Hardware Installation Guide

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

BACnet B-ASC VAV / VVT Controllers: ECB-VAVS-O, ECB-VAVS, ECB-VAV, ECB-VVTS, ECB-VAV-N BACnet B-ASC 10-Point Programmable Controller: ECB-103

1. Product Description
This document describes the hardware installation procedures for the Single Duct Variable Air Volume / Variable Volume Temperature Controllers (ECB-VAVS-O, ECB-VAVS, ECB-VAV, ECB-VVTS, and ECB-VAV-N), and the 10-Point Controller (ECB-103). The Distech Controls Variable Air Volume / Variable Volume Temperature product line is designed to control various types of HVAC equipment such as baseboards, single and multi-stage duct heaters, fans, valves, lights, etc. When connected to a Wireless Receiver, this product line can be used with a variety of wireless battery-less sensors and switches. The Distech Controls controller product line is designed to control and monitor various HVAC equipment such as fan coils, chilled ceiling, heat pumps as well as for any lighting control and power measurement applications. When connected to a Wireless Receiver, this product line can also be used with a variety of wireless batteryless sensors and switches. Each controller uses the BACnet MS/TP LAN communication protocol and are BTL -Listed as BACnet Application Specific Controllers (B-ASC). This document describes the hardware installation procedures for the following controllers: ECB-VAVS-O, ECB-VAVS, ECB-VAV, ECB-VVTS, ECB-VAV-N, and ECB-103. For more information on the specific layout and functionality of each controller, please refer to their individual datasheets.

Figure 1-1:

ECB-VAV

Figure 1-2:

ECB-VAVS

Figure 1-3:

ECB-VAV-N

Distech Controls quality management system is ISO 9001:2000 certified

2. General Installation Requirements


For proper installation and subsequent operation of the controller, pay special attention to the following recommendations:

4. Mounting Instructions
The following mounting instructions pertain to controllers that have a built-in actuator (ECB-VAVS-O, ECB-VAVS, ECB-VAV, or ECB-VVTS). If mounting a controller without a built-in actuator (ECB-VAV-N or ECB-103), simply mount the controller using the integrated mounting bracket(s) and screw(s) that are provided with the controller. Each controller is specially designed for easy installation either directly on an air duct or in a panel by using the integrated mounting collar and the screw that is provided with the controller. This mounting arrangement opposes the torque applied to the damper shaft. Mount the controller as follows: 1. Orient the controller into position on to the damper shaft so that wiring connections are easily accessible. The controller must be fitted onto the shaft such that the base of the controller is parallel to the VAV box (perpendicular to the damper shaft). If the damper shaft has an external bushing that prevents the controller from being mounted flush to the side of the VAV box, use a spacer of the same thickness to compensate and to ensure the controller is at a right-angle to the shaft to prevent binding. Condensation from the damper shaft will damage the controllers electronics. When the VAV box air supply is below 10C (50F), ensure that any condensation from the damper shaft or from the VAV box does not enter the controllers electronics. Under these conditions, mount the controller vertically above the damper shaft so that any condensation from the damper shaft will fall away from the controller. Further countermeasures may be required in some installations. 2. Using a power screwdriver, attach the controller to the VAV box with the screw provided with the controller through the controllers mounting bracket slider. Otherwise, mark the screws position on the VAV box with a punch and then drill a hole into the VAV box. Then attach the controller to the VAV box with the screw provided with the controller. Avoid over tightening the mounting screw so as to not strip the threads. Make sure the screws do not interfere with damper blade movement. 3. Find the damper position by the marking typically found on the end of the damper shaft.

It is recommended that the controller(s) be kept at room temperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature during shipping/storage to evaporate. Upon unpacking the product, inspect the contents of the carton for shipping damages. Do not install damaged controllers. Allow for proper clearance of controller enclosure, and wiring terminals for easy access, hardware configuration and maintenance. The device is designed to operate under environmental conditions that are specified in its datasheet. Ensure proper ventilation of the controller and avoid areas where corrosive, deteriorating or explosive vapors, fumes or gases may be present. Do not drop the controller or subject it to physical shock. If the controller is used and/or installed in a manner not specified by Distech Controls, the functionality and the protection provided by the controller may be impaired. Any type of modification to any Distech Controls product will void the products warranty. Before installation of the Wireless Receiver, verify that local communication regulations allow the installation of wireless devices that operate at a frequency of 315 MHz or 868.3MHz. Refer to the Open-to-Wireless Solution Guide for more information. Take reasonable precautions to prevent electrostatic discharges to the controller when installing, servicing or operating the controller. Discharge accumulated static electricity by touching ones hand to a securely grounded object before working with this controller.

3. General Wiring Recommendations


Turn off power before any kind of servicing.

All wiring must comply with electrical wiring diagrams as well as national and local electrical codes. To connect the wiring to a controller, use the terminal connectors. Use a small flat screwdriver to tighten the terminal connector screws once the wires have been inserted. Comply with all BACnet network and power supply guidelines outlined in the Network Guide. Power type cables (i.e. for power, 2- and 3-wire voltage and current inputs and outputs, as well as triac outputs) should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires. The board connectors accept wires or flat cables ranging from 22 to 14AWG (0.644-1.630mm diameter) per pole. However, power cables must remain between 18 and 14AWG (1.0241.630mm diameter). Do not connect the universal inputs, analog/digital outputs or common terminals to earth or chassis ground (unless stated otherwise). Keep all wires away from high speed data transmission cables (for example, Ethernet, etc.). Keep input and output wiring in conduits, trays or close to the building frame if possible.

Figure 4-1:

Typical Damper Shaft End Marking

4. Determine the direction required to close the damper: Clockwise (CW) or Counterclockwise (CCW). Turn the damper shaft with a pair of pliers to fully close the damper for 90 boxes or fully open the damper for 45 or 60 boxes 5. Press and hold down the Actuator Clutch For Manual Adjustment button (see Figure 5-3), and turn the controllers shaft coupler until it touches the mechanical end-stop to either the fully closed position (90 boxes) or the fully open position (45 and 60 boxes). 6. For 90 VAV boxes: If the damper closes CCW, turn the coupler to the CCW mechanical stop limit. If the damper closes CW, turn the coupler to the CW mechanical stop limit. The open mechanical stop is factory preset for 90 boxes. For 45 and 60 VAV boxes: The mechanical stops must be set for both the fully closed and fully open damper positions. By installing the controller at the fully open position, the controller provides the open mechanical stop for 45 and 60 boxes. The closed damper seal provides the fully closed stop. Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

61.5 [2.42]

7. Tighten the U-Bolt clamp on to the damper shaft using an 8 mm (5/16 in.) wrench or socket. Tighten the bolts between 11 and 15 Nm (100 and 130 lbin). 8. Test for free damper shaft movement: Press and hold down the Actuator Clutch For Manual Adjustment button and manually turn the actuator coupling to be certain that the actuator can rotate from full closed to full open positions without binding. 9. Connect the VAV boxs flow sensor tubing to the controllers Pressure Sensor Inputs. Create a condensation trap in the pneumatic tubing by forming it into a vertical loop. 10. Finalize the installation by rotating the damper to the full open position. CAUTION: Risk of Property Damage. Ensure that the damper is at the full open position before starting the air handler. Failure to rotate the damper to its full-open position may result in damage to the Variable Air Volume (VAV) box or ductwork when the air handler is started.

190 [7.48 ]

10 [0.40]

11 [0.43]

54 [2.13 ]

High pressure Low pressure 3 mm 0.12 in

Bracket mouting kit

5 [0.2]

Units Legend: mm [in]


min. 40 mm (1.5")

Figure 5-2:

VAV-N & ECB-103 series dimensions

Figure 4-2:

Mounting a controller on a damper shaft

5. Controller Dimensions & Components

Figure 5-3:

VAVS-O, VAVS, VAV & VVTS series components

Figure 5-4:

VAV-N & ECB-103 series components

Figure 5-1:

VAVS-O, VAVS, VAV & VVTS series dimensions

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

26.5 [1.04]

6. Power Wiring
Voltage: 24VAC; 15%, Class 2
This is a Class 2 Product. Use a Class 2 transformer only (rated at 100VA or less at 24VAC) to power the controller(s). The Network Guide provides extensive information and requirements for powering a VAV that uses a BACnet network for communications. It can be downloaded at the www.distechcontrols.com website. It is recommended to wire only one controller per 24VAC transformer. If only one 24VAC transformer is available, determine the maximum number of VAVs that can be supplied on a single power cable supplied by a 100 VA transformer, according to the cables wire gauge and the total cable length from the following table. Table 6-1:
AWG
Controller 1 24 VAC 24 VCOM Controller 2 24 VAC 24 VCOM

Fuse: 4 A Max . Fast Acting AC Transformer Electrical System Ground

Figure 6-1:

Power wiring

7. Input Wiring
Each controller has physical connections for inputs (marked as UIx) that are configured in EC-gfxProgram. Each input can be configured for digital, resistive, current, or voltage signals. Input types must be configured properly in software to ensure proper input readings. Before connecting sensor to the controller, refer to the installation guide of the equipment manufacturer.

Maximum Number of VAV Devices on a Power Run


Maximum Number of Devices @ 7 VA per device1 4 5 5 5 3 5 5 3 5 Maximum Number of Devices @ 10 VA per device2 2 3 4 5 2 3 4 2 3 Maximum Number of Devices@ 15 VA per device3 1 2 3 4 1 2 3 1 2

Power Run Total Cable Length 75M (250 feet) 60M (200 feet) 45M (150 feet) 30M (100 feet) 60M (200 feet) 45M (150 feet) 30M (100 feet) 45M (150 feet) 30M (100 feet)

144 14 14 14 16 16 16 18 18

For a wire length less than 75 (23m), either a shielded or unshielded 18AWG wire may be used. For a wire up to 200 (61m) long, a shielded 18AWG wire is recommended. The shield of the wire should be grounded on the controller side and the shield length should be kept as short as possible.

Wiring Digital Inputs


This input configuration is used to monitor digital dry contacts, as well as pulsed contacts.
Digital Dry Contact NO-NC UIx COM

1. Typical VAV with 1 EC-Smart-Vue and actuator activated. No external loads. 2. Typical VAV with 1 EC-Smart-Vue, 2 triac loads (1.6 VA each), 1 analog output (20 mA), and actuator activated. 3. Typical VAV with 1 EC-Smart-Vue, 4 triac loads (1.6 VA each), 2 analog outputs (20 mA each), and actuator activated. 4. Device terminals are not capable of accepting two 14 AWG wires (when daisy-chaining devices). Use a wire nut with a pig tail to make such a connection. Any installation condition that is outside of the parameters of Table 6-1 should be avoided. Use an external fuse on the 24VAC side (secondary side) of the transformer, as shown in Figure 6-1, to protect all controllers against power line spikes. Maintain consistent polarity when connecting controllers and devices to the transformer. One terminal on the secondary side of the transformer must be connected to the buildings ground. All 24V COM terminals of all controllers and peripherals throughout the BACnet MS/TP network must be connected to the grounded transformer terminal as shown in Figure 6-1. This ensures that the 24V COM terminals of all devices connected to any BACnet MS/TP bus in the building are at the same potential. A mechanical ground is unacceptable: Do not use a pipe, conduit, or duct work for a ground. The power supply must have a dedicated ground wire that comes from the main electrical supply panel. Failure to maintain consistent polarity throughout the entire BACnet MS/TP network will result in a short circuit and/or damage to the controller! The COM terminals of the controller are internally wired to the 24V COM terminal of the power supply. Connecting a peripheral or another controller to the same transformer without maintaining polarity between these devices will cause a short circuit. 4

Figure 7-1:

Digital dry contact (NO & NC)

Wiring Resistive Inputs


This input configuration is used to monitor Resistance Temperature Detectors (RTD), thermistors such as 1000 RTDs to 10k type II and III thermistors, as well as 10k and 100k potentiometers.
RTD/ Thermistor UIx COM

Figure 7-2:

RTD /Thermistor input

Figure 7-3:

10k Potentiometer input

Wiring Current Inputs


Current inputs have a range of 0 to 20mA. Depending on the transducer power requirements, any one of the following input configurations can be used. Use the following configuration for a 2wire, 0-20mA transducer powered by the controllers internal 15VDC power supply.

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

+15VDC Transducer
+

Table 8-1:
To Controllers Analog-To-Digital Converter

0-20mA 249 / W

UIx COM

T568A and T568B Terminations for an RJ-45 Connector


T568B (at both cable ends) Pair Color 2 white/orange stripe 2 green solid orange solid 3 white/orange stripe white/green stripe 1 blue solid blue solid 1 white/blue stripe white/blue stripe 3 orange solid green solid 4 white/brown stripe white/brown stripe 4 brown solid brown solid

Pin 1

T568A (at both cable ends) Pair Color 3 white/green stripe 3 2 1 1 2 4 4

Figure 7-4:

Current input 2-wire transducer powered by the controller

2 3 4 5 6 7 8

Use the following configuration for a 2-wire, 0-20mA transducer powered by an external 24 AC/DC power supply.
0-20mA

Figure 7-5:

Current input 2-wire transducer, externally powered

Use the following configuration for a 3-wire, 0-20mA transducer powered by an external 24 AC/DC power supply.
0-20mA

Figure 7-6:

Current input 3-wire transducer, externally powered

Use the following configuration for a transducer powered by its own power source.
0-20mA

The final result of a crimped RJ-45 connector is shown graphically below.


T568A T568B

1 2 3 4 5 6 7 8

Key:

1 2 3 4 5 6 7 8

Figure 7-7:

Current input Transducer with its own power source


Stripe Solid

Wiring Voltage Inputs


Voltage inputs have a range of 0 to 10VDC or 0 to 5VDC. Connect the voltage input according to the following figure if a 3-wire 0-10V or 0-5V transducer is being used.
Transducer +
Common 24VAC 24VAC

Pair 3 Pair 1 Pair 2 Pair 4

Pair 2 Pair 1 Pair 3 Pair 4

Figure 8-1:

0-10V

UIx COM

T568A and T568B Crimp Wire Sequence for an RJ-45 Connector

Figure 7-8:

Voltage input 3-wire transducer

Connect the voltage input according to the following figure if the transducer is powered by its own power source.
Transducer + 0-10V UIx COM

Figure 7-9:

Voltage input Transducer with its own power source

Figure 8-2:

Pins on RJ-45 Jack Face

8. EC-Smart-Vue Wiring
The EC-Smart-Vue is a Communicating room temperature sensor with backlit display and graphical menus. and has VAV balancing capabilities. Connect the EC-Smart-Vue to the controller with a standard Category 5e Ethernet patch cable fitted with RJ-45 connectors. If you make your own patch cable, use Category 5e cable crimped with RJ-45 connectors either as T568A or T568B.

Patch cables fitted with connectors supplied by Distech Controls are wired as T568B.

Do not crimp one connector as T568A and crimp the other connector as T568B on the same cable. Protect the controllers connector from being pulled on when a cable to the EC-Smart-Vue is connected. Create a strain-relief by looping the cable and attaching it to a solid object with a nylon tie so that a tug on the cable will not pull out the connector on the controller. 5

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

9. Output Wiring
The controllers have physical connections for either digital (triac) and/or universal outputs, depending on the type and model. The power source type for digital outputs is hardware configurable and must be configured by changing the jumper settings on the printed circuit board. The universal outputs are software configurable. Before connecting an output device (actuator, relay, etc.) to the controller, refer to the installation guide of the equipment manufacturer.
JUMPER SETTINGS

Actuator DOx Cx-x DOx ~ ~

Figure 9-4:

Digital output with internal power supply Floating actuator

Wiring Universal Outputs (UOx)


Universal outputs can be configured to provide either a discrete signal of 0 or 12VDC or a linear signal ranging from 0 to 10VDC. The discrete signal can be used to generate a pulse wave modulation (PWM) signal or a simple two-state signal. These outputs are protected by an auto-reset fuse. Wiring Discrete Outputs If a 12VDC relay is being controlled, connect it to a universal output according to the following figure.
UOx COM
A1 A2

For a wire length less than 75 (23m) long, either a shielded or unshielded 18AWG wire may be used. For a wire up to 200 (61m) long, a shielded 18AWG wire is recommended. The shield of the wire should be grounded on the controller side and the shield length should be kept as short as possible.

Wiring Digital Outputs (DOx)


The digital outputs are all made of triacs and can be configured as either powered outputs or non-powered outputs and output wiring must be done accordingly. Figure 9-5:

12VDC Relay

Discrete 0 or 12VDC universal output Relay

Wiring Voltage Outputs Connect the 0 to 10VDC output according to the following figure.
UOx COM
0-10VDC Common

The non-powered output type does not have any voltage on the output terminals when the output is active. Power must be supplied externally. - The powered output type has 24VAC on the output terminals when the output is active. Power is therefore supplied internally by the controller. It should be noted that all controllers are shipped with all digital outputs configured as powered outputs. Maximum output current for all digital outputs (whether powered or non-powered) is 0.5A continuous or 1A @ 15% duty cycle for a 10-minute period. DO1 and DO2 share the same C1-2 common terminal and are controlled by a single jumper and must therefore be set identically. Similarly, DO3 and DO4 (VAV, VVT and ECB-103 product lines only) share the same C3-4 common terminal and are controlled by a single jumper and must therefore be set identically. The jumpers are used to specify whether an internal or external power source is being used. If a 24VAC relay is being controlled using an external or internal power supply, connect the digital output according to the following figures.
DOx Cx-x JUMPER SETTINGS AC 24VAC Relay
A2

Figure 9-6:

Voltage 0-10VDC universal output

If an analog actuator is being controlled, connect the 0 to 10VDC output, along with an external 24VAC power source, to the analog actuator according to the following figure.
Actuator COM UOx ~+
24VAC 0-10VDC

Figure 9-7:

Voltage 0-10VDC universal output Analog actuator

To measure the state of a triac output, an external load must be connected.

10. Communications Wiring


The Network Guide provides extensive information and requirements to implement a BACnet MS/TP network. It contains information about network and sub network length, cable type, device addressing, etc. It can be downloaded at the www.distechcontrols.com website. For optimal performance, use Distech Controls 24 AWG (0.65 mm) stranded, twisted pair shielded cable or refer to the Network Guide for cable specification. The BACnet MS/TP communication wire is polarity sensitive and the only acceptable topology is to daisy-chain the cable from one controller to the next.

A1

Figure 9-1:

Digital output with external power supply Relay


DOx Cx-x
A2 A1

JUMPER SETTINGS

24VAC Relay

Figure 9-2:

Digital output with internal power supply Relay

If a floating actuator is being controlled using an external or internal power supply, connect the digital output according to the following figures.
Actuator DOx Cx-x DOx ~
24VAC

JUMPER SETTINGS

Figure 9-3:

Digital output with external power supply Floating actuator

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

As shown in Figure 10-1 below: - The first and last daisy-chained BACnet MS/TP device must have its EOL resistors enabled / installed. All other devices must have their EOL resistor disabled (default factory setting). - When the BACnet MS/TP data bus is connected to a following device, twist data bus shields together. - Isolate all shields with electrical tape so there is no exposed metal that can touch ground or other conductors. - The shield of the data bus must be connected to the electrical system ground at only one point usually at one end of the bus as shown below. - Connect no more than 50 devices to a BACnet MS/TP data bus.
First and last daisy-chained device: - EOL Jumpers are ON All other Devices: - EOL Jumpers are OFF Typical BACnet Device
EOL ON

1. Connect an EC-Smart-Vue to the controller with a Cat 5e patch cable. Wait for the Bell icon and the number 1 to flash on the display. 2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display. 3. Use the down button to set the number to 9995 (this is the default password). 4. Use the Menu button to select SUBNET ID. The current controllers Subnet ID is shown. 5. Use the up and down buttons to set the controllers Subnet ID. Tip: Hold down either the up or down button to fastadvance the display value. 6. Press the Menu button once to apply the value. 7. Press and hold the Menu button for 5 seconds to exit the configuration menu. The EC-Smart-Vue can now be used to go from one ECB series controller to the next for commissioning purposes.

Typical BACnet Device


EOL OFF

Typical EC-BOS Device EOL ON: For the EC-BOS as the first or last daisychained device:

NET+

NET+

NET-

NET-

- OPTIONALLY set the EOL jumper internally - AND add a 120 Ohm EOL resistor as shown here

13. Commissioning ECB-Series Controllers


+ S The shield of the data bus must be connected to the electrical system ground at only one point usually at one end of the bus as shown.

Data Bus Shields: Twist together and Isolate with electrical tape Data Bus: Shielded Twisted Pair Cable Data Bus Shield: Isolate with electrical tape

12

Up to 50 Devices Total Data Bus Shield: Connect to the S terminal

Figure 10-1:

Communications wiring

To commission the ECB-VAV (before code is downloaded to the ECB-VAV from EC-gfxProgram), connect an EC-Smart-Vue to the ECB-VAV with its Subnet ID set to 1. During commissioning, the EC-Smart-Vue is used to set the ECB-VAVs BACnet MAC Address and to perform application selection if needed. Applications are pre-loaded programs that enable the ECB-VAV to control a typical VAV box. Set the connected controllers MAC Address as follows: 1. Connect an EC-Smart-Vue to the controller with a Cat 5e patch cable. Wait for the display to show the room temperature. 2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display. 3. Use the down button to set the number to 9995 (this is the default password). 4. Use the Menu button to select GEN CFG. 5. Press the down button once to enter the GEN CFG submenu. The MAC ADDRESS menu is shown with the current controllers BACnet MAC Address. 6. Use the up and down buttons to set the controllers MAC Address. Only addresses from 1 to 127 are recommended to be used. 7. Press the Menu button once to apply the value. 8. Press and hold the Menu button for 5 seconds to exit the configuration menu. Once the BACnet MS/TP network is operational, the controller can be programmed with EC-gfxProgram. For each EC-Smart-Vue, set its Subnet ID number to the block number of its associated CommSensor block in EC-gfxProgram. This is done in the EC-Smart-Vues GEN CFG menu under SUBNET ID.

If inserting multiple wires in the terminals, ensure to properly twist wires together prior to inserting them in the terminal connectors. For more information and detailed explanations on network topology and wire length restrictions, refer to the Network Guide, which can be downloaded at the www.distech-controls.com website.

11. Device Addressing


The Network Guide provides extensive information and requirements to implement a BACnet MS/TP network. It contains information about network planning and MAC Address numbering schemes. It can be downloaded from the www.distech-controls.com website. The MAC Address must be set according to your network planning document by connecting an EC-Smart-Vue sensor to the controller as shown in Figure 21-1. The device instance (DevID) is automatically configured when setting the MAC Address to prevent network address conflict. The following formula is used to determine the device instance: DevID = 364 * 1000 + MAC For example: MAC: 37 DevID = 364 * 1000 + 37 = 364037 The Device Instance can be changed once the controller has been commissioned through the building controller.

12. Setting the EC-Smart-Vue Subnet ID


ECB Series controllers can be commissioned with an EC-Smart-Vue. The default Subnet ID for an EC-Smart-Vue is 1. To commission an ECB Series controller, the EC-Smart-Vues Subnet ID must be set to 1. If the EC-Smart-Vues Subnet ID has been set to another value (for example, the display flashes error code 1 with the Bell icon when the EC-Smart-Vue is connected to a controller for commissioning), change the Subnet ID to 1 as follows: Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com 7

14. Setting the BAUD Rate (optional)


By default, the BAUD rate for the controller is set to automatically detect the current communication BAUD rate of the connected BACnet MS/TP network (AUTO). This is the preferred setting for a controller. However, at least one controller on the BACnet MS/TP network data bus must have its BAUD rate set. The preference is to set the building controllers BAUD rate (if present). Otherwise, set the BAUD rate on one controller that will set the BAUD rate for all other controllers (to act as the master for setting the BAUD rate). When the Baud rate is set to AUTO, the controller cannot initiate any communication until it has detected the baud rate of the BACnet MS/TP network. If all controllers on the BACnet MS/TP network are set to AUTO, then all controllers will not communicate. Set the connected controllers BAUD rate as follows: 1. Connect an EC-Smart-Vue to the controller with a Cat 5e patch cable. Wait for the display to show the room temperature. 2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display. 3. Use the down button to set the number to 9995 (this is the default password). 4. Use the Menu button to select GEN CFG. 5. Press the down button once to enter the GEN CFG submenu. The MAC ADDRESS menu is shown. 6. Use the Menu button to select BAUD RATE. The current controllers BAUD rate is shown. 7. Use the up and down buttons to set the controllers Baud rate. AUTO detects and uses the Baud rate currently being used by the BACnet MS/TP network. 8. Press the Menu button once to apply the value. 9. Press and hold the Menu button for 5 seconds to exit the configuration menu.

Figure 15-1:

Location of the Wireless Receivers telephone socket

Connecting to the Controllers Wireless Port


Each controller has a wireless port in which one end of the Wireless Receivers telephone cable plugs in. Uncover the controller to locate the wireless port on the PCB board (marked as Wireless Module).

16. Network Access from the Sensor


To temporarily access the BACnet MS/TP network for commissioning and maintenance purposes, connect a portable router to the stereo audio plug located on the lower edge of the ECSmart-Vue. Wire a standard three-conductor 3.5 mm () audio jack as shown below.
LAN Access Connector NET+ NETShield BACnet MS/TP Router with Isolated RS-485 Port

15. Wireless Installation


When connected to a Wireless Receiver, controllers can receive input signals from a wide selection of wireless devices. Compatible wireless devices include temperature sensors, duct sensors, window/door contacts and light switches. These devices are easy to install, highly adaptable and have no limitations as to the building materials to which they can be mounted. The Wireless Receiver is available in 315MHz or 868.3MHz frequencies.
To Portable Router - Temporary Commissioning and Maintenance Connection - No EOL Resistors are Necessary

EC-Net Pro

Figure 16-1:

3.5mm stereo audio jack connection for a Portable Router

Connecting the Wireless Receiver


The Wireless Receiver is connected to the controller using a telephone cable with 4P4C modular connectors at both ends. The Wireless Receivers telephone socket is located inside the device. To locate it, open the Wireless Receiver by separating its front and back plates.

Ensure the BAC/LON jumper is set to the BAC position (this is the default jumper position).

BAC LON

Network Type Jumper

3.5 mm (1/8) Network Access Jack

Figure 16-2:

EC-Smart-Vue BAC/LON Jumper: Set to the BAC (BACnet) Position

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

17. Terminal Block Cover


In certain jurisdictions, terminal block covers are required to meet local safety regulations. Terminal block covers are available for all controllers and are used to conceal the controllers wire terminals. Terminal block covers are optional and are sold as peripherals. The terminal block cover can be clipped on to the controller as shown below.

20. FCC Statement


Changes or modifications not expressly approved by Distech Controls could void the user's authority to operate the equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. - Consult the dealer or an experienced radio/TV technician for help.

Figure 17-1:

Terminal block cover installation

18. Maintenance
Turn off power before any kind of servicing.

Each controller requires minimal maintenance, but it is important to take note of the following:

If it is necessary to clean the outside of the controller, use a dry cloth. Verify the tension of all wires and cables whenever the controller is serviced.

19. Disposal
The Waste Electrical and Electronic Equipment (WEEE) Directive sets out regulations for the recycling and disposal of products. The WEEE2002/96/EG Directive applies to standalone products, for example, products that can function entirely on their own and are not a part of another system or piece of equipment. For this reason Distech Controls products are exempt from the WEEE Directive. Nevertheless, Distech Controls products are

marked with the WEEE symbol , indicating that disposal of the devices shall not be done together with municipal waste. Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive.

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

21. Typical Variable Air Volume Application Wiring Diagram

Do not pull on connector

EOL Enabled at the last sensor at the end of the Bus


ON

EOL

From Previous Device


BACnet MS/TP Network

OFF

To Next Device Data Bus Shields: Twist together and Isolate with electrical tape

Wireless Port (beneath cover)

ECB-VAVS

Heating Floating Actuator


PRESSURE HIGH LOW

Fuse

24VAC

EC-Smart-Vue
L
120 / 220 VAC

N GND

Electrical System Ground

Figure 21-1:

Typical Power and Network Connections with an EC-Smart-Sensor Input and Floating Actuator Output

Do not pull on connector

Data Bus Shields: Twist together and Isolate with electrical tape From Previous Device
BACnet MS/TP Network

EC-Sensor Connectors

EC-Sensor

NET+ NETSHIELD

To Next Device

Wireless Port (beneath cover)

COMMON TEMP SETPOINT FANSPEED LED

ECB-VAVS

Heating Floating Actuator


PRESSURE HIGH LOW

Fuse

24VAC

L
120 / 220 VAC

N GND

Electrical System Ground

Figure 21-2:

Typical Power and Network Connections with an EC-Sensor Input and Floating Actuator Output

10

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

22. Troubleshooting guide


Controller is powered but does not turn on
Fuse has blown Power supply polarity Disconnect the power.Check the fuse integrity. Reconnect the power. Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the 24VCOM terminal of each controller is connected to the same terminal on the secondary side of the transformer. See Figure 61. 1. Check power supply voltage between 24VAC 15% and 24VCOM pins and ensure that it is within acceptable limits. 2. Check for tripped fuse or circuit breaker. Verify that the transformer used is powerful enough to supply all controllers. Double check that the wire connections are correct. Check the network termination(s). Configure the maximum number of master device on the MS/TP network in all devices to the controllers highest MAC address used on the MS/TP trunk. Check that the total wire length does not exceed the specifications of the Network Guide. Check that the wire type agrees with the specification of the Network Guide. Double check that the wire connections are correct. Check the network termination(s). Incorrect or broken termination(s) will make the communication integrity dependent upon a controllers position on the network. The number of controllers on a channel should never exceed 50. Use a router or a repeater in accordance to the Network Guide. Configure the maximum number of master device on the MS/TP network in all devices to the controllers highest MAC address used on the MS/TP trunk. Each controller on a BACnet MS/TP data bus must have a unique MAC Address. Use an EC-Smart-Vue to check the MAC Address of each controller. Each controller on a BACnet intranetwork (the entire BACnet BAS network) must have a unique Device ID. Use an EC-Smart-Vue to check the Device ID of each controller. Check that the wiring is correct according to this manual and according to the peripheral devices manufacturer. Using a voltmeter, check the voltage on the input terminal. Short circuit (0V) and open circuit (5V). Using the controller configuration wizard, check the configuration of the input. Refer to the controllers user guide for more information. An over-voltage or over-current at one input can affect the reading of other inputs. Respect the allowed voltage / current range limits of all inputs. Consult the appropriate datasheet for the input range limits of this controller. Disconnect the power and outputs terminals. Then wait a few seconds to allow the auto-reset fuse to cool down. Check the power supply and the output wiring. Reconnect the power. Check that the wiring is correct according to this manual and according to the peripheral devices manufacturer. Using the controller configuration wizard, check the configuration of the output. Refer to the controllers user guide for more information. Check the polarity of the 24VAC power supply connected to the actuator while connected to the controller. Reverse the 24VAC wire if necessary. Check the jumper settings for the external power supply as shown in Figure 9-3. Using the device configuration wizard, check the configuration of the input. Refer to the devices user guide for more information. 1. Recharge device with light (if solar-powered) or replace battery (if battery-powered), 2. Ensure sufficient light intensity (200lx for 4 hours/day). Reposition the device to be within the range of the Wireless Receiver. For information on typical transmission ranges, refer to the Open-to-Wireless Solution Guide. Using the device configuration plug-in or wizard, check the configuration of the input. Refer to the Wireless Batteryless Sensors and Switches Solutions Guide for more information. 1. Make sure that the tubing is installed properly and that the tubing is not bent. 2. Verify that the high and low pressure sensors are not inversed. Recalibrate the controller. Refer to the controllers user guide for more information. The two mechanical stops must be positioned to stop the damper motion when it is completely closed and completely opened. The mechanical stops can be moved by increments of 5. Set the Override to OFF in the wizard. Data is not being received from the BACnet MS/TP data bus. Data is not being transmitted onto the BACnet MS/TP data bus.

Controller cannot communicate on an BACnet MS/TP network


Absent or incorrect supply voltage

Overloaded power transformer Network not wired properly Absent or incorrect network termination Max Master parameter

Controller communicates well over a short network, but does not communicate on large network
Network length Wire type Network wiring problem Absent or incorrect network termination Number of controllers on network segment exceeded Max Master parameter There is another controller with the same MAC Address on the BACnet MS/TP data bus There is another controller with the same Device ID on the BACnet intranetwork Input wiring problem Open circuit or short circuit Configuration problem Over-voltage or over-current at an input

Hardware input is not reading the correct value

Hardware output is not operating correctly


Fuse has blown (Auto reset fuse) Output wiring problem Configuration problem 0-10V output, 24VAC powered actuator is not moving. Device not associated to controller Power discharge Device too far from the Wireless Receiver Configuration problem

Wireless devices not working correctly

Flow sensor is not giving proper readings


Tubing connection problem Controller is not calibrated properly Mechanical stops not in proper position Controller in Override

Damper is not opening or closing properly

Rx/Tx LEDs
RX LED not blinking TX LED not blinking

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com

11

Status LED Normal Operation


Fast blink Solid ON The Status LED is always OFF Initialization. The device is starting up. Firmware upgrade in progress. Controller operation is temporarily unavailable. The new firmware is being loaded into memory. This takes a few seconds. Do not interrupt power to the device during this time. The controller is operating normally.

Status LED blink patterns Repeats every 2 seconds (highest priority shown first)
Fast blink continuous:
(150ms On, 150ms Off, continuous)

Initialization or firmware upgrade The device is starting up or being upgraded.

Long Long Long blink


(800ms On, 300ms Off, 800ms On, 300ms Off, 800ms On)

The controller is offline. Appropriate action: Set the controller Online Poor-quality power; The device has browned-out: The voltage at the 24VAC and 24VCOM terminals has gone below the devices acceptable limit during power up. Invalid MAC address: The devices MAC address is set to zero (0) or is set to an address higher than the Max Master. See the Network Guide. Backup and Restore. The controller is being backed-up or restored.

Short Short Long blink


(150ms On, 300ms Off, 150ms On, 300ms Off, 800 ms On)

Short Long blink


(150ms On, 300ms Off)

Long Short Short Short Short Long Short:


(800ms On, 300ms Off, 150ms On, 300ms Off, 150ms On, 300ms Off, 150ms On, 300ms Off, 150ms On, 300ms Off, 800ms On, 300ms Off, 150ms On)

For issues with the EC-Smart-Vue, refer to the EC-Smart-Vue Hardware Installation Guide.

Hardware Installation Guide - ECB-VAVS-O, ECB-VAVS, ECB-VAV, ECB-VVTS, ECB-VAV-N, ECB-103 05DI-HIBVAVT-13
Copyright Distech Controls Inc. First printed March 2010 While all efforts have been made to verify the accuracy of information in this manual, Distech Controls is not responsible for damages or claims arising from the use of this manual. Persons using this manual are assumed to be trained HVAC specialist / installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail-safe environments. Distech Controls reserves the right to change, delete or add to the information in this manual at any time without notice. Distech Controls and the Distech Controls logo are registered trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE. NiagaraAX Framework is a registered trademark of Tridium, Inc. EnOcean is a registered trademark of EnOcean GmbH.

*05DI-HIBVAVT-13*
05DI-HIBVAVT-13

Distech Controls, Inc. Toll-free: 1-800-404-0043 Tel. International: 450-444-9898 www.distech-controls.com sales@distech-controls.com