Вы находитесь на странице: 1из 42

IEEE PES Distribution Automation Tutorial

Integrated

Volt - VAR Control


Bob Uluski Quanta Technology

What is Volt-VAR control?


The use of capacitor banks, voltage regulators, distributed generating units, static VAR compensator, and other devices :
To maintain acceptable voltages at all points along the feeder under all loading conditions To operate the distribution system as efficiently as possible without violating any load and voltage constraints To support the reactive power needs of the bulk power system during system emergencies

Page 2

The Cycle of Interest in this Topic

1 0.5 0 -0.5 -1 1 4 7 10 13 16 19 22 25

Page 3

How Is Volt-VAR Control Accomplished?


Traditional Devices for Volt-VAR Control
Fixed and switched capacitor banks (in substation and out on the feeder) Substation transformers with Load Tap Changers (LTCs) Voltage regulators (in substation and/or out on the feeder)

Future Devices for Volt-VAR Control


Distributed generating resources Static VAR compensators

Page 4

Approaches to Volt VAR


Traditional Approach

DLA Master Station

Switched Capacitor Bank

Distribution Power Flow

Distribution SCADA

SCADA Volt VAR Integrated Volt VAR

IVVC Application

Line Regulator

Substation RTU

Substation Transformer With Load Tap Changer

Substation Capacitor Bank

Page 5

Requirements for the Ideal Volt-VAR System


Maintain Acceptable Voltage Profile at all points along the distribution feeder under all loading conditions Maintain Acceptable Power Factor under all loading conditions Provide Self Monitoring alert dispatcher when a volt-VAR device fails Allow Operator Override during system emergencies Work correctly following Feeder Reconfiguration Take advantage of SmartGrid Devices (StatCOM, DG, etc.) Provide Optimal Coordinated Control of all Volt VAR devices Allow Selectable Operating Objectives as different needs arise

Page 6

Traditional Volt-VAR Control


Current/Voltage Sensor Current/Voltage Sensor Voltage Regulator "Local " Current/ Voltage Measurements Standalone Controller

Distribution Primary Line


Capacitor Bank

"Local " Current/ Voltage Measurements Standalone Controller

On/Off Control Command Signal

On/Off Control Command Signal

Volt-VAR flows managed by individual, independent, standalone volt-VAR regulating devices:


Substation transformer load tap changers (LTCs) Line voltage regulators Fixed and switched capacitor banks

Page 7

Limitations of Traditional Volt-VAR Control


Current/Voltage Sensor Current/Voltage Sensor Voltage Regulator "Local " Current/ Voltage Measurements Standalone Controller

Distribution Primary Line


Capacitor Bank

"Local " Current/ Voltage Measurements Standalone Controller

On/Off Control Command Signal

On/Off Control Command Signal

The system is not continuously monitored The system lacks flexibility to respond to changing conditions out on the distribution feeders can misoperate following automatic reconfiguration System operation may not be optimal under all conditions Cannot override traditional operation during power system emergencies System may misoperate when modern grid devices (e.g., distributed generators) are present reverse power flow from DG can trick standalone controller to believe feeder has been reconfigured
Page 8

Scorecard for Traditional Volt VAR

Volt VAR Requirements


Acceptable Voltage Profile Acceptable Power Factor Self Monitoring Operator Override Feeder Reconfiguration SmartGrid Devices Optimal Coordinated Control Selectable Operating Objectives

Traditional VAR X X

Volt-

Page 9

SCADA Controlled Volt-VAR


Volt-VAR power apparatus monitored and controlled by Supervisory Control and Data Acquisition (SCADA) Volt-VAR Control typically handled by two separate (independent) systems:
VAR Dispatch controls capacitor banks to improve power factor, reduce electrical losses, etc Voltage Control controls LTCs and/or voltage regulators to reduce demand and/or energy consumption (aka, Conservation Voltage Reduction)

Operation of these systems is primarily based on a stored set of predetermined rules (e.g., if power factor is less than 0.95, then switch capacitor bank #1 off)

Page 10

Overview of VAR dispatch


General objective is to maintain power factor as close to unity at the head end of the feeder without causing leading power factor Simplified formula for loss reduction due to average power factor improvement:
% Loss Reduction = (1 AVGPF2 / TPF2) x 100 Example: (1 - .942 / .992) = 9.84%

Simplified formula for demand reduction due to power factor improvement at peak load:
Demand Reduction = (1 / PKPF 1 / TPF) x 100 Example: (1 / .97 1 / .99) = 2.08%

Page 11

VAR Dispatch Components

Contains rules for capacitor switching

VAR Dispatch Processor

Radio

One-way communication link for capacitor bank control

Measures real and reactive power at substation end of the feeder

Substation RTU
Radio Real Power (MW)

Substation

OO
Reactive Power (MVAR)

Switched & fixed feeder capacitor banks Capacitor bank control interface Communications facility - one-way paging or load management communications is sufficient Means of monitoring 3-phase var flow at the substation Master station running VAR dispatch software

Capacitor Switch (Off Position)

Capacitor Bank Controller Capacitor Bank (Deenergized)

Page 12

Monitoring Real and Reactive Power Flow

VAR Dispatch Processor


Real/Reactive Power Measurements Reported to VAR Dispatch Processor

Radio

Substation RTU
Radio Real Power (MW)

Substation

OO
Reactive Power (MVAR)

Capacitor Switch (Off Position)

Capacitor Bank Controller Capacitor Bank (Deenergized)

Page 13

VAR Dispatch Rules Applied


VAR Dispatch Processor VAR Dispatch Applies Rules Radio Processor to Determine if Cap bank switching is Reactive power Feeder needed below thresholdMeasurements No action required

Substation RTU
Radio Real Power (MW)

Substation

OO
Reactive Power (MVAR)

Capacitor Switch (Off Position)

Capacitor Bank Controller Capacitor Bank (Deenergized)

Page 14

Real and Reactive Load Increases


VAR Dispatch Processor Applies Rules to Determine if Cap bank switching is needed

VAR Dispatch Processor


Feeder Measurements

Radio

Reactive power Above thresholdAction required

Substation RTU
Radio Real Power (MW)

Substation

OO
Reactive Power (MVAR)

Capacitor Switch (Off Position)

Capacitor Bank Controller Capacitor Bank (Deenergized)

Page 15

Reactive Power Flow Exceeds Threshold


VAR Dispatch Processor VAR Dispatch Applies Rules Processor to Determine if Cap bank switching is Feeder needed Measurements

Radio Control Signal Sent to Cap Bank

Substation RTU
Radio Real Power (MW)

Substation

OO
Reactive Power (MVAR)

Capacitor Switch (Off Position)

Capacitor Bank Controller Capacitor Bank (Deenergized)

Page 16

Capacitor Switched On
VAR Dispatch Processor Determines Additional Capacitors Needed

VAR Dispatch Processor


Feeder Measurements

Radio

Substation RTU
Real Power (MW) Cap Bank Switched On Radio

Substation

OO
Reactive Power (MVAR)

Capacitor Switch (On Position)

Capacitor Bank Controller Capacitor Bank (Energized)

Page 17

Change in Reactive Power Detected


VAR Dispatch Processor Determines Additional Capacitors Needed

VAR Dispatch Processor


Feeder Measurements

Radio

Substation RTU
Real Power (MW) Cap Bank Switched On Radio

Substation

OO
Reactive Power (MVAR) Reactive Power From Supplier Reduced

Capacitor Switch (On Position)

Capacitor Bank Controller Capacitor Bank (Energized)

Page 18

Change in Reactive Power Detected


VAR Dispatch Processor Determines Additional Capacitors Needed

VAR Dispatch Processor


Feeder Measurements

Radio

Substation RTU
Real Power (MW) Cap Bank Switched On Radio

Substation

OO
Reactive Power (MVAR) Reactive Power From Supplier Reduced

Change detected by Substation RTU

Capacitor Switch (On Position)

Capacitor Bank Controller Capacitor Bank (Energized)

Page 19

Benefits of VAR Dispatch vs Traditional

Contains rules for capacitor switching

VAR Dispatch Processor

Radio

One-way communication link for capacitor bank control

Measures real and reactive power at substation end of the feeder

Substation RTU
Radio Real Power (MW)

Substation

OO
Reactive Power (MVAR)

Capacitor Switch (Off Position)

Capacitor Bank Controller Capacitor Bank (Deenergized)

Self Monitoring Operator override capability Some improvement in efficiency

Page 20

Overview of Voltage Control


DA Voltage Control function based on concept of Conservation Voltage Reduction (CVR). Principles of CVR:
Acceptable voltage band is between 114 and 126 volts Can operate in the lower half (114 - 120) without harming customer appliances or impacting the customer U.S. average delivered voltage = 122.5 V Considerable energy savings results over time

By reducing voltage at the time of the system peak load, you can reduce the peak and thereby achieve:
reduction in investments for new capacity, or reduction in demand charges for power purchases

Page 21

Affects of Voltage Reduction


Works best with resistive load (lighting and resistive heating) because power drawn decreases with the voltage squared . devices that operate using a thermostat generally do not reduce energy the devices just run longer the most reduction occurs right when the voltage is reduced and then some of the reduction is lost as some loads just run longer
one study found that 5% voltage reduction on a residential feeder reduced load by 4% initially and diminished to a 3 % drop in 4 hours (Proess, R.F. and Warnock, V.J. Impact of Voltage Reduction on Energy and
Demand, IEEE Transactions on Power Apparatus and Systems, vol PAS-97, no. 5, pp 1665-71, Sept/Oct 1978

Page 22

Affects of Voltage Reduction (Motors)

Figure 1: Effect of voltage on motor loss At low loads, motor losses decrease as voltage decreases. Source: Westinghouse Electric Corp.

Page 23

Affects of Voltage Reduction

Page 24

Voltage Control Components


Communication link for End-of-Feeder Monitoring

Contains rules for Voltage Reduction

Voltage Control Processor

Comm Interface

Feeder measurements LTC Raise/Lower Commands LTC Controller

Substation Transformer

LTC

Substation RTU O O O O

Measures power and voltage at substation end of the feeder

Ensures that voltage does not drop below minimum acceptable value Comm Interface

Volt Meter or AMR

Current Transformer

OO
Real Power (MW) Reactive Power (MVAR)

Voltage OO TransformerOO

Bus Voltage Transformer

End of Feeder

Page 25

Load Below Voltage Control Threshold (No Control Actions)

Voltage Control Processor

Comm Interface

LTC Controller

Substation Transformer

LTC

Substation RTU O O O O OO
Real Power (MW) Reactive Power (MVAR)

Comm Interface

Volt Meter or AMR

Voltage OO TransformerOO

End of Feeder

Page 26

Load Above Voltage Control Threshold

Voltage Control Processor

Comm Interface

LTC Controller

Substation Transformer

LTC

Substation RTU O O O O OO
Real Power (MW) Reactive Power (MVAR)

Comm Interface

Volt Meter or AMR OO OO End of Feeder

Page 27

Load Above Voltage Control Threshold (lower tap setting)

Voltage Control Processor


Lower Tap Setting
LTC Controller

Comm Interface

Substation Transformer

LTC

Substation RTU O O O O OO
Real Power (MW) Reactive Power (MVAR)

Comm Interface

Volt Meter or AMR OO OO End of Feeder

Page 28

Benefits of Voltage Control versus Traditional Volt-VAR

Voltage Control Processor


Lower Tap Setting
LTC Controller

Comm Interface

Substation Transformer

LTC

Substation RTU O O O O OO
Real Power (MW) Reactive Power (MVAR)

Comm Interface

Volt Meter or AMR OO OO End of Feeder

Self Monitoring Operator override capability

Page 29

What SCADA Volt VAR Cant Do


Does not adapt to changing feeder configuration (rules are fixed in advance) Does not adapt to varying operating needs (demand reduction, energy savings, etc) (rules are fixed in advance) Overall efficiency is improved versus traditional approach, but is not necessarily optimal under all conditions Operation of VAR and Volt devices is not coordinated Does not adapt well to presence of modern grid devices such as DG

Page 30

Volt VAR Scorecard

Volt-VAR Approach
Volt VAR Requirements
Acceptable Voltage Profile Acceptable Power Factor Self Monitoring Operator Override Feeder Reconfiguration SmartGrid Devices Optimal Coordinated Control Selectable Operating Objectives
Traditional VAR X X Volt- SCADA VAR X X X X Volt-

Page 31

Integrated Volt-VAR Control (IVVC)


Develops and executes a coordinated optimal switching plan for all voltage and VAR control devices - uses optimal power flow program as its engine Achieves utility-specified objective functions:
Minimize distribution system power loss Minimize power demand (sum of distribution power loss and customer demand) Maximize revenue (the difference between energy sales and energy prime cost) Combination of the above

Can bias the results to minimize tap changer movement and other equipment control actions that put additional wear and tear on the physical equipment

Page 32

Modeling Load Voltage Sensitivity


Typical load models:
Constant power Constant current Constant Impedance Combination of the above

Accurate load model for IVVC:

Page 33

Integrated Volt-VAR Control Components


DLA Master Station
Switched Capacitor Bank

Distribution Power Flow

Distribution SCADA

IVVC Application

IVVC Software Optimal powerflow solution versus rule-based approach Processor For Running IVVC Software Centralized master station Substation based processor
Substation RTU

Line Regulator

Interfaces to field devices Substation LTC transformers Substation and line regulators Substation and line capacitor banks Voltage monitors (optional) Communication facilities (2 way preferred)
Substation Transformer With Load Tap Changer

Substation Capacitor Bank

Page 34

Solution Technique
Power flow solution used by the optimization procedure to evaluate the effectiveness of the various possible control actions. Optimal IVVC solution utilizes an iterative process designed to reach the objective function within the defined constraints and limits. Selected optimization procedure results in the least number of control actions to achieve the optimum results.

Page 35

Acquire Field Data


DLA Master Station
Cap bank status, feeder voltage
Switched Capacitor Bank

Distribution Power Flow

Distribution SCADA

IVVC Application

Tap position, feeder load & voltage

Feeder load, LTC tap position, bus voltage, cap bank status
Substation RTU

Line Regulator

Tap position, Bus voltage


Substation Transformer With Load Tap Changer

Cap bank stage 1 & 2 status

Substation Capacitor Bank

Page 36

Execute Online Powerflow Program


DLA Master Station
Real time feeder and substation data
Distribution Power Flow Switched Capacitor Bank

Cap bank status, feeder voltage

Powerflow results

Distribution SCADA

IVVC Application

Tap position, feeder load & voltage

Feeder load, LTC tap position, bus voltage, cap bank status
Substation RTU

Line Regulator

Tap position, Bus voltage


Substation Transformer With Load Tap Changer

Cap bank stage 1 & 2 status

Substation Capacitor Bank

Page 37

Determine Optimal Switching Plan


DLA Master Station
Real time feeder and substation data
Distribution Power Flow Switched Capacitor Bank

Cap bank status, feeder voltage

Powerflow results

Opt switching plan for cap banks, LTC, and line regulators

Distribution SCADA

IVVC Application

Tap position, feeder load & voltage

Feeder load, LTC tap position, bus voltage, cap bank status
Substation RTU

Line Regulator

Tap position, Bus voltage


Substation Transformer With Load Tap Changer

Cap bank stage 1 & 2 status

Substation Capacitor Bank

Page 38

Execute Switching Plan


DLA Master Station
Real time feeder and substation data
Distribution Power Flow

Switched Capacitor Bank

Switch cap bank on/off

Powerflow results

Opt switching plan for cap banks, LTC, and line regulators

Distribution SCADA

IVVC Application

Raise/lower tap setting

Feeder load, LTC tap position, bus voltage, cap bank status
Substation RTU

Line Regulator

Raise/lower tap setting


Substation Transformer With Load Tap Changer

Switch cap bank on or off

Substation Capacitor Bank

Page 39

IVVC Benefits
Dynamic model updates automatically when reconfiguration occurs Volt VAR control actions are coordinated System can model the effects of Distributed Generation and other modern grid elements Produces optimal results Accommodates varying operating objectives depending on current need

Page 40

Final Volt-VAR Scorecard

Volt-VAR Approach
Volt VAR Requirements
Acceptable Voltage Profile Acceptable Power Factor Self Monitoring Operator Override Feeder Reconfiguration SmartGrid Devices Optimal Coordinated Control Selectable Operating Objectives
Traditional VAR X X Volt- SCADA VAR X X X X Volt- Integrated VAR X X X X X X X X Volt-

Page 41

Questions?
For further information: Bob Uluski Quanta Technology Ruluski@quanta-technology.com

Page 42

Вам также может понравиться