiffener Kit
Extender Kit
Extended Drive Stud
Door Hardware Kit NEMA12/13
Door Hardware Kit NEMA 4/4X
Third Point Latch Kit
Door Hardware Kit NEMA12/13
Door Hardware Kit NEMA 4/4X
Third Point Latch Kit

Door Ring Gasket

Door Ring-Interlock

Door Gasket Kit

TDM Style Rotary


Handles

Direct Mount

Complete Kit for NEMA 1, 3R, 12

FCNRN

79.00

GO-144H

Direct Through Door

Complete Kit for NEMA 1, 3R, 12

FCNRT

79.00

GO-144H

Variable Mount

Complete Kit for NEMA 1, 3R, 12

FCNRV

102.00

GO-144H

For NEMA 1, 3R, 12, 4 and 3/16

FCNRM1

52.00

GO-144H

For NEMA 4/4X, 4 and 3/16

FCNRM2

52.00

GO-144H

For NEMA 1, 3R, 12, 6 and 1/8 - 15

FCNRM3

52.00

GO-144H

For NEMA 4/4X, 6 and 1/8 - 15

FCNRM4

52.00

GO-144H

For NEMA 1, 3R, 12

FNRH

27.00

GO-144H

For NEMA 4/4X

THCH45

303.00

GO-144A

Operating Mechanism Only

Handle Only

Hardware kits
For Wire Ranges, See Page 8
Type

Description

Single Lugs for Use with Cu or Al Cables

Lug Kits (Set of 3) for Use with Cu or Al Cables

Single Lugs for Use with Cu Cables


Lug Kits (Set of 3) for Use with Cu Cables
Mounting Screws for Mounting Plates with Tapped Holes (4 screws and lockwashers)
Mounting Screws for Mounting Plates with Clearance Holes (4 screws, lockwashers and nuts)
Nut Plates
Back Connected Studs
Line Voltage Tab

Cat. No.

List Price, GO-135H

15-20A

FCAL12

$3.00

25-60A

FCAL13

3.00

70-100A

FCAL14

3.00

15-20A

FCALK12

9.00

25-60A

FCALK13

9.00

70-100A

FCALK14

9.00

25-60A

FCO13

3.00

70-100A

FCO14

3.00

25-60A

FCOLK13

9.00

70-100A

FCOLK14

9.00

8-32 x 2 7/8

FCMSK3

6.10

8-32 x 3

FCMSK4

6.10

Kit of 3

FCNP3

2.10

Bulk Pack of 36

FCNPB

25.20

Short

FCBCS1

28.00

Long

FCBCS2
FCAL18LV

31.50
6.60

APPLICATION INFORMATION

Selection Factors
Selection Factor A. Cable Size
Applied Cable Cross Section Area as a Percent of Rated Cable Size Cross Sectional Area
Percent

50

60

70

80

90

100

125

150

200

Cable Size Selection Factor A

1.40

1.25

1.15

1.07

1.03

1.00

0.99

0.97

0.97

Selection Factor B. Ambient Temperature


Circuit Breaker or Switch Ambient Temperature
25C (77F)
Frame Size

40C (104F)

50C (122F)

60C (140F)

70C (158F)

Factor B

Min. Cable
Insulation
Rating, C

Factor B

Min. Cable
Insulation
Rating, C

Factor B

Min. Cable
Insulation
Rating, C

Factor B

Min. Cable
Insulation
Rating, C

Factor B

Min. Cable
Insulation
Rating, C

1.0

60

1.0

60

1.0

105

1.10

110

1.30

120

FC

Selection Factor C. Operating Frequency


Selection Factor C, Frequency at

Circuit Breaker
Type

Max. Rating
Amperes

50-60 Hz

100-120 Hz

150-180 Hz

200-240 Hz

300-360 Hz

400-415 Hz

FC

100

1.00

1.00

1.00

1.00

1.00

1.00

Selection Factor D. Altitude


Installation Altitude
Selection Factor D
Feet

Meters

-100 to 6,000

-30 to 1,800

1.00

6,001 to 10,000

1,801 to 3,000

1.04

10,000+

3,000+

Consult GE

Selection Factor E. Total Load Class


Total Load Class

Group Mounted (12 or


more Breakers)

Switching
Capacitors

Switching
Electromagnets

Single Motor Branch


Circuit Protection
(Normal Duty)

Single Motor Branch


Circuit Protection
(Heavy Duty)

All Other (Normal


Loads)

Selection Factor E

1.10

1.50

1.50

1.25

1.00

The total load class Factor E is the product of all the load class factors that apply to the circuit under consideration.
Refer to NEC Article 430, Part II and Table 430.22E for conductor and circuit breaker frame sizing.

Selection Factor F. Safety


A safety factor of 10% is equivalent to a current rating multiplier of 1.10.

Selection Factor G. Duty Rating


Duty Rating

Continuous Duty (Operation at constant load for


more than three hours)

Intermittent Duty (Operation at constant load for


three hours, or less)

Selection Factor G

1.25

1.00

www.GEindustrial.com

Cable & Conductor Data


Cable Size by Circuit Breaker or Switch Amp Rating
Device Ampere
Rating
15
20
25
30
35
40
45
50
60
70
80
90
100
110
125
150
175
200
225
250
275
300
325
350
400
450
500
550
600

Paralleled

Size

Two
Two
Two
Two
Two

14 AWG
12 AWG
10 AWG
10 AWG
8 AWG
8 AWG
8 AWG
8 AWG
6 AWG
4 AWG
4 AWG
3 AWG
3 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
300 kcmil
350 kcmil
400 kcmil
500 kcmil
3/0 AWG
4/0 AWG
250 kcmil
300 kcmil
350 kcmil

Approximate Correlation of Standard Cross Sections of


Round Copper Conductors (AWG and kcmil) versus ISO
Metric Cable Sizes

Aluminum or Copper Clad Aluminum


Conductor

Copper Conductor

Paralleled

Size

Two
Two
Two
Two
Two
Two
Two

12 AWG
10 AWG
10 AWG
8 AWG
8 AWG
8 AWG
6 AWG
6 AWG
4 AWG
3 AWG
2 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
300 kcmil
350 kcmil
500 kcmil
500 kcmil
4/0 AWG
4/0 AWG
250 kcmil
300 kcmil
350 kcmil
500 kcmil
500 kcmil

AWG or kcmil Size

Equivalent Cross Section (mm2)

ISO Metric Cable Size (mm2)

18

0.82

16
14
12
10
8
6
4
2
1/0
2/0
3/0

1.3
2.1
3.3
5.3
8.4
13.3
21.2
33.6
53.5
67.4
85

0.75
1
1.5
2.5
4
6
10
16
25
35
50
70
95

4/0

107.2

250
300
350
500
600

127
152
177
253
304

120
150
185
240
300

Properties of Conductors Rated for Use with Molded Case Circuit Breakers
Conductors
Size (AWG
or kcmil)

14
14
12
12
10
10
8
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750

Stranding
Diameter

Area

mm2

Circular
Mils

Quantity

2.08
2.08
3.31
3.31
5.261
5.261
8.367
8.367
13.3
21.15
26.67
33.62
42.41
53.49
67.43
85.01
107.2

4110
4110
6530
6530
10380
10380
16510
16510
26240
41740
52620
66360
83690
105600
133100
167800
211600

1
7
1
7
1
7
1
7
7
7
7
7
19
19
19
19
19
37
37
37
37
37
61
61
61

mm

Direct-Current Resistance at 75C (167F)


Copper
Aluminum
Uncoated
Coated

Overall
Diameter
in

0.620

0.024

0.780

0.030

0.980

0.038

1.230
1.560
1.960
2.200
2.470
1.690
1.890
2.130
2.390
2.680
2.090
2.290
2.470
2.640
2.950
2.520
2.720
2.820

0.490
0.061
0.077
0.087
0.097
0.066
0.074
0.084
0.094
0.106
0.082
0.090
0.097
0.104
0.116
0.099
0.107
0.111

Area

mm

in

mm2

in2

ohm/km

ohm/kFT

ohm/km

ohm/kFT

ohm/km

ohm/kFT

1.630
1.850
2.050
2.320
2.588
2.950
3.264
3.710
4.670
5.890
6.600
7.420
8.430
9.450
10.620
11.940
13.410
14.610
16.000
17.300
18.490
20.650
22.680
24.490
25.350

0.064
0.073
0.081
0.092
0.102
0.116
0.128
0.146
0.184
0.232
0.260
0.292
0.332
0.372
0.418
0.470
0.528
0.575
0.630
0.681
0.728
0.813
0.893
0.964
0.998

2.08
2.68
3.31
4.25
5.26
6.76
8.37
10.76
17.09
27.19
34.28
43.23
55.80
70.41
88.74
111.90
141.10
168
201
235
268
336
404
471
505

0.003
0.004
0.005
0.006
0.008
0.011
0.013
0.017
0.027
0.042
0.053
0.067
0.087
0.109
0.137
0.173
0.219
0.260
0.312
0.364
0.416
0.519
0.626
0.730
0.782

10.1
10.3
6.34
6.50
3.984
4.070
2.506
2.551
1.608
1.010
0.802
0.634
0.505
0.399
0.317
0.2512
0.1996
0.1687
0.1409
0.1205
0.1053
0.0845
0.0704
0.0603
0.0563

3.07
3.14
1.93
1.98
1.21
1.24
0.764
0.778
0.491
0.308
0.245
0.194
0.154
0.122
0.0967
0.0766
0.0608
0.0515
0.0429
0.0367
0.0321
0.0258
0.0214
0.0184
0.0171

10.4
10.7
6.57
6.73
4.148
4.226
2.579
2.653
1.671
1.053
0.833
0.661
0.524
0.415
0.329
0.2610
0.2050
0.1753
0.1463
0.1252
0.1084
0.0869
0.0732
0.0622
0.0579

3.19
3.26
2.01
2.05
1.26
1.29
0.786
0.809
0.510
0.321
0.254
0.201
0.160
0.127
0.101
0.0797
0.0626
0.0535
0.0446
0.0382
0.0331
0.0265
0.0223
0.0189
0.0176

16.6
16.9
0.222
0.145
6.651
6.679
4.125
4.204
2.652
1.666
1.320
1.045
0.829
0.660
0.523
0.413
0.328
0.2778
0.2318
0.1984
0.1737
0.1391
0.1159
0.0994
0.0927

5.06
5.17
3.18
3.25
2.00
2.04
1.26
1.28
0.808
0.508
0.403
0.319
0.253
0.201
0.159
0.126
0.100
0.0847
0.0707
0.0605
0.0529
0.0424
0.0353
0.0303
0.0282

Wire Range & Terminal Torque


Lug Catalog Number

Frame Amps

FCAL12
FCAL13
FCAL14
FCO13
FCO14

3, 7, 15, 20
25-60
70-100
25-60
70-100

Wire Range (75oC Insulated Conductor)


CU
AL
#12-14
#10-#6
#4-#1
#10-#6
#4-#1

#10-#12
#8-#4
#2-1/0
#8-#4
#2-1/0

Torque
Line

Load

25-32 lb-in
25-32 lb-in
25-32 lb-in
25-32 lb-in
25-32 lb-in

#12: 35 lb-in
#10: 35 lb-in / #8: 40lb-in / #6 & #4: 45 lb-in
#4-1/0: 45 lb-in
#10: 35 lb-in / #8: 40lb-in / #6&#4: 45 lb-in
#4-1/0: 45 lb-in

APPLICATION INFORMATION

Withstand Ratings
Note: The maximum withstand rating is limited by the value set forth in this table or the short circuit rating of the upstream fuse or circuit breaker,
whichever is less. The upstream protective device must have instantaneous trip function or element, and its rated amperage may not exceed the rated
current of the switch.

Fuse
Frame
FC

Type

Withstand Rating RMS Symmetrical Amps


(in thousands)

Protective Device

Molded Case Switch

Rated Amperes

FCY

Type

60 or 100

RK5, J, T or L

Circuit Breaker
Max Rating
Amperes
100

AC Voltage

Type

Max Rating
Amperes

240

480

600

MCCB, ICCB or
LVPCB

100

200

150

42

Internal Accessory Functions


UL Listed for Field Installation
Auxiliary Switch
The auxiliary switch signals primary contact position (open or closed) to other accessories for remote indication and control applications.
Switch operation is independent of the method used to open or close the breaker. Auxiliary switches do not distinguish between a trip or
open condition. Record Plus normally open switches are early make/late break type auxiliary switches and are normally open when the
breaker is open and normally closed when the breaker is closed.

Bell Alarm Mechanism


The bell alarm mechanism (BAM) is used to signal breaker trip status to other accessories for remote indication and interlocking function.
The switch operates when the breaker is tripped as a result of its protective functions, or as the result of the operation of a shunt trip or
undervoltage release. The switch is not actuated as a result of normal breaker on-off operation.

Shunt Trip
The shunt trip is used to trip (open) the circuit breaker by remote control. Record Plus shunt trips are UL listed for field installation,
meeting UL requirements for operation at 55% of rated ac voltage (120 Vac shunt trip only) and 75% of rated dc voltage for use on
ground fault systems. Record Plus shunt trips are common to all circuit breakers and molded cases switches in the product family.
These devices offer a unique combination of low power consumption and a kiss-free lock-out operation. When the breaker is in the
ON position and the shunt trip is activated, the breaker will trip and its contacts will open. The device can be constantly activated at
its normal voltage, allowing it to be used as a lock-out coil.

Undervoltage Release
The undervoltage release trips the circuit breaker when the control voltage drops to less than 35% to 70% of rating. Optional time
delay units from 100 to 250 milliseconds allow the user to minimize nuisance tripping. The time delay may be switched off to provide
an instantaneous undervoltage trip. In the event an attempt is made to reclose the circuit breaker while the undervoltage condition is
present, the undervoltage release devices will prevent the breaker contact closure. In other words, Record Plus undervoltage releases
are a kiss-free design.

GE Molded Case Circuit Breaker Cross-Reference Summary


Breaker Type

Legacy Breakers

Vac

Maximum
Ampere Rating

Poles

Line

600

100

2,3

600

100

2,3

600

100

600

Record Plus (Thermal magnetic trip)

Version

I/C

Version

I/C

Spectra

SED

18

FCS

25

Spectra

SEHA

25

FCS

25

2,3

Spectra

SEL

65

FCN

65

100

2,3

Spectra

SEP

100

FCH

100

600

100

2,3

Spectra

SEL

25

FCS

25

600

100

2,3

Core

TED

18

FCS

25

600

100

2,3

Core

THED

25

FCS

25

600

100

Core

TEC

10

FCS

25

600

100

Spectra (Switch)

SED

25

FCY

150

www.GEindustrial.com

Time Current Curves


1000
900
800
700

600

600

500

500

400

400

300

300

200

200

TOTAL CLEARING TIME VS CURRENT IN KA

.04

.04

.04

.04

.03

.03

.03

.03

.02

.02

.02

.02

.01
.009
.008
.007

480 Vac

.006

.006

.005

.005

.004

.004

.003

.003

.002

40
30

20

.002

600
700
800
900
1000

500

50 60 70 80 90

400

40

300

30

100

20

200

.001

.001

50
40

Maximum total
clearing time

30

20

10
9
8
7

10
9
8
7

600 Vac

.01
.009
.008
.007

7000
8000
9000
10000
500

480 Vac

.006

200

.006

.005

.005

.004

.004

.003

.003

240 Vac
.002

400
300

.01
.009
.008
.007

100
90
80
70
60
50
40
30

20

10
9
8
7

.002

Minimum total
clearing time

6
.001
10

20

30

40

50 60 70 80 90

500

600 Vac

100
90
80
70
60

50

6000

600

TOTAL CLEARING TIME VS CURRENT IN KA

.05

100
90
80
70
60

5000

4000

3000

2000

500

600
700
800
900
1000

400

300

1000
900
800
700

.05

10

.001

.2

.1
.09
.08
.07
.06

.1
.09
.08
.07
.06

.05

.05

.05

.04

.04

.04

.03

.03

.02

.02

.01

.01

30A
30A

.03

.02

Current limiting range, for total clearing time see above for details.
For additional data refer to Ip and I2t curves DES-028 & DES-029

35A
35A

7000
8000
9000
10000

6000

50 60 70 8090

5000

40

4000

30

3000

20

2000

6 7 8 9 10

600
700
800
900
1000

500

400

300

* 2 .2 1 2 inch

100

.5 .6 .7 .8 .9 1

200

.01

TM

Record Plus

Current Rat in gs
15, 20, 25, 30, 35Am peres

Current Rat in gs
40, 45, 50, 60Am peres
2 pole and 3 pole
Volt age Rat in gs
600 Vac , 500Vdc

Instantaneous m agneti c trip :


not adju stable.

Frequency Rat in gs
50/60 Hertz

Shift in dex fo r
lo ng-tim e delay only.

7000
8000
9000
10000

6000

5000

50 60 70 8090

4000

40

3000

30

600
700
800
900
1000

20

2000

MULTIPLES OF CURRENT RATING


6 7 8 9 10

500

400

300

200

1000
900
800
700
600

600
500

500

TOTAL CLEARING TIME VS CURRENT IN KA

300

TOTAL CLEARING TIME IN SECONDS

200

100
90
80
70
60
50
40

Maximum total
clearing time

30

20

.10
.09
.08
.07
.06

.10
.09
.08
.07
.06

.05

.05

.04

.04

.03

.03

.02

.02

600 Vac

.01
.009
.008
.007

300

200

.01
.009
.008
.007

480 Vac

.006

.006

.005

.005

.004

.004

.003

.003

240 Vac

10
9
8
7

400

.002

.002

.001

.001

TOTAL CLEARING TIME IN SECONDS

400

100
90
80
70
60
50
40
30

20

10
9
8
7

Minimum total
clearing time
600
700
800
900
1000

50 60 70 80 90

500

40

400

30

300

20

200

6
10

100

6
5

5
4

AVAILABLE THREE-PHASE SYMMETRICAL SHORT-CIRCUIT CURRENT (KILOAMPERES)

1
.9
.8
.7

.9
.8
.7

70A

.6

.6
.5

.5

.4

.4

80A

.3

Non-adjustable instantaneous pick-up band, AC only.


For DC instantaneous pick-up band conversion multiplier refer
TM
to the Record Plus circuit breaker product guide on the
GE Industrial Systems website: www.GEindustrial.com

.2

90A

.1
.09
.08
.07
.06

.2

.1
.09
.08
.07
.06

100A

.05

TIME IN SECONDS

.3

.05
.04

.04

.03

.03

.02

Current limiting range, for total clearing time see above for details.
For additional data refer to Ip and I2t curves DES-028 & DES-029

.02

.01
7000
8000
9000
10000

6000

5000

50 60 70 8090

4000

40

3000

30

2000

20

600
700
800
900
1000

6 7 8 9 10

500

400

300

200

* 2 .2 1 2 inch

100

.01
.5 .6 .7 .8 .9 1

MULTIPLES OF CURRENT RATING

* For pri nt ing t o st andard scale d size, scale log-log cycle t o 2.2 12inch per cycle for bot h ord in at e and abscis sa

M olded Case Circuit Break er


GE Industrial Systems

w it h Therm al-M agnet ic t rip unit


TM

Current Rat in gs
70, 80, 90, 100Am peres
2 pole and 3 pole
Volt age Rat in gs
600 Vac , 500Vdc
Frequency Rat in gs
50/60 Hertz

Record Plus

6 7 8 9 10

20

30

40

50 60 70 8090

MULTIPLES OF CURRENT RATING

w it h Therm al-M agnet ic t rip unit

Record Plus

- Type FC

Long-t im e D elay and Inst ant aneous Tim e-Current Curves


Enclosure Com pensat ed
o
Curves show enclo sure com pensated cir cuit breaker in open air, 40 C am bient,
w ir ed w it h conducto rs of correspondin g rati ng, no prio r load.
For all oth er am bients, use rati ng shift in dex at to p of page.

GE Industrial Systems, 41 Woodford Avenue, Plainvil le, CT 06062


R02-08/02

100

Tem p. 25 40 50

M olded Case Circuit Break er

GE Industrial Systems, 41 Woodford Avenue, Plainvil le, CT 06062

.5 .6 .7 .8 .9 1

* 2 .2 1 2 inch

A dju st m ent s
Long-tim e delay therm al tr ip :
not adju stable.

- Type FC

Long-t im e D elay and Inst ant aneous Tim e-Current Curves


Enclosure Com pensat ed
o
Curves show enclo sure com pensated cir cuit breaker in open air, 40 C am bient,
w ir ed w it h conducto rs of correspondin g rati ng, no prio r load.
For all oth er am bients, use rati ng shift in dex at to p of page.

DES-015
A dju st m ent s
Long-tim e delay therm al tr ip :
not adju stable.
Instantaneous m agneti c trip :
not adju stable.

GE Industrial Systems, 41 Woodford Avenue, Plainvil le, CT 06062


R01 05/02

10

.02

.01
.5 .6 .7 .8 .9 1

R02-08/02

1000
900
800
700

Current limiting range, for total clearing time see above for details.
For additional data refer to Ip and I2t curves DES-028 & DES-029

TM

o
Curves show enclo sure com pensated cir cuit breaker in open air, 40 C am bient,
w ir ed w it h conducto rs of correspondin g rati ng, no prio r load.
For all oth er am bients, use rati ng shift in dex at to p of page.

Frequency Rat in gs
50/60 Hertz

.03

GE Industrial Systems

- Type FC

.06

.04

60A

DES-013

Long-t im e D elay and Inst ant aneous Tim e-Current Curves


Enclosure Com pensat ed

.1
.09
.08
.07
.05

* For pri nt ing t o st andard scale d size, scale log-log cycle t o 2.2 12inch per cycle for bot h ord in at e and abscis sa

M olded Case Circuit Break er


w it h Therm al-M agnet ic t rip unit

GE Industrial Systems

.2

Non-adjustable instantaneous pick-up band, AC only.


For DC instantaneous pick-up band conversion multiplier refer
TM
to the Record Plus circuit breaker product guide on the
GE Industrial Systems website: www.GEindustrial.com

50A

MULTIPLES OF CURRENT RATING

* For pri nt ing t o st andard scale d size, scale log-log cycle t o 2.2 12inch per cycle for bot h ord in at e and abscis sa

2 pole and 3 pole


Volt age Rat in gs
600 Vac , 500Vdc

.3

45A

7000
8000
9000
10000

25A

.2

6000

Non-adjustable instantaneous pick-up band, AC only.


For DC instantaneous pick-up band conversion multiplier refer
TM
to the Record Plus circuit breaker product guide on the
GE Industrial Systems website: www.GEindustrial.com

.4

5000

.1
.09
.08
.07
.06

.3

4000

20A

.3

3000

.2

.5

.4

2000

15A

.3

.6

40A

.5

600
700
800
900
1000

.4

.9
.8
.7

.6

500

.4

1
.9
.8
.7

400

.5

300

.6

.5

200

.9
.8
.7

.6

DES-014

1
.9
.8
.7

AVAILABLE THREE-PHASE SYMMETRICAL SHORT-CIRCUIT CURRENT (KILOAMPERES)

100

AVAILABLE THREE-PHASE SYMMETRICAL SHORT-CIRCUIT CURRENT (KILOAMPERES)

DES-013

50 60 70 8090

.05

240 Vac

TIME IN SECONDS

40

.10
.09
.08
.07
.06

DES-015

30

.10
.09
.08
.07
.06

.01
.009
.008
.007

20

600
700
800
900
1000

Minimum total
clearing time

10
9
8
7

MULTIPLES OF CURRENT RATING


6 7 8 9 10

400

20

300

30

200

40

.05

100

Maximum total
clearing time

50

.10
.09
.08
.07
.06

TIME IN SECONDS

TIME IN SECONDS

100
90
80
70
60

TOTAL CLEARING TIME IN SECONDS

200

.10
.09
.08
.07
.06

TOTAL CLEARING TIME IN SECONDS

300

TOTAL CLEARING TIME IN SECONDS

400

TIME IN SECONDS

500

Shift in dex fo r
lo ng-tim e delay only.

DES-014
A dju st m ent s
Long-tim e delay therm al tr ip :
not adju stable.
Instantaneous m agneti c trip :
not adju stable.

TIME IN SECONDS

600

.5 .6 .7 .8 .9 1

TOTAL CLEARING TIME IN SECONDS

1000
900
800
700

200

7000
8000
9000
10000

6000

5000

50 60 70 8090

4000

40

3000

30

2000

20

500

MULTIPLES OF CURRENT RATING


6 7 8 9 10

600
700
800
900
1000

400

300

200

100

Tem p. 25 40 50

Shift in dex fo r
lo ng-tim e delay only.

.5 .6 .7 .8 .9 1

100

Tem p. 25 40 50

1000
900
800
700

Prices and data are subject to change without notice. Should further information be desired, or
should particular problems arise that are not sufficiently covered here for the purchasers purposes,
the matter should be referred to the General Electric Company.

GE Industrial Systems
General Electric Company
41 Woodford Avenue, Plainville, CT 06062
www.GEindustrial.com
DEP-122 11/02

2002 General Electric Company