Академический Документы
Профессиональный Документы
Культура Документы
Flaring system
Segment
Segment
Segment
Segment
Example process
Flow diagram
Why do simulations
Cold blowdown
Low temperature issues Release rate Time to safe conditions Liquefied percentage of flow
FEED-study
All possibilities, only experience available Almost all possibilities, main feature available, design basis still not fixed Less possibilities, main design starts to be set, design basis fixed. Changes are expensive, building process is going on.
Thermal radiation
ISO 23251
Heat load
Heat load
Flame emissivity
1,0 0,9 0,8 0,7
Emissivity
1 e
2,00 4,00 6,00 8,00 10,00 12,00 14,00 Flame thickness [cm] Extinction coefficient 0,2 [1/cm] 1,0 [1/cm]
Heat load
800 700 600 500 400 300 200 100 0 200 400 600 800 1000 1200 1400 1600 1800 Temperature [C] Flame emissivity 1,00 0,80 0,60 0,40 0,30 0,20 0,15 0,04
Standards
The fire-sizing equations in Clause 5 assume typical in-plant conditions for facilities within the scope of this International Standard but can be understated for vessels in partially enclosed or enclosed areas, such as those in buildings or on-offshore platforms. For further information, see References [67] or [30]; these documents provide an alternative approach based on analytical methods and can be used to model fire-heat input for all types and sizes of fire.
Standards
5.15.2.3 More rigorous calculations If the user considers that the preceding assumptions in 5.15.2.2 are not appropriate, more rigorous methods of calculations may be specified. In such cases, it can be necessary to obtain the required physical properties of the containing fluid from actual data or estimated from equations of state. It might be necessary to consider the effects of vessel mass and insulation. The pressurerelieving rate is based on an unsteady state. As the fire continues, the vesselwall temperature and the contained-gas temperature and pressure increase with time. The pressure-relief valve opens at the set pressure. With the loss of fluid on relief, the temperatures further increases at the relief pressure. If the fire is of sufficient duration, the temperature increases until vessel rupture occurs. Procedures are available for estimating the changes in average vessel-wall and contained-fluid temperatures that occur with time and the maximum relieving rate at the set pressure [51], [52]. These procedures require successive iteration. For fire-insulated segments exposed to fire, it is recommended to assume the fire temperature outside the insulation layer and that the heat input to the fluid is calculated by conduction through the insulation layer and the vessel wall. The heat-transfer resistance from the wall to the fluid is very low compared to the insulation layers resistance and can be (is usually) neglected. A more rigorous method is described in Reference [141]. There are temperature differences between the liquid and gas phases. Tools are becoming available to perform non-equilibrium temperature calculations; for further information, see Reference [30].
Standards
2 scenario applies: 1. 2. For the time period t mleak > 2 kg/s use 350/100 For the time period t mleak > 0.1 kg/s use 250/0
Each scenario shall run independently, meaning the initial temperature for each scenario is the operational temperature.
mleak is based on the hole size giving the longest leak duration. The segment is not exposed for heat during calculation of t and t.
Heat load
Unexposed segment has been used when exposure time should be found
Include time for detection and activation.
Heat load
Leak duration
Duration of leak rates > 2 kg/s for the IP-segment 18 16 14 12
Time [min]
10 8 6 4 2 0 10 15 20 25 30 35 Diameter [mm]
Heat load
200 0 0 50 100 150 200 250 300 350 400 450 500 Exposed heat flux [kW/m2] Heat tranf. [W/m2K] 0 Heat tranf. 5 Heat tranf. 30 Heat tranf. 100
Heat load
Heat load
Ref. A test method for Jet Fire Exposure, R. Wighus & L. Shirvill, 6th International Symposium on Loss Prevention and Safety Promotion in Process Industries, 1996
Heat load
Heat load
Pool fire
Heat load
Creep
Acceptance criteria
Acceptance criteria
The API recommended practice: Pressure reduction to: half the operational pressure within 15 minutes.
704C 593C
5.20 Vapour depressuring 5.20.1 General EXAMPLE If a pool fire exposes the unwetted wall of a large [25,4 mm (1 in) wall thickness] vessel fabricated from ASTM A 515 Grade 70 carbon steel, it will take about 15 min to heat the vessel walls to around 649 "C (1 200 OF), as shown in Figure 1. At this temperature, rupture due to overheating is imminent as the material's allowable stress [120 MPa (17 500 psi) at ambient temperature] approaches its rupture stress, as given in Figure 2. In contrast, if the vessel is depressurized within the 15 min heat-up time to, say, 50 % of the initial pressure (i.e., half the initial internal stress), then the time to rupture would increase to about 2 h to 3 h (see Figure 2). If vapour depressuring is required for both fire and process reasons, the larger requirement should govern the size of the depressuring facilities.
A vapour-depressuring system should have adequate capacity to permit reduction of the vessel stress to a level at which stress rupture is not of immediate concern. For pool-fire exposure and with heat input calculated from Equations (6) or (7), this generally involves reducing the equipment pressure from initial conditions to a level equivalent to 50 % of the vessels design pressure within approximately 15 min. This criterion is based on the vesselwall temperature versus stress to rupture and applies generally to carbon steel vessels with a wall thickness of approximately 25,4 mm (1 in) or more. Vessels with thinner walls generally require a somewhat faster depressuring rate. The required depressuring rate depends on the metallurgy of the vessel, the thickness and initial temperature of the vessel wall and the rate of heat input.
Fire experiment
Small fire 0.3 kg/s propane
1400
Flame temperature
18 1200
1000
17 800
[C]
600
400
18 17 200
0 0 10 5 15 [min] 10 20 15 25
1200 15 16
13 12 1000
14
800
[C] 600
400
Steel temperature
200
0 0 10 5 15 [min] 10 20 15 25
Acceptance criteria
3 000 2 500
2 000 1 500
600 1 000 500 0 0 2 4 6 8 Time [min] Pressure in vessel Max. average steel temperature 10 12 14 400 200 0
Temperature [C]
Pressure [kPa]
Acceptance criteria
3 000 2 500
2 000 1 500
800 600
1 000 500 0 0 10 20 30 40 50 60 70 Time [min] Pressure in vessel Max. average steel temperature
400 200 0
Temperature [C]
Pressure [kPa]
Acceptance criteria
Time History of Yield Stress, Applied Stress and Average Temperature of Vessel Shell
100 90 80
70 60 50 40 30 20 10 0 0,0 10,0 20,0 30,0 40,0 50,0 60,0 Time [min] UTS Calculated stress of shell Max. average steel temperature
Temperature [C]
Stress [N/mm2]
Acceptance criteria
Acceptance criteria
Theoretical basis
Theoretical basis
Definition of a segment
Orifice
Theoretical basis
10
Diameter
Theoretical basis
Theoretical basis
PSV profiles
PSV does not function as protection to fire
Theoretical basis
Vessel
Multiple vessels in a segment Liquid height Water height Inventory composition
Composition at inflow
Theoretical basis
Pipes
Diameter, wall thickness, length Liquid and gas Heat exposure principle Mill tolerance Corrosion allowance
Theoretical basis
Exposure of pipe
Theoretical basis
Longitudinal vertical
Longitudinal horizontal
1 Circumferential
0 Up
Vessel Vessel
Theoretical basis
Theoretical basis
Theoretical basis
Theoretical basis
Theoretical basis
Calculation results
Inside and outside temperature plot after 300 sec. of start exposure
Calculation results
Gas filled pipe without insulation
700 600 500 01>6-PS-23-062-CS71<Str 1400 1200
400 300 200 100 0 0 10 20 30 40 50 60 70 Time [min.] UTS Calculated stress Steel temperature
Temperature [C]
1000
Stress [MPa]
Calculation results
04>12-PS-23-051-CS71<Str 700 600 500
1400 1200
400 300 200 100 0 0 10 20 30 40 50 60 70 Time [min.] UTS Calculated stress Steel temperature
Temperature [C]
1000
Stress [MPa]
Calculation results
00>1-PL-25-195-CC11<Str 500 450 400
800 700
300 250 200 150 100 50 0 0 10 20 30 40 50 60 70 Time [min.] UTS Calculated stress Steel temperature
Temperature [C]
Stress [MPa]
350
600
Petrell as Olav Tryggvasonsgt. 40 NO-7011 Trondheim Phone: (+47) 73 80 55 00 Fax: (+47) 73 80 55 01 E-mail: petrell.petrell.no www.petrell.no www.vessfire.com
Petrell AS Olav Tryggvasons gate 40 NO-7011 Trondheim Norway Phone: (+47) 73805500 Fax: (+47) 73805501 post@petrell.no www.petrell.no