Introduction
This lecture will primarily cover the basic principles of ventilation, the main focus being on natural strategies. A good introduction to the topic can also be found in McMullan (2007, pp. 73-77). This lecture will cover the following topics: Why ventilation is needed How much ventilation is needed, i.e. ventilation rates Approaches to ventilation Energy use Thermal Comfort Wind effects on ventilation Methods of ventilation Infiltration Modelling ventilation
* Revised and edited by Sam Saville (2008), Kelvin Mason (2008), Frances Hill and Kate Millbank (2011).
21/10/2011 12:13:52
too much results in an energy loss with consequent cost and possibly carbon emission penalties. The Passivhaus website provides a good overview of Pas sivhaus design principles and construction standards. In practice, it is very difficult if not impossible to prevent air movement in and out of buildings, particularly in older designs. This process of unwanted ventilation is termed air infiltration. Many building materials and most constructions are somewhat permeable to infiltration. Though infiltration through building elements may be small, over a large area this this can amount to significant heat loss. Gaps, cracks, chimneys and ill-fitting components are all pathways for air infiltration. Modern buildings generally have better control over ventilation than older ones. However in the drive towards improving energy performance care must be taken to avoid hermetically sealing indoor spaces. Typically, buildings are designed on the principle build tight and ventilate right in order to provide building occupants with a balance of good air quality, comfortable conditions and efficient use of energy.
CIBSE have published their Guide B: Heating, Ventilating, Air Conditioning and Refrigeration report, which includes details on ventilation approaches, ventilation rates and how to assess ventilation requirements.
Progressive building designs find better ways of achieving this balance. The Passive House (Passivhaus) concept for example, is based on the principle of achieving a very low energy building with limited air infiltration (0.6 or less air changes per hour). Instead Passivhaus designs rely on a controlled ventilation strategy using mechanical ventilation with heat recovery (MVHR). This system provides sufficient fresh air to the indoor environment whilst also reducing the energy required to heat a property. It does this by pre-heating any incoming fresh air with recovered heat energy from exhaust stale air using a heat exchanger.
Ventilation rates
All occupied spaces need to be ventilated. Ventilation rates depend on the occupancy and type of building. Details for different building types and different occupancy levels can be obtained from the UK Chartered Institution of Building Services Engineers guide (Guide B: Heating,
For a guide to typical ventilation requirements see Environmental Science in Building (sixth edition) by Randall McMullan. Chapter 4 Air Control in Buildings, pp. 74
Table 1: Ventilation rates according to building use. Source: CIBSE Knowledge Series KS6: Comfort
Building type
Domestic habitable rooms Domestic bathrooms Kitchens
Ventilation rate
21/10/2011 12:13:53
Ventilating, Air Conditioning and Refrigeration), although there is a fee for downloading the publication. For a guide to typical ventilation requirements see McMullan (2007, p74). Part F of the Building Regulations also gives guidance for achieving adequate IAQ levels in the UK. Table 1 summarises some of the main ventilation requirements for different spaces. These requirements are for people alone. Additional ventilation may be needed for any process that produces pollutants or heat, as Figure 1 shows. The units for expressing ventilation rate are: Air changes per hour (ACH) which, logically enough, is simply the number of times the air in a space is changed each hour. The occupancy ventilation rate is measured in litres per second per person, which is used to specify ventilation rates in spaces that may vary in size but have known and relatively high occupancy levels (such as a school) and are largely mechanically ventilated.
The ventilation rate is related to the air change rate by the following equation: Vr = V ACH 1000 3600 where Vr = ventilation rate (l/s) V = volume of indoor space (m3) ACH = air change per hour 3600 = seconds in an hour 1000 = litres per cubic CM The recommended fresh air ventilation requirements for spaces with high occupancy levels cause problems in naturally ventilated buildings in cold climates in winter. When the air is cold outside, high ventilation rates mean an energy penalty and heat recovery is not usually feasible for naturally ventilated spaces. Moreover, the large volumes of incoming cold air are also likely to cause thermal discomfort. In such cases, controlled mechanical ventilation generally gives a better solution. The inverse parallel problem can occur in hot climates, where the air change rate suggested by high occupancy can result in the building overheating.
21/10/2011 12:13:53
Approaches to ventilation
By definition, mechanical ventilation, which can vary from a simple fan to full air conditioning, involves the use of energy, usually by means of electricity. Electricity is generally an expensive form of energy and in most situations its generation results in carbon emissions, contributing to the problem of climate change. Carefully designed, natural processes can provide ventilation at low or zero running costs. Natural ventilation is often considered to be the most energy efficient and healthy solution. It is a fundamental part of passive design, which involves the integration of daylight, thermal mass, insulation and solar radiation into the overall concept of a building. In some situations natural ventilation strategies will need extra consideration due to: Noise infiltration in urban areas - research into this suggests balconies can attenuate some noise from street canyons (see Wilson et al, 2005). Health and Safety: the height of windows might be an issue for health and safety and security. Also smoke will follow ventilation paths, so fire strategies need consideration. The majority of contemporary approaches to ventilation, particularly in non-domestic buildings, tend to opt for hybrid approaches. Incorporating some mixture of natural and artificial ventilation is known as mixed mode. This could mean using natural ventilation in summer and mechanical during winter. Mixed-mode often represents the most energy efficient solution to ventilation requirements. Figures 2 and 3 illustrate examples of the different ventilation techniques. The youngest air is nearest the supply and, for efficient air distribution, the oldest air should be nearest the exhaust.
Seminar Discussion Point: Is natural or mechanical ventilation the way forward for sustainable buildings of the future that are trying to balance high levels of energy efficiency with adequate ventilation and internal air quality?
21/10/2011 12:13:53
21/10/2011 12:13:54
Figure 4: Variation in ventilation heat loss for a typical factory in relation to transmission losses through the fabric and infiltration
21/10/2011 12:13:54
21/10/2011 12:13:55
21/10/2011 12:13:55
Note that forms such as trees and walls can be used to provide shelter, creating areas of positive or negative pressure. Pressure gradients across the buildings can facilitate natural ventilation if required.
21/10/2011 12:13:56
Pressure coefficients
We have seen that the pressure at any point on a building envelope depends on building form and local topography. It can be calculated for a given wind speed and direction by using the pressure coefficient (Cp). This is defined as the ratio of the dynamic pressure (Pd) on the envelope of a building, to the pressure at the wind speed reference height, effectively the static pressure (Ps). The pressure coefficient is normally only derived from wind tunnel tests. The value of Cp. will be positive on the windward side of the building and negative on the leeward side, as shown in Figure 10. The pressure difference P across a building due to wind can be calculated using: P = 0.5v2 (Cp1 - Cp2) Where Cp1 and Cp2 are the pressure coefficients for the windward and leeward sides of the building. For an example of this please refer to appendix A (2) Ventilation Calculations.
Figure 10: Windward and leeward pressures
H o m e b uil ding an d Renovation Magazine provide a useful summary of wind assisted passive stack ventilation at BedZED, whilst BDSP (environmental consultants for Londons Iconic Gherkin building designed by Norman Foster), feature some useful modelling images of passive stack ventilation and air flow (click on Projects Highrise 30 St Mary Axe).
Here is a YouTube clip showing airflow modelling for Norman Fosters Swiss Re building (otherwise know as the Gherkin or 30 St Mary Axe).
Another good description of the passive stack effect can be found on the Green Building Advisor website
21/10/2011 12:13:57
21/10/2011 12:13:57
12 Lecture: Principles of Natural Ventilation, Module A3/ CEM 160, MSc: AEES DL
21/10/2011 12:13:58
MSc: AEES DL, Module A3 /CEM 160, Lecture: Principles of Natural Ventilation 13
21/10/2011 12:14:04
Solar Chimneys Figure 14 shows an example of a solar chimney. Solar chimneys can be constructed in a narrow, vertical passage, such as a conventional chimney previously used for expelling smoke. An absorber, typically metal painted with a selective black coating, is situated behind a glazed front that is exposed to solar radiation. The chimney space is well insulated from the house. For the device to work, the chimney must terminate above the roof level. A rotating metal turbine is constructed with an integral opening that faces away from the prevailing winds. Thus, heated air can exhaust without being blown back down the chimney. The rotating turbine increases the flow of air due to the stack effect. A similar principle is adopted by the evaporative downdraft cooling tower (Figure 15) which is closely related to the solar chimney. Rather than rely on the process of hot air rising to create passive stack effect, evaporative downdraft cooling uses the process of evaporation from water (present at the top of the cooling tower) to cool incoming air and draw it down into the building. This can offer a good cooling strategy and alternative to air conditioning in hot climates.
Figure 15: Passive Downdraft Cooling. The Zion National Park Visitor Center. Source: National Renewable Energy Laboratory
14 Lecture: Principles of Natural Ventilation, Module A3/ CEM 160, MSc: AEES DL
21/10/2011 12:14:04
Louvres Louvres are used to provide a weather protected ventilation opening. They are used as the air intake/exhaust for mechanical ventilation systems, for natural ventilation in some industrial buildings (for example where there is a process generating a lot of heat that requires high rates of natural ventilation) for offshore platforms, and on ventilation turrets. Louvres are usually calibrated by their manufacturer in terms of a pressure flow relationship. Windows Different window designs will produce different air flows and ventilation rates, as shown in Figure 17. Heiselberg et al (2001) provide a detailed analysis of the characteristics of airflow from open windows.
The air flow through windows can either be one-directional or, as in the case of stack flow, air can enter at the lower zone and leave at the upper zone. There are a number of theoretical methods for predicting the flow through a large opening, including the de Gids and Phaff method. These can be found in appendix A (4) Ventilation Calculations. However, as Tine Larsen and Per Heiseberg (2008) point out, calculating the flow through even a single window is more complicated than it seems: Even though opening a window for ventilation of a room seems very simple, the flow that occurs in this situation is rather complicated. The amount of air going through the window opening will depend on the wind speed near the building, the temperatures inside and outside the room, the wind direction, the turbulence characteristics in the wind and the pressure variations caused by e.g. wind gusts. Finally, it also depends on the size, type and location of the opening. Many of these parameters are unsteady which makes the calculation of air-change rates even more complicated... (pp.1031)
MSc: AEES DL, Module CEM160, Lecture: Principles of Natural Ventilation 15
21/10/2011 12:14:05
Infiltration
As already discussed infiltration is the uncontrolled flow of air through openings or cracks in the building envelope. This occurs when there is a pressure differential due to wind, temperature difference or mechanical ventilation. The extent of infiltration will depend on the air tightness of the building, the greater the air leakage the larger the infiltration rate. The flow through cracks and openings can be predicted given the size and nature of the crack or opening and the pressure difference across it. Not all cracks and openings allow air to pass through them with equal ease. Typical Infiltration and air leakage Table 3 shows some typical infiltration coefficients of windows and Table 4 shows some effective air leakage areas of building components.
Figure 18: Typical air leakage and infiltration in a building. Source: Infrared Visions
21/10/2011 12:14:05
For tall buildings: CIBSE crack length model This model can be used to predict the ventilation rate for tall buildings, given an effective perimeter crack length of the window framing. It allows for wind and stack effects, building height, location and window system. The method uses a chart technique. The sequence for using the chart (Figure 19) is as follows: 1. Enter the building height on the left-hand horizontal axis; 2. Plot a line vertically until it intersects with the sloping line appropriate to the general terrain in which the building is situated; 3. Plot a line horizontally until it intersects with the sloping line which is appropriate to the window system; 4. Plot a line vertically to read off the infiltration rate on the top right horizontal axis. This is the rate per unit length of open window joint.
Window Type
Horizontal or vertically pivoted, weather stripped Horizontally or vertically pivoted, non-weather stripped Horizontally or vertically sliding weather stripped Horizontally or vertically sliding , non-weather stripped
21/10/2011 12:14:06
Table 4: Effective air leakage areas of building components. Source: Hong Kong University
Building components
Ceiling
general drop recessed lights surface-mounted lights
Unit
cm2/m2 cm2/m2 cm2/each cm2/each cm2/each cm2/each cm2/m2 cm2/m2 cm2/lmc cm2/lmc cm2/m2 cm2/m2 cm2/m2 cm2/m2 cm2/m2 cm2/m2 cm2/m2 cm2/m2 cm2/lmc cm2/lmc cm2/lmc cm2/lmc cm2/lms cm2/lms cm2/lms cm2/lms cm2/lms cm2/lmc cm2/each cm2/each cm2/each cm2/each cm2/each cm2/each
Best estimate
1.8 0.19 10 0.82 21 12 11 8 0.9 4 0.5 0.68 1.2 3.5 1.1 0.25 1.6 0.8 0.28 0.24 2.5 0.65 0.87 0.67 0.44 0.8 0.018 0.21 2.5 0.15 6 2 10 20
Range
0.79 - 2.8 0.046 - 0.19 1.5 - 21
Doors
single, not weatherstripped single, weatherstripped double, not weatherstripped double, weatherstripped interior (stairs) mail slot 12 - 53 4 - 27 7 - 22 3 - 23 0.25 - 1.5
Walls (exterior)
cast-in place concrete clay brick cavity wall (finished) precast concrete panel low-density concrete block (unfinished) low-density concrete block (painted) high-density concrete blk. (unfinished) 0.048 - 1.8 0.05 - 2.3 0.28 - 1.65 1.3 - 4 0.52 - 1.1
Windows
awning, not weatherstripped awning, weatherstripped casement, not weatherstripped casement, weatherstripped double-hung, not weatherstripped double-hung, weatherstripped single-hung, weatherstripped single horizontal slider, weatherstripped single horizontal slider, wood single horizontal slider, aluminium storm inside, heat shrink window sill 0.8 - 2.4 0.4 - 1.2 0.1 - 3 0.86 - 6.1 0.2 - 1.9 0.62 - 1.24 0.2 - 2.06 0.27 - 0.99 0.27 - 2.06 0.009 - 0.018 0.139 - 0.212 0.5 - 6.2 0.08 - 3.5 2 - 24 1-2 2.5 - 20 6.1 - 22
Electrical outlets/switches
no gaskets with gaskets
Piping/plumbing/wiring penetrations
uncaulked caulked
Vents
bathroom with damper closed bathroom with damper open
Notes:
1. lmc = linear metre of crack; lms = linear metre of sash. 2. Data based on a pressure difference of 4 Pa and CD = 1. 3. Data source: 1997 ASHRAE Fundamental Handbook, Ch. 25.
18 Lecture: Principles of Natural Ventilation, Module A3/ CEM 160, MSc: AEES DL
21/10/2011 12:14:06
Conclusion
This lecture has covered natural ventilation along with some types of mechanical ventilation. We have seen that ventilation can provide clean air and cooling. Ventilation rates depend on the type and function of the building, occupancy and the nature of that occupancy: a small hotel kitchen in which a team of chefs are at work will require more ventilation than a domestic sitting room. Natural ventilation can provide cooling and clean air with no energy input, as required for mechanical systems. Running costs and carbon emissions are therefore likely to be reduced. Where natural ventilation cannot meet the needs of building occupants, hybrid (mixed-mode) systems can be considered. Ventilation of any sort is likely to exhaust warm air from a building and so has an energy penalty. Thermal comfort and ventilation are closely related and both air temperature and air movement (draughts) must be considered in this regard. We have considered wind effects and how these can cause areas of positive and negative pressures in the envelope of a building. Methods of natural ventilation we have considered include the stack effect and, of course, windows. Infiltration has been considered as unwanted and uncontrolled ventilation. Finally, we have looked very briefly at modelling ventilation and infiltration. The numerous equations we have considered throughout (and in Appendix A) should help with getting a quantitative feel for the theory. It is not the intention that they should be committed to memory, however!
The Journal of Ventilation website might be a useful place to start further research
21/10/2011 12:14:06
3. The pressure difference due to a stack effect can be calculated using the following equation:
Ps = P2 P1 Where: P1 is the pressure (Pa) at a height, h1, say downstairs P2 is the pressure (Pa) at a height, h2, say upstairs Ps = 2V2g/A 2 1V1g/A1 Where: 2 is the density of air (kg/m3) at temperature T2, the upstairs temperature (K) 1 is the density of air (kg/m3) at temperature T1, the downstairs temperature (K)
20 Lecture: Principles of Natural Ventilation, Module CEM160, MSc: AEES DL
21/10/2011 12:14:06
V2 is the volume the upstairs space (m3) V1 is the volume the downstairs space (m3) A 2 is the combined area of all the internal surfaces in the upstairs space (m2) A1 is the combined area of all the internal surfaces in the downstairs space (m2) g is the acceleration due to gravity, assumed constant on this scale (9.81 m/s2) So: Ps = (2V2/A 2 1V1/A1)g We can see that in a building such as that in Figure 11, where upstairs and downstairs room areas and volumes are equal, the pressure difference is a function of the difference in air density, which is directly proportional to air temperature. The stack effect is driven by a vertical internal pressure gradient in relation to external pressure. For calm conditions the external pressure will be uniform and equal to the neutral plane value. When we are considering the difference in pressure between two points h1 and h2 in the same room (space) we can employ a different formula to obtain a reasonable approximation: Ph = TAgh(1/Te 1/Ti) Where: is the density of air (kg/m3) at the average temperature TA TA (K) is the average temperature (Te + Ti)/2 g is the acceleration due to gravity (9.81 m/s2) h is the height difference (h2 h1) between the two points (m) Ti is the internal temperature (K) Te is the external temperature (K)
Worked Example
What is the pressure difference between two openings 8m apart (vertically) in an atrium, when the internal air temperature is 26C and the external air temperature is 8C? Ti = 273 + 26 = 299K Te = 273 + 8 = 281K The density of air at 290K (TA) is approximately 1.2 kg/m3 Ph = 1.2 293 9.81 8 (1/281 - 1/299) = - 5.91 Pa
N.B. The negative value merely indicates the pressure at h2 is the higher.
MSc: AEES DL, Module CEM160, Lecture: Principles of Natural Ventilation 21
21/10/2011 12:14:07
4. For predicting air flow through open windows the de Gids and Phaff method employs the formulae:
1. ve = (C1vr2 + C2HT + C3) 2. Q = 0.5Ave Where: ve is the effective air speed through the window (m/s) vr is the reference wind speed at the (local) weather station H is the window height (m) T is difference between internal and external temperatures (K) Q is the volume flow rate of air through the window (m3/s) C1, C2 and C3 are the regression constants 0.001, 0.0035 and 0.01 respectively For large openings, such as open windows and doors, it is possible to model the air flow using the CIBSE single sided model. This can predict the flow due to wind effects or the inflow and outflow through one or two vertically displaced openings due to the stack effect. Where wind and stack effects are similar the larger of the two may be selected. The effective equivalent area of openings in parallel (AP) can be obtained by summing the individual areas: AP = A1 + A 2 ... + An The equivalent area of openings in series AS, meanwhile, can be obtained from: 1/AS2 = 1 / (A1 +A 2 + ... + An)2
21/10/2011 12:14:07
References
Awbi, H. (2003) Ventilation of Buildings, Taylor & Francis. BS 5925 (1991) Code of practice for ventilation principles and designing for natural ventilation, BSI. CIBSE (2005) Handbook of Domestic Ventilation, BSE. CIBSE (2005) Natural Ventilation in Non-Domestic Buildings, CIBSE. CIBSE (2000) Mixed Mode Ventilation, CIBSE. CIBSE (2006) Knowledge Series KS6: Comfort, CIBSE, January. Heiselberg, P, Svidt, K and Nielsen, P (2001) Characteristics of airflow from open windows, Building and Environment, 36, pp. 859-869. Infrared Visions, Typical air leakage and infiltration in a building. Available at: http://www.infraredvision.co.uk/pages/content. php?subID=24&catID=8 (Accessed Oct 2010). Greenbuilder (2007) Passive Solar guidelines, in A Sourcebook for Green and Sustainable Building. Available at: http://www.greenbuilder. com/sourcebook/PassSolGuide3.html (Accessed October 2010). Larsen, T. S. and Heiselberg, P. (2008) Single-sided natural ventilation driven by wind pressure and temperature difference, Energy and Buildings, 40(6), pp. 1031-1040. National Renewable Energy Laboratory, Passive Downdraft Cooling. The Zion National Park Visitor Center. Available at: http://www.nrel.gov/ docs/fy02osti/32157.pdf (Accessed Oct 2010). Asfour, O. S. and Gadi, M. (2007) A comparison between CFD and Network models for predicting wind-driven ventilation in buildings, Building and Environment, 42(12), pp. 4079-4085. Parker, J. and Teekaram, A. (2005) Wind-driven Natural Ventilation, BSRIA. Allard, F. and Santamouris, M. (1998) Natural Ventilation in Buildings: A Design handbook (BEST: Buildings, Energy and Solar Technology), Earthscan. Wilson, M., Nocol, F., Solomon, J. and Shelton, J. (2005) Noise Level and natural ventilation Potential in Street Canyons, in Natural Ventilation in the Urban Environment: Assessment and Design, London: Earthscan, pp. 103-123.
21/10/2011 12:14:07
Additional Resources
Ghiaus, C, and Allard, F. (2005) Natural ventialtion in the Urban Environment: Assessment and Design. Buildings, Energy and Solar Technology Series. London: Earthscan. The Whole Building Design Guide (WBDG) gives some introductory notes and design guidance for the U.S.A. http://www.wbdg.org/ resources/naturalventilation.php (Accessed October 2011) Mahdavi, A. and Doppelbauer E-A. (2010) A performance comparison of passive and low-energy buildings, Energy and Buildings, 42(8), pp. 1314-1319.
The Journal of Ventilation website: http://www.ijovent.org.uk/ The Engineering Tool Box: http://www.engineeringtoolbox.com/airproperties-d_156.html