Академический Документы
Профессиональный Документы
Культура Документы
48RCL
Model:
Controller: RDC2
TP-6811 4/12
Table of Contents
Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List of Related Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 9 9
Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Section 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Controller Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Engine Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4 Engine Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5 Alternator Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.6 Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.7 Service Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 2 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Service Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.1 Oil Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.2 Oil Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.3 Oil Additions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.4 Oil and Filter Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.5 Resetting the Maintenance Reminder . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.7 Spark Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.8 Fuel System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 3 Controller 3.1 3.2 3.3 ....................................................................... Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SiteTech and OnCue Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.1 Controller Parameters Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.2 Notes on Selected Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.7.1 Calibration using the RDC2 Controller Keypad and Menus . . . . . . . . . . 3.7.2 Calibration Using SiteTech . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the OnCue Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 11 11 11 11 12 12 13 15 15 16 17 17 17 17 17 18 18 19 19 20 21 23 23 23 24 24 24 37 38 40 43 43 45 47 49 49 49 49 51 51 51 51 52 52 53 53
3.8
Section 4 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Clean Radiator Fins and Inspect Hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Engine Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4 Cooling System Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 Checking and Filling Coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.6 Draining Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.7 Flushing and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.8 Filling Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.9 Pressure Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.10 Cooling Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.10.1 Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TP-6811 4/12
Table of Contents
Section 5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.1 Line Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.2 Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.3 Controller Internal Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4 Fuel System Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5 Controller Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6 Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.7 Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.8 Generator Set Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.9 Controller Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 6 Component Testing and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Alternator Excitation Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.1 Low to No Voltage Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.2 Erratic Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.3 Overvoltage Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.4 Manual Excitation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3 Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 Additional Alternator Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5 Voltage Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5.1 Voltage Adjustments Using SiteTech . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5.2 Voltage Regulator Average Voltage Adjustment . . . . . . . . . . . . . . . . . . . . 6.5.3 Volts/Hz Slope and Cut-In Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5.4 Voltage Regulator Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.6 Frequency Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.6.1 Engine Speed Governor Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.6.2 Hunting/Surging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.7 Generator Set Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.7.1 Engine Compartment Air Temperature Sensor . . . . . . . . . . . . . . . . . . . . . 6.7.2 Other Switches and Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.8 Fuel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.8.1 Fuel Solenoid Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.8.2 Checking the Fuel Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.8.3 Fuel Conversion Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 7 Disassembly/Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 Initial Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4 Connection Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 Other Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6 Alternator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 8 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Appendix A Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix B Common Hardware Application Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix C General Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix D Common Hardware Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 97 98 99
Table of Contents
TP-6811 4/12
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS. This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
Accidental Starting
WARNING
WARNING
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes. Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid. Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area. Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects.
DANGER
Danger indicates the presence of a hazard that will cause severe personal injury, death, or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
Battery
WARNING
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related. Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
TP-6811 4/12
Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases. Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Combustible materials. A fire can cause severe injury or death. Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the buildings occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturers instructions. Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following: D Light-headedness, dizziness D Physical fatigue, weakness in joints and muscles D Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Exhaust System
WARNING
Carbon monoxide. Can cause severe fainting, or death. Fire. Can cause severe injury or death. Do not smoke or permit flames or sparks near fuels or the fuel system. Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor. Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the air cleaner removed.
nausea,
Fuel System
WARNING
The exhaust system must be leakproof and routinely inspected. Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Explosive fuel vapors. Can cause severe injury or death. Use extreme care when handling, storing, and using fuels.
TP-6811 4/12
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation. Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage. Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure. Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM). Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution. Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by turning off the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage.
WARNING
Hazardous voltage. Moving parts. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.
WARNING
Hazardous Noise
CAUTION
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death. If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
Hazardous noise. Can cause hearing loss. Never operate the generator set without a muffler or with a faulty exhaust system.
TP-6811 4/12
Engine block heater. Hazardous voltage can cause severe injury or death. The engine block heater can cause electrical shock. Remove the engine block heater plug from the electrical outlet before working on the block heater electrical connections. High voltage test. Hazardous voltage can cause severe injury or death. Follow the instructions of the test equipment manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure. Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death. Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies). Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment. Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines. Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine batterycharging alternator connections. (5) Attach the weld ground connection close to the weld location.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically. (600 volts and under)
WARNING
Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools. Servicing the alternator. Hot parts can cause severe injury or death. Avoid touching the alternator field or exciter armature. When shorted, the alternator field and exciter armature become hot enough to cause severe burns. Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation.
Heavy Equipment
WARNING
Notice
Unbalanced and elevated weight. Improper lifting can cause severe injury or death and equipment damage. Do not lift the generator set from the engine or alternator eyes. Never stand under a unit being lifted. Always maintain a safe distance from the unit being lifted. See the lifting instructions in the installation manual that was provided with the unit.
NOTICE
Canadian installations only. For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
NOTICE
Electrostatic discharge damage. Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short, to ground.
Hot Parts
WARNING
Hot coolant and steam. Can cause severe injury or death. Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
TP-6811 4/12
Introduction
This manual provides troubleshooting and repair instructions for the generator set models listed on the front cover. This manual may also be supplied for similar models not listed on the front cover. Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever. Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference. The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Maintenance work must be performed by appropriately skilled and suitably trained maintenance personnel familiar with generator set operation and service. For engine service procedures not covered in this manual, refer to the Engine Service Manual.
6811
Figure 1
Model 48RCL
TP-6811 4/12
Introduction
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
GeneratorsElectric.
D Visit
China North China Regional Office, Beijing Phone: (86) 10 6518 7950 (86) 10 6518 7951 (86) 10 6518 7952 Fax: (86) 10 6518 7955 East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550 India, Bangladesh, Sri Lanka India Regional Office Bangalore, India Phone: (91) 80 3366208 (91) 80 3366231 Fax: (91) 80 3315972 Japan, Korea North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727 Latin America Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
the Kohler Power Systems website at KohlerPower.com. or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444. D Outside the US and Canada, call the nearest regional
office. Headquarters Europe, Middle East, Africa (EMEA) Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone: (33) 1 49 178300 Fax: (33) 1 49 178301 Asia Pacific Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
10
Service Assistance
TP-6811 4/12
Section 1 Specifications
1.1 Introduction
The specification sheets for each generator set provide specific generator and engine information. Refer to the generator set specification sheet for ratings and other data not supplied in this manual. Consult the generator set installation manual, engine operation manual, and engine service manual for additional specifications. Consult the generator set nameplate for specific generator set ratings.
Cylinder arrangement
Displacement, L (cu. in.) Bore and stroke, mm (in.) Compression ratio Piston speed, m/min. (ft./min.) Main bearings: quantity, type Rated rpm Max. power at rated rpm, kW (HP) Cylinder head material Piston type and material Crankshaft material Valve (exhaust) material Governor type Frequency regulation, no-load to full-load Frequency regulation, steady state Frequency Air cleaner type, all models Exhaust System Exhaust manifold type Exhaust flow at rated kW, m3/min. (cfm) Exhaust temperature at rated kW, dry exhaust, _C (_F) Maximum allowable back pressure, kPa (in. Hg) Exhaust outlet size at engine hookup, mm (in.) Engine Electrical System Ignition system Battery charging alternator: Ground (negative/positive) Volts (DC) Ampere rating Starter motor rated voltage (DC) Battery, recommended cold cranking amps (CCA): Qty., rating for --18_C (0F) Battery voltage (DC)
One, 630 12
TP-6811 4/12
Section 1 Specifications
11
Fuel System Fuel type Natural gas fuel supply pressure, kPa (in. H2O) LPG vapor withdrawal fuel supply pressure, kPa (in. H2O) Lubricating System Type Oil pan capacity, L (qt.) Oil pan capacity with filter, L (qt.) Oil filter: quantity, type Radiator System Ambient temperature, _C (_F) Radiator system capacity, including engine, L (gal.) Engine jacket water flow, Lpm (gpm) Heat rejected to cooling water at rated kW, dry exhaust, kW (Btu/min.) Water pump type Fan diameter, mm (in.) Fan power requirements (powered by engine battery charging alternator) 60 Hz 45 (113) 17 (4.5) 117.3 (31) 98.4 (26) Full Pressure 4.7 (5.0) 6.2 (6.5) 1, Cartridge 50 Hz LP Gas or Natural Gas 1.74--2.74 (7-11) 1.24--2.74 (5-11)
48.4 (2750)
42.9 (2440)
12
Section 1 Specifications
TP-6811 4/12
19
18
17 16
15
14
13
12
11
10
26 32
27 24
20
21
22
23 24
25
GM83070 ADV-7962
11
31
30
29
28
Air cleaner Nameplate location Oil check (dipstick) Engine ECM and EPR (electronic fuel pressure regulator) Engine fuses See cooling system detail Exhaust outlet Coolant fill access Coolant drain Coolant drain access panel Spark plugs Block heater connection valve Fuel inlet (1 in. NPT) Fuel solenoid valves (two required for UL 2200) Customer load lead access Customer connection access panel
17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32.
Line circuit breaker Generator set master control buttons (on RDC2 controller) RDC2 controller Radiator Pressure cap (engine coolant fill) Coolant level sensor location Engine compartment temperature sensor Fans (qty. 3) Coolant overflow bottle Oil fill (on valve cover) Fan fuses Battery Oil drain valve Lube oil filter Block heater connection valve Cooling air inlet
Figure 1-1
TP-6811 4/12
Section 1 Specifications
13
Notes
14
Section 1 Specifications
TP-6811 4/12
WARNING
The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts. See the Safety Precautions and Instructions at the beginning of this manual before attempting to service, repair, or operate the generator set. Have an authorized Kohler distributor/dealer perform generator set service. Engine Service. Perform generator set engine service at the intervals specified by the engine operation manual. Generator Set Service. Perform generator set service at the intervals specified by the generator set operation manual.
WARNING
Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools. Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation.
Routine Maintenance. Refer to the following generator set service schedule, the engine service schedule, and the runtime hours shown on the RDC2 controller to determine when to schedule routine maintenance. Service generator sets that are subject to extreme weather or dusty or dirty conditions more frequently. Maintenance Reminders. The RDC2 controller displays a reminder message every 150 hours of engine run time. Change the oil and perform other maintenance tasks listed on the service schedule. Then reset the reminder. See Section 2.3.5 for instructions to reset the maintenance reminder. Maintenance and Service Parts. Obtain maintenance and service parts from an authorized Kohler distributor/dealer.
TP-6811 4/12
15
Operation GENERAL MAINTENANCE Check for fluid leaks Check all bolts and nuts for tightness ] Check PCV valve, hose, and fittings ] Replace PCV valve, if equipped ] Check belts and belt tension Inspect vacuum lines and fittings LUBRICATION SYSTEM Check engine oil level Change engine oil and filter [ AIR INTAKE SYSTEM Inspect and clean air cleaner element [ Replace air cleaner element [ Check air induction for leaks Check intake manifold for vacuum leaks COOLING SYSTEM Check coolant level * Inspect and clean radiator exterior ] Replace engine coolant ]* Inspect coolant hoses ELECTRICAL SYSTEM Check battery charge and fluid level ] Inspect electrical system Clean battery cables ] EXHAUST SYSTEM Inspect exhaust manifold for leaks Inspect exhaust piping for leaks Inspect catalyst inlet and outlet (if equipped) Check HEGO (oxygen) sensor connections FUEL SYSTEM Replace fuel filter w Check fuel shutoff valve for leaks and function Check fuel regulator pressure Test fuel lines for leaks Inspect/drain vaporizer for oil buildup IGNITION SYSTEM Check spark plug wires Clean secondary ignition coil wires Replace distributor cap and rotor (3.0--5.7 L) Replace spark plugs Replace spark plug wires * [ ] w
Daily X X
X X X
X X
X X
X X X X X X X X
X X X X X
X X
X X X X X X X X X X X X X X X X X
Check engine coolant condition and protection, hoses, and clamps annually (prior to cold weather). More frequent intervals may be required in dusty or dirty operating conditions. Seasonal or as required. More frequent intervals may be required with dirt in fuel system.
16
TP-6811 4/12
2.3.3
Oil Additions
Use oil that displays the American Petroleum Institute (API) Starburst certification mark FOR GASOLINE ENGINES on the container. Do not use straight-weight oils recommended for industrial or stationary engines. CC or CD classification oils, even when labeled Heavy Duty or For Natural Gas Engines are not acceptable. Multi-viscosity oils are recommended. Figure 2-1 shows the recommended Society of Automotive Engineers (SAE) viscosity designation for a given operating temperature.
Ambient Temperature --18_C (0_F) and above Below --18_C (0_F) Engine Oil Type SAE 10W-30 SAE 5W-30
Adding some oil between oil changes is normal. The amount varies with generator set usage. Open the oil fill cap and pour in a small amount of oil using a funnel or other suitable pouring device. See Section 1, Service Views, for the oil check and oil fill locations.
2.3.4
Change the oil according to the service schedule or before generator set storage. Change the oil more frequently if the generator set operates under dirty, dusty conditions. Change the oil while the engine is still warm. See Section 1, Service Views, for oil fill, oil check, and oil filter locations. Dispose of all waste materials (engine oil, fuel, filter, etc.) in an environmentally safe manner. Note: Reset the maintenance timer on the RDC2 controller after changing the oil. Oil Change Procedure Whenever possible, drain the oil while it is still warm. 1. Drain the oil. a. Press the OFF button on the RDC2 generator set controller. b. Disconnect the power for the battery charger. c. Disconnect the generator set engine starting battery, negative (--) lead first. d. Remove the housing side panel. e. Remove the plug from the oil drain fitting and install a drain hose.
Figure 2-1
2.3.2
Oil Check
Check the oil level in the crankcase every 24 hours of operation. Do not check the oil level while the generator set is running. To check the oil level, remove the dipstick and wipe the end clean. Reinsert the dipstick and wait at least 30 seconds. Remove the dipstick and check the level. Maintain the oil level between the Full and Add marks on the dipstick, as shown in Figure 2-2. See Section 1, Service Views for the dipstick location. Note: Do not operate the set if the oil level is below the Add mark or above the Full mark on the dipstick.
f. Open the oil drain valve on the engine. g. Allow time for the engine oil to drain completely. h. Close the oil drain valve.
TP-5586-3
i. Replace the oil drain plug. 2. Replace the oil filter. a. Remove the oil filter by rotating counterclockwise with an oil filter wrench. it
Figure 2-2
b. Clean the contact surface of the oil filter adapter. c. Apply a light coat of clean oil to the rubber seal of the new oil filter.
TP-6811 4/12
17
d. Install the new oil filter following the instructions provided with the filter. Tighten the oil filter to 25 Nm (18 ft. lbs.) 3. Fill with oil. See Figure 2-1 for oil selection and Figure 2-3 for oil capacity.
Model 48RCL Oil Capacity, L (qt.) 4.7 (5.0)
Figure 2-3
Oil Capacity
4. Check for leaks. a. Press the OFF button on the RDC2 generator set controller. b. Reconnect the generator set engine starting battery, negative (--) lead last. c. Reconnect the power for the battery charger. d. Start the generator set and check for leaks around the oil filter. e. Stop the generator set and tighten the oil filter to stop any leaks. f. Reinstall the housing side panel. 5. Stop the generator set. Check the oil level. Add oil, as necessary, to bring the level up to the Full mark. Note: Too high an oil level causes high oil consumption and engine carbonizing. Too low a level damages the engine. 6. Reset the maintenance timer on the RDC2. See Section 2.3.5.
A--273699
1. Cover 2. Housing
Figure 2-4
Air Cleaner
1. Remove the wing nuts to open the housing and remove the air silencer element. 2. Tap the element lightly against a flat surface to dislodge loose surface dirt. Do not clean the element in any liquid or use compressed air as these will damage the filter element. 3. Examine the element and housing for damage. Replace the element or housing if necessary. 4. Wipe the cover and housing with a clean rag to remove dirt. Make sure the sealing surfaces fit correctly. 5. Replace the cover and secure using the wing nut.
2.3.5
1. In the Overview menu, step down to the Next Maintenance screen. 2. Press the Select button. 3. Press the Up arrow button so that Reset Maint Timer? Yes is displayed. 4. Press the Select button. The next maintenance interval and date will be displayed.
18
TP-6811 4/12
WARNING
Sulfuric acid in batteries. Can cause severe injury or death. nausea, Wear protective goggles and clothing. Battery acid may cause blindness and burn skin. Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid. Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area. Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases. Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
The exhaust system must be leakproof and routinely inspected. Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon monoxide detectors on each level of the building. Locate the detectors to adequately warn the buildings occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturers instructions.
At the interval specified in the service schedule, inspect the exhaust system components (exhaust manifold, exhaust outlet, exhaust line, exhaust clamps, and muffler) for cracks, leaks, and corrosion. Exhaust System Inspection Points
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is unobstructed. D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal leaks as needed.
D Check that all covers and doors are undamaged, in
monoxide (CO) detectors on each level of any building near the generator set.
2.6 Battery
Consult the battery manufacturers regarding battery care and maintenance. instructions
TP-6811 4/12
19
Note: Do not sandblast, wire brush, scrape, or otherwise service spark plugs in poor condition. Obtain a new plug for best results. 9. Check the spark plug gap before installing any spark plug. See Figure 2-5 and Figure 2-6. Attain a correct gap when the feeler (or wire) passes between the spark plug electrode. It should pass easily but with some resistance or drag; otherwise adjust as necessary.
Model 48RCL Spark plug gap 0.9 mm (0.035 in.)
Figure 2-5
6. Use compressed air to remove dirt from around each spark plug to prevent dirt particles from falling into the combustion chamber. 7. Remove spark plugs, one at a time, and examine. Identify a normal spark plug in good operating condition by observing a light tan or gray deposit on firing tip. See Figure 2-7 to evaluate engine condition by color/condition of a problem spark plug. 8. Clean spark plugs by wiping them with a rag. File the center electrode to keep it parallel to the side electrode.
Problem/Condition Gap-bridged spark plug Oil-fouled spark plug Means of Identification Built-up deposits and gap between electrodes closing. Wet, black deposits on the insulator shell, bore, and electrodes.
1. 0.9 mm (0.035 in.) gap 2. Spark plug electrodes
1-514
Figure 2-6
Possible Cause/Solution Oil or carbon fouling. Clean and regap the spark plug. Excessive oil entering combustion chamber through worn rings and pistons, excessive clearance between valve guides and stems, or worn or loose bearings. Replace the spark plug. Incorrect spark plug, weak ignition, clogged air intake, overrich fuel mixture, or excessive no-load operation. Clean and regap the spark plug. Caused by highly leaded fuel. Replace the spark plug. Wrong type of fuel, incorrect timing or advance, too hot a plug, burned valves, or engine overheating. Replace the spark plug. Engine overheating, wrong type of fuel, loose spark plugs, too hot a plug, low fuel pressure or incorrect ignition timing. Replace the spark plug. Caused by normal wear and failure to replace spark plug at prescribed interval. Replace the spark plug.
Black, dry, fluffy carbon deposits on insulator tips, exposed shell surfaces and electrodes.
Lead-fouled spark plug Dark gray, black, yellow, or tan deposits; or a glazed coating on the insulator tip. Pre-ignition damaged spark plug Melted electrodes and possibly blistered insulator. Metallic deposits on insulator suggest internal engine damage.
Overheated spark plug White or light gray insulator with small black or gray/brown spots with bluish (burned) appearance on electrodes. Worn spark plug Severely eroded or worn electrodes.
Figure 2-7
20
TP-6811 4/12
10. Use a gapping tool to gently bend the side electrode closer to or farther from the center electrode to set the correct gap. See Figure 2-8. Position the side electrode directly over the center electrode.
13. Use a ratchet wrench to final tighten an additional 1/4 turn. Do not overtighten, as doing so may strip the threads or alter the electrode gap setting. 14. Check the spark plug wire connector in the boot for accumulated dirt, grease, and other debris, and clean as necessary. 15. Firmly push the spark plug boot onto the spark plug. 16. Reconnect the generator set engine starting battery, negative (--) lead last. 17. Reconnect the power for the battery charger.
Figure 2-8
11. Reinstall the spark plug. Do not bump the electrode against the cylinder head. Rotate the spark plug clockwise until you feel resistance. 12. Use a torque wrench to torque each spark plug to 15 Nm (11 ft. lbs.). Otherwise, hand-tighten the spark plug until you feel resistance.
Routine service items include draining water/sediment from piping at petcock or pipe end cap, checking for fuel leakage at pipe connections, checking flexible sections for cracking or chafing, and keeping components clean including fuel regulator vent holes. A grease or wax residue tends to accumulate in the piping and fuel regulators over time. If fuel system problems persist, disassemble the fuel system components and check for residue buildup. Remove any residue with a brush and mild detergent.
TP-6811 4/12
21
Notes
22
TP-6811 4/12
Section 3 Controller
3.1 Introduction
The RDC2 controller manages the operation of the generator set, a Model RXT transfer switch (if equipped), an optional Programmable Interface Module (PIM) and an optional Load Control Module (LCM). See the generator set Operation Manual for controller operation instructions. This section covers adjustment and replacement of the RDC2 controller. See Section 5 for troubleshooting procedures. See the service view and Figure 3-3 for the controller location. Use a USB cable to connect the personal computer directly to the device. See Figure 3-2. The USB cable must have a male USB A connector on one end and a male mini-B connector on the other and must be less than 5 m (16.4 ft.) long. See Figure 3-1.
Figure 3-1
USB Cable
1
1. USB cable connection to PC 2. USB cable connection to controller
TP-6805
Figure 3-2
TP-6811 4/12
Section 3 Controller
23
3.3.2
Genset Info Model numbers and serial numbers are factory-set for each unit. If the controller is replaced, the genset model number and serial number will need to be entered by the installer. For the genset model number, select 48RCL from the dropdown list. Find the generator set serial number on the nameplate and enter it using SiteTech. See Section 3.5, Controller Replacement, for information about other setup required on a replacement controller. Changing the genset model number will update the engine model number automatically. Select the genset model number and then click Apply Changes in SiteTech to see the updated engine model number.
The Genset Fuel Type setting is located in the Genset System Configuration group in SiteTech. Generator set power and current ratings are different for different fuel types (natural gas or LP). The fuel type setting is available with controller firmware versions 4.5 and higher. Changing the Genset Fuel Type setting automatically updates the the Genset Power Rating and Genset Rated Current settings. The power rating is used to determine setpoints for the optional load control module (LCM). If an LCM is connected and the generator set is converted to a different fuel, use SiteTech to change the Genset Fuel Type setting. ECM Model Do not change the ECM Model setting (located in the Genset Personality Profile group). Changing the ECM model to the wrong setting can damage the controller. Genset Voltage Phase Connection The Genset Voltage Phase Connection setting appears in the Genset System Configuration group in SiteTech. A dropdown list allows selection of one of four possible configurations:
D Single phase D Single phase dogleg D Three phase wye D Three phase delta
Figure 3-3
Controller Location
3.3.1
The table on the following pages lists controller parameters that are visible in SiteTech. Settings marked Read Only are not user-adjustable. Some parameters that are visible in SiteTech do not apply to all models. Those parameters are marked in the last column, and the line in the table is shaded gray. The table indicates the following:
D Factory default settings D Adjustment range for adjustable settings
If the alternator is reconnected to a different voltage/phase configuration than the original factory setup, select the appropriate new configuration from the
24
Section 3 Controller
TP-6811 4/12
dropdown list. See the generator set Installation Manual for reconnection instructions. Digital Inputs and Outputs Digital inputs and outputs are available only if the optional Programmable Interface Module (PIM) is connected to the RDC2 controller. One PIM provides two digital inputs and 6 digital outputs. Dropdown menus allow selection of the digital input and output events. Be sure to select Digital Inputs B1--B2 and Digital Outputs B1--B6 in SiteTech. Digital Inputs A1--A2 and Digital Outputs A1--A2 do not apply to the PIM. Digital outputs B7--B12 are reserved for the Load Control Module (LCM) and cannot be changed by the user. These outputs will display LCM relay status. Refer to Installation Instruction Sheet TT-1584, provided with the PIM, for information about the input and output events. RBUS Devices A maximum of three RBUS devices, including one Model RXT transfer switch, one programmable
interface module (PIM), and/or one Load Control Module (LCM), can be connected to the Model 48RCL generator set. RBUS devices 4 through 8 appear in SiteTech but do not apply to the 48RCL. RBUS devices are numbered according to the device serial numbers, which are read by the RDC2 controller. RBUS Device B1 is the RXT transfer switch, PIM or LCM with the lowest serial number. Look at the RBUS device type to determine which device is B1, B2, or B3. Temperature Settings In SiteTech, all temperature settings are shown in degrees F but stored as degrees C. When you highlight a parameter value (click it), the _F value changes to the equivalent _C value. Enter temperature settings in _F. The new setting is calculated from a conversion equation, so the final value may include some rounding that makes the setting higher or lower by 1 degree.
TP-6811 4/12
Section 3 Controller
25
SiteTech Group Identity Identity Identity Engine Metering Engine Metering Engine Metering Engine Metering Engine Metering Engine Metering Engine Metering Engine Metering Engine Metering Engine Speed Governor Engine Speed Governor Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Generator Metering Vendor Product
Parameter
Units
Default Setting Kohler Company RDC 2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 50 50 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Notes [
Firmware Version Engine Speed Engine Target Speed Engine Oil Pressure Engine Coolant Temperature Battery Voltage Lube Oil Temperature Genset Controller Temperature Engine Low Oil Pressure Switch Engine Compartment Temperature Engine Speed Adjustment Engine Speed Gain Adjustment Generator Rotation Actual Generator Current Lead/Lag L1 Generator Current Lead/Lag L3 Generator Current Total Lead/Lag Generator Power Factor L1 Generator Power Factor L3 Generator Total Power Factor Generator Apparent Power L1 Generator Apparent Power L3 Generator Total Apparent Power Generator Reactive Power L1 Generator Reactive Power L3 Generator Total Reactive Power Generator True Power L1 Generator True Power L3 Generator True Total Power Generator True Percent Of Rated Power Generator Voltage L1-L2 Generator Voltage L2-L3 Generator Voltage L3-L1 Generator Voltage Average Line To Line Generator Current L1 Generator Current L3 Generator Current Average Generator Frequency Generator Metering Firmware Version VA VA VA VAR VAR VAR W W W % V V V V A A A Hz _C R/min R/min kPa _C V _C _C
Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only 0 -- 99 See Section 3.3.2. No effect. Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
N/A
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
26
Section 3 Controller
TP-6811 4/12
SiteTech Group Genset Info Genset Info Genset Info Genset Info Genset Info Genset Info
Parameter Genset Model Number Select Genset Serial Number Alternator Part Number Genset Controller Serial Number Engine Part Number Engine Model Number
Units
Adjustment Range * 48RCL (Dropdown list) 0--20 characters 0--20 characters 1--10 characters 0--20 characters GM 5.0 (Auto select with genset model)
Notes [
N/A N/A
Genset Info Genset Info Genset Run Time Genset Run Time Genset Run Time Genset Run Time Genset Run Time Genset Run Time
Engine Serial Number Genset State Genset Controller Clock Time Genset Controller Total Operation Time Engine Total Run Time Engine Total Run Time Loaded Engine Total Number Of Starts Genset Date Time Of Last Maintenance
N/A h h h
0--10 characters Read Only Read Only Read Only Read Only Read Only Read Only Read Only (See Section 2.3.5, Resetting the Maintenance Timer)
N/A N/A N/A N/A N/A N/A 1/1/01 12:00:00 AM 200.0 MM/DD/ YYYY 12 Hr N/A 365 31536000 1/1/01 12:00:00 AM GM ECM
Genset Run Time Genset Run Time Genset Run Time Genset Run Time Genset Run Time Genset Run Time Genset Run Time
Engine Run Time Until Maintenance Genset Controller Date Format Genset Controller Time Format Genset Date Time of Next Maintenance Maintenance Period In Days Maintenance Period Remaining Genset Controller Clock Time Zone Offset ECM Model
days s
Auto select with genset model DO NOT CHANGE A Read Only Locked _C/F _C/F RPM RPM RPM 77 -- 140 _C Locked 300 --1000 600 -- 3000 1000 -- 3900 No effect. No effect.
Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile
Maximum Alternator Current Engine Number Of Flywheel Teeth Engine Warmed Up Temperature Engine Cooled Down Temperature Engine Crank Disconnect Speed Engine Idle Speed Engine Run Speed Engine Coolant Temperature Protectives Enabled Engine Coolant Temperature Sensor
920 1 32_C (90_F) 79_C (174_F) 750 1350 1800 N/A N/A See note in Section 3.3.2.
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
TP-6811 4/12
Section 3 Controller
27
SiteTech Group Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile
Parameter Engine High Coolant Temperature Inhibit Delay Engine Low Coolant Temperature Warning Delay Engine High Coolant Temperature Warning Delay Engine Low Coolant Temperature Shutdown Delay Engine High Coolant Temperature Shutdown Delay Engine Low Coolant Temperature Warning Limit Engine High Coolant Temperature Warning Limit Engine High Coolant Temperature Shutdown Limit Engine Coolant Temperature Deadband Personality Alternator Manufacturer Personality Alternator Toc Time Constant Personality Alternator Number Of Poles Personality Alternator Type Personality Fixed Voltage 50 Hz Personality Power Rating Single Phase 50 Hz 10 PF Personality Power Rating Single Phase 50 Hz 8 PF Personality Power Rating Fixed Volt 50 Hz Personality Power Rating 50 Hz 220 440 Personality Power Rating 50 Hz 208 415 Personality Power Rating 50 Hz 200 400 Personality Power Rating 50 Hz 190 380 Personality Power Rating 50 Hz 173 346 Personality Power Rating 50 Hz Delta Personality Fixed Voltage 60 Hz Personality Power Rating Single Phase 60 Hz 10 PF Personality Power Rating Single Phase 60 Hz 8 PF Personality Power Rating Fixed Volt 60 Hz
Units s s s s s _C _C _C _C
Adjustment Range * No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect.
Default Setting
Notes [ N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
V kW kW kW kW kW kW kW kW kW V kW kW kW
No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect.
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
28
Section 3 Controller
TP-6811 4/12
SiteTech Group Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset Personality Profile Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset System Configuration Genset Calibration Genset Calibration
Parameter Personality Power Rating 60 Hz 240 480 Personality Power Rating 60 Hz 230 460 Personality Power Rating 60 Hz 220 440 Personality Power Rating 60 Hz 208 416 Personality Power Rating 60 Hz 190 380 Personality Power Rating 60 Hz Delta Genset System Voltage Genset System Frequency Genset Voltage Phase Connection Genset Power Rating Genset Rated Current Genset System Battery Voltage Prime Power Application Current Transformer Ratio Local Start Mode Measurement System ECM Power Alarm Silence Always Allowed Display Contrast Using Voltage Selector Switch Genset System Language Genset Maximum Percent Capacity Generator Overloaded Percent Genset Fuel Type Genset Calibration Factor Voltage L1-L2 Genset Calibration Factor Voltage L2-L3
Units kW kW kW kW kW kW V Hz
Adjustment Range * No effect. No effect. No effect. No effect. No effect. No effect. 110 -- 600 50/ 60 0--3
Default Setting
240.0 60.0 Single Phase 48 200 12 Standby 400 Off English False Always 50 N/A N/A 70.0 85.0 Natural Gas 1.0063 0.9909 N/A N/A
kW A V
10-- 5000 Read Only 12 / 24 Standby or prime Locked Read Only English or metric True or False Always or Auto only pull down list 0 -- 100 No effect. No effect.
% %
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
TP-6811 4/12
Section 3 Controller
29
SiteTech Group Genset Calibration Genset Calibration Genset Calibration Advanced Speed Control Advanced Speed Control Advanced Speed Control Advanced Speed Control Voltage Regulator
Parameter Genset Calibration Factor Voltage L3-L1 Genset Calibration Factor Current L1 Genset Calibration Factor Current L2 Proportional Gain Transient Integral Gain Derivative Gain Slow Correction Integral Gain Voltage Regulator Average Voltage Adjustment Voltage Regulator Volts Per Hertz Slope Voltage Regulator Volts Per Hertz Cut In Frequency Voltage Regulator Gain Voltage Regulator Firmware Version Engine Start Delay Engine Cool Down Delay Engine Crank On Delay Engine Crank Pause Delay Engine Number Of Crank Cycles After Crank Disconnect Fault Inhibit Delay Genset Low Battery Voltage Warning Delay Genset High Battery Voltage Warning Delay Genset Low Battery Voltage Warning Limit Genset High Battery Voltage Warning Limit Genset Battery Low Cranking Voltage Warning Delay Genset Battery Low Cranking Voltage Warning Limit Engine High Oil Temperature Shutdown Delay Engine Low Oil Pressure Shutdown Delay Engine Locked Rotor Shutdown Delay Genset Low Engine Speed Shutdown Limit Genset High Engine Speed Shutdown Limit Engine Oil Pressure Protectives Enabled
Units
Adjustment Range * 0.9 -- 1.1 0.9 -- 1.1 0.9 -- 1.1 No effect. No effect. No effect. No effect.
Notes [
N/A N/A N/A N/A 240.0 (System voltage) 4 59 16 N/A 0 300 15 15 3 30 90 10 100 125 6 60 5 5 3 85 N/A N/A N/A N/A
108 -- 660
Voltage Regulator Voltage Regulator Voltage Regulator Voltage Regulator Engine Timing Engine Timing Engine Timing Engine Timing Engine Timing Genset Protection Genset Protection Genset Protection Genset Protection Genset Protection Genset Protection Genset Protection Engine Protection Engine Protection Engine Protection Engine Protection Engine Protection Engine Protection
% Hz
s s s s s s s % % s % s s s % %
0 -- 300 300 -- 600 10 -- 30 1 -- 60 1 -- 6 Read Only Read Only Read Only 80 -- 100 110 -- 135 Read Only Read Only Read Only 5 3 75 -- 95 No effect. No effect.
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
30
Section 3 Controller
TP-6811 4/12
SiteTech Group Engine Protection Engine Protection Engine Protection Engine Protection Engine Protection Engine Protection Engine Protection Engine Protection Generator Protection Generator Protection Generator Protection Generator Protection Generator Protection Generator Protection Generator Protection Generator Protection Generator Protection Generator Protection Digital Input A1 Digital Input A1 Digital Input A1
Parameter Engine Oil Pressure Sensor Engine High Oil Pressure Inhibit Delay Engine High Oil Pressure Warning Delay Engine High Oil Pressure Shutdown Delay Engine Low Oil Pressure Warning Limit Engine High Oil Pressure Warning Limit Engine High Oil Pressure Shutdown Limit Engine Oil Pressure Deadband Loss Of AC Sensing Shutdown Delay Genset Low Voltage Shutdown Delay Genset High Voltage Shutdown Delay Genset Low Voltage Shutdown Limit Genset High Voltage Shutdown Limit Genset Short Term Low Frequency Shutdown Delay Genset Long Term Low Frequency Shutdown Delay Genset High Frequency Shutdown Delay Genset Low Frequency Shutdown Limit Genset High Frequency Shutdown Limit Digital Input A1 Value Digital Input A1 Enabled Digital Input A1 Event
Adjustment Range * No effect. No effect. No effect. No effect. No effect. No effect. No effect. No effect. Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only True or False See dropdown list in SiteTech. ] 3
Default Setting
10 2 80 120 10 60 10 90 110 False True Fuel Pressure Low Warning False True Auxiliary Input Warning False False None (0) False False N/A N/A N/A
Read Only True or False See dropdown list in SiteTech. ] Read Only True or False See dropdown list in SiteTech. ] Read Only True or False
Digital Input B1 Digital Input B1 Digital Input B1 Digital Input B2 Digital Input B2
Digital Input B1 Value Digital Input B1 Enabled Digital Input B1 Event Digital Input B2 Value Digital Input B2 Enabled
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
TP-6811 4/12
Section 3 Controller
31
Parameter Digital Input B2 Event Digital Output A1 Value Digital Output A1 Event
Units
Adjustment Range * See dropdown list in SiteTech. ] Read Only See dropdown list in SiteTech. ] Read Only See dropdown list in SiteTech. ] Read Only See dropdown list in SiteTech. ] Read Only See dropdown list in SiteTech. ] Read Only See dropdown list in SiteTech. ]
Default Setting None (0) False NFPA 110 Alarm Active N/A N/A False Generator Running False Common Fault False Low Battery Voltage Warning False Not In Auto Warning False Engine Cool Down Active False Normal Source Failure False 65004 False 65007 False 65003 False 65005 False 65006 False 65008 N/A N/A N/A N/A N/A
Digital Output A2 Digital Output A2 Digital Output B1 Digital Output B1 Digital Output B2 Digital Output B2 Digital Output B3 Digital Output B3
Digital Output A2 Value Digital Output A2 Event Digital Output B1 Value Digital Output B1 Event Digital Output B2 Value Digital Output B2 Event Digital Output B3 Value Digital Output B3 Event
Read Only See dropdown list in SiteTech. ] Read Only See dropdown list in SiteTech. ]
PIM PIM
PIM PIM
Read Only See dropdown list in SiteTech. ] Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only V V Read Only Read Only
PIM PIM
Digital Output B7 Digital Output B7 Digital Output B8 Digital Output B8 Digital Output B9 Digital Output B9 Digital Output B10 Digital Output B10 Digital Output B11 Digital Output B11 Digital Output B12 Digital Output B12 ATS Metering Summary ATS Metering Summary Source 1 Metering Source 1 Metering Source 1 Metering
Digital Output B7 Value Digital Output B7 Event Digital Output B8 Value Digital Output B8 Event Digital Output B9 Value Digital Output B9 Event Digital Output B10 Value Digital Output B10 Event Digital Output B11 Value Digital Output B11 Event Digital Output B12 Value Digital Output B12 Event ATS Contactor Position ATS Sources Available Source 1 Rotation Actual Source 1 Voltage L1-L2 Source 1 Voltage L2-L3
LCM LCM LCM LCM LCM LCM LCM LCM LCM LCM LCM LCM RXT RXT RXT RXT RXT
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
32
Section 3 Controller
TP-6811 4/12
SiteTech Group Source 1 Metering Source 1 Metering Source 1 Metering Source 2 Metering Source 2 Metering Source 2 Metering Source 2 Metering Source 2 Metering Source 2 Metering ATS Connection Configuration Source 1 System Configuration Source 1 System Configuration Source 1 System Configuration Source 1 System Configuration Source 1 System Configuration Source 1 Calibration Source 1 Calibration Source 1 Calibration Source 2 System Configuration Source 2 System Configuration Source 2 System Configuration Source 2 System Configuration Source 2 System Configuration Source 2 Calibration Source 2 Calibration Source 2 Calibration ATS Exercise ATS Exercise ATS Exercise
Parameter Source 1 Voltage L3-L1 Source 1 Voltage Average Line To Line Source 1 Frequency Source 2 Rotation Actual Source 2 Voltage L1-L2 Source 2 Voltage L2-L3 Source 2 Voltage L3-L1 Source 2 Voltage Average Line To Line Source 2 Frequency ATS Source Source 1 System Voltage
Units V V Hz V V V V Hz
Adjustment Range * Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
Default Setting N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Genset System Voltage Genset System Frequency 0.5 90 90 1 1 1 240.0 60.0 0.5 90 90 1 1 1 Weekly 20 Unloaded Cycle (2)
Notes [ RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT
110.0 -- 600.0
Hz
48.0 -- 62.0
RXT
Source 1 Voltage Debounce Delay Source 1 Low Voltage Pickup Source 1 Low Voltage Dropout Source 1 Calibration Factor Voltage L1-L2 Source 1 Calibration Factor Voltage L2-L3 Source 1 Calibration Factor Voltage L3-L1 Source 2 System Voltage Source 2 System Frequency Source 2 Voltage Debounce Delay Source 2 Low Voltage Pickup Source 2 Low Voltage Dropout Source 2 Calibration Factor Voltage L1-L2 Source 2 Calibration Factor Voltage L2-L3 Source 2 Calibration Factor Voltage L3-L1 Exercise Interval Exercise Run Duration Exercise Mode
s % %
RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT RXT
V Hz s % %
110.0 -- 600.0 48.0 -- 62.0 0.1 -- 9.9 85 -- 100 75 -- 98 Read Only Read Only Read Only Weekly or Every Other Week
min
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs. TP-6811 4/12 Section 3 Controller 33
SiteTech Group ATS Exercise ATS Delays ATS Delays ATS Delays Network Configuration Network Configuration Network Configuration Network Configuration Network Configuration Network Configuration Network Configuration
Parameter Exercise Warning Enabled ATS Transfer From Preferred Delay ATS Transfer From Standby Delay ATS Source 2 Engine Start Delay DHCP Enabled Static IP Address Static Subnet Mask Static Default Gateway Static DNS Server 1 Static DNS Server 2 Server Host Name
Units s s s
Adjustment Range * True or False 1 -- 10 1 -- 600 1 -- 10 True or False 0.0.0.0 -255.255.255.255 0.0.0.0 -255.255.255.255 0.0.0.0 -255.255.255.255 0.0.0.0 -255.255.255.255 0.0.0.0 -255.255.255.255 oncue.kohler.com 3
Notes [ RXT RXT RXT RXT OnCue OnCue OnCue OnCue OnCue OnCue OnCue
120 3 True 0.0.0.0 0.0.0.0 0.0.0.0 0.0.0.0 0.0.0.0 oncue. kohler. com 0.0.0.0 0.0.0.0 0.0.0.0 0.0.0.0 0.0.0.0 N/A 0.0.0.0 False False False 0 100 0 0 N/A N/A N/A N/A N/A N/A N/A N/A N/A
Network Status Network Status Network Status Network Status Network Status Network Status Network Status Network Status Network Status RBUS Network RBUS Network RBUS Network RBUS Network RBUS Network RBUS Devices B1 RBUS Devices B1 RBUS Devices B1 RBUS Devices B1 RBUS Devices B1 RBUS Devices B1 RBUS Devices B1 RBUS Devices B1 RBUS Devices B2
IP Address Subnet Mask Default Gateway DNS Server 1 DNS Server 2 MAC Address Connected Server IP Address Network Connection Established Media Connected RBUS Active RBUS Connection Count RBUS Net Cycle Time RBUS Timeouts RBUS Errors RBUS Devices B1 Serial Number RBUS Devices B1 Type RBUS Devices B1 Communication Errors RBUS Devices B1 Communication Timeouts RBUS Devices B1 Modbus Id RBUS Devices B1 Last Connection Date RBUS Devices B1 Firmware Version RBUS Devices B1 Connected RBUS Devices B2 Type ms
Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only (RXT, PIM, or LCM) Read Only Read Only Read Only Read Only Read Only Read Only Read Only (RXT, PIM, or LCM)
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
34
Section 3 Controller
TP-6811 4/12
SiteTech Group RBUS Devices B2 RBUS Devices B2 RBUS Devices B2 RBUS Devices B2 RBUS Devices B2 RBUS Devices B2 RBUS Devices B3 RBUS Devices B3 RBUS Devices B3 RBUS Devices B3 RBUS Devices B3 RBUS Devices B3 RBUS Devices B3 RBUS Devices B3 RBUS Devices B4 RBUS Devices B4 RBUS Devices B4 RBUS Devices B4 RBUS Devices B4 RBUS Devices B4 RBUS Devices B4 RBUS Devices B4 RBUS Devices B5 RBUS Devices B5 RBUS Devices B5 RBUS Devices B5 RBUS Devices B5 RBUS Devices B5 RBUS Devices B5 RBUS Devices B5
Parameter RBUS Devices B2 Communication Errors RBUS Devices B2 Communication Timeouts RBUS Devices B2 Modbus Id RBUS Devices B2 Last Connection Date RBUS Devices B2 Firmware Version RBUS Devices B2 Connected RBUS Devices B3 Serial Number RBUS Devices B3 Type RBUS Devices B3 Communication Errors RBUS Devices B3 Communication Timeouts RBUS Devices B3 Modbus Id RBUS Devices B3 Last Connection Date RBUS Devices B3 Firmware Version RBUS Devices B3 Connected RBUS Devices B4 Serial Number RBUS Devices B4 Type RBUS Devices B4 Communication Errors RBUS Devices B4 Communication Timeouts RBUS Devices B4 Modbus Id RBUS Devices B4 Last Connection Date RBUS Devices B4 Firmware Version RBUS Devices B4 Connected RBUS Devices B5 Serial Number RBUS Devices B5 Type RBUS Devices B5 Communication Errors RBUS Devices B5 Communication Timeouts RBUS Devices B5 Modbus Id RBUS Devices B5 Last Connection Date RBUS Devices B5 Firmware Version RBUS Devices B5 Connected
Units
Adjustment Range * Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only (RXT, PIM, or LCM) Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
Default Setting N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
TP-6811 4/12
Section 3 Controller
35
SiteTech Group RBUS Devices B6 RBUS Devices B6 RBUS Devices B6 RBUS Devices B6 RBUS Devices B6 RBUS Devices B6 RBUS Devices B6 RBUS Devices B6 RBUS Devices B7 RBUS Devices B7 RBUS Devices B7 RBUS Devices B7 RBUS Devices B7 RBUS Devices B7 RBUS Devices B7 RBUS Devices B7 RBUS Devices B8 RBUS Devices B8 RBUS Devices B8 RBUS Devices B8 RBUS Devices B8 RBUS Devices B8 RBUS Devices B8 RBUS Devices B8
Parameter RBUS Devices B6 Serial Number RBUS Devices B6 Type RBUS Devices B6 Communication Errors RBUS Devices B6 Communication Timeouts RBUS Devices B6 Modbus Id RBUS Devices B6 Last Connection Date RBUS Devices B6 Firmware Version RBUS Devices B6 Connected RBUS Devices B7 Serial Number RBUS Devices B7 Type RBUS Devices B7 Communication Errors RBUS Devices B7 Communication Timeouts RBUS Devices B7 Modbus Id RBUS Devices B7 Last Connection Date RBUS Devices B7 Firmware Version RBUS Devices B7 Connected RBUS Devices B8 Serial Number RBUS Devices B8 Type RBUS Devices B8 Communication Errors RBUS Devices B8 Communication Timeouts RBUS Devices B8 Modbus Id RBUS Devices B8 Last Connection Date RBUS Devices B8 Firmware Version RBUS Devices B8 Connected
Units
Adjustment Range * Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
Default Setting N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Notes [ N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
* Read Only = Not adjustable [ Notes indicate applicability to genset or accessories. N/A = Not applicable to the Model 48RCL generator set. ] See TT-1584 for more information about digital inputs and outputs.
36
Section 3 Controller
TP-6811 4/12
Battery 12.3V
Date: Time:
02DEC2011 HR:MNpm
SW Version: 4.03
<---- Return
tp6804
Figure 3-4
TP-6811 4/12
Section 3 Controller
37
door on the service side of the generator set. See Figure 3-5. 2. Press the OFF button on the controller. 3. Disconnect utility power to the generator set by opening the circuit breaker in the distribution panel.
Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.
4. Disconnect the generator set engine starting battery, negative (--) lead first.
1
If the troubleshooting procedures in Section 5 identify a failed controller, use the procedure in this section for controller replacement. Always check the controller settings, wiring, and connections before replacing the controller. Some setup is required after the new controller is installed. There are several ways to set up the controller:
D The controller can be set up using the buttons on the
1. RDC2 controller
ADV-7962
controller.
D The controller can be set up using a personal
Figure 3-5
a personal computer connected directly to the controller with a USB cable can be used to set the genset serial number and model. When OnCue is connected through USB, a window will open to prompt you for the information if it has not already been entered into the controller using one of the other methods shown above.
D If a controller settings file was created at installation
or at some other time when the controller was known to be operating correctly, a personal computer (laptop) with Kohler SiteTech software can be used to load the settings onto the new controller. Note: Load the old controller settings onto the new controller only if you are certain that the settings are correct. Many controller operation problems can be caused by incorrect settings. In some cases, the Kohler Generator Service Department may provide a settings file to load onto the controller for testing or troubleshooting. See TP-6701, SiteTech Software Operation Manual, for instructions to export and import settings after controller replacement. Controller Replacement Procedure 1. Using the enclosure locking tool provided with the generator set, open and remove the enclosure
38 Section 3 Controller TP-6811 4/12 1. 2. 3. 4.
3 4
GM66569
Controller screws (qty. 2) Nameplate location Utility power entry point Customer connection access panel
Figure 3-6
5. Remove the customer connection access panel and use a voltmeter to confirm that utility power has been disconnected. See Figure 3-6. 6. Remove the two (2) screws securing the controller to the junction box and carefully lift the bottom edge of the controller. See Figure 3-6. Note: Be careful of the leads and harness connected to the controller panel. 7. Note the connections on the back of the controller, and then disconnect P1, P2, P4, P5, and P6. See Figure 3-7 or the wiring diagram. Note: The auxiliary winding mini-breaker on the RDC2 controller is not connected on the Model 48RCL generator set.
8. Remove the old controller. 9. Reconnect all harnesses to the new controller assembly. See Figure 3-7 or the wiring diagram. 10. Install the controller onto the junction box using the two (2) screws removed in step 6. 11. Replace the access panel and secure with the screws. 12. Reconnect the engine starting battery, negative (--) lead last. 13. Reconnect the utility power to the generator set by closing the circuit breaker in the distribution panel. 14. Check the firmware version on the controller, and update to the latest released version, if necessary. See Section 3.4 and TP-6701, SiteTech Software Operation Manual, for instructions. 15. The controller will prompt you to set the date and time, and then to set the exerciser. See the generator set Operation Manual for instructions, if necessary. 16. Set up the controller as instructed in Section 3.6, Controller Setup.
17. Calibrate the voltage. See Section 3.7, Voltage Calibration. 18. If OnCuer is used to monitor this generator set, reset the OnCue password on the controller and note the new password. See Section 3.8, Setting the OnCue Password. Then connect with OnCue and enter the new password.
GM81217
3
1. 2. 3. 4. 5. P6 Ethernet connection for OnCue P1 Field circuit breaker (Not connected on 48RCL) P2 P5
19. Verify that OnCuer can communicate with the generator set over the Internet before leaving the job site.
Figure 3-7
Controller Connections
TP-6811 4/12
Section 3 Controller
39
c. Kohlerr OnCuer software (version 3.1 or higher) and a personal computer connected directly to the controller with a USB cable can be used to set the genset serial number and model. When OnCue is connected through USB, a window will open to prompt you for the information if it has not already been entered into the controller using one of the other methods shown above. 2. Check the voltage calibration and adjust, if necessary. See Section 3.7, Voltage Calibration. Exporting Settings from a File If a personal computer (laptop) and Kohlerr SiteTecht software were used to create a controller settings file at the time of generator set installation (when the controller was known to be operating correctly), then SiteTech software can be used to load the saved settings onto the new controller. See TP-6701, SiteTech Software Operation Manual, for instructions to export and import controller settings. Note: Load the old controller settings to the new controller only if you are certain that the settings are correct. Many generator set operation problems can be caused by incorrect settings.
System Voltage
120/208 120/240 120/240 277/480 220/380 230/400 240/416
when the Genset Model Number is selected and the change is applied.
D The Fuel Type parameter is available with controller
firmware versions 4.5 or higher. The fuel type setting affects the generator set power rating, which is used to determine setpoints for the optional load control module (LCM). Setting the Fuel Type is recommended if the generator set is connected to an LCM. Controller Setup Procedure 1. Use one of the methods listed below to set the parameters shown in Figure 3-9. a. Use the buttons on the controller to navigate through the controller menus and change the settings. See the required controller menus in Figure 3-10 and Figure 3-11. See the generator set operation manual for additional instructions, if necessary. b. Use a personal computer and Kohlerr SiteTecht software to change the settings. See Figure 3-12. Refer to TP-6701, SiteTech Software Operation Manual, for instructions if necessary.
Parameter
Genset Model Number Genset Serial Number Fuel Type [ Phase Connection Genset System Voltage Genset System Frequency [ Fuel Type is available with controller firmware versions 4.5 or higher. Genset System Genset Information
Phases
3 1 3 3 3 3 3
Phase Connection
Three-Phase Wye Single Phase Three-Phase Delta Three-Phase Wye Three-Phase Wye Three-Phase Wye Three-Phase Wye
Figure 3-8
Controller Menu
SiteTech Group
Genset Info
Figure 3-9
Controller Setup
40
Section 3 Controller
TP-6811 4/12
<---- Return
tp6810
Genset System
---->
See Note.
Next Exercise System Freq: 60 Hz Exercise Mode: VR Voltage Adj: 240.0V Exercise Freq: System Phase: Single Weekly Unloaded Cycle 06:30p 15Dec2011
System Battery: 12 V
Contrast: 50
<----
Return
tt1589
Note: Fuel Type is shown on controllers with firmware version 4.5 or higher.
TP-6811 4/12
Section 3 Controller
41
1. Genset model and serial numbers 2. System settings 3. Fuel type (controller firmware version 3.5 or higher)
tt1589
42
Section 3 Controller
TP-6811 4/12
3.7.1
The controllers voltage calibration can be adjusted using the controller keypad. See Figure 3-13 and follow the procedure below. Note: A digital voltmeter is required for these adjustments. 1. With the generator set off, connect a digital multimeter to measure output voltage across L1 and L2. Set the meter to measure AC volts. 2. Start the generator set by pressing the RUN button on the RDC2 controller. 3. On the RDC2 controller, press the Select button and then use the arrow buttons to navigate to the Generator Metering menu on the RDC2 controller. 4. Press the Select button to display Volts L1-L2. Compare the number displayed with the voltmeter reading. 5. If the correct voltage is not displayed, follow these steps to adjust it: a. Press the Select button. The voltage will flash. b. Press the up or down arrow button to adjust the voltage to match the voltmeter reading. c. Press Select to save the voltage setting. The voltage stops flashing. d. Wait for the voltmeter reading to stabilize. This may take 30 to 60 seconds. 6. For three-phase models, press the Down arrow button and repeat the calibration procedure for voltage across L2--L3 and L3--L1. 7. Use the arrow buttons to step down to the Return screen. Press Select to exit the Generator Metering menu. 8. Press OFF to stop the generator set. Reset Calibration Pressing the select button when Reset Calibration? Yes is displayed will discard the changes and reset the calibration to the original settings. See Figure 3-13.
Hazardous voltage. Moving parts. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically. (600 volts and under) Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Correct voltage calibration is necessary for proper generator set operation. Check the voltage calibration after controller replacement or generator set reconnection, and adjust if necessary. The RDC2 controller can be calibrated using the controller keypad and menus, or using a personal computer with Kohlerr SiteTecht software.
TP-6811 4/12
Section 3 Controller
43
Generator ----> Metering Three-phase Volts L1--L2: 240 V Calibrate Single-phase Volts: 240V Calibrate
Calibrate
Frequency: 60.0 Hz
To Calibrate Voltage: 1. Press Select when the voltage is displayed. The voltage flashes. 2. Press the Up or Down arrow button to change the setting. 3. Press the Select button to save the setting. 4. Press the down arrow button to move to the next menu.
Calibrate
Reset Calibration
Reset Calibration? No
<---- Return
Note: Pressing select when Reset Calibration: Yes is displayed will discard the changes and reset the calibration to the original settings.
tp6811
44
Section 3 Controller
TP-6811 4/12
3.7.2
voltage readings again. Repeat the procedure using the new values, if necessary. Note: If you would like to simplify the calculation, set the calibration factor to 1.0000 and then repeat the calibration procedure from step 3. 8. Press OFF to stop the generator set.
Voltage calibration factors can be adjusted using SiteTech software to calibrate the RDC2 controller. Connect a personal computer (laptop) to the controller using a USB cable and follow this procedure to use Kohlerr SiteTecht software to calibrate the controller. The voltage calibration factors are located in the Genset Calibration group in SiteTecht. Find the parameter labelled Genset Calibration Factor Voltage, L1--L2. See Figure 3-15. Note: A digital voltmeter is required for these adjustments. 1. With the generator set off, connect a digital multimeter to measure output voltage across L1 and L2. Set the meter to measure AC volts. 2. Start the generator set by pressing the RUN button on the RDC2 controller. 3. Compare the voltage reading on the digital voltmeter to the voltage displayed by the controller. 4. If the voltage displayed on the controller does not match the measured voltage, use the equation in Figure 3-14 to calculate a new value for Genset Calibration Factor Voltage, L1--L2. 5. Type the new value for Genset Calibration Factor Voltage, L1--L2 into SiteTech and click on Apply Changes. See Figure 3-15. 6. Allow a few seconds for the controller to adjust to the new factor and then compare the voltmeter reading with the voltage displayed on the controller. 7. If the voltage readings do not match, check your calculations. Check the calibration factor and both
9. Repeat the procedure for voltage across L2--L3 and L3--L1, if necessary. (Three-phase only.)
TP-6811 4/12
Section 3 Controller
45
1
#
46
Section 3 Controller
TP-6811 4/12
5. Press and HOLD the Select button until Reset OnCue Password? No appears. The word No will flash. 6. Press the Up arrow button to change the word No to Yes. 7. Press Select to reset the password. The generator set serial number and new password are displayed for 10 seconds. Be sure to write down the new password for entry into the OnCue program.
Networking----> Information
Networking----> Status
HOLD
Networking Configuration
DHCP: Enabled
<---- Return
tp6804
TP-6811 4/12
Section 3 Controller
47
Notes
48
Section 3 Controller
TP-6811 4/12
WARNING
1 Hot coolant and steam. Can cause severe injury or death. Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
Before servicing, allow the engine to cool. Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the overflow bottle. Note: Block heater damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm and refill the radiator to purge the air from the system before energizing the block heater.
1. Thermostat
Figure 4-1
Item
Thermostat
Figure 4-2
Thermostat Rating
TP-6811 4/12
49
1 2 3 4 8 9 5
10
6 7
1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
Radiator Radiator fill/pressure cap Upper radiator hose Engine compartment temperature sensor Engine compartment fan Lower radiator hose Coolant overflow bottle Coolant overflow tube Low coolant level sensor Radiator fans
GM83070
Figure 4-3
50
TP-6811 4/12
remove dirt and foreign material with a soft brush or cloth to avoid damaging the radiator fins.
D Check the hoses and connections for leaks and
pump belt(s).
D Check the rubber seal of the radiators pressure cap.
Remove dirt and other debris from the pressure cap and filler neck. Replace a cracked or deteriorated cap.
TP-6811 4/12
51
5. Add coolant to the radiator to just below the overflow tube on the filler neck. See Section 1, Service Views, for the overflow tube location. 6. Replace the radiators pressure cap. 7. Maintain the coolant level in the coolant overflow bottle between the High and Low markings. See Section 1, Service Views, for the coolant overflow bottle location. 8. Re-energize the block heater, if equipped.
Figure 4-4
Coolant Capacity
Note: Do not add coolant to a hot engine. Adding coolant to a hot engine can cause the cylinder block or cylinder head to crack. Wait until engine has cooled. 1. Close the radiators coolant drain valve and tighten the hose clamps. 2. Fill the radiator with the recommended coolant mixture of 50% ethylene glycol and 50% clean, softened water to inhibit rust/corrosion and prevent freezing. The coolant capacity is shown in Figure 4-4. 3. Operate the engine with the radiator cap removed until the thermostat opens and the upper radiator hose becomes hot. 4. Stop the engine and allow it to cool.
Figure 4-5
52
TP-6811 4/12
temperature returns to an operating temperature below 46_C (115_F), the fan returns to low-speed operation. Note: The engine compartment fan continues to run for 2 minutes after the engine stops to evacuate residual engine and exhaust system heat.
The engine compartment fan is operated in low-speed mode by configuring the relays to connect the fan in series with a power resistor which is housed within protective covers behind the fuse/relay terminal block. For high-speed fan operation, the fan is connected directly across the 12 VDC battery supply. The RDC2 controls operating speed based on engine compartment temperature, as measured by the engine compartment temperature sensor located on the bulkhead wall adjacent to the engine compartment fan. The fan is set to low-speed mode on engine startup (for a minimum of the first 10 seconds of operation). High-speed operation is selected when engine compartment temperature exceeds 57_C (135_F). If the engine compartment
GM78527
Figure 4-6
Sensor
Coolant Engine Compartment
High Speed
93 57 (200) (135)
Low Speed
79 46 (175) (115)
Figure 4-7
Corrective Action
TP-6811 4/12
Check fan fuses. Check fan for obstruction. Check that the fan blades rotate freely. Check fan motor for open coil (continuity). Check harnesses from fuse/relay terminal block to fans and controller for damaged leads or terminations. Evaluate relays for functionality. Check for transition at threshold temperatures noted in Figure 4-7.
Check sensor function. Check harnesses from fuse/relay terminal block to fans and controller for damaged leads or terminations. Evaluate relays for functionality. Check continuity of the coil. Check for transition at threshold temperatures noted above.
Check radiator and enclosure openings for air flow blockage. Check sensor function. Check harnesses from fuse/relay terminal block to fans and controller for damaged leads or terminations. Evaluate relays for functionality. Check continuity of the coil. Check for transition at threshold temperatures noted above.
54
TP-6811 4/12
Section 5 Troubleshooting
5.1 Introduction
Corrective action and testing in many cases requires knowledge of electrical systems and electronic circuits. Have an authorized distributor/dealer or trained service technician perform testing and service. Refer to the engine service manuals for engine service information. See the List of Related Materials for the document part number. If the troubleshooting procedures in this section identify a failed part, refer to the parts catalog for replacement part numbers. See the List of Related Materials in the Introduction for the parts catalog number.
5.3.1
The line circuit breaker interrupts the generator output in the event of an overload condition or a fault in the wiring between the generator and the load. If the circuit breaker trips, reduce the load and check the wiring.
5.3.2
Fuses
Always identify and correct the cause of a blown fuse before restarting the generator set. Refer to Figure 5-4, Troubleshooting Chart, for conditions that may indicate a blown fuse. Obtain replacement parts and service from an authorized Kohler distributor/dealer. Fan Fuses. Three 30 amp fan fuses are located in the fan fuse and relay box. See Section 1.7, Service Views, for location. Engine Fuses. Engine fuses are located in the engine fuse box. See the service views in Section 1.7 for the fuse box location.
D Fuse F1, 5 amps D Fuse F2, ECM 10 amps D Fuse M3, battery charging alternator, 70 amps D Fuse F4, ignition,15 amps. D Fuse F6, starter, 20 amps.
Check for damaged primary or secondary fuel regulators, loose connections to the fuel solenoid valve, a damaged or closed fuel shutoff valve, an empty LP fuel tank, or other problems with the fuel supply. Check the fuel supply pressure to the generator set. See Section 6.8, Fuel Systems.
controller display. Section 5.6 describes the warning and shutdown fault messages. If a fault message is displayed, identify and correct the cause of the fault condition. Then reset the controller.
D Incorrect controller settings.
5.3.3
Always check the controller settings before replacing the controller. See Section 3.3.1 for controller settings. Refer to the operation manual for instructions to check and change the controller settings from the controller keypad, or use a personal computer and Kohlerr SiteTecht software.
The controller is equipped with internal circuit protection for accessory and main power overload conditions. Press OFF to reset.
TP-6811 4/12
Section 5 Troubleshooting
55
Figure 5-1
56
Section 5 Troubleshooting
TP-6811 4/12
Some fault conditions are reported to the RDC2 controller by the engine ECM. Refer to the Engine Service Manuals for more information. Identify and correct the cause of the fault condition. Then press the OFF button to reset the controller after a fault shutdown.
Check Check for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
Action Shutdwn
Description/ Comments The controller shut down the generator because there was less than 5% of rated voltage measured on Phase A (or B or C if 3 Phase) for 3 seconds, only in AUTO, only after acceptable voltage (> 5% of UV setting) has been detected. The controller has measured less than 5% of rated voltage on Phase A (or B or C on 3 Phase), for 1 second, 10 seconds after crank disconnect. The controller has lost communications with the RXT ATS that had previously been communicating properly. The RXT ATS has reported a fail to transfer, the digital output for ATS Fail To Transfer (PIM) is active (contacts closed). The RXT ATS has reported a Phase Rotation Mismatch (3 phase only) and the ATS will not transfer. The controller shut down the generator because the digital input for a custom shutdown (AuxiliaryInputShutdown PIM) was activated (low). The digital input for a custom warning (AuxiliaryInputWarning - PIM) is active (low). The digital input for Battery Charger Fault Warning (PIM) is active (low). For an external battery charger only, not applicable to the RDC2 built-in battery charging. The controller has measured battery voltage that is above the high warning setting for 10 seconds or more. Operates during exercise and normal operation.
AC Sens Loss Warning (Loss of AC sensing warning) ATS ComError Warning (ATS communication error) ATS Fail Xfr Warning (ATS fail to transfer) ATS PhaseRot Warning (ATS phase rotation) Aux Input Shutdwn * (Auxiliary input shutdown) Aux Input Warning * (Auxiliary input warning) Batt Chg Flt Warning * (Battery charger fault warning)
Warning
Check for loose wiring and connections. Check all AC leads. Troubleshoot alternator. Check connection to ATS module. Consult ATS manual for troubleshooting.
Warning
Warning
Warning
Check wiring to ATS Consult ATS manual for troubleshooting. Check customer equipment connected to the PIM module.
Shutdown
Warning
Check customer equipment connected to the PIM module. Check customer equipment connected to the PIM module.
Warning
Warning
Shutdown
Battery voltage dropped to 11 VDC or less for 30 seconds or more. Operates after the genserator set has been running for at least one minute. The controller has measured battery voltage that is below the low warning setting for 90 seconds or more. The battery voltage is checked before allowing an exercise to start.
Check cranking battery. Check battery charger DC output voltage from RDC2 on lead CHO to the battery. Check cranking battery. Check battery charger DC output voltage from RDC2 on lead CHO to the battery. Troubleshoot engine operation per the engine service manual.
Warning
CAN Shutdown
Shutdown
The ECM shut down the engine and reported an unknown fault code.
* Programmable Interface Module (PIM) required [ Applies during exercise runs and normal operation.
TP-6811 4/12
Section 5 Troubleshooting
57
Fault Message Chk DateTime Warning (Check date and time warning)
Action Warning
Description/ Comments DC power to the controller has been interrupted and the date and time may not be correct. Event history may not have accurate time/date stamps. The controller shutdown the generator because engine compartment air temperature has exceeded 174_F (79_C). The controller has detected engine compartment temperature that is above 167_F (75_C). The controller shutdown the engine because the coolant level sensor indicated low coolant for 5 seconds or more.
Check Verify the time and date settings to ensure proper operation of scheduled operations and for event history logging. Troubleshoot fan circuit failure and/or temperature sensor circuit. Check for blockage of intake or exhaust vents. Troubleshoot fan circuit failure and/or temperature sensor circuit. Check for blockage of intake or exhaust vents. Check coolant level and fill as needed. Check for air in cooling system. Check the coolant level sensor operation.
Shutdown
Warning
Shutdown
Shutdown
The ECM shutdown the engine and reported high coolant temperature as the fault.
Check engine cooling system. Check radiator fans for proper operation. Check for blockage of inlet and exhaust vents. Check engine cooling system. Check radiator fans for proper operation. Check for blockage of inlet and exhaust vents. Check cooling system. Check cooling system and coolant level sensor circuit. Configure settings as needed or as required for desired operation. Verify no other devices connected and broadcasting on the CAN bus. Check CAN communication wiring between controller and ECM. Verify controller configuration using SiteTech. Consult local service technician. Check E-stop circuit for open switches, broken wires, disconnected wires, etc. Troubleshoot engine operation per the engine service manual.
Warning
Warning Shutdown
The ECM is reporting low coolant temperature. The ECM shutdown the engine and reported no coolant temperature signal as the fault. The controller has been loaded with default parameters. The controller shut down the generator because there is a conflict in addressing on the ECM CAN bus. The controller shut down the generator because communication with the ECM was lost, for 4 or more seconds. The controller shut down the generator because the ECM does not match any of the supported models. The controller shut down the generator because the emergency stop circuit was tripped (open circuit). The controller shut down the generator because engine speed, as calculated from AC frequency, was above the high speed setting for 0.3 seconds or more; or the ECM shut down the engine and reported overspeed as the fault code.
Warning
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
* Programmable Interface Module (PIM) required [ Applies during exercise runs and normal operation.
58
Section 5 Troubleshooting
TP-6811 4/12
Action Shutdown
Description/ Comments The controller shut down the generator, after crank disconnect, because engine speed, as calculated from AC frequency, was below the low speed setting for 3 seconds or more. There is no exercise scheduled. The controller shut down the generator because the frequency measured on Phase A exceeded the high frequency setting for 10 seconds, 10 seconds or more after crank disconnect. The controller shut down the generator because the frequency measured on Phase A was less than the low limit for 10 seconds or the measured frequency was 10 Hz or more less than rated for 60 seconds or more, 10 seconds or more seconds after crank disconnect. The controller shut down the generator because the digital input for Fuel Tank Leak Shutdown (PIM) was activated (low). The digital input for Fuel Tank Leak Warning (PIM) is active (low). The digital input for Critically High Fuel Level Warning (PIM) is active (low). The digital input for High Engine Fuel Level Warning (PIM) is active (low). The controller shut down the generator because the digital input for Low Fuel Level Shutdown (PIM) was activated (low). The digital input for Low Fuel Level Warning (PIM) is active (low). There is voltage at the generator set but no voltage measured on the emergency side of the ATS (Model RXT transfer switch). The digital input for Ground Fault Warning (PIM) is active (low). During cranking, the controller measured battery voltage less than 60% (7.2V or 14.4V) for 6 seconds or more during cranking. The controller shut down the generator because no rotation of the engine or alternator was detected, for 3 seconds or more, during cranking.
Warning Shutdown
Set the exercise schedule. Troubleshoot engine operation per the engine service manual.
Shutdown
Shutdown
Fuel Leak Warning * Fuel Level CrHi Warning * Fuel Level High Warning * Fuel Level Low Shutdwn *
Check customer equipment connected to the PIM module. Check customer equipment connected to the PIM module. Check customer equipment connected to the PIM module. Check customer equipment connected to the PIM module.
Fuel Level Low Warning * GenBrkerOpen Warning (Generator Circuit Breaker Open)
Warning Warning
Check customer equipment connected to the PIM module. Check line circuit breaker. Check for and correct short circuits or overloading on the load side before resetting the circuit breaker. Check customer equipment connected to the PIM module. Check cranking battery.
Warning Warning
Shutdown
Check cranking circuit. Troubleshoot the engine. See Engine Service Manuals. Check alternator connections to controller and auxiliary winding circuit breaker. Troubleshoot the alternator. Check crank, run, and flash relay circuits for short circuits.
MainPwrOverL Shutdwn
Shutdown
The internal current limit circuit has tripped, indicating an overcurrent condition on the DC power supply circuit.
* Programmable Interface Module (PIM) required [ Applies during exercise runs and normal operation.
TP-6811 4/12
Section 5 Troubleshooting
59
Action Warning
Description/ Comments Engine run time, or calendar days, has exceeded the maintenance reminder setting.
Check Change the oil and perform other service according to the service schedule in Section 2.2. Reset the maintenance timer after service. See Section 2.3.5. Press the Auto button to ensure automatic system operation.
Warning
The RDC2 controller is not in AUTO. The generator will not start from an ATS or remote device. The digital output for Not In Auto (PIM) is active (contacts closed). Communications with option board #1 has been lost. Communications with option board #2 has been lost. Communications with option board #3 has been lost. Communications with option board #4 has been lost. The controller shut down the generator because the digital input for Low Oil Level Shutdown (PIM) was activated (low). The digital input for Low Oil Level Warning (PIM) is active (low). The ECM shutdown the engine and reported low oil pressure as the fault. The ECM is reporting a low oil pressure warning. The ECM shutdown the engine and reported no oil pressure signal as the fault. The ECM shutdown the engine and reported no oil pressure signal as the fault. The controller shut down the generator, and ceased cranking, because the engine was not successfully started after the completion of the last of the crank cycles setting delay 15 seconds. The controller has lost communications with a PIM or LCM that had previously been communicating properly. The controller, or the ECM, shutdown the generator because the speed signal was lost. The controller shut down the generator because the voltage measured from Phase A to Phase B exceeded the high limit for a time greater than the delay setting 2 seconds.
OB1 CommLoss (PIM, LCM, or RXT) OB2 CommLoss (PIM, LCM, or RXT) OB3 CommLoss (PIM, LCM, or RXT) OB4 CommLoss (PIM, LCM, or RXT) Oil Level Low Shutdwn *
Check RBUS wiring to inoperative option board. Check RBUS wiring to inoperative option board. Check RBUS wiring to inoperative option board. Check RBUS wiring to inoperative option board. Check customer equipment connected to the PIM module.
Warning Shutdown
Check customer equipment connected to the PIM module. Check for oil leaks. Check the oil level and add oil if low. Check the oil pressure sensor; see Engine Service Manuals. Check engine oil pressure sensor and wiring to the ECM. Troubleshoot engine. Check engine oil pressure sensor and wiring to the ECM. Troubleshoot engine. Check fuel supply. Check cranking circuit. Check cranking battery. Troubleshoot engine; see Engine Service Manuals. Check connection to the PIM or LCM. Check speed sensor and circuitry to ECM. Troubleshoot alternator; see alternator service manual.
Warning
Warning
Shutdown
Shutdown
Warning
Spd Sens Flt Shutdwn (Speed sensor fault) Volts L1-L2 High Shutdwn [
Shutdown
Shutdown
* Programmable Interface Module (PIM) required [ Applies during exercise runs and normal operation.
60
Section 5 Troubleshooting
TP-6811 4/12
Action Shutdown
Description/ Comments The controller shut down the generator because the voltage measured from Phase A to Phase B was greater 5% of rated, but less than the low voltage setting for a time greater than the delay setting 10 seconds. The controller shut down the generator because the voltage measured from Phase B to Phase C exceeded the high limit for a time greater than the delay setting 2 seconds. The controller shut down the generator because the voltage measured from Phase B to Phase C was greater 5% of rated, but less than the low voltage setting for a time greater than the delay setting (default 10 seconds). The controller shut down the generator because the voltage measured from Phase C to Phase A exceeded the high limit for a time greater than the delay setting. (default delay time is 2 seconds.) The controller shut down the generator because the voltage measured from Phase C to Phase A was greater 5% of rated, but less than the low voltage setting for a time greater than the delay setting.
Shutdown
Shutdown
Shutdown
Shutdown
* Programmable Interface Module (PIM) required [ Applies during exercise runs and normal operation.
Figure 5-2
digital input is activated; the optional Programmable Interface Module (PIM) is required for display of those messages as noted in the table.
Check Click on the output in OnCues Power Chain view to turn the output on or off. See the OnCue Operation Manual. To reset the digital output to a function controlled by the generator set, use SiteTech software to re-assign the output event. Check customer equipment connected to the PIM module.
Description/ Comments OnCues Power Chain view has been used to control this digital output. The digital output is no longer controlled by the generator set. Applies to digital outputs B3 through B6 on the PIM only.
Always On *
Notice
Notice
The digital output for Chicago Code Active (PIM) is active (contacts closed), indicating the digital input for Chicago Code Active (PIM) is active (low) and thus master switch is locked in the AUTO position.
* Programmable Interface Module (PIM) required [ Load Control Module (LCM) required
TP-6811 4/12
Section 5 Troubleshooting
61
Action Notice
Description/ Comments The digital output for Common Fault (PIM) is active (contacts closed), indicating the generator is shutdown for any (all) fault. The digital output for Common Warning (PIM) is active (contacts closed), indicating the any (all) warning is active. The digital output for EPS Supplying Load (PIM) is active (contacts closed), indicating there is current output (>5%) from the alternator, only if CTs are installed. The digital output for Engine Cooldown Active (PIM) is active (contacts closed), indicating the generator is running in cooldown. (delay 5 min.) The digital output for Fuel Spill (PIM) is active (contacts closed), indicating any of the digital inputs for Fuel Tank Leak Warning, Fuel Tank Leak Shutdown, Engine Fuel Level Warning or Engine Fuel Level Critically High (PIM) is active (low). The digital output for Generator Running (PIM) is active (contacts closed), indicating the generator is running.
Check Check for faults and troubleshoot any/all fault conditions individually. Check for warnings and troubleshoot any/all warning conditions individually. Nothing to check.
Common Warng
Notice
Notice
Notice
Check remote start circuit if it was expected that the generator should be running. Consult ATS operations manual. Check customer equipment connected to the PIM module.
Fuel Spill *
Notice
Gen Running
Notice
Check controller front panel buttons for potential RUN command. If in AUTO, check remote start lines. Consult ATS operation manual for events that may cause the generator to start. Check customer equipment connected to the PIM module.
Low Fuel *
Notice
The digital output for Low Fuel (PIM) is active (contacts closed), indicating any of the digital inputs for Low Fuel Pressure Warning, Low Fuel Level Warning or Low Fuel Level Shutdown (PIM) is active (low). The digital output for Minor Fault (PIM) is active (contacts closed), indicating either the digital input for Ground Fault Indicator Warning (PIM) is active (low) or the controller detected Low Cranking Voltage. The digital output for NFPA Alarm Active (PIM) is active (contacts closed), indicating that at least one of the NFPA faults or warnings is active. The normal power source (source1) is disconnected, unavailable or unacceptable. Communications with option board #1 has been lost. Communications with option board #2 has been lost. Communications with option board #3 has been lost. Communications with option board #4 has been lost.
Minor Fault
Notice
Check customer equipment connected to the PIM module. Check cranking battery condition.
NFPA Alarm
Notice
Check for faults and troubleshoot any/all fault conditions individually. Check for utility source power outage. Check wiring and connections to the ATS. Check RBUS wiring to inoperative option board. Check RBUS wiring to inoperative option board. Check RBUS wiring to inoperative option board. Check RBUS wiring to inoperative option board.
Notice
OB1 CommLoss (PIM, LCM, or RXT) OB2 CommLoss (PIM, LCM, or RXT) OB3 CommLoss (PIM, LCM, or RXT) OB4 CommLoss (PIM, LCM, or RXT)
* Programmable Interface Module (PIM) required [ Load Control Module (LCM) required
62
Section 5 Troubleshooting
TP-6811 4/12
Action Notice
Description/ Comments The controller has received a remote start signal while the master switch is in AUTO, and will go to normal running. The RUN button on the controller has been pushed. The digital output for Engine Start Delay (PIM) is active (contacts closed), indicating the engine is in between active cranking cycles. The digital output for System Ready (PIM) is active (contacts closed), indicating the generator has no active faults or warnings. A diagnostic exercise request has been received by the controller. The digital output for LoadPriority1Shed is active (contacts closed), indicating the 1st priority load shed (LCM) has been activated. The digital output for LoadPriority2Shed is active (contacts closed), indicating the 2nd priority load shed (LCM) has been activated. The digital output for LoadPriority3Shed is active (contacts closed), indicating the 3rd priority load shed (LCM) has been activated. The digital output for LoadPriority4Shed is active (contacts closed), indicating the 4th priority load shed (LCM) has been activated. The digital output for LoadPriority5Shed is active (contacts closed), indicating the 5th priority load shed (LCM) has been activated. The digital output for LoadPriority6Shed is active (contacts closed), indicating the 6th priority load shed (LCM) has been activated.
Check Verify remote start signal. Consult ATS operations manual for cause of generator start. NA NA
Notice Notice
System Ready
Notice
NA
VSpdStartCmd (Variable Speed Start Command Issued) Load Shed 1 Status Info [
Notice
Check for a remote exercise command from OnCue. Remove loads as required. Check building wiring for proper load distribution. Check engine fuel supply. Remove loads as required. Check building wiring for proper load distribution. Check engine fuel supply. Remove loads as required. Check building wiring for proper load distribution. Check engine fuel supply. Remove loads as required. Check building wiring for proper load distribution. Check engine fuel supply. Remove loads as required. Check building wiring for proper load distribution. Check engine fuel supply. Remove loads as required. Check building wiring for proper load distribution. Check engine fuel supply.
Notice
Notice
Notice
Notice
Notice
Notice
* Programmable Interface Module (PIM) required [ Load Control Module (LCM) required
Figure 5-3
TP-6811 4/12
Section 5 Troubleshooting
63
service manuals. For issues with generator output voltage, refer to the alternator service manual in addition to the items mentioned in the tables below. See the List of Related Materials in the Introduction section of this manual for engine and alternator service manual part numbers.
Corrective Action Recharge or replace the battery. Check for DC voltage on lead CHO to the battery. Check for 120 VAC on the black and white leads to controller P5-1 and P5-3 for battery charging. Check 120 VAC utility power connection to the generator set.
Reversed or poor battery connections. Inoperative controller. Controllers internal circuit protection has tripped.
Check the battery connections and ground connection. Check power to the controller. Troubleshoot the controller. Press the OFF button to reset the controller. W/D Section 8 Section 5.9 W/D Section 8 W/D Section 8
Open circuit in engine or controller Check for loose connections. connections. Check the wire harness continuity. Poor ground (--) connection. Clean and tighten. Generator set is OFF. Press the RUN button to start the engine or press AUTO to allow remote starting. Generator set engine cranks but does not start. Engine problem. Air cleaner clogged. Weak battery. Troubleshoot/service the engine. Clean and/or replace the air cleaner. Recharge or replace the battery. Check for DC voltage on lead CHO to the battery. Check for 120 VAC on the black and white leads to controller P5-1 and P5-3 for battery charging. Check 120 VAC utility power connection to the generator set. Poor battery connection. Spark plugs. Spark plug connections. No fuel or low fuel pressure. Loose connections or faulty wiring. Clean and tighten the battery connections. Check the spark plugs. Regap or replace if necessary.
Section 2.7
Tighten connections. Replace spark plug wires Section 2.7 if necessary. Check the fuel supply, regulators, fuel supply lines, and valves. Check connections to fuel solenoid valves. Check the engine/controller connections and wiring. Section 5.4 Section 6.8, Fuel System W/D Section 8 Section 5.6 and Alternator S/M Engine S/M Engine S/M
Check for locked rotor shutdown. Replace the fuse. If the fuse blows again, troubleshoot/service the engine. Troubleshoot/service the engine.
I/M = generator set installation manual; O/M = generator set Operation Manual; S/M = service manual; W/D = wiring diagram.
64
Section 5 Troubleshooting
TP-6811 4/12
Corrective Action Clean and/or replace the air cleaner. Recharge or replace the battery. Check for DC voltage on lead CHO to the battery. Check for 120 VAC on the black and white leads to controller P5-1 and P5-3 for battery charging. Check 120 VAC utility power connection to the generator set.
Poor battery connection. Clean and tighten the battery connections. Spark plugs.. Regap or replace spark plugs. Spark plug wire connection loose. Tighten the spark plug connections. Replace wires if necessary. Low fuel pressure. Check the fuel supply. Verify that fuel supply lines and meters are sized to support all gas appliances.
Section 2.7
Section 5.4
Engine problem. Low oil pressure shutdown. Generator set stops suddenly. No fuel or inadequate fuel pressure.
Troubleshoot/service the engine. Engine S/M Check for oil leaks. Check the oil level and add oil if necessary. Check fuel supply. Check fuel lines for restrictions or leaks. Verify that fuel system is sized to supply all gas appliances. Section 5.4
Identify and correct the cause of the fault shutdown. Then press OFF to clear the fault. Clean and/or replace the air cleaner. Check air intake, oil level, air outlets. Check the coolant level. Check the cooling fan fuses, relays, and operation. Check temperature sensors.
Section 5.6, Fault Messages Generator set operation manual Generator set operation manual Section 4, Cooling System Section 6.7 and Engine S/M LCM documentation Engine service manuals
Engine overloaded.
Reduce the load. If the system is equipped with a load control module (LCM), troubleshoot the LCM.
Replace the fuse. If engine fuses blow repeatedly, troubleshoot/service the engine.
Remote stop command received from a remote switch, ATS, or OnCuer. Loss of generator output voltage to controller. Engine problem.
Note:
Check the remote switch position. Check the ATS/OnCue. Check controller connections. Check continuity of AC sensing leads 7 and 8 (1-phase) or 7--8--9 (3-phase). Troubleshoot/service the engine. Engine service manuals W/D, Section 8
I/M = generator set installation manual; O/M = generator set Operation Manual; S/M = service manual; W/D = wiring diagram.
TP-6811 4/12
Section 5 Troubleshooting
65
Possible Cause Air cleaner clogged Inadequate cooling (hot engine only)
Corrective Action Replace element. Inspect air inlet and outlet. Check the coolant level. Check the cooling fan fuses, relays, and operation. Check temperature sensors.
Refer to the engine service manual for troubleshooting and repair information. Inspect cooling system for obstructions. Check the coolant level. Check the cooling fan fuses, relays, and operation. Check temperature sensors.
Air cleaner clogged Generator set is Exhaust system leaks noisy Engine not running smoothly
Replace element. Check and repair as necessary. See Generator set operates erratically in this table.
Broken or damaged vibromount(s) Check and replace as necessary. Loose or vibrating sheet Retighten screws, replace rivets. metal/housing
Exhaust piping or air inlets/outlets Inspect for loose parts and secure if necessary. not securely installed Excessive engine/generator vibration High generator output voltage Incorrect controller settings Incorrect controller voltage settings Loose voltage sensing connections Controller Generator set lacks power Air intake restriction Low fuel pressure. Inadequate cooling Check, rotor, crankshaft, bearing, etc. (disassembly of engine and/or alternator may be required). Check and adjust the controller configuration parameters. See the Alternator S/M and Engine S/M Section 3.6
Check and adjust the controller voltage settings Sections 3.6, 3.7, and voltage calibration. and 6.5 Check connections: stator leads 7 and 8 (for 1-phase models) or leads 7, 8, and 9 (for 3-phase models) and P2 controller connection. Check wiring and connections. Inspect air intakes and exhaust for obstructions. Check the air cleaner. Section 2.4 Check the fuel supply, regulators, fuel lines, and valves. Check the coolant level. Check the cooling fan fuses, relays, and operation. Check temperature sensors. Section 4, Cooling System W/D, Section 8
W/D, Section 8
Section 2.7
Tighten connections. Replace spark plug wires Section 2.7 if necessary. Reduce load. If the system is equipped with a load control module (LCM), troubleshoot the LCM. Check controller settings for engine speed and generator set frequency. Refer to the Engine Service Manual for troubleshooting and repair instructions. Generator Set I/M LCM documentation Section 6.6 Engine S/M
I/M = generator set installation manual; O/M = generator set Operation Manual; S/M = service manual; W/D = wiring diagram. TP-6811 4/12
Section 5 Troubleshooting
Corrective Action Reduce the load. If the system is equipped with the load control module (LCM), troubleshoot the LCM.
Reference LCM documentation Section 3.6 Sections 3.6, 3.7, and 6.5 Alternator S/M
Check system voltage, frequency, and engine model settings. Check and adjust the voltage settings and voltage calibration on the RDC2 controller. Perform separate excitation procedure to isolate problem to the alternator or the control system. Check the controller settings. Check the controller wiring and connections.
Controller
Section 3.6 W/D, Section 8 Alternator S/M Alternator S/M Section 3.6 Engine S/M
Rotor (open, grounded, or shorted Test and/or replace. windings) Stator (open, grounded, or shorted windings) Low engine speed causing voltage roll-off Test and/or replace. Check system voltage, frequency and engine model settings. Troubleshoot the engine. No AC output voltage. AC circuit breaker tripping because of short circuit
Check for AC voltage on the generator side of the circuit breaker. If there is AC voltage on the generator side of the breaker, then a problem in the load circuits is causing the line circuit breaker to trip. Check for and correct short circuits or overloading on the load side before resetting the circuit breaker. Reduce the load on the generator set. If the system is equipped with the load control module (LCM), troubleshoot the LCM. Check and adjust the controller settings. Check for loose connections. Check the generator set wiring. Perform separate excitation procedure to isolate the problem to the alternator or the control system. Then troubleshoot the alternator or control system components as follows. Perform separate excitation procedure from alternator service manual. LCM documentation Section 3.6 W/D, Section 8
AC circuit breaker tripping because of overload Controller settings incorrect Controller connections
Alternator S/M
Rotor (open, grounded, or shorted Check voltage and continuity. windings) Stator (open, grounded, or shorted windings)
Note:
I/M = generator set installation manual; O/M = generator set Operation Manual; S/M = service manual; W/D = wiring diagram.
Figure 5-4
TP-6811 4/12
Section 5 Troubleshooting
67
Check wiring and connections. Generator set Installation Verify that cable size and length Manual or accessory module of run comply with the documentation. instructions in the Installation manual. Check generator set battery connections and condition. See Low or no battery voltage above.
Bad connections
Check wiring and connections. Generator set Installation Verify that cable size and length Manual or LCM documentation. of run comply with specifications. Check generator set battery connections and condition. See Low or no battery voltage above.
Date is flashing.
Check battery connections. Check controller connections. Check utility power connection to the generator set terminal block. Reset the time, date, and exercise schedule. Generator set Operation Manual W/D, Section 8
Figure 5-5
68
Section 5 Troubleshooting
TP-6811 4/12
The generator set produces AC voltage by rotating a magnetic field inside the stator windings. This magnetic field is produced by current in the rotor windings (or field). The current is generated in the exciter armature by rotating in the fixed magnetic field produced by permanent magnets attached to the rotor bearing assembly on the back of the alternator. The field current is controlled by the RDC2 controller using a PWM (pulse-width modulated) signal which drives an LED on the stationary LED board (SLB) (mounted under the end cover on the alternator) varying the intensity of the light to the rotating exciter board, the rotating exciter board controls the field current in the rotor based on the intensity of the light received by the photo-detector.
1. 2. 3. 4. 5. 6. 7. 8.
1 7 3 6 4 5 2
Excitation control circuit (3B, 5B) Excitation control stationary LED board (SLB) Rotating photo exciter board Exciter armature Permanent exciter magnets Main field (rotor) Stator windings Sensing leads
Figure 6-2
8 7 1 2 6 5 3 4
This section covers the operation of the alternator excitation and troubleshooting information for low or no voltage output. Before beginning the test procedures, read all safety precautions at the beginning of this manual. Many of the test procedures include additional safety precautions. The spinning exciter and exciter board make measurement of the field voltage and current difficult while the generator is running. However, the alternator and rotating exciter board can be analyzed relatively accurately while the generator is not running. For advanced troubleshooting procedures for the alternator, please refer to the alternator service manual, TP-6783.
1. 2. 3. 4. 5. 6. 7. 8.
Excitation control circuit (3B, 5B) Excitation control stationary LED board (SLB) Rotating photo exciter board Permanent exciter magnets Exciter armature Main field (rotor) Stator windings Sensing leads (11 and 44)
Figure 6-1
TP-6811 4/12
69
Before beginning the troubleshooting steps in this section, verify that the controller is trying to excite the field on the generator. This can be determined by observing that the generator set is in one of the following states:
D Running D Unloaded full speed exercise D Unloaded cycle diagnostic mode (only during the 3
line circuit breaker open, the SLB may not be working correctly. 8. With the generator set running, disconnect P4 from the RDC2 controller and measure the voltage between pins P4--2 (+) and P4--1 (--). If this voltage is greater than 3 VDC, connect an ammeter between pins P4--2 (+) and P4--1 (--) and measure the current that the RDC2 controller can provide. If the current is greater than 50 mA, check the wiring between the RDC2 and the SLB for short circuits or damaged wiring. 9. Reconnect P4 to the RDC2 controller. Disconnect the plug from the SLB and measure the voltage between wire 3B (+) and 5B (--). If this voltage is greater than 3 VDC, connect an ammeter between wire 3B (+) and 5B (--) and measure the current that the RDC2 controller can provide. If this is greater than 50 mA and the generator does not output any voltage with the SLB connected and in the correct position and the line circuit breaker open, the SLB may not be working correctly. 10. If the RDC2 controller is not able to source greater than 3 VDC when P4 is disconnected or is not able to source greater than 50 mA to a ammeter, and the generator is shutting down on undervoltage after starting (indicating that the controller is trying to excite the field), it is possible that the RDC2 controller is damaged. Investigate the wiring from the controller to the SLB and check the SLB carefully to determine the cause of the controller failure.
minute full speed portion of the test) If the generator state is in one of the following states, the controller is deliberately not exciting the alternator field and no voltage is produced:
D Cooldown D Unloaded cycle diagnostic mode (except during
the 3 minute full speed portion of the test) To further isolate the cause of low or no output voltage: 1. Verify that the generator frequency is above the cut-in frequency for the volts/Hz curve. See Section 6.5.3. 2. Verify that the RDC2 controller is configured to output the correct voltage and that it is metering accurately. Check the system voltage setting and the voltage calibration. 3. Open the line circuit breaker to see if the voltage recovers (the generator may be feeding a short circuit). 4. To isolate a controller/voltage regulator problem from an internal alternator problem, perform the alternator manual excitation procedure described in Section 6.2.4. 5. If the alternator is able to produce greater than rated voltage while manually excited, the problem most likely lies in the stationary portion of the alternator excitation control system. If not, proceed with advanced troubleshooting of the alternator. See the alternator service manual, TP-6783. 6. Check the wiring from the controller to the stationary LED board (SLB) on the back of the alternator. 7. Start the generator set and measure the DC voltage between P4--2 (+) and P4--1 (--) on the RDC2 controller while P4 is connected. If this voltage exceeds 3 VDC, remove the end cover and measure the voltage between 3B (+) and 5B (--) at the SLB with the SLB connected. If this is greater than 3 VDC and the generator does not output any voltage with the SLB in the correct position and the
70 Section 6 Component Testing and Adjustment
TP-6811 4/12
6.2.2
damaged. Check the wiring and the SLB to determine the cause of the controller failure. 3. If the overvoltage condition persists with P4 unplugged, check for both AC and DC voltage between 3B (+) and 5B (-) of the disconnected P4. If voltage is found, check the wiring to the SLB. 4. If no voltage is found between 3B (+) and 5B (-), verify that the back cover from the alternator is intact and that no light is reaching the photoreceptor on the rotating exciter board. 5. Refer to the Alternator Service Manual TP-6783 for additional troubleshooting procedures.
Dramatic variations in the alternator voltage (more than 5 VAC) while the generator is operating at a steady load may cause flicker. Connect a flicker lamp to the generator output to determine if the generator is producing flicker. If flicker is observed, it can be caused by any of the following:
D Load Fluctuation D Engine speed fluctuation. Refer to Section 6.6 and
6.2.4
This procedure is also included in the alternator service manual. The following procedure provides information on testing the alternators LED optic board. Certain steps require that the generator set be running. When the generator set is not running, disable the generator set. See the safety precautions listed below. Disconnect all load from the generator set during this test.
high. Try decreasing to 1 to see if erratic fluctuations stop. See Section 6.5.4.
D Incorrect cut-in frequency or slope for the Volts/Hz
curve. Verify that the settings match the factory defaults. See Section 6.5.3, Volts/Hz and Cut-In Frequency.
D Loose connection(s) in wiring to the SLB or RDC2
controller.
WARNING
6.2.3
Overvoltage Condition
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
The alternator field can be overexcited, causing excessive output voltage. If this failure is observed, ensure that the line circuit breaker is open and that no customer loads can be damaged by continued testing of this condition. Do not run the generator set for extended periods of time in an overvoltage condition. To further isolate the cause of an overvoltage condition: 1. Remove the connector from P4 on the RDC2 controller. If the overvoltage conditions clears (the voltage should decay to a few volts), check the voltage sensing wiring and verify the configuration and metering accuracy of the RDC2 controller. Check the system voltage setting and the voltage calibration. 2. If the configuration in the controller is correct and the voltage is being metered accurately (shuts down for overvoltage) the RDC2 controller may be
TP-6811 4/12
71
WARNING
2. Refer to the respective generator set controller operation manual for starting/stopping procedures. With the generator set running at no load, shine a flashlight at the exposed photo transistor on the FRX activator board. See Figure 6-4.
Hazardous voltage. Moving parts. Can cause severe injury or death. 1 Operate the generator set only when all guards and electrical enclosures are in place. Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by turning off the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Testing the photo transistor circuit board. Hazardous voltage can cause severe injury or death. When the end cover is removed, do not expose the photo transistor circuit board mounted on the generator set end bracket to any external light source, as exposure to light causes high voltage. Keep foreign sources of light away from the photo transistor circuit board during testing. Place black electrical tape over the LED on the circuit board before starting the generator set.
TP-6783-3
2 3
Figure 6-4
Note: A flashlight is required for this test of the LED optic board. 1. Remove the junction box panels from the generator end of unit and remove the LED optic board holder/LED optic board. See Figure 6-3.
3. Observe the AC output voltage controller display or connect a voltmeter to the output leads. High AC output voltage indicates the FRX activator board is functioning properly. The fault is likely in the wiring, controller with voltage regulator, or LED optic board as the output voltage should drop to low level when the flashlight is removed. If no output is observed, check the FRX activator board. 4. If high output voltage exists with the flashlight off, stop the generator set and place a small piece of black electrical tape over the photo transistor. Restart the unit.
If the output voltage is reduced, there is a source of external light contamination. STOP the generator set. Find the external light source and eliminate it or block it from reaching the photo transistor. If the output voltage remains high, there is a failure in the FRX activator board.
1. FRX activator board 2. LED optic board holder 3. LED optic board
TP-6783-3
Figure 6-3
72
TP-6811 4/12
5. With the generator set running at no load, approximately 1--2 volts DC should be observed at 3B (+) and 5B (--) at the LED optic board. See Figure 6-5. 6. Shine the flashlight on the photo transistor. The DC voltage reading should drop, showing that the controller with voltage regulator is functioning. If voltages are not observed, check the F3 fuse in the controller and refer to the controller operation and/or service manuals for further information regarding the voltage regulator adjustment and troubleshooting. 7. STOP the generator set.
(-)
KEEP P6 CONNECTED
Operate the generator set only when all guards and electrical enclosures are in place. Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically. (600 volts and under) Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
(+)
TP-6783-3
Figure 6-5
TP-6811 4/12
73
6.5.1
6.5.2
The SiteTech parameters used to adjust the voltage in the following procedures are shown in Figure 6-6 and Figure 6-7.
SiteTech Group
Genset System Configuration Voltage Regulator
Voltage regulation is performed by the controller. The controller monitors generator output voltage and adjusts the excitation current to the rotor. Excitation current control is performed by the patented Kohler Hybrid Voltage Regulator. This regulator consists of a fast-reacting analog inner loop and a slower digital outer loop. The inner loop regulates the average output voltage to a setpoint which is controlled by the outer loop, allowing the voltage to recover very quickly during transient conditions. The outer loop measures the RMS magnitude of the voltage and adjusts the setpoint for the inner loop until the RMS voltage amplitude matches the Voltage Regulator Average Voltage Adjustment setpoint. The Hybrid Voltage Regulator regulates to the average RMS voltage of all three phases on a three-phase generator set. The Hybrid Regulator should require no voltage adjustment, as it regulates the RMS output voltage to the configured output voltage. The Voltage Regulator Average Voltage Adjustment setpoint may require alteration to more closely match the utility voltage at a particular location or to compensate for voltage drop on wiring between the generator and the ATS. The Voltage Regulator Average Voltage Adjustment can be adjusted from the Voltage Regulator menu on the RDC2 controller, or adjusted using SiteTech. See Figure 6-7 and Figure 6-8.
Parameter
Genset System Voltage Average Voltage Adjustment Volts per Hertz Slope Volts per Hertz Cut-in Frequency Voltage Regulator Gain
Figure 6-6
tp6805
1
1. Voltage regulator parameter group
Figure 6-7
74
TP-6811 4/12
Genset System
---->
System Freq: 60 Hz
System Freq: 60 Hz
Press the Up or Down arrow button to change the setting. Press the Select button to save the setting and move to the next screen.
System Battery: 12 V
<----
Return
tp6809
Figure 6-8
Voltage Regulator Voltage Adjustment Using RDC2 Controller4 Menus and Keypad
TP-6811 4/12
75
6.5.3
6.5.4
The Volts/Hz setting for the voltage regulator performs the following functions on the generator:
D Serves as a method for unloading the engine to allow
avoid saturating the field (rotor heating) at low frequencies The slope and cut-in frequency of the volts/Hz curve are set at the factory to allow the generator to meet factory performance standards. They should not be adjusted except under unique circumstances and under direction from a Kohler factory representative. If the slope of the Volts/Hz curve is set too low, the engine will not be unloaded quickly enough to recover from a quick load increase. If the slope is set too high, the voltage will dip dramatically with a quick load increase, which will cause temporary brownouts. The cut-in frequency is typically set to 1 Hz below system frequency so that normally small frequency variations do not cause the voltage to vary. Setting the cut-in frequency further from rated frequency may adversely affect the generators ability to recover frequency after a sharp load increase. See Figure 6-9 for an illustration of the volts/Hz curves for 50 and 60 Hz.
The gain of the inner loop of the hybrid regulator is set at the factory and is not adjustable in the field. The Voltage Regulator Gain listed in SiteTech is for the outer loop. The outer loop is responsible for correcting the setpoint to the inner loop to ensure that the generator output is regulated to the RMS regulator setpoint. The outer loop thus corrects for wave-shape distortion, temperature variations in the inner loop circuitry, inter-board metering variations, etc. Typically the outer loop only adjusts the setpoint to the inner loop on initial startup (battery is first plugged in) and after calibration has changed. At a gain setting of 1, it will take 128 seconds to adjust the voltage output 1%. At a gain setting of 255, the voltage adjustment rate is related to the difference between the target voltage and the measured voltage, but could vary up to 3.1% per second. At lower gains, the voltage may reach the target value very slowly, but the chance of overshoot from the two controller loops fighting is minimal. At higher gains, there is a chance that the outer loop will change the setpoint faster than the inner loop can accommodate, resulting in unstable output voltage. This may show up as slight flicker on a light bulb. Note: The RMS correction outer loop is not active when the controller is in Volts/Hz mode; the last known correction factor, or inner loop setpoint, is used.
Figure 6-9
Volts/Hz Curves
76
TP-6811 4/12
6.6.2
Hunting/Surging
The engine speed regulation gains reside in the engine ECU and are not adjustable. Most Hunting or surging problems are caused by fuel supply pressures that are out of spec, dirty air filters, air intake restriction, etc. If Hunting or surging occurs, verify the following:
D The load is stable (not changing significantly). D The fuel pressure is within the acceptable range both
6.6.1
The default setting for the engine speed adjustment is 50. This gives engine speeds of 1800 RPM for 60 Hz models, and 1500 RPM for 50 Hz models. The setting can be adjusted from 0 to 99. Changing the setting will change the engine speed according to the following formula: (System Frequency x 30) + (Setting -- 50) = RPM Examples: System frequency of 60 Hz, changing the setting to 40: (60 x 30) + (40 -- 50) = 1790 RPM System frequency of 50 Hz, changing the setting to 60: (50 x 30) + (60 -- 50) = 1510 RPM The engine speed gain adjustment has no effect for the Model 48RCL as the engine speed is controlled by the engine ECM.
airflow in or out of the engine compartment. If the hunting/surging persists, refer to the engine service manual for additional troubleshooting procedures. See the List of Related Materials in the Introduction of this manual for the engine service manual part numbers.
TP-6811 4/12
77
1. Engine Speed Adjustment 2. Engine Run Speed Setting (changes automatically with Genset System Frequency) 3. Genset System Frequency Setting (50 or 60 Hz)
Check the high engine compartment temperature sensor by performing the following test procedure. If the sensor does not function as described, replace it. Temperature Sensor Test Procedure 1. Press the OFF button on the controller to stop the generator set and allow the generator set to cool.
Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools. Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation.
2. Disconnect the temperature sensor and use an ohmmeter to measure the resistance across the sensor. The sensor resistance varies with temperature and should be within the values shown in Figure 6-11. 3. If the resistance is very low (indicating a short circuit) or very high (indicating an open circuit), replace the sensor.
Temperature, _C (_F) 30 (86) 100 (212) Resistance, Ohms 2100--2400 180--200
WARNING
Hazardous voltage. Moving parts. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set. Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
GM69754
6.7.1
6.7.2
The temperature sensor is used to monitor engine compartment air temperature for the cooling fan operation. See the service views in Section 1.7 for the air temperature sensor location. The cooling fan operation is temperature-dependent. See Section 4.10 for information about fan operation.
Other switches and sensors, such as the low oil pressure sensor, are installed on the engine and communicate with the engine ECM. Refer to the engine service manuals for troubleshooting and service information.
TP-6811 4/12
79
allowable inlet pressure for the secondary regulator. The secondary regulator is factory-installed on the generator set engine and is designed for a maximum inlet pressure of 2.7 kPa (6 oz./in.2) or 280 mm (11 in.) water column. This regulator is electronically controlled. Do not attempt to adjust the fuel mixture or engine speed by adjusting the regulators.
Explosive fuel vapors. Can cause severe injury or death. Use extreme care when handling, storing, and using fuels.
The fuel system on the engine includes the electronic fuel pressure regulator and mixer. Refer to the engine service manuals for troubleshooting and repair of the engines fuel system. Note: The Integrated Electronic Pressure Regulator (IEPR) and air/fuel mixer are specially calibrated emission-control devices. Do not adjust the IEPR or the air/fuel mixer. Refer to the troubleshooting instructions in Section 5, Troubleshooting, to identify generator set operation problems that may be caused by an inadequate fuel supply, incorrect adjustments, or damaged fuel system components.
The fuel supplier provides and maintains manual shut-off valves and the primary regulator. See the generator set installation manual for fuel pipe size recommendations. Verify that the fuel system capacity is adequate to supply the generator set plus all other gas appliances. The typical gaseous fuel system uses two regulators. The primary regulator reduces the line pressure to an
4 3
1. 2. 3. 4.
Integrated electronic pressure regulator (IEPR) Air/fuel mixer Fuel inlet connection Fuel solenoid valves (2)
GM78523
80
TP-6811 4/12
6.8.1
6.8.3
Two 12 VDC solenoid valves are mounted upstream of the engine on the generator set skid. See Figure 6-13. The fuel solenoid valves provide automatic fuel on/off control. See Figure 6-13. The engine starting battery powers the solenoid valve and the engine starting controls open the valves when the engine cranks or runs. Fuel Valve Operation Test Procedure 1. Disconnect the positive (+) battery lead from the gas valve terminal. 2. Apply 12 VDC to the gas valve terminal and listen for an audible click, indicating that the valve actuates. 3. Replace the gas valve if it does not actuate in step 2.
Note: The Integrated Electronic Pressure Regulator (IEPR) and air/fuel mixer are specially calibrated emission-control devices. Do not adjust the IEPR or the air/fuel mixer. Check the connections to the fuel solenoid valves to verify that the fuel system is set up for the type of fuel that will be used. See Figure 6-13 for the location of the fuel solenoid valves. To change the fuel type, change the connection to the fuel solenoid valves as described below and shown in Figure 6-15. LP Connections:
D Disconnect lead 73A from the fuel valve. D Connect lead 73B to the fuel valve. D Connect lead 65 to lead N3 (ground).
6.8.2
Connect a pressure gauge or manometer to the port on the bottom of the second (downstream) fuel solenoid valve to measure the fuel pressure to the engine. See Figure 6-13 and Figure 6-14. Measure the fuel pressure with the generator set running at rated load. The fuel pressure should be 5--11 in. water column or 1.2--2.7 kPa. Contact the fuel supplier if the inlet pressure is not within the specified range.
GM79871
TP-6811 4/12
81
Nameplate Converting the fuel will change the generator set rating. See the generator set specification sheet for ratings with natural gas and LP. Order a new nameplate with the updated rating and fuel information from an authorized distributor/dealer, if necessary. Provide the following information from the original nameplate:
D D D D D Model Number Spec Number Serial Number Fuel (original and new) kW D D D D kVA Amps Volts Hz
Fuel Type Setting Change the fuel type setting on the RDC2 controller to match the new fuel type. The fuel type setting affects the generator set power rating setting in the controller, which in turn affects the load add and load shed settings for the optional Load Control Module (LCM). Use the RDC2 controller menus or a personal computer (laptop) with Kohler SiteTech software to change the fuel type. On controllers with firmware version 4.5 or higher, the fuel type is located in the Genset System menu. In SiteTech, the fuel type is located in the Genset System Configuration group.
82
TP-6811 4/12
Section 7 Disassembly/Reassembly
7.1 Introduction
This section provides information about removing the enclosure and other components to gain access to the alternator. Refer to the alternator service manual for instructions to disassemble and reassemble the alternator. Before beginning the disassembly procedure, carefully read all safety precautions at the beginning of this manual. 2. Shut off the fuel supply. Disconnect the fuel system if necessary to tilt the generator set. Ventilate the area to clear fumes. 3. Allow the generator set and engine to cool. 4. Verify that any hoists or lifting devices used in the disassembly or reassembly procedure are rated for the weight of the generator set.
7.3 Enclosure
See Figure 7-1 for an illustration of enclosure parts. Remove enclosure panels as necessary to access the alternator. Note: When reassembling the enclosure, do not over-tighten the screws into the aluminum enclosure panels.
1 8 7
7 3 6
1. 2. 3. 4. 5. 6. 7. 8. Roof Front panel Exhaust mounting bracket Silencer Front panel Tool, latch opening Door End panel assembly
4 5
Note: Maximum torque for screws into aluminum enclosure panels: 5.7 Nm (50 in. lbs.).
GM82895_A
Figure 7-1
Enclosure
TP-6811 4/12
Section 7 Disassembly/Reassembly 83
Lower access panel removed. 1. 2. 3. 4. Connection box RDC2 controller Mounting bolts, qty. 4 Circuit breaker
tp6809
Figure 7-2
Connection box
Section 7 Disassembly/Reassembly 84
TP-6811 4/12
GM78526
GM78527
1. Air cleaner assembly. Disconnect and remove if necessary. 2. Cooling fan relay/fuse box and resistor. Disconnect as needed.
Figure 7-3
TP-6811 4/12
Section 7 Disassembly/Reassembly 85
7.6 Alternator
The alternator is shown in Figure 7-4. Note: Refer to the alternator service manual for instructions to disassemble and reassemble the alternator.
5 2
1. 2. 3. 4. 5.
Junction box top cover Alternator adapter Fan guard Alternator assembly Junction box
GM78543_B
Figure 7-4
Section 7 Disassembly/Reassembly 86
TP-6811 4/12
Figure 8-1
TP-6811 4/12
Figure 8-2
TP-6811 4/12
Figure 8-3
TP-6811 4/12
Figure 8-4
TP-6811 4/12
Figure 8-5
TP-6811 4/12
Figure 8-6
TP-6811 4/12
Figure 8-7
TP-6811 4/12
Notes
TP-6811 4/12
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ABDC AC A/D ADC adj. ADV Ah AHWT AISI ALOP alt. Al ANSI AO APDC API approx. AQMD AR AS ASE ASME assy. ASTM ATDC ATS auto. aux. avg. AVR AWG AWM bat. BBDC BC BCA BCI BDC BHP blk. blk. htr. BMEP bps br. BTDC Btu Btu/min. C cal. CAN CARB CB cc CCA ccw. CEC cert. cfh ampere after bottom dead center alternating current analog to digital advanced digital control; analog to digital converter adjust, adjustment advertising dimensional drawing amp-hour anticipatory high water temperature American Iron and Steel Institute anticipatory low oil pressure alternator aluminum American National Standards Institute (formerly American Standards Association, ASA) anticipatory only Air Pollution Control District American Petroleum Institute approximate, approximately Air Quality Management District as required, as requested as supplied, as stated, as suggested American Society of Engineers American Society of Mechanical Engineers assembly American Society for Testing Materials after top dead center automatic transfer switch automatic auxiliary average automatic voltage regulator American Wire Gauge appliance wiring material battery before bottom dead center battery charger, battery charging battery charging alternator Battery Council International before dead center brake horsepower black (paint color), block (engine) block heater brake mean effective pressure bits per second brass before top dead center British thermal unit British thermal units per minute Celsius, centigrade calorie controller area network California Air Resources Board circuit breaker cubic centimeter cold cranking amps counterclockwise Canadian Electrical Code certificate, certification, certified cubic feet per hour cubic feet per minute center of gravity cubic inch displacement centerline centimeter complementary metal oxide substrate (semiconductor) cogen. cogeneration com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CRT cathode ray tube CSA Canadian Standards Association CT current transformer Cu copper cUL Canadian Underwriters Laboratories CUL Canadian Underwriters Laboratories cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dB(A) decibel (A weighted) DC direct current DCR direct current resistance deg., degree dept. department DFMEA Design Failure Mode and Effects Analysis dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung e. V. (also Deutsche Industrie Normenausschuss) DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator E, emer. emergency (power source) ECM electronic control module, engine control module EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems Association EIA Electronic Industries Association EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection Agency EPS emergency power system ER emergency relay ES engineering special, engineered special ESD electrostatic discharge cfm CG CID CL cm CMOS est. E-Stop etc. exh. ext. F fglass. FHM fl. oz. flex. freq. FS ft. ft. lb. ft./min. ftp g ga. gal. gen. genset GFI GND, gov. gph gpm gr. GRD gr. wt. HxWxD HC HCHT HD HET hex Hg HH HHC HP hr. HS hsg. HVAC HWT Hz IC ID IEC IEEE IMS in. in. H2O in. Hg in. lb. Inc. ind. int. int./ext. I/O IP ISO J JIS estimated emergency stop et cetera (and so forth) exhaust external Fahrenheit, female fiberglass flat head machine (screw) fluid ounce flexible frequency full scale foot, feet foot pounds (torque) feet per minute file transfer protocol gram gauge (meters, wire size) gallon generator generator set ground fault interrupter ground governor gallons per hour gallons per minute grade, gross equipment ground gross weight height by width by depth hex cap high cylinder head temperature heavy duty high exhaust temp., high engine temp. hexagon mercury (element) hex head hex head cap horsepower hour heat shrink housing heating, ventilation, and air conditioning high water temperature hertz (cycles per second) integrated circuit inside diameter, identification International Electrotechnical Commission Institute of Electrical and Electronics Engineers improved motor starting inch inches of water inches of mercury inch pounds incorporated industrial internal internal/external input/output iron pipe International Organization for Standardization joule Japanese Industry Standard
TP-6811 4/12
Appendix 95
kilo (1000) kelvin kiloampere kilobyte (210 bytes) Kohler communication protocol kilogram kilograms per square centimeter kgm kilogram-meter kg/m3 kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, k kilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb. pound, pounds lbm/ft3 pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display ld. shd. load shed LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side Lwa sound power level, A weighted LWL low water level LWT low water temperature m meter, milli (1/1000) M mega (106 when used with SI units), male m3 cubic meter m3/hr. cubic meters per hour m3/min. cubic meters per minute mA milliampere man. manual max. maximum MB megabyte (220 bytes) MCCB molded-case circuit breaker MCM one thousand circular mils meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, m milliohm MOhm, Mmegohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard ms millisecond m/sec. meters per second MTBF mean time between failure
k K kA KB KBus kg kg/cm2
mean time between overhauls mounting Motoren-und Turbinen-Union megawatt milliwatt microfarad normal (power source) not available, not applicable natural gas National Bureau of Standards normally closed National Electrical Code National Electrical Manufacturers Association NFPA National Fire Protection Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillipsr head Crimptiter (screw) PHH Phillipsr hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only memory psi pounds per square inch psig pounds per square inch gauge pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency) power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head RHM round head machine (screw) rly. relay
rms rnd. ROM rot. rpm RS RTU RTV RW SAE scfm SCR s, sec. SI SI/EO sil. SN SNMP SPDT SPST spec specs sq. sq. cm sq. in. SS std. stl. tach. TD TDC TDEC TDEN TDES TDNE TDOE TDON temp. term. THD TIF TIR tol. turbo. typ. UF UHF UL UNC UNF univ. US UV V VAC VAR VDC VFD VGA VHF W WCR w/ w/o wt. xfmr
root mean square round read only memory rotate, rotating revolutions per minute right side remote terminal unit room temperature vulcanization read/write Society of Automotive Engineers standard cubic feet per minute silicon controlled rectifier second Systeme international dunites, International System of Units side in/end out silencer serial number simple network management protocol single-pole, double-throw single-pole, single-throw specification specification(s) square square centimeter square inch stainless steel standard steel tachometer time delay top dead center time delay engine cooldown time delay emergency to normal time delay engine start time delay normal to emergency time delay off to emergency time delay off to normal temperature terminal total harmonic distortion telephone influence factor total indicator reading tolerance turbocharger typical (same in multiple locations) underfrequency ultrahigh frequency Underwriters Laboratories, Inc. unified coarse thread (was NC) unified fine thread (was NF) universal undersize, underspeed ultraviolet, undervoltage volt volts alternating current voltampere reactive volts direct current vacuum fluorescent display video graphics adapter very high frequency watt withstand and closing rating with without weight transformer
96 Appendix
TP-6811 4/12
Steps for common hardware application: 1. Determine entry hole type: round or slotted. 2. Determine exit hole type: fixed female thread (weld nut), round, or slotted. For round and slotted exit holes, determine if hardware is greater than 1/2 inch in diameter, or 1/2 inch in diameter or less. Hardware that is greater than 1/2 inch in diameter takes a standard nut and SAE washer. Hardware 1/2 inch or less in diameter can take a properly torqued whiz nut or spiralock nut. See Figure 2. 3. Follow these SAE washer rules after determining exit hole type: a. Always use a washer between hardware and a slot. b. Always use a washer under a nut (see 2 above for exception). c. Use a washer under a bolt when the female thread is fixed (weld nut). 4. Refer to Figure 2, which depicts the preceding hardware configuration possibilities.
3
G-585
1. 1/2 of bolt diameter 2. Min. 1 full thread beyond top of nut 3. Below top of nut
Figure 1
G-585
1. 2. 3. 4. 5. 6.
Cap screw Entry hole types Standard nut and SAE washer Whiz nut or spiralock: up to 1/2 in. dia. hardware Weld nuts: above 1/2 in. dia. hardware Exit hole types
Figure 2
TP-6811 4/12
Appendix
97
Size
8-32 10-24 10-32 1/4-20 1/4-28 5/16-18 5/16-24 3/8-16 3/8-24 7/16-14 7/16-20 1/2-13 1/2-20 9/16-12 9/16-18 5/8-11 5/8-18 3/4-10 3/4-16 1-8 1-12
Grade 5
2.3 3.6 3.6 10.8 12.2 21.7 23.1 38.0 42.0 60.0 68.0 92.0 103.0 133.0 148.0 183.0 208.0 325.0 363.0 721.0 789.0 (20) (32) (32) (96) (108) (192) (204) (28) (31) (44) (50) (68) (76) (98) (109) (135) (153) (240) (268) (532) (582)
Grade 8
14.9 16.3 29.8 32.5 53.0 60.0 85.0 95.0 130.0 146.0 187.0 209.0 259.0 293.0 458.0 513.0 1109.0 1214.0 (132) (144) (264) (288) (39) (44) (63) (70) (96) (108) (138) (154) (191) (216) (338) (378) (818) (895)
See Note 3
Metric Fasteners Torque Specifications, Measured in Nm (ft. lb.) Assembled into Assembled into Cast Iron or Steel Aluminum Grade 5.8 or 8.8 Grade 5.8 Grade 8.8 Grade 10.9 Size (mm)
M6 M8 M8 x 1.00 x 1.25 x 1.00 6.2 15.0 16.0 30.0 31.0 53.0 56.0 83.0 87.0 127.0 132.0 179.0 189.0 (4.6) (11) (11) (22) (23) (39) (41) (61) (64) (94) (97) (132) (140) 9.5 23.0 24.0 45.0 47.0 80.0 85.0 126.0 133.0 194.0 201.0 273.0 289.0 (7) (17) (18) (34) (35) (59) (63) (93) (98) (143) (148) (201) (213) 13.6 33.0 34.0 65.0 68.0 115.0 122.0 180.0 190.0 278.0 287.0 390.0 413.0 (10) (24) (25) (48) (50) (85) (90) (133) (140) (205) (212) (288) (305) See Note 3
M10 x 1.50 M10 x 1.25 M12 x 1.75 M12 x 1.50 M14 x 2.00 M14 x 1.50 M16 x 2.00 M16 x 1.50 M18 x 2.50 M18 x 1.50
Notes: 1. The torque values above are general guidelines. Always use the torque values specified in the service manuals and/or assembly drawings when they differ from the above torque values. 2. The torque values above are based on new plated threads. Increase torque values by 15% if non-plated threads are used. 3. Hardware threaded into aluminum must have either two diameters of thread engagement or a 30% or more reduction in the torque to prevent stripped threads. 4. Torque values are calculated as equivalent stress loading on American hardware with an approximate preload of 90% of the yield strength and a friction coefficient of 0.125.
98
Appendix
TP-6811 4/12
Nuts
Nut Styles
Hex Head Lock or Elastic Square Cap or Acorn Wing
Hardness Grades
American Standard
Grade 2 Grade 5 Grade 8 Grade 8/9 (Hex Socket Head)
Metric
Number stamped on hardware; 5.8 shown
5.8
Washers
Washer Styles
Plain Split Lock or Spring Spring or Wave External Tooth Lock
Drive Styles
Hex Internal Tooth Lock Hex and Slotted Internal-External Tooth Lock Phillipsr Slotted Hex Socket Allent head screw is a trademark of Holo-Krome Co. Phillipsr screw is a registered trademark of Phillips Screw Company.
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts)
1/4-20 x 1 Length In Inches (Screws and Bolts) Threads Per Inch Major Thread Diameter In Fractional Inches Or Screw Number Size
Plain Washers
9/32 x 5/8 x 1/16 Thickness External Dimension Internal Dimension
Lock Washers
5/8 Internal Dimension
TP-6811 4/12
Appendix 99
American Standard
Part No. Dimensions Hex Head Bolts (Grade 5)
X-465-17 X-465-6 X-465-2 X-465-16 X-465-18 X-465-7 X-465-8 X-465-9 X-465-10 X-465-11 X-465-12 X-465-14 X-465-21 X-465-25 X-465-20 X-125-33 X-125-23 X-125-3 X-125-31 X-125-5 X-125-24 X-125-34 X-125-25 X-125-26 230578 X-125-29 X-125-27 X-125-28 X-125-22 X-125-32 X-125-35 X-125-36 X-125-40 X-125-43 X-125-44 X-125-30 X-125-39 X-125-38 X-6238-2 X-6238-10 X-6238-3 X-6238-11 X-6238-4 X-6238-5 X-6238-1 X-6238-6 X-6238-17 X-6238-7 X-6238-8 X-6238-9 X-6238-19 X-6238-12 X-6238-20 X-6238-13 X-6238-18 X-6238-25 1/4-20 x .38 1/4-20 x .50 1/4-20 x .62 1/4-20 x .75 1/4-20 x .88 1/4-20 x 1.00 1/4-20 x 1.25 1/4-20 x 1.50 1/4-20 x 1.75 1/4-20 x 2.00 1/4-20 x 2.25 1/4-20 x 2.75 1/4-20 x 5.00 1/4-28 x .38 1/4-28 x 1.00 5/16-18 x .50 5/16-18 x .62 5/16-18 x .75 5/16-18 x .88 5/16-18 x 1.00 5/16-18 x 1.25 5/16-18 x 1.50 5/16-18 x 1.75 5/16-18 x 2.00 5/16-18 x 2.25 5/16-18 x 2.50 5/16-18 x 2.75 5/16-18 x 3.00 5/16-18 x 4.50 5/16-18 x 5.00 5/16-18 x 5.50 5/16-18 x 6.00 5/16-18 x 6.50 5/16-24 x 1.75 5/16-24 x 2.50 5/16-24 x .75 5/16-24 x 2.00 5/16-24 x 2.75 3/8-16 x .62 3/8-16 x .75 3/8-16 x .88 3/8-16 x 1.00 3/8-16 x 1.25 3/8-16 x 1.50 3/8-16 x 1.75 3/8-16 x 2.00 3/8-16 x 2.25 3/8-16 x 2.50 3/8-16 x 2.75 3/8-16 x 3.00 3/8-16 x 3.25 3/8-16 x 3.50 3/8-16 x 3.75 3/8-16 x 4.50 3/8-16 x 5.50 3/8-16 x 6.50
Dimensions
1-8 6-32 8-32 10-24 10-32 1/4-20 1/4-28 5/16-18 5/16-24 3/8-16 3/8-24 7/16-14 1/2-13 7/16-20 1/2-20 5/8-11 3/4-10 1/2-20
Type
Standard Whiz Whiz Whiz Whiz Spiralock Spiralock Spiralock Spiralock Spiralock Spiralock Spiralock Spiralock Spiralock Spiralock Standard Standard Standard
X-25-46 .125 X-25-9 .156 X-25-48 .188 X-25-36 .219 X-25-40 .281 X-25-85 .344 X-25-37 .406 X-25-34 .469 X-25-26 .531 X-25-15 .656 X-25-29 .812 X-25-127 1.062
100 Appendix
TP-6811 4/12
Metric
Hex head bolts are hardness grade 8.8 unless noted. Part No. Dimensions Hex Head Bolts (Partial Thread)
M931-05055-60 M931-06040-60 M931-06055-60 M931-06060-60 M931-06060-SS M931-06070-60 M931-06070-SS M931-06075-60 M931-06090-60 M931-06145-60 M931-06150-60 M931-08035-60 M931-08040-60 M931-08045-60 M931-08050-60 M931-08055-60 M931-08055-82 M931-08060-60 M931-08070-60 M931-08070-82 M931-08075-60 M931-08080-60 M931-08090-60 M931-08095-60 M931-08100-60 M931-08110-60 M931-08120-60 M931-08130-60 M931-08140-60 M931-08150-60 M931-08200-60 M931-10040-82 M931-10040-60 M931-10045-60 M931-10050-60 M931-10050-82 M931-10055-60 M931-10060-60 M931-10065-60 M931-10070-60 M931-10080-60 M931-10080-82 M931-10090-60 M931-10090-82 M931-10100-60 M931-10110-60 M931-10120-60 M931-10130-60 M931-10140-60 M931-10180-60 M931-10235-60 M931-10260-60 M960-10330-60 M931-12045-60 M960-12050-60 M960-12050-82 M931-12050-60 M931-12050-82 M931-12055-60 M931-12060-60 M931-12060-82 M931-12065-60 M931-12075-60 M931-12080-60 M931-12090-60 M931-12100-60 M931-12110-60 M5-0.80 x 55 M6-1.00 x 40 M6-1.00 x 55 M6-1.00 x 60 M6-1.00 x 60 M6-1.00 x 70 M6-1.00 x 70 M6-1.00 x 75 M6-1.00 x 90 M6-1.00 x 145 M6-1.00 x 150 M8-1.25 x 35 M8-1.25 x 40 M8-1.25 x 45 M8-1.25 x 50 M8-1.25 x 55 M8-1.25 x 55* M8-1.25 x 60 M8-1.25 x 70 M8-1.25 x 70* M8-1.25 x 75 M8-1.25 x 80 M8-1.25 x 90 M8-1.25 x 95 M8-1.25 x 100 M8-1.25 x 110 M8-1.25 x 120 M8-1.25 x 130 M8-1.25 x 140 M8-1.25 x 150 M8-1.25 x 200 M10-1.25 x 40* M10-1.50 x 40 M10-1.50 x 45 M10-1.50 x 50 M10-1.25 x 50* M10-1.50 x 55 M10-1.50 x 60 M10-1.50 x 65 M10-1.50 x 70 M10-1.50 x 80 M10-1.25 x 80* M10-1.50 x 90 M10-1.50 x 90* M10-1.50 x 100 M10-1.50 x 110 M10-1.50 x 120 M10-1.50 x 130 M10-1.50 x 140 M10-1.50 x 180 M10-1.50 x 235 M10-1.50 x 260 M10-1.25 x 330 M12-1.75 x 45 M12-1.25 x 50 M12-1.25 x 50* M12-1.75 x 50 M12-1.75 x 50* M12-1.75 x 55 M12-1.75 x 60 M12-1.75 x 60* M12-1.75 x 65 M12-1.75 x 75 M12-1.75 x 80 M12-1.75 x 90 M12-1.75 x 100 M12-1.75 x 110
TP-6811 4/12
Appendix 101
Metric, continued
Part No. Hex Nuts
M934-03-50 M934-04-50 M934-04-B M934-05-50 M934-06-60 M934-06-64 M6923-06-80 M982-06-80 M934-08-60 M6923-08-80 M982-08-80 M934-10-60 M934-10-60F M6923-10-80 M6923-10-62 M982-10-80 M934-12-60 M934-12-60F M6923-12-80 M982-12-80 M982-14-60 M6923-16-80 M982-16-80 M934-18-80 M982-18-60 M934-20-80 M982-20-80 M934-22-60 M934-24-80 M982-24-60 M934-30-80
Dimensions
M3-0.50 M4-0.70 M4-0.70 M5-0.80 M6-1.00 M6-1.00 M6-1.00 M6-1.00 M8-1.25 M8-1.25 M8-1.25 M10-1.50 M10-1.25 M10-1.50 M10-1.50 M10-1.50 M12-1.75 M12-1.25 M12-1.75 M12-1.75 M14-2.00 M16-2.00 M16-2.00 M18-2.5 M18-2.50 M20-2.50 M20-2.50 M22-2.50 M24-3.00 M24-3.00 M30-3.50
Type
Standard Standard Brass Standard Standard Std. (green) Spiralock Elastic Stop Standard Spiralock Elastic Stop Standard Standard Spiralock Spiralock[ Elastic Stop Standard Standard Spiralock Elastic Stop Elastic Stop Spiralock Elastic Stop Standard Elastic Stop Standard Elastic Stop Standard Standard Elastic Stop Standard
ID
3.2 4.3 5.3 6.4 8.4 10.5 13.0 15.0 17.0 19.0 21.0 25.0
102 Appendix
TP-6811 4/12
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-457-4441, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
TP-6811 4/12
E 2012 by Kohler Co. All rights reserved.