current for specified time is given by A= (I/8.5)x(t/) A= (I/13)x(t/) A= (I/4.5)x(t/) A= (I/2.5)x(t/) For Aluminium For Copper For Iron For Lead
Where A=Cross sectional Area in Sqmm I=Short Circuit Current in Amps t=Withstand time in sec 8.5= Constant for Aluminium 13= Constant for Copper 4.5= Constant for Iron 2.5= Consatnt for Lead =Temprature rise in Degree Celcius 180 Degree Celcius upto 2 Sec for Uninsulated Conductors 120 Degree Celcius upto 2 Sec for insulated Conductors 215 Degree Celcius above 2 Sec for Uninsulated Conductors 145 Degree Celcius above 2 Sec for insulated Conductors I in kA 50 16 22.5 35 50 70 85 t in Sec 1 1 1 1 1 1 1 Temp rise 285 180 215 180 180 215 180 A=in Sqmm Aluminium Iron 348 658 140 265 181 341 307 580 438 828 562 1061 745 1408
EARTH STRIP SIZE CALCULATION AS PER IS 3043 PAGE (29-31) Qc=Volumetric haet capacity of conductor material(J/Degree centrigade mm3) B=Reciprocal of temprature coefficient of resistivity at 0 degree centrigade for the conductor(degree centrigade) 20=Electrical resisitivity of conductor material at 20 degreee centrigade(ohm-mm) i=Initial Temprature of conductor(degree centrigade) t=Final Temprature of conductor(degree centrigade) The minimum cross-sectional area of earthstrip size required to withstand specified short-circuit current for specified time is given by A= (Ixt)/k Where A=Cross sectional Area in Sqmm I=Short Circuit Current in Amps t=Withstand time in sec k= Constant Where k can be calculated as below
k= ((Qc*(B+20))/20)LN(1+((t-1)/(B+1)))
Aluminium
0.025
234.50
0.0001724
228
0.00028264
Steel
0.0038
202
0.000138
325 40 126.0548519
500 40 80.68683215
Copper
lead
Steel