(for Enterprise, Premium, Suite, Professional, Termo, Duct and Sani program version) Professional program for designers of heating, cooling, ventilation, potable water and drainage installations.
Introduction Cover page Introduction to the program System requirements Program installation Program fundamentals Starting the program and basic program settings Project settings Main menu Info window Product catalogue Calculations Short description of abbreviations Heat load according to EN 12831 Heat transmission coefficient calculation Heat gains calculation VDI 2078 Radiator selection in a two pipe system Radiator selection in a one pipe system Underfloor heating / cooling calculation Wall heating / cooling calculation Fan coil selection Heating pipeline calculation Fan coil pipeline calculation Ventilation ducts Potable water pipeline calculation Drainage water pipeline calculation Print Calculations and material list Function overwiew CAD Drawing basics Commands and definitions Admin Introduction Radiators Rooms IntegraCAD news IntegraCAD packages Download last program version from web site Internet training Contact Contact
Introduction
Program packages
You can purchase IntegraCAD 2011 in four different packages. Sani, Duct, Termo, Professional, Suite, Premium, Enterprise. The program packages include the same program framework (program interface, CAD, print, database) but a different amount of calculation modules. You can compare the different packages in the table below:
CAD
The CAD moduel can be used to work with technical drawings. You can use drawings in dwg (up to version 2010) and dxf file formats. The program CAD module is completely autonomous and you do not need for any other CAD software to be installed on the computer to work with the drawings. You can create new or edit existing drawings. To find out more follow these links: CAD basics and CAD functions overview
Print
The print module of the program has the following features: - Standard text editing tools - Edit material lists with capability to add products directly from the program database - Translate the printouts to seeral languages (Albanian, Bulgarian, Bosnian, Chinese (simplified), English, Croatian, Hungarian, Macedonian, Romanian, Russian, Slovenian, Serbian, Turkish.) - Export printouts to xls format - Print with print preview function
Product catalogue
The program has an included products catalogue with technical data, descriptions pictures and article numbers. All products are sorted into groups to allow easyer browsing. The calculation modules use the same technical data as displayed in the catalogue module of the program. You can also use these data to edit material lists in the print module.
and a possibility to explore some questions deeper. Program presentations can be individual or public. Getting help for a current issue has never been easier. Program users can contact us by phone, e-mail or Skype and we will organize a support session as soon as possible. You can ask general questions (how to start a program function, avoid problems, etc.) or questions related to a current project. In general, the explanations will be made with standard support projects. For bigger issues, you can send us your project and drawing files and we will do our best to help. If the problems cannot be resolved during the support session, we will transfer them to our standard technical support procedure. Internet training allows for a thorough insight into a part of the program. As a program user you have two options: you can request an individual training or you can join one of the regular public trainings. In the first case you can select the training topic freely but you need to make your training request at least 7 days in advance. In the case of public trainings the topic and date are already set and you need to apply at least 24 hours in advance. Public training dates will be announced on our website www.integracad.com at least two weeks in advance.
System requirements
IntegraCAD 2011 Computer system Minimum CPU RAM Viewscreen Hard disk Operating system Licence Licence time 1,4 GHz 512 MB (min. for win XP) 19" 400 MB Windows XP (at least SP2), Vista or Win 7 (32/64 bit) portable licence with USB stick is period of 30; 90 or 365 days. After that time program will stop working. Licence time you choose when buying program licence.
Note! Before you install IntegraCAD program close all running programs. If you have Windows XP on your computer please make sure that you have installed at least Service Pack 2 (My Computer / Control Panel / System / Service Pack no.) Compatible Service Pack and dot net framework you can copy and install from the IntegraCAD installation CD (folder Windows): * Service Pack * Windows -> XP -> WindowsXP-KB942288-v3-x86.exe * dot net framework * Windows -> dotnetfx35.exe or if you don't have IntegraCAD installation CD than download components from following link: http://dl.dropbox.com/u/5681482/Windows.zip
Take the CD out of the casing and insert it into your CD-ROM drive. Click the My Computer icon and choose the CD-ROM unit containing the CD Click the name, find IntegraCAD 2011 Setup (language).exe, copy that on your Desktop run it and follow the instructions shown on the screen.
Warning! Before you install IntegraCAD program close all running programs. If you have Windows XP on your computer please make sure that you have installed at least Service Pack 2 (My Computer / Control Panel / System / Service Pack no.) Compatible Service Pack and dot net framework you can copy and install from the IntegraCAD installation CD (folder Windows): * Service Pack * Windows -> XP -> WindowsXP-KB942288-v3-x86.exe * dot net framework * Windows -> dotnetfx35.exe or if you don't have IntegraCAD installation CD than download components from following link: http://dl.dropbox.com/u/5681482/Windows.zip
After program installation try to run IntegaCAD program (check that USB key is inserted into your computer!)
If you start a IntegraCAD program then Step number II. will not be needed! If program (after you run it) show following window
Program registration
This serial number is your private number and it allows you to use the program. Before you start working with IntegraCAD you should contact the program distributor or Impuls ing d.o.o and supply them with exact information on the name of your program, its Version label and the Serial Number (i.e. IntegraCAD 2011 Enterprise, INT50, 4111588392). You'll get an Activation key for starting the program. Run the program and type the activation key in the required spot (delete the zero). If everything was fine you'll se the button OK activated and be able to start working. You need to type the activation key only once; at all other times the program will run without asking this information (in licence time period that you buy 30, 90 or 365 days). After that time period IntegraCAD 2011 version of the program will stop working
Program fundamentals
After the program loads you first need to crate a new project. While you are doing this you will also select the calculations that you need for this project. This is just an initial calculation selection and you can change this afterwards by loading/unloading all calculation modules available in the program. By creating and saving a project the program will make a file with a .int ending. This is your project file and it holds all necessary calculation data like the layout of the building, calculation settigngs, finished calculations etc. To save this data permanently you need to save on a hard disk. If you have installed the program on severral computers you can copy this file and use it to work on other computers with the installed software. To crate a new project select "New" from the File menu or click the icon in the toolbar. The new project wizard will open in a new window. You can now select the calculations you want to do and proceed or crate a new project template with the calculations you most commonly use. You can crate several project templates for this program. From the project wizard select "Custom project" and press the "Forward" button. Check the calculations you want to work on this project and click "OK".
In future projects you can select this new project template form the initial project wizard screen and speed up your calculation selection. You can make several project templates if you like.
Project settings
After creating the project the program will load the selected calculations and setup some basic program settings. After these preparations the first thing you have to do is to create a new building structure. An empty project as initially created by the program is displyed below:
In the upper part of the screen you can see the main menu and toolbar. They include the most common program functions like loading and saving projects, selecting settings, loading/unloading calculation modules etc. On the left side of the screen you can see the tree controls (Project, CAD, Installations, Catalogue) and everything on the right is the main Workspace. The program has four tree controls, each with a distinctive purpose: The project tree - its purpose is to create, edit and view the building and its parts (floors, flats, rooms). The position on this tree often determines to what part of the building some calculation is reffering (e.g if you are positioned on the first floor in the project tree and want to do a radiator selection, the program will do the selection for all rooms on the first floor.)
The CAD tree - its purpose is to view and change different settings related to the CAD module. This tree is generally active only when you disply the CAD module on your workspace. You can look at object settings selected inside the CAD drawing surface or look at a list of pipeline drawing connection errors and warnings. You can use this list to quickly jump from one problem to another which is very usefull in a large project drawing. The installation tree - its purpose is to create, edit and view the building pipeline installations (pipelines). This is the place to add new instalations, floor entry points and manifolds. The installation tree is connected to the project tree (e.g. the program will know on which floor a floor entry point is set) but it is not a copy of its structure. You have to define the structure separately from the building structure. You can for example have risers going through each floor but having only floor entry points at every second floor. In this event the number of floor entry points on one riser does not correspond to the number of floors it passes through. The catalogue tree - its purpose is to enable you a look on the products included in the program database in a hierarchical way for easyer product browsing. You can search the products while in the Catalogue module or use it to create CAD drawings in the CAD module or insert products in lists of material in the print module.
The workspace is right of the tree controls and covers the majority of the screen. Most actions happen in it like calculations, print preparation etc. The workspace consists from five interconecting parts: Info, Calculation, CAD, Print and Catalogue. You can switch between these modules simply by clicking on the tab names. Info is the part that is active when you start a new project and its main purpose is to display information about parts of the project. Calculation is the part that includes all calculation modules that can be activated in the program. To move between the different calculations you have to click on the tabs with the calculation names (top of the workspace). To move inside a particular calculation you have to click on the vertical tabs with the calculation part names located in between the tree controls and the workspace. CAD is the part where you can create and edit drawings. This module is compatible with the drawing formats dwg and dxf and includes most common drawing functions found in specialized CAD drawing software programs. To bind drawings to a project you have to make a connection between the drawing file and the floor it represents. Print is the part where you can create and edit different representations of the calculated data. The print module consists of calculation results and lists of material (Bills of Material). Catalogue is the part where you can view and browse products from the program database. You select different products using the Catalogue tree control and the product data is displayed in the Catalogue module on the workspace.
Below the workspace is an information bar where the program displays messages to the user, mostly about the progress of started functions like "Calculation finished" or "Project loaded". Most actions that take a longer time to execute will display progress information in the information bar.
Changing the tree position of floors, appartments and rooms * Select an entity in the tree control. * Using the arrow buttons up and down until it reaches the desired position. change the current entity position
Main menu
The Main menu is used to manage a project; the appearance and position of windows, main files and the help system. It is divided into the following sub menus: File, Edit, View, Print, Help.
File - used to manage basic project functions. New - creates a new project, Open opens an existing project, Close - closes the active project, Save - saves the active project, Save as ... - saves the project named as, Print - prints project, Print preview, Printer settings - sets parameters of the printer; these options are followed by path and names of the last four projects used. The option Exit is used to exit the IntegraCAD program.
Edit - this menu contains standard data editing tools - Undo - move previous command, Redo - returns to previous command, Cut - cuts data (makes a copy but doesn't keep the original); Copy - for copying data (makes a copy and keeps the original; Paste - pastes cut or copied data on a chosen place, Settings - adjust program settings and CAD module in IntegraCAD program, Admin - tool for radiator or room importing, if the same does not exist in the IntegraCAD program.
View - contains settings which apply to the whole program and all the projects. Tool bar - used to turn on/off all tool bars in the program (main, for print...) or some for program tree (project, installation, catalogue). Function "Reset toolbal position" - will cancel all current settings, and return it to the standard form in which the program is delivered. Option - "Status bar" - can turn on or turn off status bar window (at the bottom of the IntegraCAD program window) - that displays information about last program activities.
Print - Menu where you can turn on / off some prints. There are two possible ways: 1.) direct from the menu (shorter display)
2.) or by "Print settings" button (in that menu) - graphically displays individual prints
Help - used to obtain basic information on IntegraCAD program and advice on using it. Help content - opens a new window with the program's help file displayed. About - build number (RC number) - e.g. on picture RC34, and some basic informations about authors.
Info window
On project level: Here you can enter some basic datas about project, they are not required, but can be helpful in further work. Insert datas can also be printed.
* Enter object name and project number. * Select date from calendar * In field "Note" you can enter some text for project description . * Enter data about designer and investor.
On floor level: Here you can define some basic geometry floor attribute (ceiling height, room height, height above ground), path where the drawing file is stored on the disk, drawing measure, label text height in the drawing. IntegraCAD 2011 works with standard .dwg drawings, and it's compatible with AutoCAD drawing files up to version AutoCAD 2010. Under basic geometry attributes there are some heating and cooling calculation datas for every room on floor.
* Select floor (on project tree). * On left you can enter floor dimensions, like ceiling height, room height, height above ground. * In "Drawing settings" part you can set DWG file path. * On default settings press button (DWG file path) and select drawing (drawing path), that you want to join to the floor. Drawing must be in .dwg or in .dxf format.
We recommend that the *.int and *.dwg file record in the same directory. * Press button on default settings (Measure) to define measure, measure units and text style settings.
Here you can also set the some element labels that you will later used in the calculations. Default labels are: F - floor label; A - apartment label; R - room label. Also some tags can be customized according to the building, according to the floor or to the flat. Program accepted new settings by pressing a Set button.
In table below you can see some datas related with rooms in project. Label Room A (m2) ti (C) Qn (W) Qinst (W) Qres (W) Qi(two) (W) Qi(one) (W) Qi(flh) (W) Qi(wall) (W) Qi(fc) (W); room label room name room name internal temperature in (C) heat gains in (W) installed heating capacity in (W) remaining heat quantity (W) total installed heat capacity with two pipe system in (W) total installed heat capacity with one pipe system in (W) total installed heat capacity with floor heating /cooling in (W) total installed heat capacity with wall heating /cooling in (W) total installed heat capacity with fancoil /cooling heating in (W)
Product catalogue
You can activate the product catalogue by clicking the Catalogue tab in the Tree view and also on the main workspace (you need to click both). Within the catalogue tree view the products are sorted by : * group (pipe, fittings, sink points, manifolds, radiators...) * subgroups (FUSIOTHERM-Pipe SDR 6 (PN 20) ...) * products (Fusiotherm SDR 6 16 x 2,7 , Fusiotherm SDR 6 20 x 3,4 , ... ) .
If
you
want
to
get
more
information
about
an
item
just
click
on
it.
On the workspace you will get more detailed data (most details are for products): * Manufacturer logo * Product picture * Article number * Short and long product description * Technical data
parametar B' for building P (m) Floor perimeter Ag (m2) Floor surface Parametar B' for all rooms without external walls separating the heated B' space under consideration from the external enviroment, and for all rooms with well insulated floor
The "Recalculate heat losses" button will make a complete heat load Recalculate heat calculation using the values set in the calculation defaults. You can use losses this for example to recalculate the heat load using a different design external temperature The "Transfer heat loss to equipment selection" will overwrite and heat loss values in the equipment selection calculation modules (radiator Transfer heat loss selection, underfloor heating ...). You can use this before the initial to equipment equipment selection but also when you made some changes to the heat selection load calculation and want to see the effects on the already selected equipment. CALCULATION Input room data A/a (m2/m) b (m) c (m) h (m) V (m3) O (m2) Theta su, i (C) V su,i (m3/h) Nr. of openings ei n min (1/h) f vi Theta int,i T (m) Gw fg1 fh,i f RH
Room surface or length Room width Room height Floor height from ground Room volume Superficial area of room Temperature of supply air for mechanical ventilation Supply air flow rate for mechanical ventilation Number of exterior openings Shielding coefficient Minimal air exchange rate in one hour Temperature reduction factor (depending on internal room temperature, supply air temeprature and external design temperature) Internal roo mtemperature Depth of ground water Ground water correction factor Correction factor taking into account the influence of annual variation of external temperature. Correction factor for room height (rooms between 5 m and 15 m heigh) Correction factor for heating-up
Calculation results Theta e (C) External design temperature (C) Phi V, inf (W) Infiltration ventilation losses Phi V, min (W) Hygiene air flow ventilation losses Phi V, mech, inf Mechanical ventilation losses for building (W) Phi V, su (W) Room supply air mechanical ventilation losses Phi V, mech (W) Total mechanical ventilation losses
Phi T, i (W) Phi V, i (W) Phi RH (W) Phi (W) Phi/A (W/m2) Phi/V (W/m3) Table Lab. Surface to OR Nr. LEN (m) H/W (m) A (m2) R A' (m2) P (m2) B'(m2) Z (m) U (W/m2K) Ueq (W/m2K) Theta u/as (C) ek
Transmission heat loss Ventilation heat loss Heating-up capacity heat loss Heat load Heat load per square meter Heat load per cubic meter
Building element label Surface type on the other side of the building element (exterior, nonheated room, ground etc.) Orientation of building element Number of equal elements (equal by dimmension, U coeff., position etc.) Length of building element in meters Height of width of building element in meters Surface of building element Surface reduction factor Building element net surface Room perimeter in contact with ground Characteristic parameter Depth of floor slab Heat transmittance coefficient Equivalent heat transmittance coefficient Temperature of non-heated space / space heated to a lower temperature Correction factor for the exposure taking into account climatic influences such as different insulation, moisture absorption of building elements, wind velocity and temperature, provided these influences have not already been taken into account in the determination of the U values. Temperature reduction factor taking into account the difference between temeprature of the unheated space and the external design temperature. Temprature reduction factor taking into account the difference between temperature of the adjacent space and the external design temperatre. Temperature reduction factor taking into account the difference between annual mean external temperature and external design temperature. Thermal bridge The transmission heat loss coefficient of the building element. The transmission heat loss of the building element.
Material table Layer material d (m) Ro (kg/m3) d*Ro (kg/m2) L (W/mK) R (m2K/W) double click on this cell and new window for material selection will appear. thickness material density product of thickness and material density material thermal conduytivity thermal conductivity resistance
button for adding new climate zone button for deleteing existing climate zone in program When you add a new zone you can save it with this button. Save active zone Once you save it new zone will be stored in the customer base (User.dat) that could be used in other projects also. Program will set the heat gains in all areas of the project to the maximum Adopt gains gains calculated in the VDI2078 calculation. If we did before calculation of heat losses by eg. EN12831 standard, then Copy surfaces to we can take advantage of areas that are defined there. Open the dialog to cooling load choose which areas you want to copy to the gains heat calculation. If define wrong house orientation, eg. we didn't know, we get that information later, or we just wan't to see how much gains will be if we Change oriented object differently, then we can "Change object orientation". e.g. orientation what was to the north is now actually south, then program will (in a circle) change all orientations on all surfaces, northeast will be the outhwest, etc. Recalculate recalculate calculation Default settings Room type Room type selection - depending on the construction (XL-very light, L-light, M-medium, S-heavy) date selection solar radiation (W/m2) room orientation turbidity factor room temperature in (C) area radiation hour selection cooling zone number
Date qs(W/m2) Orientation T ti (C) Radiation type Hour Cooling zone Default values for set default values of some room room
CALCULATION Input room data Room type Orientation Radiation type Date T Hour qs(W/m2) Cooling zone a (m) b (m) c (m) V (m3) O (m2) Ap (m2) ti (C) Room type selection - depending on the construction (XL-very light, L-light, M-medium, S-heavy) room orientation area radiation date selection turbidity factor hour selection solar radiation (W/m2) cooling zone number room lenght (m) room width (m) room height (m) room volume (m3) superficial room area (m2) room surface (m2) room temperature in (C)
Output room data Qp (Persons) (W) heat gains due to persons (W) Qb (Lights) (W) heat gains due to lighting (W) Qm (Machines) heat gains due to machines and appliances (W) (W) Qg (Material heat gains due to material throughput (W) transit) (W) Qr (Transmision) heat gains due to different temperatures in adjacent rooms (W) (W) Qc (Rest) (W) other heat supply and heat removal (W) Qw (Walls and heat gains through external walls and roofs (W) roofs) (W) Qt (Window heat gains due to transmission through windows (W) transmission) (W) Qs (Window heat gains due to radiation (W) radiation) (W) Qlf (Infiltration) heat gains due to infiltration (W) (W) Total (W) total cooling load (W) Qtot (W) total room cooling load (W) 3 Qtot (W/m ) total cooling load per m3 (W/m3) Copy from room copy data from some room
ti; Persons; Lights; Machines; Material throughput; Adjacent room; Surfaces; Ventilation; Graph
Inner temperature inner temperature flow is shown in tables and graphs. Data in tables be can flow changed. When calculating the heat gains from people it is important the time that people spend working in some area (select work time), and the type of work (heavy, medium or light work). Light calculation takes into account several parameters:Light group, Work time, Convection ratio, Installed light power (P), Room load factor due to lighting (l) and simultanelty factor (mb). Select machine (add new one or change name for existing one), select work time, accumulation function, rated machine power (P), main motor efficiency (n), load factor of the machine at the time in question (may) and simultaneity factor (l). Press Fill button to fill tables below. this calculation refers to some outside materials that will be entered into heated room. Select material throughput (add new one or change name for existing one), work time, accumulation function, mass of the material brought into the room or removed from it in the unit of time (m), main specific heat capacity (c), inlet temperature (te), outlet temperature (ta). Press Fill button to fill tables below. heat gains from adjacent room. Lbl - room label; LEN - length in (m); L/W - length/width in (m); A surface in (m2) ; U - thermal transmittance of building element (W/m2K); OT - outside air temperature in C (temperature behind the wall); T temperature difference in C (temperature difference behind the wall and room temperature) ;Q - Capacity in Watt.
Persons
Lights
Machines
Material throughput
Adjacent room
Surfaces
heat gains calculation through the surfaces that are exposed to sun, windows, walls or roofs. Lbl - surface label; Or. - orientation; Type - surface type; BC - building construction class (used only for walls and roof); z - time adjustment (used only for walls and roof); SP - surface (window) protection, user can select external/none or internal; Num. - number of same surfaces; Len length in (m); H/W - hight/width in (m); A - surface in (m2); R - reduction column (for windows enter - ); As - surface effective area (takes into account if some window is shaded) ; Au - total surface area (As x Num.= Au); U - thermal transmittance in (W/m2K); de1 - equivalent temperature difference in Kelvin (calculated as the outdoor temperature minus room temperature); de2 - equivalent temperature difference for painted walls and roofs in Kelvin; b - mean transmission coefficient b of solar radiation (select by double-clicking on the column); qs - solar radiation in (W/m2); Qok - heat gains due to transmission in (W); Qoz - heat gains due to solar radiation in (W) Ventilation influence on heat gains. Regeneration/recuperation percentage; i - air exchange rate. Represents the sum of heat gains by the hour for all performed calculations.
Ventilation
Graph
EN442
Security factor Input the security factor if needed. If you want to cover a 15% higher heat loss with radiators you need to input the security factor of 1,15. Security factor (Qi/Qn) Also if you want to cover only 60% of the needed heat loss with radiators and the reast with alternative heating equipment, write 0,6 into the field. Temperature Supply water temperature (C) Return water temperature (C) input supply water temperature Regardless of the method of calculation program internally calculates radiator capacity for input values of supply water temperature. input return water temperature Regardless of the method of calculation program internally calculates radiator capacity for input values of return water temperature.
Calculation type Calculate radiators with same dimensions Calculate radiators with different dimensions
if this button is selected than program will do calculation according to radiators with same dimensions if this button is selected than program will do calculation according to radiators with different dimensions In you later (after you already select your radiator) change their temperature in some other (e.g. from 20 (C) in 18 (C)) than click on this button so that program can recalculate new capacity according to new temperature. If you want that program in new capacity calculation takes into acount new radiator dimensions check this button. If this button is unchecked, than program will do new capacity calculation without new dimensions, just with new Supply and Return water temperature.
Table ti (C) Manufacturer Group Radiator input room inner temperature (e.g. 20 - means 20 (C)) select radiator manufacturer. select radiator group (group depends on previously selected manufacturer.) Select radiator type (radiator type depends on previously selected radiator group and radiator manufacturer.) select one of 11 radiator mounting types: 1 - Connection from floor with standard valve; 2 - Connection from wall with standard valve; 3 - Connection from floor with standard valve; 4 - Connection from wall with standard valve; 5 - Connection from floor with compact valve; 6 - Connection from wall with compact angle valve; 7 Connection from floor with valve with riser/immersion pipe; 8 Connection from floor with valve with immersion pipe; 9 Connection from floor with central connection point; 10 - Direct connection from above ; 11 - Direct connection from above Radiator height. Select it by double-clicking on this field. Program will choose radiator height acc. to this value. maximum radiator length value When program starts with selection he will start from a minimum length for a given height of the radiator and will never exceed the maximum value entered here Balance valve selection. If some radiator have integrated valve in it than program will mark it with "Integrated valve". select termostatic valve Command is used to check the maximum height and length after the change of selected groups of radiators. Dimensions that do not exist in the selected group will be highlighted in red. pressing this button program will find radiator group for the set height. This button is used for the radiator selection with buttons + (select all) and - (unselect all).
Mt
Check dimensions Find groups Radiator type CALCULATION Options Calculate all Delete all Add
select connection point -> the program will add radiators in all listed rooms according to the default radiator setup. This will delete all radiators for all rooms listed in the table, and only the basic room data will be displayed (temperature, surface, heat loss). Select the connection from the new window -> one radiator is added to the line (room) with your current table position.
Delete
In the event that there is just one radiator in the room, it will be deleted and the row will display only the basic room data. If there are more than one raditors in the room, the selected radiator will be deleted, the list will move up for one row and the capacity of the radiators in the room will be racalculated. will show only those radiators whose group you selected in the default settings
Show only radiators from selected group Radiator selection for heat load Calculation for: Project/Floor/Room Table Room Nr.(pcs) ti (C) A (m2) Qn (W) Qni (W) Qn(r) (W) Qi (W) Vertical Label Radiator
Mt
name of the room where there radiators are Number of radiators that automatically should be selected for a selected room Inner room temperature Room surface Heat losses Total installed heat capacity (beside radiator, includes other heaters too) Norm radiator capacity Installed radiator capacity Radiator connection (manifold or direct on some floor) radiator label (radiator ID made of radiator label) RD and some number - e.g. RD1; RD2 ... radiator name select one of 11 radiator mounting types: 1 - Connection from floor with standard valve; 2 - Connection from wall with standard valve; 3 - Connection from floor with standard valve; 4 - Connection from wall with standard valve; 5 - Connection from floor with compact valve; 6 - Connection from wall with compact angle valve; 7 Connection from floor with valve with riser/immersion pipe; 8 Connection from floor with valve with immersion pipe; 9 Connection from floor with central connection point; 10 - Direct connection from above ; 11 - Direct connection from above Number of glides (for glide radistors) Radiator height Radiator lenght Radiator mask factor Radiator capacity
RADIATOR ADDITIONS Project/Floor/Room radiator position in project name / floor name / room name - (see project tree) short description of the column in the table on which you are positioned. room label (where the radiator is located) room name (where the radiator is located) radiator label radiator name (type; height/width). If you want to change some of the radiator then you have to do in previous "Calculation" part. select one of 11 radiator mounting types: 1 - Connection from floor with standard valve; 2 - Connection from wall with standard valve; 3 - Connection from floor with standard valve; 4 - Connection from wall with standard valve; 5 - Connection from floor with compact valve; 6 - Connection from wall with compact angle valve; 7 Connection from floor with valve with riser/immersion pipe; 8 Connection from floor with valve with immersion pipe; 9 Connection from floor with central connection point; 10 - Direct connection from above ; 11 - Direct connection from above thermostatic valve. For selection it is necessary to double click into the field. settings for thermostatic valve For the selection it is necessary to double click into the field. unless if radiator already have integrated balance valve in it (then this field will be filled). It is not possible to choose radiator console for all radiator typs because this option depends of radiator manufacturer. For radiators which has these additions you can choose between: wall console radiators mounted on the wall or floor console - radiators mounted on the floor (standing alone). depends on the previous column "console type" and on preferences of individual producers. if in previous column selection is possible then here you can choose this two wall typs: treated wall - plastered wall; untreated wall - wall that is not fully processed. console name that corresponding for some radiator type. Depends on the previous column selection "console type" and "wall type". select color for radiators. Note! this option depends of radiator producer.
Mt
console type
wall type
console color
EN442
Security factor Input the security factor if needed. If you want to cover a 15% higher heat loss with radiators you need to input the security factor of 1,15. Also if you want to cover only 60% of the needed heat loss with radiators and the reast with alternative heating equipment, write 0,6 into the field.
Temperature Supply water temperature (C) Return water temperature (C) input supply water temperature Regardless of the method of calculation program internally calculates radiator capacity for input values of supply water temperature. input return water temperature Regardless of the method of calculation program internally calculates radiator capacity for input values of return water temperature. select pipe. Press button (with three points) and in the new open window from the drop-down menu select group of pipes and pipe for one pipe system. In you later (after you already select your radiator) change their temperature in some other (e.g. from 20 (C) in 18 (C)) than click on this button so that program can recalculate new capacity according to new temperature.
button
Table ti (C) Manufacturer Group Radiator input room inner temperature (e.g. 20 - means 20 (C)) select radiator manufacturer. select radiator group (group depends on previously selected manufacturer.) Select radiator type (radiator type depends on previously selected radiator group and radiator manufacturer.) select one of 11 radiator mounting types: 1 - Connection from floor with standard valve; 2 - Connection from wall with standard valve; 3 Connection from floor with standard valve; 4 - Connection from wall with standard valve; 5 - Connection from floor with compact valve; 6 Connection from wall with compact angle valve; 7 - Connection from floor with valve with riser/immersion pipe; 8 - Connection from floor with valve with immersion pipe; 9 - Connection from floor with central connection point; 10 - Direct connection from above ; 11 - Direct connection from above Radiator height. Select it by double-clicking on this field. Program will choose radiator height acc. to this value. maximum radiator length value When program starts with selection he will start from a minimum length for a given height of the radiator and will never exceed the maximum value entered here Balance valve selection. If some radiator have integrated valve in it than program will mark it with "Integrated valve". percentage of valve permeability local resistance on radiator select termostatic valve
Mt
HEATING CIRCUIT Circle name Qn,one (W) tpsup (C) tret (C) Pipe L (m) Roug. (mm) Sum. P const. t w (m/s) M (kg/h) Lekv (m) R (kPa/m) name of heating circle heat loss that should be covered in (W) supply water temperature return water temperature pipes used in heating circle pipe length in the heating circuit pipe roughness total local resistance in pipeline calculation according to constant pressure drop temperature difference water velocity in pipes mass flow in heating circuit equivalent pipe length pressure drop per meter
(kPa) Qone Inst (W) Ris. Options New circuit Add room Calculate all Delete all Add
pressure drop in heating circuit installed heating capacity in heating circuit connection spot
Delete
makes new heating circuit Select the connection from the new window -> one radiator is added to the line (room) with your current table position. select connection point -> the program will add radiators in all listed rooms according to the default radiator setup. This will delete all radiators for all rooms listed in the table, and only the basic room data will be displayed (temperature, surface, heat loss). Select the connection from the new window -> one radiator is added to the line (room) with your current table position. In the event that there is just one radiator in the room, it will be deleted and the row will display only the basic room data. If there are more than one raditors in the room, the selected radiator will be deleted, the list will move up for one row and the capacity of the radiators in the room will be racalculated.
Move The order of the rooms in the circle can be changed by pressing the "Up" button. Changing the order of the rooms program will do calculation again. The order of the rooms in the circle can be changed by pressing the "Down" button. Changing the order of the rooms program will do calculation again.
Up
Down
Table Room ti (C) Qn (W) Qinst (W) Qn,one (W) Qone Inst (W) Qn(r) (W) Valve % Label name of the room where there radiators are Inner room temperature Heat losses total installed heat capacity (beside radiator, includes other heaters too) heat capacity that shoud be compensate to radiators in one pipe system installed radiator capacity in room in one pipe system Norm radiator capacity termostatic valve percentage of valve flow capacity local resistance on radiator
Radiator
Mt
T. valve x Nr. gl. Len. (mm) Hei. (mm) FM tm (C) Q Inst(r) (W)
radiator type select one of 11 radiator mounting types: 1 - Connection from floor with standard valve; 2 - Connection from wall with standard valve; 3 Connection from floor with standard valve; 4 - Connection from wall with standard valve; 5 - Connection from floor with compact valve; 6 Connection from wall with compact angle valve; 7 - Connection from floor with valve with riser/immersion pipe; 8 - Connection from floor with valve with immersion pipe; 9 - Connection from floor with central connection point; 10 - Direct connection from above ; 11 - Direct connection from above termostatic valve on radiator thermostatic valve position adjustment Number of glides (for glide radiators) radiator lenght radiator height Radiator mask factor medium water temperature in radiator installed radiator capacity
RADIATOR ADDITIONS Project/Floor/Room radiator position in project name / floor name / room name - (see project tree) short description of the column in the table on which you are positioned. room label (where the radiator is located) room name (where the radiator is located) radiator label radiator name (type; height/width). If you want to change some of the radiator then you have to do in previous "Calculation" part. select one of 11 radiator mounting types: 1 - Connection from floor with standard valve; 2 - Connection from wall with standard valve; 3 Connection from floor with standard valve; 4 - Connection from wall with standard valve; 5 - Connection from floor with compact valve; 6 Connection from wall with compact angle valve; 7 - Connection from floor with valve with riser/immersion pipe; 8 - Connection from floor with valve with immersion pipe; 9 - Connection from floor with central connection point; 10 - Direct connection from above ; 11 - Direct connection from above thermostatic valve. For selection it is necessary to double click into the field. settings for thermostatic valve For the selection it is necessary to double click into the field. unless if radiator already have integrated balance valve in it (then this field will be filled).
Mt
console type
wall type
console color
It is not possible to choose radiator console for all radiator typs because this option depends of radiator manufacturer. For radiators which has these additions you can choose between: wall console - radiators mounted on the wall or floor console - radiators mounted on the floor (standing alone). depends on the previous column "console type" and on preferences of individual producers. if in previous column selection is possible then here you can choose this two wall typs: treated wall - plastered wall; untreated wall - wall that is not fully processed. console name that corresponding for some radiator type. Depends on the previous column selection "console type" and "wall type". select color for radiators. Note! this option depends of radiator producer.
Auto pipe step selection Auto pipe step selection min max Border values Maximum pressure drop Maximum loop lenght This value is given by the manufacturer, as his recommendation of a maximum value over that we should not be allowed to go. value can be changed. This value is given by the manufacturer, as his recommendation of a maximum value over that we should not be allowed to go. value can be changed. For selected floor heating / cooling system you can limit pipe step by using minimum and maximum values. To do that select this window. Select minimum pipe step (values depends on previously selected floor system. Don't forget to mark previous "Auto pipe step selection" window) Select maximum pipe step (values depends on previously selected floor system. Don't forget to mark previous "Auto pipe step selection" window)
Maximum floor temperature Maximum habitation zone temperature. This value is given according to standard, but you can change it. Maximum border zone temperature. This value is given according to Border zone standard, but you can change it. Habitation zone floor surface temperature in bathroom This value is given Bathroom according to standard, but you can change it. Bathroom Difference between the inner room temeprature and the floor temperature in temperature + the occupied area. This value is given according to standard, but you can (C) change it. Temperature of input temperature of room underneath. This value is given according to room underneath standard, but you can change it. Habitation zone Heating temperature Wanted supply Wanted supply water temperature on manifold for heating temperature Temp. difference Temperature difference in kelvin for heating minimum water temperature difference by zones (Habitation or Border) in min kelvin for heating. This values are given according to standard, but you can change it. maximum water temperature difference by zones (Habitation or Border) in max kelvin for heating. This values are given according to standard, but you can change it. Cooling temperature Wanted supply Wanted supply water temperature on manifold for cooling temperature Temp. difference Temperature difference in kelvin for cooling minimum water temperature difference by zones (Habitation or Border) in min kelvin for cooling. This values are given according to standard, but you can change it. maximum water temperature difference by zones (Habitation or Border) in max kelvin for cooling. This values are given according to standard, but you can change it. Additional Additional insulation width in (mm) insulation width Element label Loop label Set Underfloor system loop label. Initial label can be changed, in that case program will accept new ones after you press "Set" button. Initial underfloor system loop label can be changed (previous field) in that case program will accept new loop label after you press this button.
Recalculate
Sort labels
pressing this button program will recalculate a complete floor heating / cooling calculation according to some new set values. This button is used to re-sort the loops in the floor system. (e.g.you have loops marked as WF1; WF2; WF3 and WF4 and you decide to earse for e.g. loops WF2 and WF3. Program will than have loops WF1 and WF4. If we decide to add one new loop, program will label it as WF5. So now we have WF1; WF4 and WF5. Pressing on this button program will sort loop labels (from WF1; WF4; WF5 to WF1; WF2; WF3).
FLOOR HEATING Floor heating: Project/Floot/Room Qn (W) Floor surface (m2) Surface for floor heating (m2) ti (C) Qn' (W) Qinst (W) Qre (W) Loop surface (m2) Max. floor temp. (C) Coating R coat. (m2*K/W) Screed R screed (m2*K/W) Calculation for fixed loop number Number of loops Additional insulation Pipe Wanted supply water temperature (C) Temperature of room underneath Heat losses Floor surface Surface for floor heating internal temperature needed heating capacity installed heating capacity remaining heat quantity all loop surfaces in room maximum floor temperature select some of the floor coating. ceramics tiles; Parquet; Marble; Stone panels; Carpet; Linoleum ... coating thermal conductivity resistance select screed screed thermal conductivity resistance If you want to make a calculation for a certain loop number than select this box. This field is associated with the following field "Number of loops". Number of loops in room select additional insulation for floor heating system select pipe for floor heating system Wanted supply water temperature on manifold for heating temperature of room underneath
(C) Maximum pressure drop (kPa) Maximum loop lenght (m) Cooling Qn (W) Coverage (%) Wanted supply temperature (C) Calculation by mass flow from heating System Subsystem Add Add X
Heat load Percent of installed cooling capacity Wanted supply water temperature on manifold for cooling calculation by mass flow from heating
select floor heating system select floor heating subsystem pressing this button program will add new floor heating loop, that can cover entire given surface. To shorten the calculation process use the button "Auto". This function will attempt to find the optimal floor cooling loop/s with preset loop size, floor temperature, pressure drop etc. As mentioned before, there are cases in which it is not possible to meet all needs with just floor heating and the "Auto" function will not find an optimal solution in these cases. The calculation is also adjustable. pressing this button program will delete selected floor heating loop from project. pressing this button program will delete all floor heating loops in one room pressing this button program will recalculate a complete floor heating calculation according to some new set values.
Auto
Delete Delete all Recalculate Table V/M Label D (mm) RlaB (m2K/W) Qn (W) A (m2) T (mm)
manifold that is connected with loop. loop label thickness of floor coverings Coating thermal conductivity, value is calculated Heat losses Floor surface pipe step - value can be changed by double-clicking on the column
tp (C) q (W/m2) Qn (W) A (m2) T (mm) tp (C) q (W/m2) t (C) l (m) ld (m) Qi(k) (W) Qtot (W) m (kg/h) p (kPa) Valve pos.
Floor temperature heat capacity that loop gives heat capacity - value for border zone Floor surface - value for border zone pipe step - value for border zone floor temperature - value for border zone amount of heat that loop gives - value for border zone Temperature difference between supply and return water loop lenght lenght of connecting pipe in loop upwards installed capacity total floor heating capacity mass flow pressure droop Manifold balance valve position
FLOOR COOLING Floor cooling: Project/Floor/Room Qn (W) Floor surface (m2) Surface for floor cooling (m2) ti (C) Qn' (W) Qinst (W) Qre (W) Loop surface (m2) Max. floor temp (C) Coating R coat. (m2*K/W) Screed R screed (m2*K/W) Calculation for fixed loop number Heat losses Room floor surface Surface for floor cooling internal temperature needed cooling capacity installed cooling capacity remaining cooling quantity all loop surfaces in room maximum floor temperature select some of the floor coating. ceramics tiles; Parquet; Marble; Stone panels; Carpet; Linoleum ... coating thermal conductivity resistance select screed screed thermal conductivity resistance If you want to make a calculation for a certain loop number than select this box. This field is associated with the following field "Number of loops".
Number of loops Additional insulation Pipe Wanted supply water temperature (C) Temperature of room underneath (C) Maximum pressure drop (kPa) Maximum loop lenght (m) Heating Qn (W) Coverage (%) Wanted supply temperature (C) Calculation by mass flow from cooling System Subsystem Add (Ins) Add X
Number of loops in room select additional insulation for cooling system select pipe for floor cooling system Wanted supply water temperature on manifold for cooling
Heat load Percent of installed heating capacity Wanted supply water temperature on manifold for heating Calculation by mass flow from cooling
select floor cooling system select floor cooling subsystem pressing this button program will add new floor cooling loop, that can cover entire given surface. To shorten the calculation process use the button "Auto". This function will attempt to find the optimal floor cooling loop/s with preset loop size, floor temperature, pressure drop etc. As mentioned before, there are cases in which it is not possible to meet all needs with just floor heating and the "Auto" function will not find an optimal solution in these cases. The calculation is also adjustable. pressing this button program will delete selected floor cooling loop from project. pressing this button program will delete all floor cooling loops in one room pressing this button program will recalculate a complete floor cooling calculation according to some new set values.
Auto
Table V/M Label Type Screed D (mm) RlaB (m2K/W) Qn (W) A (m2) T (mm) tp (C) q (W/m2) Qn (W) A (m2) T (mm) tp (C) q (W/m2) t (C) l (m) ld (m) Qi(k) (W) Qtot (W) m (kg/h) p (kPa) Valve pos. manifold connected on loop. loop label loop according to zone type (H - Habitation zone, B- Border zone, IB Integrated border zone, X - connection pipe , Y - insulated supply pipe). select screed thickness of floor coverings Coating thermal conductivity, value is calculated Heat losses Floor surface pipe step - value can be changed by double-clicking on the column Floor temperature heat capacity that loop gives heat capacity - value for border zone Floor surface - value for border zone pipe step - value for border zone floor temperature - value for border zone amount of heat that loop gives - value for border zone Temperature difference between supply and return water loop lenght lenght of connecting pipe in loop upwards installed capacity total floor cooling capacity mass flow pressure droop Manifold balance valve position
Auto pipe step selection Auto pipe step selection min. max. For selected wall heating / cooling system you can limit pipe step by using minimum and maximum values. To do that select this window. Select minimum pipe step (values depends on previously selected wall system. Don't forget to mark previous "Auto pipe step selection" window) Select maximum pipe step (values depends on previously selected wall system. Don't forget to mark previous "Auto pipe step selection" window)
Border values Max. pressure drop Maximum loop lenght Maximum wall temperature Maximum pressure drop. This value is given by the manufacturer, as his recommendation of a maximum value over that we should not be allowed to go. value can be changed. This value is given by the manufacturer, as his recommendation of a maximum value over that we should not be allowed to go. value can be changed. This value is given by the manufacturer, as his recommendation of a maximum value over that we should not be allowed to go. value can be changed.
Heating temperature Wanted water Wanted water temperature on manifold for wall heating temperature (C) Temperature Temperature difference between supply and return water temperature in difference kelvin minimum water temperature difference by zones in kelvin for heating. This min. values are given according to standard, but you can change it. maximum water temperature difference by zones in kelvin for heating. This max. values are given according to standard, but you can change it. Cooling temperature Wanted water Wanted supply water temperature on manifold for cooling temperature (C) Temperature Temperature difference in kelvin for cooling difference minimum water temperature difference by zones in kelvin for cooling. This min. values are given according to standard, but you can change it. maximum water temperature difference by zones in kelvin for cooling. This max. values are given according to standard, but you can change it. WALL HEATING Wall heating: Project/Floor/Room Qn (W) ti (C) Wanted water temperature (C) Qn' (W) Qinst (W) Qre (W) Loop surface (m2) Heat losses inner room temperature. This value is given according to selected room (by standard), but you can change it. Wanted supply water temperature on manifold needed heating capacity installed heating capacity remaining heat quantity loop area of all loops on the wall in one room
Cooling calculation Qn (W) Heat load Coverage (%) Percent of installed cooling capacity Wanted water Wanted supply water temperature on manifold for wall cooling temperature (C)
System select wall heating system Pipe for system select pipe for wall heating system Connection pipe select connection pipe for wall heating system - pipe for Tichelmann pressing this button program will recalculate a complete wall heating Recalculate calculation according to some new set values. Maximum maximum pressure drop. This value is given by the manufacturer, as his pressure drop recommendation of a maximum value over that we should not be allowed (kPa) to go. value can be changed. This value is given by the manufacturer, as his recommendation of a Maximum loop maximum value over that we should not be allowed to go. value can be lenght (m) changed. Coating select one of two wall coating: ceramics tiles or paint Coating thermal conductivity Coating thermal conductivity value (W/m*K) Coating width This value depands of previus selected wall coating, Program will (mm) automatically put some standard value, but you can it. R coat. coating thermal conductivity resistance (m2*K/W) Inner coating Inner coating thermal conductivity. This value depands of previus selected thermal cond. wall coating, Program will automatically put some standard value, but you (W/m*K) can it. Inner coating Inner wall coating width, Program will automatically put some standard width (W/m*K) value, but you can it. R plaster inner plaster thermal conductivity resistance (m2*K/W) Table column for wall (pipes) connection in the tichelmann system. This function you'll can use if you have at least 2 walls written in the table along with theirs lengths of x-zones. Then you can simply with drag mouse function connect that pipes in the tichelmann system. In column than will be printed label of tichelmann system and the required length of pipe (needed for that connection). Label that is associated with the U coefficient calculation. If you already calculated U coefficient value in coefficient calculation, that just in this column type the same label (as there), and program will automatically pull that value in this Wall calculation part and place it in "U (W/m2)" column. wall label (made automatically by program) (WL + number that program automatically assigns). Label can be changed.
Tichelmann
Lbl
Label
V/M U(W/m2) Out. temp Lenght (m) Height (m) A (m2) X-zone T (mm) tw (C) t (C) l (m) Qins (W) Qtotal (W) q (W/m2) m (kg/h) w (m/s) p (kPa) Valve. pos.
manifold that is connected with loop. Thermal transmittance of building element. If you already calculated U coefficient value in coefficient calculation, that just in column "Lbl" type the same label (as there), and program will automatically pull that value here. outdoor temperature (temperature behind the wall) wall lenght wall height wall surface that you want to fill with loop lenght of x-zone pipe step - value can be changed by double-clicking on the column. wall temperature temperature difference between supply and return water loop length (that goes on that wall) installed heating capacity total wall heating capacity amount of heat that loop gives mass flow needed water flow pressure droop manifold balance valve position
WALL COOLING Wall cooling: Project/Floor/Room Qn (W) ti (C) Wanted water temperature (C) Qn' (W) Qinst (W) Qre (W) Loop surface (m2) heat gains inner room temperature. This value is given according to selected room (by standard), but you can change it. Wanted supply water temperature on manifold needed cooling capacity installed cooling capacity remaining cooling quantity loop area of all loops on the wall in one room
Heating calculation Qn (W) Coverage (%) Heat losses Percent of installed heating capacity
Wanted water Wanted supply water temperature on manifold for wall heating temperature (C) Calculate by cooling mass calculation by mass flow from cooling flow System select wall cooling system Pipe for system select pipe for wall cooling system Connection pipe select connection pipe for wall cooling system - pipe for Tichelmann pressing this button program will recalculate a complete wall cooling Recalculate calculation according to some new set values. Maximum pressure drop (kPa) Maximum loop lenght (m) Coating Coating thermal conductivity (W/m*K) Coating width (mm) R coat. (m2*K/W) Inner coating thermal cond. (W/m*K) Inner coating width (W/m*K) R plaster (m2*K/W) Table column for wall (pipes) connection in the tichelmann system. This function you'll can use if you have at least 2 walls written in the table along with theirs lengths of x-zones. Then you can simply with drag mouse function connect that pipes in the tichelmann system. Than in this column will be printed label of tichelmann system and the required length of pipe (needed for that connection)./td> Label that is associated with the U coefficient calculation. If you already calculated U coefficient value in coefficient calculation, that just in this column type the same label (as there), and program will automatically pull maximum pressure drop. This value is given by the manufacturer, as his recommendation of a maximum value over that we should not be allowed to go. value can be changed. This value is given by the manufacturer, as his recommendation of a maximum value over that we should not be allowed to go. value can be changed. select one of two wall coating: ceramics tiles or paint Coating thermal conductivity value This value depands of previus selected wall coating, Program will automatically put some standard value, but you can it. coating thermal conductivity resistance Inner coating thermal conductivity. This value depands of previus selected wall coating, Program will automatically put some standard value, but you can it. Inner wall coating width, Program will automatically put some standard value, but you can it. inner plaster thermal conductivity resistance.
Tichelmann
Lbl
Label V/M U(W/m2) Out temp. Lenght (m) Height (m) A (m2) X-zone T (mm) tw (mm) (C) t (C) l (m) Qins (W) Qtot (W) q (W/m2) m (kg/h) w (m/s) p (kPa) Valve. pos.
that value in this Wall calculation part and place it in "U (W/m2)" column. wall label (made automatically by program) (WL + number that program automatically assigns). Label can be changed. manifold that is connected with loop. Thermal transmittance of building element. If you already calculated U coefficient value in coefficient calculation, that just in column "Lbl" type the same label (as there), and program will automatically pull that value here. outdoor temperature (temperature behind the wall) wall lenght wall height wall surface that you want to fill with loop lenght of x-zone pipe step - value can be changed by double-clicking on the column. wall temperature temperature difference between supply and return water loop length (that goes on that wall) installed cooling capacity total wall cooling capacity amount of cooling that loop gives mass flow needed water flow pressure droop manifold balance valve position
CALCULATION Options Calculate all Clicking on this button program will delete existing fan coil units and replace them with some new according to some new calculation settings. (e.g. calculation according to water temperature or according to water flow temperature) Pressing this button a new window will appear Then program will automatically add one fan coil in the row in the table where you are positioned. pressing this button program will delete currently selected fan coil pressing this button program will erase all existing fan coil units. Calculation will be made by water temperature. To make calculation accoding to water temperature (after you mark Calculation accoding to water temperature radio button) press "Calculate All" button. Calculation will be made by water flow temperature. To make calculation accoding to water flow temperature (after you mark Calculation accoding to water flow temperature radio button) press "Calculate All" button.
Calculation for: Project/Floor/Room Table 1 Label Qh (W) Qs (W) ph (kPa) Qg (w) pg (kPa) Noise (dBa) Length (mm) Width (mm) Heigth (mm) fan coil name cooling capacity sensory cooling capacity cooling pressure drop heat capacity heating pressure drop fan coil noise - depends on the selected fan coil velocity fan coil length fan coil width fan coil heigth Short description of the calculation position
Table 2 Room According to: ti Qn (W) sum Qi (W) Qi (W) Speed V/M Label Model m (kg/h) p (kPa) Z (kPa) t (C) Noise (dBa) room name for which we do calculation calculation selection according to heating or cooling inner room temperature required capacity installed capacity sum installed capacity fan coil speed label for floor entry point / Riser fan coil label (FC-2 two pipe fan coil or FC4 four pipe fan coil) fan coil model - associated with the column "Label" from the previous table 1 Mass flow Pressure drop additional pressure drop Flow and return temperature difference noise at the selected speed
Warning!
Pipe group Supply water temp. (C) Return water temp. (C)
Physical characteristic of water Mean water temp. (C) Water temp. difference (C) Water density (kg/m3) Water viscosity (m2/s*10^6) Spec. water heat (kJ/kgK) medium water temperature - program will give this value about physical characteristics of water Water temperature difference - program will give this value about physical characteristics of water Water density - program will give this value about physical characteristics of water Water viscosity - program will give this value about physical characteristics of water Specific water heat - program will give this value about physical characteristics of water
Optimized calculation Pipe dimensioning according to maximum water flow velocity. check box and enter values in the next to fileds Water flow velocity in vert. pipeline (m/s) and Water flow velocity in hor. pipeline (m/s). If this check box is unchecked Pipe dimensioning according to max. water flow velocity will not be possible.
Water flow velocity in vert. pipeline Water flow velocity in vertical pipeline (m/s) Water flow velocity Water flow velocity in horizontal pipeline in hor. pipeline (m/s)
According to const. Pipe dimensioning according to constant pressure drop. check box and pressure drop (Pa/m) enter value. If this check box is unchecked Pipe dimensioning according to constant pressure drop will not be possible. Balancing valve Vertical Horizontal select balancing valve for vertical branch calculation select balancing valve for horizontal branch calculation After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only the reduction, t pieces and couplings. All previously installed fittings will be deleted.
Construct pipeline
Assign fittings
VERTICAL Table 1 R*L+Z (kPa) m (kg/h) Total pressure drop on branch mass flow
After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree Construct pipeline (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only Assign fittings the reduction, t pieces and couplings. All previously installed fittings will be deleted. Copy flow or return If you already made flow sections, than (pressing this button) program sections can copy in this table the same flow sections as return sections. Table 2 sections type (flow or return sections). Red arrows is mark for flow section, blue arrows is mark for return section. Program first begin to enter flow sections, and then continues with return sections. You can replace this two sections types on simple way if you do double click with left mouse button in this column. Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1).
Type
From
DN
Pipe t (C) w (m/s) R (kPa/m) R*L (kPa) Z (kPa) R*L+Z (kPa) kv xb HORIZONTAL
section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. Double-click in column field "Device" and select floor entry that is connected to section endpoint. section capacity mass flow volume flow section lenght Minor loss coefficient. Double-click in this column and you can define types and number of local pressure drop (T-pieces; elbows..). Program will calculate total coefficient of local pressure drops based on selected types and number of elements. If you do not want to choose fitting products from the database you can manually enter the "Zeta" value. Value will be taken into account later in the calculations. exterior pipe diameter. if you want to change some pipe than here type some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program will select first pipe (from program datebase) whith that DN. Pipe selection: program select pipe according to heat flow, but you can for every section select some other pipe. For selection do double-click in column. Section water temperature (selected on default settings). Value can be changed. section flow - program calculate this value pressure drop in section due to local pressure drop line pressure drop in section pad tlaka zbog lokalnih otpora maksimum pressure drop coefficient flow on valve adjustment valve position
After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree Construct pipeline (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only Assign fittings the reduction, t pieces and couplings. All previously installed fittings will be deleted. Copy flow or return If you already made flow sections, than (pressing this button) program sections can copy in this table the same flow sections as return sections.
Table 2 sections type (flow or return sections). Red arrows is mark for flow section, blue arrows is mark for return section. Program first begin to enter flow sections, and then continues with return sections. You can replace this two sections types on simple way if you do double click with left mouse button in this column. Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1). section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. Double-click in column field "Device" and select floor entry that is connected to section endpoint. section capacity mass flow volume flow section lenght Minor loss coefficient. Double-click in this column and you can define types and number of local pressure drop (T-pieces; elbows..). Program will calculate total coefficient of local pressure drops based on selected types and number of elements. If you do not want to choose fitting products from the database you can manually enter the "Zeta" value. Value will be taken into account later in the calculations. exterior pipe diameter. if you want to change some pipe than here type some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program will select first pipe (from program datebase) whith that DN. Pipe selection: program select pipe according to heat flow, but you can for every section select some other pipe. For selection do double-click in column. Section water temperature (selected on default settings). Value can be changed. section flow - program calculate this value pressure drop in section due to local pressure drop line pressure drop in section pad tlaka zbog lokalnih otpora maksimum pressure drop coefficient flow on valve adjustment valve position
Type
DN
Warning!
Pipe group
Calculation mode
Physical characteristic of water Mean water temp. (C) Water temp. difference (C) Water density (kg/m3) Water viscosity (m2/s*10^6) Spec. water heat (kJ/kgK) medium water temperature - program will give this value about physical characteristics of water Water temperature difference - program will give this value about physical characteristics of water Water density - program will give this value about physical characteristics of water Water viscosity - program will give this value about physical characteristics of water Specific water heat - program will give this value about physical characteristics of water
Optimized calculation Pipe dimensioning according to maximum water flow velocity. check box and enter values in the next to fileds Water flow velocity in vert. pipeline (m/s) and Water flow velocity in hor. pipeline (m/s). If this check box is unchecked Pipe dimensioning according to max. water flow velocity will not be possible.
Water flow velocity Water flow velocity in vertical pipeline in vert. pipeline (m/s) Water flow velocity Water flow velocity in horizontal pipeline in hor. pipeline (m/s) Pipe dimensioning according to constant pressure drop. check box and According to const. enter value. If this check box is unchecked Pipe dimensioning pressure drop (Pa/m) according to constant pressure drop will not be possible. Balancing valve Vertical Horizontal select balancing valve for vertical branch calculation select balancing valve for horizontal branch calculation After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only the reduction, t pieces and couplings. All previously installed fittings will be deleted.
Construct pipeline
Assign fittings
VERTICAL Table 1 R*L+Z (kPa) m (kg/h) Total pressure drop on branch mass flow
After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree Construct pipeline (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only Assign fittings the reduction, t pieces and couplings. All previously installed fittings will be deleted. Copy flow or return If you already made flow sections, than (pressing this button) program sections can copy in this table the same flow sections as return sections.
Table 2 sections type (flow or return sections). Red arrows is mark for flow section, blue arrows is mark for return section. Program first begin to enter flow sections, and then continues with return sections. You can replace this two sections types on simple way if you do double click with left mouse button in this column. Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1). section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. Double-click in column field "Device" and select floor entry that is connected to section endpoint. section capacity mass flow volume flow section lenght Minor loss coefficient. Double-click in this column and you can define types and number of local pressure drop (T-pieces; elbows..). Program will calculate total coefficient of local pressure drops based on selected types and number of elements. If you do not want to choose fitting products from the database you can manually enter the "Zeta" value. Value will be taken into account later in the calculations. exterior pipe diameter. if you want to change some pipe than here type some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program will select first pipe (from program datebase) whith that DN. Pipe selection: program select pipe according to heat flow, but you can for every section select some other pipe. For selection do double-click in column. Section water temperature (selected on default settings). Value can be changed. section flow - program calculate this value pressure drop in section due to local pressure drop line pressure drop in section pad tlaka zbog lokalnih otpora maksimum pressure drop coefficient flow on valve adjustment valve position
Type
DN
HORIZONTAL After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree Construct pipeline (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only Assign fittings the reduction, t pieces and couplings. All previously installed fittings will be deleted. Copy flow or return If you already made flow sections, than (pressing this button) program sections can copy in this table the same flow sections as return sections. Table 2 sections type (flow or return sections). Red arrows is mark for flow section, blue arrows is mark for return section. Program first begin to enter flow sections, and then continues with return sections. You can replace this two sections types on simple way if you do double click with left mouse button in this column. Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1). section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. Double-click in column field "Device" and select floor entry that is connected to section endpoint. section capacity mass flow volume flow section lenght Minor loss coefficient. Double-click in this column and you can define types and number of local pressure drop (T-pieces; elbows..). Program will calculate total coefficient of local pressure drops based on selected types and number of elements. If you do not want to choose fitting products from the database you can manually enter the "Zeta" value. Value will be taken into account later in the calculations. exterior pipe diameter. if you want to change some pipe than here type some other exterior pipe diameter (DN) (e.g. 20, 25, 30,...). Program will select first pipe (from program datebase) whith that DN. Pipe selection: program select pipe according to heat flow, but you can for every section select some other pipe. For selection do double-click in column. Section water temperature (selected on default settings). Value can be changed. section flow - program calculate this value
Type
DN
pressure drop in section due to local pressure drop line pressure drop in section pad tlaka zbog lokalnih otpora maksimum pressure drop fan coil valve coefficient flow on valve adjustment valve position
Warning!
Building type Cold water temp. (C) Hot water temp. (C) Cold water pipe (...) Hot water pipe (...)
Armatures on installation
Constant water velocity Pipe dimensioning according to maximum water flow velocity. Select window (if you want to do dimensioning according to maximum water flow velocity) and type maximum water flow velocity in vertical and horizontal pipeline. Type water flow velocity in vertical pipeline. This field is visible only Water flow velocity if field "Pipe dimensioning according to max. water flow velocity" is in vert. pipeline (m/s) checked. Type water flow velocity in horizontal pipeline. This field is visible Water flow velocity only if field "Pipe dimensioning according to max. water flow velocity" in hor. pipeline (m/s) is checked. Pipe dimensioning according to max. water flow velocity Watermeter Vgv (l/s) Pgw (kPa) Filter Vgf (l/s) Pgf (kPa) Quick calculation Inner diameter for connection pipe used information field that shows inner diameter of selected connection pipe. for calculation info field shows selected selected connection pipe VERTICAL Table 1 hgeo (m) Pgeo (kPa) Pwz (kPa) Pfil (kPa) Peh (kPa) Pdos (kPa) Pte (kPa) Pap (kPa) PminFL (kPa) geodetic height difference pressure drop for geodetic difference watermeter pressure drop filter pressure drop pressure drop on water softening device pressure drop on dosing equipement pressure drop on water heating device pressure drop on other devices minimal hydraulic pressure type maximum water flow through the filter. type pressure drop on filter. type maximum water flow through the watermeter. type pressure drop on watermeter.
pressure drop in separate sections local pressure drop pressure drop on branch After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only the reduction, t pieces and couplings. All previously installed fittings will be deleted.
Construct pipeline
Assign fittings
Table 2 sections type (flow or return sections). Red arrows is mark for flow section, blue arrows is mark for return section. Program first begin to enter flow sections, and then continues with return sections. You can replace this two sections types on simple way if you do double click with left mouse button in this column. Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1). section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. section lenght minor loss coefficient. Double-click in column field "Device" and select floor entry that is connected to section endpoint. (here you connects floor to vertical pipeline section. Duble click on the cell and choose floor entry for the pipeline section.) total flow inner pipe diameter pipe dimension calculation flow water temperature water velocity pressure drop per meter pressure drop in pipes caused by fiction pressure drop caused by local resistance total pressure drop in section
Type
From To L (m) Device Vri (l/s) DN Pipe Vs (l/s) t (C) w (m/s) R (kPa/m) R*L (kPa) Z (kPa) R*L+Z (kPa)
HORIZONTAL After you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes through all sections and sets fittings. This command adds only the reduction, t pieces and couplings. All previously installed fittings will be deleted.
Construct pipeline
Assign fittings
Table sections type (flow or return sections). Red arrows is mark for flow section, blue arrows is mark for return section. Program first begin to enter flow sections, and then continues with return sections. You can replace this two sections types on simple way if you do double click with left mouse button in this column. Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1). section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. section lenght minor loss coefficient. Double-click in column field "Device" and select floor entry that is connected to section endpoint. (here you connects floor to vertical pipeline section. Duble click on the cell and choose floor entry for the pipeline section.) total flow inner pipe diameter pipe dimension calculation flow water temperature water velocity pressure drop per meter pressure drop in pipes caused by fiction pressure drop caused by local resistance total pressure drop in section
Type
From To L (m) Device Vri (l/s) DN Pipe Vs (l/s) t (C) w (m/s) R (kPa/m) R*L (kPa) Z (kPa) R*L+Z (kPa)
Table From To L (m) Fittings Device Aws (l/s) qs (l/s) Gradient (%) DN Pipe Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1). section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. section lenght by double click on this column a new window will appear. Here you can select fitting grups and number of fittings. Double-click in column field "Device" and select floor entry that is connected to section endpoint. (here you connects floor to vertical pipeline section. Duble click on the cell and choose floor entry for the pipeline section.) water flow for drainage points total flow of building drainage pipe gradient pipe inner diameter pipe dimension
HORIZONTAL after you define branches, click "Construct pipeline". Branches will be automatically sorted and you can review them on a branch tree (clicking on the desired branch) or in tables (clicking in any branch field in the table). For selected heating installation (marked on the branch tree) program passes Assign fittings through all sections and sets fittings. This command adds only the reduction, t pieces and couplings. All previously installed fittings will be deleted. Construct pipeline Table From To L (m) Fittings Device Aws (l/s) qs (l/s) Gradient (%) DN Starting section point. Program will automatically put endpoint of section in column "To" (Note: first section must start with number 1). section endpoint. After you finish with flow section input in table, you can do return sections. In next table line for a starting point tipe again number 1, or use "Copy flow or return sections" button. section lenght by double click on this column a new window will appear. Here you can select fitting grups and number of fittings. Double-click in column field "Device" and select floor entry that is connected to section endpoint. (here you connects floor to vertical pipeline section. Duble click on the cell and choose floor entry for the pipeline section.) water flow for drainage points total flow of building drainage pipe gradient pipe inner diameter
VENTILATION DUCTS
DEFAULT SETTINGS Calculation selection for rectangular ducts: Calculation of rectangular ducts according to hydraulic diameter is Calculation calculated by formula: Dh=4A/P (Dh - hydraulic diameter; A - Area of according to ventilation duct cross-section; P - ventilation duct cross-section hydraulic diameter perimeter). Ventilation calculation by ASHARE, for diameters - according to Calculation Huebscher (1948) formula. De=1,30(ab)0,625/(a+b)0,250 (De - circular according to equivalent of rectangular duct for same length, fluid resistance and flow, ASHARE mm ; a,b - sides of rectangular duct, mm Default settings Duct material (...) Set Duct type Set Fresh air temperature (C)/td> Set all select one of duct materials that program offer Material settings. Here you can check or change some basic material data such as name, values of density and roughness. if you change material, click "Set" button so that program can accept changes. Click on drop-down menu and select type of ventilation ducts (O - round elements, P - rectangular elements) if you change duct type, click "Set" button so that program can accept changes. Input value for temperature of fresh air. Program has entered a default value that can be changed. if you press this button program will accept all changes that you made on default settings window and use them in all ventilation ducts.
Calculation according to: Calculation according to constant velocity. If you do Calculation constant velocity according to this method, than enter velocity value. (w - velocity (m/s)) w - velocity (m/s) Velocity that should not be cross during this calculation. Calculation according to constant pressure drop If you do Calculation constant pressure according to this method, than enter pressure drop value. (R - pressure drop drop (Pa)) R - pressure drop pressure drop that should not be cross during this calculation. (Pa)
Element label Program will show that fitting label in calculation. Default label depends Fitting label of program language (e.g. for english language it's F - (as Fitting). Default label also can be changed. if you change default fitting label press this button so that program can Reset label accept changes. Program will show that grill label in calculation. Default label depends of Grill label program language (e.g. for english language it's G - (as Grill). Default label also can be changed. if you change default grill label press this button so that program can Reset label accept changes. Program will show that duct element label in calculation. Default label Duct element label depends of program language (e.g. for english language it's EL - (as Element Label). Default label also can be changed. if you change default element label press this button so that program can Reset label accept changes. Duct dimensioning Calculate by constant (mm) ducts width select this window if you want do dimensioning of rectangular duct according to constant ducts width or height. Enter a constant value in mm. select this radio button if you want do dimensioning of rectangular duct according to constant ducts width. If the button is not visible select "Calculate by constant (mm)" select this radio button if you want do dimensioning of rectangular duct according to constant ducts height. If the button is not visible select "Calculate by constant (mm)" Maximum aspect ratio for rectangular ducts. If this field is not visible select "Calculate by constant (mm)"
VOLUME Select volume calculation type Volume calculation according to free entry value. In this calculation type, it is necessary to input needed supply air volume (V su). Red row represents heating values, and blue row represents cooling values. In this type of calculation you don't need to write room dimensions (a, b, c, A, V), fresh air temperature (tw) and inner room temperature (ti)
0 - Free entry
Volume calculation according to room type and number of persons. In this calculation type, it is necessary to input number of air exchange rate (nr. of air ex.), number of persons that staying in the room (nr. of per.), volume per person (V per. per.) and volume of 1m of surface. Multiply with room surface to get total room volume. Used with the type 1 calculation only if the resulting room volume is bigger than the calculated volume from air exchange and number of persons (V per. surf.). Required values can be written in field or selected from special window by double clicking on field. Depending on data, program calculates needed air flow volume. In this type of calculation data for room dimension is required. Volume calculation according to required heating/cooling capacity In this calculation type it is necessary to input internal room temperature (ti), fresh air temperature (tw) heat losses/ gains (Q) (losses - red row, gains blue row). Depending on data program calculates needed air flow volume. After you select one of three volume calculation type press this button so that program can accept selected calculation. pressing this button new window will appear where you can download (transfer) heat losses or heat gains.
Transfer
Table Label Room Type a (m) b (m) c (m) A (m2) V (m3) ti (C) tw (C) nr. of air ex. (h-1) nr. of per. (n) V per. per. (m3/h) V per surf. (m3/(m2/h)) V su. (m3/h) Q (W) Room label (same label as in project tree) Room name Volume calculation type (0 - free entry; 1 - room type/number of persons:; 2 - required heating/cooling capacity:) room length in m room width in m room height in m room area in m2 room volume in m3 Internal room temperature in (C) fresh air temperature in (C) Number of air exchanges with fresh air during 1 hour in room number of persons in room needed air flow volume per person Needed air flow volume in one hour per square meter of room Sum of exchange Air flow volume Heat loss/gains
short description of the column from the table above where you are positioned blue marked line in the table that displays cooling data pink marked line in the table that displays heating data
VENTILATION DUCTS You can add only one grill on each ventilation section. Procedure: click on any cell of ventilation section where you want to add grille/ click on "Add grille" button/ enter value of volume flow on grille/ select type of Add grille ventilation ducts (round or rectangular)/ enter value of grille dimensions (diameter for round grille or width and height of rectangular grille)/ enter value of pressure drop on grille / click on "Add" button. With fitting we connect ventilation sections. Procedure: Click on some cell of ventilation section where fitting starts / Click on "Add fitting" button (new window will appear) / In drop-down menu Fitting group select which type of fitting you need. Program suggests possible groups Add fitting of fittings depending on number of continuing connected sections. / Select fitting. If there is no listed fitting you want to put, select some similar and manually input drag coefficients/ Specify ventilation sections order / Input fitting technical data / Click on "Ok" button. Ventilation element can be any part of ventilation who causes some pressure change (e.g. silencer, flap) and you can not add it on any other way. Procedure: Click on some cell of ventilation section where you Add duct element want to add duct element./ Click on the "Add duct element" button (new window will appear)/ Enter duct element name / Enter pressure drop value/ Click on the "Add" button After changes in tabular calculation part click on this button and program Construct will recalculates pressure drop and dimensions of ventilation ducts. If ventilation pipeline you don't want to recalculate dimensions of ventilation ducts turn off option ''Reset ventilation duct dimensions''. if this button is checked program will display ID column in down table. Show element ID (ID column displays fitting, grills or duct element labels) If button is unchecked ID column will not be visible. maximum pressure drop on ventilation installation. On branch tree select p max,i branch for which you want to see this value. pressure drop on selected ventilation branch. On branch tree select p grane branch for which you want to see this value. Maximize table view (see all ventilation duct sections together with all (+) fittings, grills ...) Minimize table view (see just ventilation duct sections without fittings, (-) grills ...)
Table From To V (m3/h) l (m) Material type OP D/a (mm) b (mm) Dh (mm) s (mm) w (m/s) R (Pa/m) R*l (Pa) Z (Pa) R*l+Z (Pa) beginning of ventilation section end of ventilation section Volume flow length of ventilation ducts section ventilation duct material ventilation ducts type (O - round elements, P - rectangular elements) D - Diameter of round duct/ a - side A on rectangular duct Side B on rectangular duct Equivalent diameter of rectangular duct Calculation depends of selected formula in default settings Thickness of ventilation duct material Air velocity in ventilation duct local pressure drop coefficient major loss per meter of ventilation duct major loss per section of ventilation duct minor loss on section (element of section) total head loss (pressure drop) on section of ventilation ducts
Calculation print: Select "Print" module on the main IntegraCAD window and then click the vertical tab "Calculation". When you click on that print module, program will automatically create those print calculations which you use in program (e.g. you used two pipe calaculaton (radiators) and heating pipeline calculation in that case program will automatically set these two calculations in his print module). If you selected all calculation in program, you will must use "Move" toolbar with four buttons to see them all, because all will not fit in print window. If you already at the beginning know what prints you will need, you can set them in the main Print menu of program. There are two possible ways: 1.) direct from the menu (shorter display)
2.) or by "Print options" button (in that menu) - graphically displays individual prints
Print editing is possible by program print toolbars or directly by typing and modifying data If later come to some changes in calculations, calculations data must be refreshed by function Refresh print data located in the toolbar. Warning ! All manually entered datas and changes in the print list will be deleted by using that update function. That is why we recommend that first fully complete calculation part and than continue with editing. All prints created by the program are listed by lower left edge of the print window. You also can change currently displayed print list name by clicking on his name. Lists of material: Select "Print" module on the print window (if it is not already active), and then click the vertical tab "Material list". At the top of the window there are buttons for createing and some functions to work with a lists of materials like:
Insert list - create a new list of materials Delete list - delete the currently active list of materials Open - loading already creted material list (document with .ISD extension) Save - saveing active material list (document with have .ISD extension) Save as - saveing the material list under a different name Once you save material list as .ISD file you will can open it in any IntegraCAD program version, change it and save agein The difference between .INT file (project files) and .ISD file (list materials file) is that .INT file contains all information about a project, .ISD file only contains a list of materials, without calculations data, structure object data etc... Once created a material list can be changed at any time, but there is no automatic connection with calculation in which was created. If there is a change of some calculation, the list of material information can be refreshed using the function "Refresh data", or you can create a new print materials list that shows the current situation.
If you need you can have more different lists - made from the same project. To create a new list of materials, click on the button "Insert List" - new window will appear with all parameters for adjustment the new look for material list (insert on one list, on more lists, description types (long, short, without descriptions)
Function overwiew
Calculation print list can be arrange by special tools on the toolbar.
PRINT: Export to excel - functions that exports program data in Excel (xls) file. OPTIONS: Add total price - this function add column with total price in print list Price properties- price options (e.g. discounts, tax...) BILL OF MATERIAL: Insert row - program insert rows in the table Delete row - program delete rows in the table Refresh data- with this funkcion program do refreshing for some changed data Undo - Undo the last operation Redo - this function cancel Undo function Align left - align left text and/or numbers in print list Center - center yours text and/or numbers in print list Align right - aligns right text and/or numbers in print list Sort by number - sort by number in print list Most of the functions in this menu you can also choose from the toolbar List
If you click whith right mouse button on some print list, program will open up additional menu from which you also can call some standard functions like "Insert Row", "Delete Row" cut, copy, paste ... TEXT: Bold, Italic, Underline - editi letter style Font size - select font size from the drop-down menu Font type - select font type from the drop-down menu Cell color - an additional dialog will appear in which you can choose one of the listed colors, or create your own colors from the palette attributed. Cell color - an additional dialog will appear in which you can choose one of the listed colors, or create your own colors from the palette attributed. Print language - Choosing one of the available languages from the drop-down menu you can translate the prints on several language. This function can translate all the text that was created with this program. (titles, calculation names, table names etc.) and some of products (if we have translation for tham in program database). This function can not translate the text that user alone add in print list. Most of the functions in this menu you can also choose from the Text toolbar
CAD
Creates straight line segments Integra CAD draws a line segment and continues to prompt for points. You can draw a continuing series of line segments, but each line segment is a separate object. Specify first point: Specify a point Specify next point or [Close/Undo] Finish command with right click or choosing Close Close: Line Crta LINE Ends the last line segment at the beginning of the first line segment, which forms a closed loop of line segments. You can use Close after you have drawn a series of two or more segments. Undo: Erases the most recent segment of a line sequence. Entering u more than once backtracks through line segments in the order you created them. Creates an arc defined by center and radius Arc Luk ARC Specify center of arc Specify radius of arc Specify first point of arc Specify last point of arc Creates an arc defined by 3 points Specify first point of arc Specify last point of arc Specify point on arc
3T
3T
ARC3T
Creates circle defined by center and radius Specify center point Specify radius of circle: enter value or specify point. (The distance between this point and the center point determines the radius of the circle.) Creates circle defined by two points Circle 2P Krunica 2T CIRCLE2T Specify first point on circle Specify second point on circle Creates circle defined by three points Circle 3P Krunica 3T CIRCLE3T Specify first point on circle Specify second point on circle Specify third point on circle Creates the ellipse defined by center point, endpoint of one axis and radius to other axis Specify center of ellipse Specify endpoint of axis Specify distance to other axis Creates 2-dimensional polyline (connected lines forming one object) Specify start point: Specify a point Specify next point or [Close/Undo] Close: Ends the last line segment at the beginning of the first line segment, which forms a closed loop of line segments. You can use Close after you have drawn a series of two or more segments. Undo: Erases the most recent segment of a line sequence. Entering u more than once backtracks through line segments in the order you created them.
Circle
Krug
CIRCLE
Elipse
Elipsa
ELLIPSE
Polyline
Polilinija
PLINE
Draws a rectangular polyline Rectangle Pravokutnik RECT Specify one corner of rectangle Specify opposite corner of rectangle Command for writing single line text Text Tekst TEXT Specify where you want to start Specify direction of writing Write text Press Enter for finish Creates an aligned linear dimension Specify first extension line orgin Specify second extension line Specify location of dimension line Creates an vertical linear dimension Specify first extension line orgin Specify second extension line Specify location of dimension line Creates an horizontal linear dimension Horizontal Dimens. Horizontalna kota DIMHOR Specify first extension line orgin Specify second extension line Specify location of dimension line Creates an angular dimension Specify angle vertex: Specify a point (1) Specify first angle endpoint: Specify a point (2) Specify second angle endpoint: Specify a point (3) Specify dimension line location Creates quick dimension Specify line for Dimension: Specify location of dimension line Creates diameter dimensions for circles and arcs Specify circle or arc
DIMALI
Vertical Dimension
Vertikalna kota
DIMVER
Angular Dimension
Kotiranje kuta
""
Quick dimension
Brzo kotiranje
QDIM
Diameter Dimension
Kotiranje promjera
DIMDIA
Radial Dimension
Kotiranje polumjera
DIMRAD
Creates radial dimensions for circles and arcs Specify circle or arc Creates a block definition from objects you select
Make Block
Stvori blok
MBLOCK
Block name: Specify insertion point: Select entities Places named block into the current drawing Opens dialog box where you can define insertion point, scale and rotation. By clicking on checkbox you can select insertion point, scale and rotation on screen. Opens dialog box to save block in file Opens dialog box to import image in file
Insert block
Umetni blok
INSERT
Write Block
Zapii blok
WBLOCK
Picture
Slika
IMAGE Select image to import Specify insertion point Specify external reference Select where font files are located
XREF STYLE
- MODIFICATION -
Removes objects from a drawing Erase Brisanje ERASE Select the objects to erase and press ENTER Displaces objects a specified distance in a specified direction Move Pomicanje MOVE Select entities: Move from point: Move to point: Duplicates objects Copy Kopiranje COPY Select entities: Copy from point: Copy to point
Moves objects about a base point Rotate Rotiranje ROTATE Select entities Rotation base point Rotation angle (write or select with mouse) Enlarges or reduces selected objects proportionally in the X, Y, and Z directions Scale Skaliranje SCALE Select entities Specify base point Specify scale factor Breaks a compound object into its component objects Select entities Moves or stretches objects Select entities Window select 1st point Window select 2nd point (Inside of the window are points which will be streched) Strech from point Move to point Extends an object to meet another object Extend Proiri EXTEND Select entities Select entities to extend (first select where to select, then what to extend) Trims objects at a cutting edge defined by other objects Trim Odrei TRIM Select entities Select entities to trim (first select where to select, then what to trim) Creates concentric circles, parallel lines, and parallel curves Select entitiy to offset Offset distance Side to offset
Explode
Eksplodiranje
EXPLODE
Stretch
Razvuci
STRETCH
Offset
Offset
OFFSET
Breaks the selected object between two points Break Prekini BREAK Select entity Select first break point Select second break point Rounds and fillets the edges of polyline FILLET Fillet radius Specify polyline Creates a mirror image copy of objects Mirror Zrcali MIRROR Select entities Specify first point on mirror line Specify second point on mirror line Measuring distance between selected points Specify first point Specify second point After specifiying all wanted points, with right click finish command. Distance is printed in command line (in real units if drawing is made in mm, distance will be printed in mm with no regard to mesure we set) Useful for determing units in which drawing is created. - OSNAP -
Fillet PolyLine
Zaobli poliliniju
Distance
Udaljenost
DIST
When one or more OSNAP (Object snap) buttons is turned on, you can specify required point at an exact location on an object. When more options are selected INTEGRACAD applies the selected snap modes to return a point closest to the cursor. Osnap End Osnap End Snaps to endpoint of line, arc, (Alt + E) (Alt + E) polyline, object Osnap Mid (Alt + M) Osnap Cen Osnap Mid (Alt + M) Osnap Cen Snaps to midpoint of line, arc, polyline segment Snap to center of circle or arc
(Alt + C) Osnap Per (Alt + P) Osnap Nea (Alt + N) Snaps to a point perpendicular to an arc, line, circle, polyline... Snaps to nearest point on object It is recommened to turn on only when is needed (because of easier selection of other osnap points) Snaps to a point in extension of lines for to selected objects (apparent intersection) When using this osnap it i needed to click twice to snap on point! Select first object By moving mouse cursor near other objects, program is calculatinng where would be intersections with other objects. You select one intersection. If first object is selected with this osnap, you can't use osnap points other than apparent intersections. It is recommened to turn on only when is needed (because of easier selection of other osnap points) Turn off all osnap functions
Osnap
Osnap Dialog
Dialog (Alt + O)
(Alt + O)
functions.
Recommended osnap functions turned on Insertion - snap to point of block insertion Node (point) - snap to single point Quadrant - snaps to a quadrant point of an arc, circle, ellipse. Quadrant point are located on intersections of imaginary coordinate system with origin in center of object (direction of x and y axis od coordinate system are same as current UCS). Osnap Quadrant is on priority list before osnap center, and is recommnded to turn it on only in case of need. Tangent - enables selection tangent vertex on the circle, ellipse or a circular arc Intersection (one point) - select intersection of two objects
Zooms to display an area specified by two opposite corners of a rectangular window Window Prozor ZW Specify first corner Specify opposite corner Zooms to display the drawing extents and results in the largest possible display of all the objects. Zooms to display the previous view. Zoom in for default value Use mouse scroll up to zoom in Zoom out for default value Use mouse scroll down to zoom out Shifts location of view in any direction. While pan cursor is active (hand instead of cross), press point on the screen and move mouse in wanted direction you want to move view location. You can activate pan by clicking middle mouse button. In this case press point on screen with middle mouse button and drag cursor to direction you want and release middle mouse button. All Sve Zooms to display the entire drawing in the current viewport.
ZE ZP ZI ZO
PAN
Naredba PAN
PAN
- LAYER -
Layers are primary organizational tool in INTEGRACAD. Similar objects we can associate similar objects in same layer. For example you can separate construction lines, text, dimension lines in separate layers. For every layer we can control name, colour, linetype and lineweight. Layers can be frozen (forzen layer is invisible and excluded from regeneration and plotting) and locked (objects are visible but can't be edited or selected). INTEGRACAD uses specific layers for drawing hot and cold water pipes. If you draw lines in other CAD program, layer has to be exactly the same as INTEGRACAD layer, otherwise collectiong pipeline won't work. Turning freeze on and of on some layers, drawing becomes more clear and it is easier to manage inside of it. Creating layers: 1. Open dialog box manage layers 2. Write the name of the layer 3. Click on button New layer 4. Find it in table below, click on the row and modify if needed. Click on the button Set current to make layer active. Layer Properties Manager Shoutcout for command is LAYER
<> - PIPE -
Crtanje cijevi polaza tople vode Crtanje cijevi povrata hladne vode
PIPEHOT
Draw flow water pipe. Pipes are drawn like polylines Draw return water pipe. Pipes are drawn like polylines Simultaneusly draw flow and return water pipes.First you draw flow pipe and then clik side to automaticly draw return water pipe.
PIPECOLD
Warm and Istovremeno cold water crtanje polaza pipe i povrata drawing Drawing Crtanje cijevi cold water hladne vode pipes Drawing Crtanje cijevi hot water tople vode pipes Circulation pipe drawing Drainage pipe drawing Join sections Crtanje cijevi cirkulacije Crtanje cijevi odvodnje
DOUBLEPIPE
PIPECOLDWATE Draw cold water pipes. Pipes are R drawn like polylines PIPEHOTWATER Draw hot water pipes. Pipes are drawn like polylines Draw circulation pipes. Pipes are drawn like polylines. Draw drainage pipes. Pipes are drawn like polylines. Joint sections joint pipes which are connected in one ending point to become one pipe. Specify first section Specify second section Secton break divides section in two sections Specify break point Lowering pipe height- Only in UCS (user specified coordinate system) Specify place which you want to lower on height of world coordinate system Specify place where you want to lower on height of world coorinate system Program draws line from first point to second point in user specified coordinate system (UCS), in second point program lowers line to height of world UCS (height z=0) CALCPIPELINE Construct pipeline-
PIPECIRC
PIPEDRAIN
Spajanje dionica
Section break
Prekid dionice
Construct
Slaganje
pipeline
cjevne mree
Specify area where you want to construct pipeline. Pipes (lines representing pipes) must be conected to radiators/fan coils and floor entry points. Every radiator and fan coil must have specific identification number (they should't be coopied from the drawing, you have top add them from list of equipement) Integrity check of pipeline Turn it on and off before using command construct pipeline. If it is on, connstruct pipeline won't make calculation of pipeline. It will just make check if all the lines are correctly connected in CAD drawing. You can mark pipes, radiators, manifolds and other elements of pipeline. After turning command on, you have to choose element you want to mark (e.g. pipe). Select location you want to place mark (you can see it while moving mouse). Mark is writen like block and you need to use command Explode if you want to edit text. Before generating riser scheme you have to select branch on instalation tree. Program draws scheme of instalations in new drawing (command for generating scheme stays pressed and indicates working on riser scheme). After editing riser scheme you need to save it using standard command save drawing. For return on groung plan you have to turn off command generate riser scheme by pressing it again and after that click on floor. WARNING: compulsory save ground plan before generating riser scheme. Automatic elements connection
Element selection
Oznaavanje elemenata
Elements
Automatsko
automatic connection
spajanje elemenata
From right to left select elements you want to connect From right to left select pipes where you want to join elements. - 3D VIEW -
WORLD
WORLD
WORLD
Basic coordinate system of drawing Orgin point is (0,0,0) and axis are in direction od main axis User defined coordinate system by current view User defined coordinate system by three points Specify orgin point of UCS Specify height of orgin point Specify point in x direction Specify height of the point on x direction Specify point in y direction Specify height of the point on y direction Used defined coordinate system defined by object coordinates. Top view (plane X-Y) ground plan Bottom view (plane X-Y) Left view (plane Y-Z ) body plan Right view (plane Y-Z) Front view (plane X-Z) plan Back view (plane X-Z) 3D view from South-West 3D view from South-East 3D view from North-East 3D view from North- West
UCS
UCS
UCS
UCS iz 3 toke
UCS
UCS object View top View bottom View left View right View front View back View SW View SE View NE View NW Rotate3D
UCS objekt Pogled odozgo Pogled odozdo Pogled s lijeva Pogled s desna Prednji pogled Stranji pogled Pogled SW Pogled SE Pogled NE Pogled NW 3D rotiranje
UCS
Dynamic
Click point on the screen with first mouse button, hold and rotate view by moving mouse. Move view by presing and holding middle mouse button. Pogled odozgo Pogled objekta View te orgin of current UCS on specific height View acording to selected point of view and point to view Specify point of view - UCS VIEW -
UCS view
UCS pogled
Click on icon for saving current UCS Write the name of UCS Click on OK Saved UCS you can select in any moment in drop down box located in toolbar UCS view. delete selected UCS view.
- EDIT -
Undo Redo
Poniti Ponovi
U REDO
UNDO actions in CAD, can be activated multiple times. REDO actions canceld with UNDO.
- LOOP -
Automatic Automatsko double crtanje duple parallel loop paralelne drawing petlje
Automatic parallel loop drawing tool Specify area of room which will be covered with floor heating. (Specify end points of room, when you select last point, click right mouse button to connect it with first point) Specify entry point... (You specify where loop will enter the room) Window pops up where you have to select manifold on which loop is connected. After that you have to select distance between pipes in the loop, offset from wall and direction of drawing loop. Default way of drawing floor heating is counterclockwise. It is recommended to choose direction on longer side. Automatic double parallel loop drawing tool Specify area of room which will be covered with floor heating. (Specify end points of room, when you select last point, click right mouse button to connect it with first point) Specify entry point... (You specify where loop will enter the room) Window pops up where you have to select manifold on which loop is connected. After that you have to select distance between pipes in the loop, offset from wall and direction of drawing loop. Default way of drawing floor heating is counterclockwise. It is recommended to choose direction on longer side.
Automatsko crtanje
Automatic spiral loop drawing tool Specify area of room which will be
drawing
spiralne petlje
covered with floor heating. (Specify end points of room, when you select last point, click right mouse button to connect it with first point) Specify entry point... (You specify where loop will enter the room) Window pops up where you have to select manifold on which loop is connected. After that you have to select distance between pipes in the loop, offset from wall and direction of drawing loop. Default way of drawing floor heating is counterclockwise. It is recommended to choose direction on longer side. Cut part of loop Specify first point to cut Specify second point to cut Reset loop label Take name from calculation and set it on CAD drawing Calculate loop length Program calculates real length of loops from CAD drawing. - TOOLS -
Ponovno postavi oznake petlji Proracunaj Calculate stvarne duljine loop length petlji
Tool for seting room area Select room from project Specify end points of room, when you select last point, click right mouse button to connect it with first point Program calculates room area
Tool for specifying wall length Click two times in calculation field
where you want to take length from drawing. Drawing is automaticly opened. Select points you want to measure from drawing. Length you measure is scaled depending on measure set for dwg file in info tab. Hide foreing layers Sakrivanje stranih slojeva Tool for freezing all non INTEGRACAD layers set drawing reference point Select floor heating loop. Loop edges are rounded and second half of the loop is transfered in layer return. - VENTILATION CANALS Draw supply ventilation ducts Draw drainage ventilation ducts Crtanje dovodnih ventilacijskih kanala Crtanje odvodnih ventilacijskih kanala
Set drawing Postavi baznu reference toku crtea point Zavrna Finalize obrada petlji loop podnog drawing grijanja
Draw supply ventilation ducts. Pipes are drawn like polylines Options: draw rectangular and circular ventilation ducts. Draw drainage ventilation ducts. Pipes are drawn like polylines Options: draw rectangular and circular ventilation ducts. Setting up a network of ventilation ducts Specify area where you want to construct network of ventilation ducts. Ventilation ducts must be conected to floor entry points.
Mark
Oznai
ventilation element
element ventilacije
After turning command on, you have to choose element you want to mark. Select location you want to place mark (you can see it while moving mouse). Mark is writen like block and you need to use command Explode if you want to edit text.
Admin
Introduction
Admin is a simple tool for radiator or room input into program, if they do not exist in it.
Starting the admin module: Menu -> Edit -> Admin (Picture 1)
Picture 1
WINDOW DESCRIPTION:
File - used to manage basic admin functions. New - creates a new project, Open opens an existing project, Close - closes the active project, Save - saves the active project, Save as ... - saves the project named as, Recent file - , Exit - used to exit the Admin. Edit - this menu contains standard data editing tools. Undo - move previous command, Cut - cuts data (makes a copy but doesn't keep the original); Copy - for copying data (makes a copy and keeps the original; Paste - pastes cut or copied data on a chosen place. View - turns off/on status bar window. Window - contains some standard window options like: New window, Cascade, Tile, Arange icons, 1 Admin (currently open admin window). Help - short informations about current Admin version
Function selection program have two admin functions Radiators and Room
Admin radiators
(Note! All changes will be visible only after you restart program.). Input radiators in the program database First table: insert radiator manufacturer. Press " Add new " button and write manufacturer name. Confirm your input name pressing " Add " button, or cancel this step pressing " Cancel " button. insert radiator group name Note! first you must enter radiator manufacturer because without this inforamtion radiator admin will not work insert radiator Type - 0 - for panel radiators, 1 - for glide radiators insert radiator short Description- (Note: this is optional field) Erase- mark this field and erase one radiator group from program database.
Second table: Radiator name - radiator (e.g. Radiator XL 358/500) Height - Radiator height in mm Length - Radiator length in mm Depth - Radiator depth in mm n - exponent (If you don't know this information input 1,30 as the standard for all radiators Surface - Radiator surface in m2 (Note: this is optional field) Volume - radiator volume in liter (Note: this is optional field) Mass - radiator mass in kg (Note: this is optional field) q60 - radiator capacity in (W) according to DIN4703/4 for temperature regime 90/70/20 C q50 - radiator capacity in (W) according to EN442 for temperature regime 75/65/20 C
Erase - mark this field and erase one radiator from radiator group in program database Every change you make and want to keep press Refresh button to confirm that information.
Admin room
(Note! All changes will be visible only after you restart program.)
Input new room in the program database enter the following data in table: Room name - input new room name Temperature - average room temperature W / m2 - input watt per square meter for underfloor heating Air exchange - input air exchange for a period of one hour Erase - mark and earse rooms one or more rooms from list and from program database Every change you make and want to keep press Refresh button to confirm that information.
IntegraCAD news
IntegraCAD packages
You can purchase IntegraCAD 2011 in seven different packages: * Sani * Duct * Termo * Professional * Suite * Premium * Enterprise
The program packages include the same program framework (program interface, CAD, print, database) but a different amount of calculation modules. You can compare the different packages in the table below:
Versions are available for download on the official IntegraCAD website (0-24h), for all IntegraCAD users. New software upgrade comes out every 3 months, and after we release a new version you'll get notification on your email.
DOWNLOAD PROCEDURE: * please open www.integracad.com * in upper right corner press Customer area (cro. lang. Partnerske stranice)
User name (cro. lang. Korisniko ime): xxxxxxx Password (cro. lang. Lozinka): xxxxxxx
* Click on Login button (cro. lang. Prijava) * If everything is OK, the following window will appear:
After you download the latest IntegraCAD program version (e.g. on your Desktop) you will receive IntegraCAD .zip file
Unzip IntegraCAD file to get IntegraCAD 2011 Setup.exe (you can also do that on your Desktop) after that you're ready to install program
WARNING !!! Before installing the new program version, uninstall the old one from your computer !!!
Internet training
We offer Internet support through a specialised web conferencing system. During the conference the participants can see the presenters screen and follow the session in real time. All users see the same video output (the presenters screen) and can communicate with each other through a live audio connection. An Internet presentation is the simplest and fastest way to experience the capabilities of the program. Without generating costs and with a minimum time investment, everybody with an interest in the program can get the answers to his/her questions. The presentation will give you a general overview of the software without discussing the fine points. After the presentation phase there will be time for Q&A and a possibility to explore some questions deeper. Program presentations can be individual or public. Getting help for a current issue has never been easier. Program users can contact us by phone, e-mail or Skype and we will organize a support session as soon as possible. You can ask general questions (how to start a program function, avoid problems, etc.) or questions related to a current project. In general, the explanations will be made with standard support projects. For bigger issues, you can send us your project and drawing files and we will do our best to help. If the problems cannot be resolved during the support session, we will transfer them to our standard technical support procedure. Internet training allows for a thorough insight into a part of the program. As a program user you have two options: you can request an individual training or you can join one of the regular public trainings. In the first case you can select the training topic freely but you need to make your training request at least 7 days in advance. In the case of public trainings the topic and date are already set and you need to apply at least 24 hours in advance. Public training dates will be announced on our website www.integracad.com at least two weeks in advance. TECHNICAL PREREQUISITES Internet Software Hardwar e Fast connection (DSL, optical cable) Mozilla Firefox 3.5 or Internet Explorer 8 E-mail client for the initial communication Headphones and microphone compatible to Windows OS
Contact
Contacts
We thank you for using our software. If you need help or have suggestions or improvement requests do not hesitate to contact us: Adress: Impuls d.o.o. Furicevo 90 HR - 51216 Viskovo Croatia Europe tel. +385 51 545 880 fax. +385 51 545 881 e-mail: General information info@integracad.com Technical support support@integracad.com Website www.integracad.com