LIGHTOLIER A PHILIPS 48"L. X 2"W. X 3.187"H. LINEAR 2x 120 TO 277V 50/60Hz ELECTR / Luminaire Data Sheet
Luminous emittance 1: See our luminaire catalog for an image of the luminaire.
Luminous emittance 1:
Page 1
Project 1
08.06.2012
Room 1 / Summary
Height of Room: 4.550 m, Mounting Height: 3.000 m, Light loss factor: 0.90 Surface Workplane Floor Ceilings (5) Walls (4) U [%] / 20 77 50 Eav [lx] 553 522 167 281 Emin [lx] 127 159 2.48 34
Values in Lux, Scale 1:195 Emax [lx] 781 681 3754 645 u0 0.229 0.304 / /
Workplane: Height: 0.800 m Grid: 128 x 64 Points Boundary Zone: 0.000 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.463, Ceiling / Working Plane: 0.303. Luminaire Parts List No. 1 Pieces 34 Designation (Correction Factor) LIGHTOLIER A PHILIPS 48"L. X 2"W. X 3.187"H. LINEAR 2x 120 TO 277V 50/60Hz ELECTR (1.000) Total: ) (Luminaire) [lm] 6600 224400 Total: ) (Lamps) [lm] 10000 P [W] 113.1
340000 3844.4
Specific connected load: 12.03 W/m = 2.17 W/m/100 lx (Ground area: 319.67 m)
Page 2
Project 1
08.06.2012
Page 3
Project 1
08.06.2012
Uniformity on the working plane u0: 0.229 (1:4) Emin / Emax: 0.162 (1:6) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.463, Ceiling / Working Plane: 0.303. Specific connected load: 12.03 W/m = 2.17 W/m/100 lx (Ground area: 319.67 m)
Page 4
Project 1
08.06.2012
Values in Lux, Scale 1 : 186 Not all calculated values could be displayed. Position of surface in room: Marked point: (11.338 m, 8.188 m, 0.800 m)
Grid: 128 x 64 Points Eav [lx] 600 Emin [lx] 413 Emax [lx] 777 u0 0.687 Emin / Emax 0.531