Cover Page .................................................................1 Table of Contents ........................................................3 Intro Page ...................................................................4 1 Roofing.....................................................................5 2 Exterior.....................................................................6 3 Garage .....................................................................9 4 Interiors ..................................................................10 5 Structural Components .......................................... 11 6 Plumbing System ...................................................13 7 Electrical System ...................................................16 8 Heating / Central Air Conditioning..........................20 9 Insulation and Ventilation .......................................23 10 Built-In Kitchen Appliances ..................................26 General Summary.....................................................27 Invoice.......................................................................32 Back Page.................................................................33
Page 3 of 33
Date: 5/25/2012 Property: 1001 Tokedokey Trail Connestee Falls Brevard NC 28712
Comment Key or Definitions The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property. Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear. Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting. Not Present (NP) = This item, component or unit is not in this home or building. Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
In Attendance: Vacant (inspector only) Type of building: Single Family (1 story) Approximate age of building: Over 10 Years
Weather: Clear
Radon Test: No
Water Test: No
Page 4 of 33
IN NI NP RR 1.0 Roof Coverings 1.1 Flashings 1.2 Skylights, Chimneys and Roof Penetrations 1.3 Roof Drainage Systems
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
IN NI NP RR
Comments:
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Page 5 of 33
IN NI NP RR 2.0 Wall Cladding Flashing and Trim 2.1 Doors (Exterior) 2.2 Windows Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining 2.3 Walls (With respect to their effect on the condition of the building) 2.4 Eaves, Soffits and Fascias
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
IN NI NP RR
Comments:
Page 6 of 33
2.0 Picture 3 Chimney Flashing 2.1 The two sliding glass doors, one in each bedroom, are difficult to slide from the midpoint to the fully open position. Recommend further evaluation/repair by a window and door specialist.
Page 7 of 33
Page 8 of 33
IN NI NP RR
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
Comments:
Page 9 of 33
IN NI NP RR 4.0 Ceilings 4.1 Walls 4.2 Floors 4.3 Steps, Stairways, Balconies and Railings 4.4 Counters and Cabinets (representative number) 4.5 Doors (representative number) 4.6 Windows (representative number)
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
IN NI NP RR
Comments: 4.6 1) The kitchen window will not stay in the open position. 2) The master bath window is operable, but very difficult to open and the sill is loose. 3) The laundry room window is not operable and the sill is loose. 4) The second bath window is operable, but difficult to open. 5) The dining room windows to the left of the door, the middle of the right side, and the right side rear are inoperable. 6) The dining room window to the right of the door is operable, but with difficulty. Recommend further evaluation/repair by a window and door specialist.
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Page 10 of 33
IN NI NP RR Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water 5.0 penetration into the building or signs of abnormal or harmful condensation on building components.) 5.1 Walls (Structural) 5.2 Columns or Piers 5.3 Floors (Structural) 5.4 Ceilings (Structural) 5.5 Roof Structure and Attic
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
IN NI NP RR
Comments:
Page 11 of 33
Page 12 of 33
IN NI NP RR 6.0 Plumbing Drain, Waste and Vent Systems 6.1 Plumbing Water Supply, Distribution System and Fixtures 6.2 Hot Water Systems, Controls, Chimneys, Flues and Vents 6.3 Main Water Shut-off Device (Describe location) 6.4 Fuel Storage and Distribution Systems (Interior fuel storage, piping, venting, supports, leaks)
Plumbing Water Distribution (inside home): POLY Washer Drain Size: 2" Diameter Plumbing Waste: PVC Water Heater Power Source: Electric Water Heater Capacity: 50 Gallon (2-3 people) Manufacturer: Whirlpool Water Heater Location: Crawlspace
IN NI NP RR
Comments:
Page 13 of 33
Page 14 of 33
6.1 Picture 1 6.2 Water Heater: Model:E2F40RD45U Serial: 0721139159 Manufactured: 1992
6.3 The main water supply enters through the front foundation wall. The shut-off is located near the point of entry.
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Page 15 of 33
IN NI NP RR 7.0 Service Entrance Conductors 7.1 7.2 Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage
Connected Devices and Fixtures (Observed from a representative number operation 7.3 of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) Polarity and Grounding of Receptacles within 6 feet of interior plumbing fixtures, all 7.4 receptacles in garage, carport and exterior walls of inspected structure 7.5 Operation of GFCI (Ground Fault Circuit Interrupters) 7.6 Location of Main and Distribution Panels 7.7 Smoke Detectors 7.8 Carbon Monoxide Detectors
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
IN NI NP RR
Comments:
Page 16 of 33
7.1 Picture 2
7.1 Picture 3 Service Entrance Conductor 7.2 The service panel has two circuits labeled "heat pump", one 30 amp and one 60 amp. The maximum circuit breaker for the heat pump is 30 amp. The air handler was probably mislabeled "heat pump". A 60 amp breaker may be correct for the air handler with electrical heat strips, however, the maximum circuit breaker size was not shown on the air handler, and because at least one of the circuit breakers labeled "heat pump" is a 60 amp, it is possible that the circuit breaker for the heat pump is oversized. Recommend further evaluation by a licensed electrician.
Page 17 of 33
Page 18 of 33
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Page 19 of 33
IN NI NP RR 8.0 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 Heating Equipment Normal Operating Controls Automatic Safety Controls Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) Presence of Installed Heat Source in Each Room Chimneys, Flues and Vents (for fireplaces, gas water heaters or heat systems) Solid Fuel Heating Devices (Fireplaces, Woodstove) Gas/LP Firelogs and Fireplaces Cooling and Air Handler Equipment Normal Operating Controls
(excluding wood): One Heat System Brand: TRANE Ductwork: Insulated Filter Type: Disposable Filter Size: 20x25 Types of Fireplaces: Solid Fuel Insert Operable Fireplaces: One Number of Woodstoves: None Cooling Equipment Type: Heat Pump Forced Air (also provides warm air) Cooling Equipment Energy Source: Electricity Central Air Manufacturer: NONE Number of AC Only Units: None
IN NI NP RR
Comments:
Page 20 of 33
8.1 The HVAC system responds to normal operating controls. The thermostat is located in the living room. On the day of the inspection the outside air temperature was in the low-70s, which is suitable for operating the system in both heating and cooling mode. 8.3 There is an electrical wire that was apparently routed through the main HVAC trunk line, which is a non-standard practice. Recommend further evaluation by a licensed electrician.
Page 21 of 33
8.5 Picture 1 Metal Cap on Chimney 8.6 A prefabricated wood-burning insert is located in the living room. Make: Heatilator Model: BH42 MFG: 2/84 The wood-burning insert was not operated as part of this inspection.
The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Page 22 of 33
IN NI NP RR 9.0 Insulation in Attic 9.1 Insulation Under Floor System 9.2 Vapor Retarders (in Crawlspace or basement) 9.3 Ventilation of Attic and Foundation Areas 9.4 Venting Systems (Kitchens, Baths and Laundry) 9.5 Ventilation Fans and Thermostatic Controls in Attic
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
IN NI NP RR
Comments: 9.0 The cellulose insulation in the attic are in contact with the recessed lighting fixtures. According to the warning label on the recessed lighting fixtures, contact with cellulose insulation is a fire hazard. Recommend further evaluation/repair by an insulation contractor.
Page 23 of 33
9.1 Picture 1 Fallen Insulation 9.3 See Sec 2.4 (2) 9.4 Both bath vents exhaust to the attic. The moist air from the bath vents condenses on the sheathing and has caused discoloration. The condensation will continue to damage the sheathing unless the bath vents are routed to an exterior exhaust vent.
Page 24 of 33
Page 25 of 33
IN NI NP RR 10.0 Dishwasher 10.1 Ranges/Ovens/Cooktops 10.2 Range Hood (s) 10.3 Trash Compactor 10.4 Food Waste Disposer 10.5 Microwave Cooking Equipment
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace
IN NI NP RR
Comments: 10.5 The microwave oven is located over the range and includes a recirculating fan.
The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Page 26 of 33
General Summary
Ussery Home Inspections, Inc. 564 Turkey Pen Road Mills River, North Carolina 28759 (828) 891-1607 Customer Mr. Address 1001 Tokedokey Trail Connestee Falls Brevard NC 28712
The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.
2. Exterior
2.0 Wall Cladding Flashing and Trim Inspected, Repair or Replace
1) The rear wall has most of the siding removed, apparently in conjunction with the repair and improvement of the rear porch. 2) A small hole (about 1 inch) is located on the left front side of the house. The hole may allow water to enter and potentially damage building components. 3) Small fastener holes that appear to have been filled with clear caulk are located around the windows and door on the front of the house. 4) The only visible flashing at the chase/chimney is metal coil, which is considered less effective than step flashing for this location. Inadequate flashing may allow water penetration which may damage building components. Recommend further evaluation/repair of 2) by a siding contractor, and 4) by a roofing contractor. 2.1 Doors (Exterior) Inspected, Repair or Replace
Page 27 of 33
4. Interiors
4.6 Windows (representative number) Inspected, Repair or Replace 1) The kitchen window will not stay in the open position. 2) The master bath window is operable, but very difficult to open and the sill is loose. 3) The laundry room window is not operable and the sill is loose. 4) The second bath window is operable, but difficult to open. 5) The dining room windows to the left of the door, the middle of the right side, and the right side rear are inoperable. 6) The dining room window to the right of the door is operable, but with difficulty. Recommend further evaluation/repair by a window and door specialist.
5. Structural Components
5.0 Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) Inspected, Repair or Replace A small crack is evident in the foundation wall on the left side of the house. Small cracks are not unusual and are not necessarily a structural concern, but may allow water penetration. Recommend further evaluation/repair by a masonry contractor.
6. Plumbing System
6.0 Plumbing Drain, Waste and Vent Systems
Page 28 of 33
1) The water supply piping is polybutylene with brass/copper fittings. The polybutylene piping appears to be functioning as intended. The following text is recommended language from the NCHILB website: Polybutylene plumbing supply lines (PB) are installed in this house. PB was used as water distribution piping in many homes built from the mid 1980s until the mid 1990s. The piping and associated fittings have had a failure rate and subsequent leakage sufficient to have been the subject of several nationwide class action lawsuits. Copper and brass fittings used in later years seem to have reduced the failure rate, but the piping may still fail due to problems with poor installation, improper handling, or chemical reaction with the water supply. The piping in this house has (circle which apply) Brass/Copper Plastic fittings 2) The hose bib under the rear porch is loose. The supply line to the hose bib is prone to damage from abrasion from the masonry block wall. Recommend further evaluation/repair by a licensed plumber.
7. Electrical System
7.1 Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels Inspected, Repair or Replace 1) The ground wire has been spliced, which is considered potentially unsafe because the mechanical connection of the two wires may not provide a secure connection. 2) The service entrance conductor is routed from the meter base under the floor framing and through the wall cavity to the service panel in the laundry room. The service entrance conductor is not protected by an overcurrent device from the point of entry to the main overcurrent device at the service panel, which is considered a potentially unsafe condition. Recommend further evaluation/repair by a licensed electrician. 7.2 Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage Inspected, Repair or Replace The service panel has two circuits labeled "heat pump", one 30 amp and one 60 amp. The maximum circuit breaker for the heat pump is 30 amp. The air handler was probably mislabeled "heat pump". A 60 amp breaker may be correct for the air handler with electrical heat strips, however, the maximum circuit breaker size was not shown on the air handler, and because at least one of the circuit breakers labeled "heat pump" is a 60 amp, it is possible that the circuit breaker for the heat pump is oversized.
Page 29 of 33
1) The overhead switches were tested using wall switches and all were operable. The wall switches located 1) adjacent to the living room closet, 2) over the television in the master bedroom, 3) and the middle switch adjacent to the master bedroom door did not apparently operate any overhead or outdoor fixture. It is possible that these switches are for receptacles or outdoor fixtures that are not visible, or, it may be that they are defective. 2) The wire for the roof-mounted satellite dish is loosely draped over the second bedroom porch. The loose wire is a safety hazard (tripping). Recommend further evaluation by a licensed electrician. 7.7 Smoke Detectors Inspected, Repair or Replace There are two smoke detectors in the house, one over each of the bedroom doors. The smoke detector over the master bedroom door did not respond to the test button. Recommend further evaluation by a licensed electrician.
Page 30 of 33
Recommend further evaluation/repair by an insulation contractor. 9.3 Ventilation of Attic and Foundation Areas Inspected, Repair or Replace See Sec 2.4 (2) 9.4 Venting Systems (Kitchens, Baths and Laundry) Inspected, Repair or Replace Both bath vents exhaust to the attic. The moist air from the bath vents condenses on the sheathing and has caused discoloration. The condensation will continue to damage the sheathing unless the bath vents are routed to an exterior exhaust vent.
Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.
Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Milton Ussery