Air conditioning: Conditioning the Air by modifying / altering TEMPARATURE / HUMIDITY LEVEL & purify the air to satisfy human comfort conditions. T = 26C / 76F R.H = 50% AIR CONDITIONING
RELATIVE HUMIDITY :- Moisture Present in sample of Air / Moisture in saturated Air
REFRIGERANTS are heat carrying mediums , which during their cycle in the refrigeration system absorb heat at LOW tem. Level & discard the heat so absorbed at higher level.
R -11 , R -12 , R 22 , R 123 , R 134a , R 717. Chloro fluoro carbons ( CFCS) , Dichloro di fluoro methane R12, Monochloro di fluoro methane R22
DRY BULB TEMPARATURE (DBT) 3 It I the temperature recorded by a Thermometer whose bulb I not affected by moisture or radiation. WET BULB TEMPERATURE (MBT) It is the temperature recorded by a Thermometer whose bulb is covered by mulin wick wetted by water & is moved past the unsaturated air at a velocity of 4 to 5m/s.
As the air stream flow pat the wick, some water evaporates, taking the latent heat from the wick, thus decreasing the temperature & making the surrounding thin film of air saturated when equilibrium condition is reached there is a balance between the bulb , wick & surrounding saturated air. This decreased temp. of surrounding thin film of saturated air is defined a WET BULB TEMP. 13 1 BTU is the quantity of heat that when added to one pound of water (at atmospheric pressure) raises the water temp. by one degree Fahrenheit. SENIBLE heat changes only the temp. of a substance. It can be felt & measured by an ordinary Dry Bulb Thermometer. Latent heat does not change the DBT of a substance. It is the hidden heat that is absorbed or released when the physical state of a substance is changed. 1 Lb. water(212F) + 970.3 BTU = 1 Lb. steam (212F) 1 Ton refrigeration = 12000 BTU/hr (or) 3000 Kcal/hr Qty. of heat removed to freeze 1Ton (2000 pounds) of water at 32Fahrenheit to ice at the same temperature in 24 hours.
120 CFM Chlorofluorocarbons Ozone layer shields the earths surface from the ultraviolet rays which are harmful to humans. Ozone depleting is because of chlorine, I, (or) bromine atoms (Fluorine atoms do not have this effect.) The solution to the ozone problem was to use halogenated hydrocarbons which contained no chlorine, just fluorine atoms. These materials are called fluorocarbons. H-CFC (fewer chlorine atoms) Ex:- R-22 (one carbon atom, one chlorine atom one Hydrogen atom and two fluorine atoms). H-CFC have a far slighter effect on the ozone layer & in Europe its use will be banned in 2011 year. HFC Hydro fluorocarbons 1 st fluorocarbon to be made available commercially was R-134a which was used as a replacement for R-12 THE REFRIGERATION CYCLE
5 7 Cooling take place when liquid evaporates to become gas. COMPRESSOR: Most refrigerant gases can be made into the liquid form by raising its pressure (and cooling it, which IS handled by the condenser). CONDENSER: During compression the refrigerant becomes hot because of two reason: (a) work done on it. (b) Refrigerant is converted from gas to liquid releasing its latent heat. This heat has to be removed to enable the gas to condense into a liquid easily. EVAPORATOR: The liquid refrigerant from the condenser is injected through capillary (or) expansion valve into the cooling coil which has a bundle of tubes. Inside the cooling coil pressure is low because of throttling device on one side & the compressor suction on the other side. In the low pressure, the liquid refrigerant starts evaporating rapidly by soaking surrounding sensible heat & this is what causes the cooling.
Compressor :- Its aim is to increase the refrigerant vapor pressure so that its corresponding condensation temperature is higher than the cooling medium temperature of the condenser. Types:- Reciprocating, Rotary, centrifugal & Screw type 6/7 7/7 1) Hermetic compressor. a) Mechanical + Electrical B) Low Capacity c) Usage window ac, split ac and refrigerators.
2) Semi Hermetic Compressor. a)Mechanical + Electrical b)Medium Capacity 32 COMPRESS OR scroll Reciprocati ng Screw centrifugal Absorption TYP appl.(TR) 30-100 40-300 >300 >500 >500 Refrigerant R22 R22/R134A R22/R134A/ R407C R123/R22/R 134A water Energy efficiency good good v. good v. good Poor (good only if waste heat used or cheap natural gas available) Initial cost/ton low low high high Highest Maintenan ce friendlines s easy easy Need SPL competen ce Complicat ed complicat ed 14 EVAPORATOR
Classification of Evaporation : (1) According to types of flow a) Flooded Evaporator b) Dry Expansion Evaporator (2) According to medium to be cooled i) Air cooling evaporator. (A) According to types of construction a) Bare tube evaporator b) Plate surface evaporator c) Finned tube evaporator (B) According to mode of heat transfer a) Natural convection evaporator b) Forced convection evaporator ii) Liquid cooling evaporator (A) Double pipe evaporator (B) Baude lot cooler (C) Shell & Coil chiller (D) Shell & Tube chiller 1/7 Condenser:- It is a heat exchanger where heat transfer takes place between the super heated refrigerant received from the compressor and the cooling medium of the condenser. The refrigerant is first cooled to saturation and then Condensed to liquid state. 2/7 Types of Condenser:- Air cooled condensers Water Cooled condensers Shell and tube condensers Shell and coil condensers Double pipe condensers Evaporative condensers 3/7 EXPANSION VALVE: The expansion valve reduces the pressure of the liquid refrigerant received from the condenser. Another equally important function of the expansion valve is to regulate the flow of the refrigerant to the evaporator and to avoid flooding of evaporator with refrigerate. 4/7 Types of Expansion Valve: a)Capillary tube b)Constant pressure expansion valve. c)Thermostatic Expansion valve (mostly used now a days.)
19
DISC VALVE CFM 4 15-100 6 30-180 8 40-240 FLY FAN:- Increases the suction Pressure of roof mounted Fan & It should Be connected in Line. Static Pressure Description static pressurewg Straight Duct 1m 0.004wg 90 Elbow 0.2wg 45Elbow 0.1wg Baffle Filter 0.5wg DUCT CONNECTION 8 27 DUCT MATERIAL
1. G.I (Galvanized Iron) Low cost & EASY FABRICATION. 2. ALUMINIUM SHEET METAL Is used for LIGHT WEIGHT & RESISTANCE TO MOISTURE APPLICATION. 3.FIBER GLASS DUCT LOW VELOCITY APPLICATION ONLY OTHERWISE HEAVY VIBRATION WILL GENERATE. 4. THICK BLACK MILD STEEL SHEET ARE USED FOR EXHAUST DUCT. 5. HIGH CORROSION RESISTANCE APPLICATIONS- MARINE GALVANIZED STEEL SHEETS WITH HEAVY DEPOSITION OF ZINC( not less than 270gms/sq.m) for INTERNALDUCTING & STAINLESS STEEL GRADE 316L for EXTERNAL Ducting. 6. PUF (Polyurethane foam) duct are Flexible & do not require insulation a PUF is an insulating material. But it is costly & may generate Toxic gases in case of fire.
28 CLAIFICATION OF DUCTS 1) LOW PRESURE DUCT:- Velocity <600mpm & static pressure < or = 5cm of H2O gauge. (mpm stands for miles per minute) . No specified requirements of class of cleanliness. . Space do not require specific +ve pressure. . Conditioned Air is supplied through supply air ducts which is often surrounded by return Air over the false ceiling. 2) MEDIUM PRESSURE DUCT WORK:- Velocity < 600mpm & static pressure 5-15cm of H2O gauge. . Specified class of cleanliness often incorporates deburring (exclude) of coil, Absolute filters, supply, Return, Exhaust & Fresh air ducts. . Clean room application require Medium pressure duct work because heavy pressure loses take place through high efficiency filters. . Care to be taken to seal all duct joints to prevent leakage. Joint should be soldered or sealed with good quality sealant. . Sheet used should be free from flaking or any such defects as this likely to add eroded metal particles to the conditioned air. 29 3) HIGH PRESSURE DUCT WORK:- Velocity >600mpm & static pressure >15cm of H2O gauge * For specified class or marine applications. * Pressure drop in supply Air Ducting: 10-15cm of H2O gauge. * Pressure drop in Return Air Ducting: 5-10cm of H2O gauge. * Circular (or) spiral ducting (machine fabricated) is recommended as the helically wound longitudinal joints provide adequate mechanical strength.
RECOMMENDED GI GAUGE (LONGER SIDE IN CM) Low pressure medium press. High press. G.I sheet metal gauge. Up to 30cm _ _ 26 0.5mm 30 - 75 Up to 45 _ 24 0.6mm 75-135 45 - 120 Up to 120 22 0.7mm 135-120 120-180 120-180 20 0.9mm Above 210 Above 180 180-240 18 1.2mm - - Above 240 16 31 METHOD FOR DUCT DESIGN 1.VELOCITY REDUCTION METHOD:- V=(Q/A) In this method arbitrary reduction are made in the air velocity as we go down the duct run. 2. EQUAL FRICTION METHOD:- The frictional pressure drop per unit length of the duct is maintained constant throughout the duct system & size is maintained accordingly. If an equal friction design has a mixture of short & long runs of duct, the shortest duct will need a considerable amount of damping. This is a drawback of the equal friction design. 3. STATIC REGAIN METHOD:- The principle of the static regain method is to maintain a constant static pressure before each terminal & each branch to provide same flow. This is achieved by sizing the duct in such a manner that after each branch or outlet the static pressure gain due to reduction in velocity, exactly balance the pr. drop in the succeeding. 17 Duct Circular Equation of A rectangular Duct:- Where d=diameter of circular duct (inc) a=width of duct (inches) b=height of duct (inch) Friction Losses in a Circular Duct:- Pd=Friction (pressure loss) in inches of water gauge/100duct d = Equivalent duct dia. In Inches.
Duct Section CFM FPM Duct size (w x h) Round Diamet er (d) Aspect Ration Frictio n/100 (pd) Duct Length Frictio n/Duct Length AB 2200 800 22x18
10 d=1.3x(axb) (a+b) 0.25 0.628 Pd=(0.109136 Q ) d 1.9 5.02 33 Duct section. This process requires the iteration in velocity. This is balanced system & do not require the use of damper any where used for medium & high pressure ducting . ` e . 21 25 P=2L+W Wall type Hood P=2L+2W Island type Hood
CFM=200xP Heavy cooking CFM=150xP Medium cooking CFM=100xP Light cooking
*Exhaust/makeup air 1500-2200 /fpm duct velocity *Duct to be terminated 40 above the roof. *Cleanouts to be provided at the Base of Riser and every 20feet. *Duct sheet metal gauge (a) 16ga. Galvanized Steel (b) 18ga. 304 S.S *Hood construction 18ga.minimum. 26 Black steel Duct is used for all kitchen ducts (Hoods) S.Steel Duct is used for laundry Exhaust.
Stainless Steel 430 cheap & catches Rust Easily 304 This type is used for hood. 316 317L Special & Pure Stainless Steel for operation theater in Hospitals. (Low Carbon)
INFILTRATION ESTIMATE ( CRACK METHOD)
The leaking of air into a building through small crack is called Infiltration. The forcing of outdoor air into a building by means of a fan is called Ventilation.
Window (or) frame CFM =[ Crack length x Leakage rate (cf/hr) ] / 60 min 43 DESCRIPTION LEAKAGE RATE Windows Frame 14cf/hr 13cf/hr 45 INFILTRATION Q = 1.1x CFM x T Q = Sensible heat loss Btu/hr. T = Out door Temp Indoor Temp (F )
Q = Latent heat Btu/hr W = Indoor humidity ratio in grains water/Lb dry air W = outdoor humidity ration in grains water/Lb dry air Typical allowable design air Infiltration rates through exterior windows & Doors.
Infiltration Rates for Frequent Door usage
s s Q = 0.68 x CFM x (w w ) L o i component Infiltration Rate Windows 0.37 cfm/ft of sash crack Residential Doors 0.5cfm/sqft of door area Non-residential Doors 1:00cfm/sqft of Door area Type Ft / person Swing door, no vestibule 900 Swinging door, vestibule 550 Revolving door 60 3 L o i 118
1.08 = 0.244 x 60/13.54
Specific volume of Moist air at 70 F db and 50% RH Room Latent Heat = 0.68xCFMx w 0.68 = 60/13.5 x 1076/7000 Average heat removal required to condense one pound of water vapor from the room air. Room Latent Heat = 0.68xCFMx w Min/hr Min/hr Specific volume of moist air at 70 F db & 50% RH. Grains/Lb 4.45=60/13.5 Min/hr Specific volume of moist air at 70 F db & 50% RH. Specific heat of moist air at 70 F db and 50% RH, BTU/(deg F) (Lb of dry air) Room Sensible Heat = 1.08xCFMx T 51 Central plants are comprised of COMPRESSORS CONDENSERS AIR HANDLING UNITS WATER CHILLERS COOLING TOWERS Direct Expansion (DX) system:- Air is cooled & conditioned in the plant room. Treated air is pumped to various parts of the building. Return air is sucked through a coil fin arrangement by a fan. Refrigerant inside the coil picks up heat from this air & evaporates. The cold air is then pumped back to the air conditioned space. Heat exchange take place in AHU. 53 -55 CHILLED WATER SYSTEM:- Refrigerant & water interaction takes place. The refrigerant in the shell of a shall & tube heat exchanger, evaporates by picking up heat from the water which is in the other portion of the heat exchanger. This chilled water is then circulated to various water air heat exchanger, called FAN coil units / Air Handling units. Hypothermia Temp. increase 98 F Hyper pyraxia Temp. decrease Thinking ability reduces Heat stroke. 54 Expansion Tank:- used to provide volumetric expansion of chilled water due to thermal expansion in case of plant shut down or maintenance.
Expansion Tank should be connected using a branch line to the suction side of the chilled water pump. Chiller AHU AHU Expansion Tank No shut off valve on this line 50 Chilled water system (or) Air-water system (or) hypersonic system. Chilled water system design pressure is 125 PSI 1. Open piping System piping is not a closed circuit. Incorporates a water sump/Tank.
2. Closed Piping system:- Chiller AHU AHU 52 3. 2-way piping System (or) direct return system
4. 3-way System (or) Reverse return system most preferred piping arrangement as it reduces pressure drop in chilled water coils.
2 nd Riser takes a U Trap & Returns back to chiller. Chiller AHU AHU3 AHU AHU2 AHU1 Chiller AHU2 AHU1 AHU3 AHU4 65 Chilled water system:- Chilled water is produced in the chiller (Shell & Tube Heat exchanger) & Is circulated VIA chilled Water pumps to Air- handling units (AHU) & Fan coil unit (FCU) Chilled water entering temperature = 55F (T2) Chilled water leaving Temperature = 45F (T1) Chilled water temperature rise =T2-T1= T =55-45 T=10 F Chilled water system Design pressure = 125PSI Chilled water G.P.M (Gallons per Minute)=volume of chilled water to be circulated by the pump is expressed in G.P.M Tr=Tons of Refrigeration T=Water Temperature Rise=10 F G.P.M = 24xTr/10= 2.4xTr Electrical Requirements Per Ton of A/C:- 1.2 kw for 1 Ton of central plant 1.5 kw for 1 Ton of window/split (non-central plant) Air cooled 1.25Tr/kw Water cooled 0.55-0.8 Tr/kw G.P.M=2.4xTr/ T 66 Types of chillers:- 1. DX-chiller: commercial Air conditioning (shell & tube heat Exchanger) shell-water; tubes-refrigerant. 2. Flooded chiller: industrial refrigeration (shell & tube heat exchanger) shell-refrigerant; tubes-water. Arrangements of chillers:- 1. Parallel Arrangement commercial A/C both the chillers/all chillers should be of same capacity.
1. Series Arrangement Industrial Applications
Both the chillers are of un Equal capacity. Note: The Pressure Drop in a Chiller should not Exceed 20 of w.guage ft =2.31xPSI pressure drop= difference of chiller inlet pressure & outlet pressure. 3. Multiple chillers/Boilers(500Tr)
, chiller chiller C1=50Tr C1=50Tr Common supply Heads Return Heads chiller chiller C1=60Tr C1=40Tr T>10 F T>10 F 125 Tr C1 125 Tr C2 125 Tr C3 125 Tr C4 Lead chiller 5/7 Evaporator:- An evaporator is heat exchanger where transfer of heat takes place between the substance area to be cooled and the refrigerant. Types:- Natural convection Evaporators Flooded evaporators. Liquid Chillers:- A) shell and tube type chiller. B) Shell and coil type chillers C) Double pipe evaporator D) plate-surface evaporator E) Finned Evaporators F) Boudelet cooler.
56 The piping material most commonly used in hydronic system is either low carbon (black) steel pipe or copper tube, these are standardized by ASTM (American Society of Testing Materials). The term Black steel pipe is used in trade but this refers to ASTM A 120 (or) ASTM A 53 low carbon steel. 1/6 PIPE:- Is a conduit (enclosed area) through which any liquid or gas can be passed. In A/C the pipe which joins the compressor, condenser & Evaporator in all the A/C M/Cs through which the ref. gas is passed is called primary piping or Ref. gas piping. In chillers there is an additional piping which joins the pumps, chillers, FCUS & AHUS in which the chilled water is passed is called secondary Ref. piping or chilled water piping. The primary & secondary piping are also called closed piping because the recirculation of the same Ref. takes place. 2/6 The condensers piping which join the pump, condenser, the cooling tower is called HOT WATER PIPING OR OPEN PIPING. CLASIFICATION OF PIPE Metallurgy:- The pipes are available in different sizes, thickness and materials or metals. Hence they are named as SS (stainless steel), Cu (copper), Ms (mild steel), Bs (black steel), CI (cast iron), GI (Galvanized iron), PVC (Poly vinyl chloride), N (Nylon), and HDPE (High density poly ethylene pipe). These pipes are used in A/C, plumbing, & fire fighting. The duty of a Mechanical Engineer is to calculate the exact pipe dimensions based on heat load calculation.
3/6 USES:- 1) S.S.Pipe:- These are used in the manufacturing of evaporator of a chiller i.e.. shell & tube heat exchangers are of stainless steel. 2) Copper & Aluminum pipe are used in the manufacturing of condensers & evaporators of all the A/C machines and their connections. 3) The Ms pipes are used to pass the chilled water into the pumps, chillers & up to FCUS & AHUS. 4) Nylon pipe is flexible plastic pipes which are used to drain the condensing tray water in to the nearest plumbing connection. 5) Galvanized Iron pipes are used to supply drinking water into the building. 6) Ms (mild steel) pipes are used in the Fire Fighting system. 7) C.I (cast iron) pipe is used to drain water from kitchen and toilets. Now-a-days it is replaced by PVC pipes because its light in weight, can be easily joined, low in cost and non corrosive. 4/6 CLASSIFICATION OF PIPES ACCORDING TO MANUFACTURING. Extrusion is the process which manufactures pipes. As welding is used in joining the two pipes where required length is quite larger than a given pipe. Welding is classified in two ways i.e.. 1. SEAMLESS PIPES. 2. WELDED PIPES. 1) Seamless pipes:- These pipes are perfect in shape and with stand high pressures up to 40 bar. The refrigerant gas piping in all the air-condition machine should be seamless pipe. Only disadvantage in this pipe is power consumption is high. 2) Welded pipes:- This pipe will have internal bur & external bur during its manufacturing process only external bur can be removed and internal bur will remain.
5/6 The only way to differentiate a welded pipe from seamless pipe in physical way. These pipes are used in plumbing, firefighting and chilled water system. CLASSIFICATION OF PIPES ACCORDING TO GRADES: 1. A class pipe or schedule 20 pipe or light duty pipe. 2. B class pipe or scheduled 40 pipe or Medium duty pipe. 3. C class pipe or schedule 60 pipe or heavy duty pipe. A class pipe is used in water supply system and can withstand pressure of 8 bars. 6/6 B class pipes are used in chilled water piping and can withstand pressure of 1 bars. C class pipes are used in fire fighting system and can withstand pressure of 6-8 bars. CLASSIFICATION ACCORDING TO LOCATION The chilled water piping which joins pumps, chillers & OTS. The piping system used on roof is called ROOF PIPING. From roof the pipe which brings the water till ground floor these pipes are called RISER PIPES. The pipe which moves in horizontal direction on every floor which carries the water from riser to FCU or AHU is called FLOOR PIPING. 6 Counter-flow Parallel Flow
Air Air
Connect the water Inlet to the bottom of the cooling coil header on the air-leaving side of the coil & the water outlet to the top of the header at the air-entering side of the coil to achieve counter flow of water & air. The air velocity across the chilled water coil & direct expansion coils should be generally 2.5m/sec. However it must not exceed 2.8m/sec to prevent water carry-over. 63 MAXIMUM WATER VELOCITY TO MINIMIZE EROSION
Normal = operation of chillers in hrs/year = (No. of months x No. of days/month x No. of hr/day). NOMINAL OPERATION (HR/YR) WATER VELOCITY (FPS) 1500 12 2000 11.5 3000 11 4000 10 6000 9 8000 8 64 Example:- If a chiller operates for 10months, 30days, 14hours daily, find the water velocity & normal operation of chillers in hours per year.
= 10month x 30days x 14 hr/day = 4200 hours/year. water velocity = 10 fps (ref. above chart values)
8/2 AESHRAE:- American society of heating refrigeration & air-conditioning Engineers. AIR:- Air conditioning & Refrigeration Institute. ASTM:- American society for testing & Materials. FM:- Factory Mutual Insurance Company. NEPA:- National electrical Manufacturers Association. SMACNA:- Sheet Metal & Air Conditioning contractors National Association. UL:- Under Writers Laboratories Incorporated. OSHA:- Occupational safety & health Administration. IAQ:- Indoor Air Quality.
Valves
VALVE FOR CONTROLLING FLOW ARE DIVIDED INTO THREE CLASE STOPPING FLOW: Gate valve used for complete isolation equipment for service, GV has straight through flow passage resulting in low pressure loss.
REGULATING FLOW: Globe valve, ball valve, butterfly used to adjust flow rate manually. LIMITING FLOW DIRECTION: check valve valves that allow flow in one direction only. SWING CHECK: Horizontal lines, vertical lift check (or) spring- loaded check- vertical lines. N.R.V PRESSURE REGULATING VALVES: PRV This valve limits the discharge pressure to a present valve.
Make- up water supply line to a system.
59 61 RELIEF VALUE : Used to relieve excess pressure in boiler.
TRAINER : Are used to remove solid particles from the circulating system.
Y type , Basket type installed at the suction side of pumps & before large automatic control values.
69 = [162.6x1200] / [(55-45) x 500] = 390.2 US GPM. PUMP selected for (400 USGPM / 85 FT WC) CALCULATION OF PRESSURE DROP IN CHILLED WATER SYSTEM 1) LINE A PIPE SIZE = 100mm (dia.) GPM = 200 PIPE LENGTH : 2.5mts x 3.28 = 8.2ft ELBOW : 1 NO. x 10 ft EQ. length = 10.0 ft TEE : 1 No. x 21 ft EQ. length = 21.0 ft DRV ( globe value) : 1 No. x 120 ft EQ. length = 120.0ft TOTAL LENGTH = 159.2 ft
71 FRICTION LOSS I 2.3ft in 100ft i.e.. For 159.2ft friction loss = 3.7ft 2) LINEB PIPE SIZE : 125mmdia. FLOW :400GPM PIPE LENGTH : 9.5mts x 3.28 = 31.16 ft Friction loss is 2.8ft in 100ft i.e.. For 31.16ft friction loss = 0.9ft 3) LINEC PIPE SIZE : 100mmdia. FLOW : 200 GPM PIPE LENGTH : 13.5mts x 3.28 : 44.28ft ELBOW : 2 NO. x 10ft EQ length : 20.00 ft TEE : 1NO. x 21 ft EQ length : 21.00ft
TOTAL LENGTH = 85.28 ft 73
Friction loss is 2.3ft in 100ft i.e.. For 85.28ft friction loss = 2.0ft 4) Line D PIPE IZE : 80mmdia. FLOW : 100GPM PIPE LENGTH :9.3mt x 3.28 :30.5ft Elbow :1no.x 1.7ftEq. length :7.5ft Tee : 1no.x15ftEq. length : 15.0ft Total length is 53.0ft Friction loss is 2.4ft in 100ft i.e.. For 53.0ft Friction loss = 1.27ft. 5) Line E i.e.. For 56.33ft Friction loss = 2.8ft. 75 6) LINEF i.e.. For A3.1ft Friction loss = 1ft
7) LINEG IV : 1no.x 1ftEq. length = 1.0ft i.e.. For 18.44ft friction loss = 0.7Aft 8) LINEH DRV: 1no.x 29ftEq. length = 29.0ft 3 WAY.M.V: 1no.x 29ftEq. length = 29.0ft i.e.. For 74.78ft friction loss = 3.0ft 9) LINEI i.e.. For 43.1ft friction loss = 1ft 10) LINEJ i.e.. For 56.33ft Friction loss = 2.8ft 77 11) LINE K i.e.. For 52ft friction loss = 1.25ft 12) LINEL i.e.. For 105ft friction loss = 2.4ft 13) LINEM i.e.. For 39.2ft friction loss = 1.1ft 14) LINEN I V : 1no. x 6ftEq. Length = 6.0ft ST : 1no. x 58ftEq. Length = 58.0ft Reducer : 1no. x 5ftEq. Length = 5.0ft i.e.. For 11404ft friction loss = 3.2ft 15) LINEO I V : 1no. x 6ftEq. Length = 6.0ft ENLARGER : 1no. x 15ftEq. Length = 15.0ft NRV : 1no. x 50ftEq. Length = 50.0ft i.e.. For 100.1ft friction loss = 2.8ft 79 16) LINE P i.e.. For 70.4ft friction loss = 2.0ft 17) LINEQ IV : 1no. x 4.5ftEq. Length = 4.5ft i.e.. For 42.1ft friction loss = 1ft Total pressure drop (friction loss ) in pipe line = friction loss in A + B + C + D + E + F + G + H + I + J + K + L + M + N + O + P + Q = 33ft of WC pressure drop in pipe line = 33ft of WC pressure drop across chiller = 17ft of WC pressure drop across FCV = 3.5ft of WC TOTAL ^h = 53.5ft of WC Add 10% safety = 5.5ft of WC Total system pressure = 59.0ft of WC Drop ^H 67 FLOW RATE CALCULATION Chiller Capacity 81.3 TR x 2NOS = 162.6 TR. WATER ENTERING TEMPERATURE 55 F WATER LEAVING TEMPERATURE A 5 F WATER FLOW RATE = TR x 12,000 / ^T x 500 Hp= GPM x head x sp. gravity 3960 x % of Efficiency = ( 30 x 97 x 1 ) / ( 3960 x 0.5 ) = 1.5 HP.
121 Classification of Fans 1. According to max total pressure:-
2. According to air flow direction:- a) centrifugal fan:- Types= forward curved, Radial curved, Backward curved. Air enters axially & flows radially over the impellers (or blades) & discharged radically. Used for duct system as pressure can be developed. Quite in operation. High in cost.
b) Axial flow fan:- Types= Propeller, Tube axial, vane axial fan. Air flows parallel to the axis of the fan. Should not be used for duct AC Systems as they are incapable to develop high pressure. Used as exhaust fan. Low in cost. (a) Class I- Pressure up to 95mm wg (b) Class II - Pressure from 96-170mm wg (c) Class III - Pressure from 171-310 mm wg. (d) Class Iv - Pressure above 310 mm wg. 123 Classification of pumps 1. Working Principle Impeller pumps displacement pumps Rotary Reciprocating Screw vane lobe gear peristaltic piston diaphragm pump Archimedean Progressive cavity Twin-screw Triple-screw Multi-screw. 2. Layout of working axis(Horizontal, Vertical & inclinded) 3. Conformity to standards API pumps & ISI marked Pumps 4. Construction features by method of shaft sealing gland packed Mech 62 -DRINKING -TOILET -BATHING -DRINKING CLOTH WASHING 100Lit / day 50Lit / day
Total no. of occupants = 280 ~300 i.e.. Total liters of water consumption per day = 300 x 50 = 15000 lit.
15000 / 30 = 500 cu ft i.e.. Tank volume L x W x H = 500 ft3 Let w = 6 , H = 5 i.e.. L = (500 / ( 6 x 5)) = 16.6
WATER SUMP CAPACITY RESIDENTIAL COMMERCIAL 1 cu ft = 28.32 lit ~ 30 lit 64 CAPACITY OF OVER HEAD TANK 15000lit/2 = 7500lit. i.e.. Tank volume L x W x H = 7500 let W = 6, H = 5 L = 7500 / ( 6 x 5) = 8.2 PUMP CAPACITY (SUPPLY DRINKING WATER) GPM & Head = { L x (fr/100)} 1 Gallon = 4lit i.e.. (7500/4)lit = 1875 Gallons = 1875/60 = 31.25 ~ 30 GPM
DITRICT COLLING SYSTEM
District Cooling could be simply defined a:- A centralized cooling plant that serve multiply buildings. A centralized cooling plant that is designed as a utility. A centralized and operated for maximum life- usually 25 years or more. A centralized cooling plant that I designed to operate at maximum efficient at all time. 58 76 A centralized plant that is designed for flexibility in operation. A centralized cooling plant that is deigned to make full use of the operation /consumers that it serves. A centralized plant that I operated by an independent organization that operates, maintains, and charges consumers for the energy that is CONSUMED. 78 In our minds, unless all of these parameters are met, a centralized cooling plant cannot de classified as a district cooling plant unless all of the above criteria are met. The operation must be classified a a utility operator and must be responsible to its consumers, the community and the environment. Similar organization in Dubai are EMPOWER, Tabreed, and Palm District cooling. 80 How is District Cooling different from a Central Cooling plant? A Central plant is not much different that a district plant. In fact, the basic equipment is the same. The difference lie in the definition of a District Cooling plant. The following is a list of some of the basic differences between the two systems. 82 CENTRAL PLANT It is operated by the owner of the building or the developer. It serves single building or small group of buildings known as campus. The connections to buildings are not metered. Designed to operate efficiently capital investment is usually not a great concern for the plant itself. The capital is concern for the entire development.
DISTRICT COOLING PLAN Operated by a company that is certified to be a utility provider. Serves large district with many buildings with many examples. All consumer connections are metered. Designed to operate efficiently, and cost effective from a capital investment perspective. These plants are designed to minimize operational costs and hence max. profitability. 84 Deigned to be reliable usually a ingle point of failure from the power supply and return feeds, etc. Generally there plants utilize electricity as their main source of energy. Designed usually with a higher degree of reliability and include implementation such as:- i) Networked chilled water supplies. ii) Multiple electrical feeds. iii) Industrial grade equipment for control and operation. iv) Distributed cooling plants. Deferent technologies are available for these plants: i) Gas fired engine driven chillers. ii) Absorption chillers. 86 It utilize municipal domestic water for cooling tower heat of rejection. These plants can be designed for use with: Treated sewage effluent. Sea water Ground water. These plants are generally designed by the engineers that design the buildings. Designed by professionals that are experienced in the district cooling field. 109 Dehumidifier capacity is usually measure in pints (1L = 1.816 pint (pt) ) 24 hours and is determined by two factors : the size of the space that needs to be dehumidified and the conditions that exist in the space before dehumidification. 111 Condition without dehumidification 500 1,000 1,500 2,000 2,500 Moderately damp (space feels damp and has musty odor only in humid weather.) 10 14 18 22 26 Very damp (space always feels damp and has musty odor. Damp sports show on walls and floor.) 12 17 22 27 32 Wet (space feels and smells wet. Walls or floor sweat, or seepage is present.) 14 20 26 32 38 Extremely wet (laundry drying, wet floor, high load conditions.) 16 23 30 37 44 Area (Sq . Feet) 113 Allowances: 20% in Duct Weight 15% in Insulation Area 10% in Accoustic Lining
DUCT SIZE cm DUCT RUN M PERIME TER IN METER 2(W+H) AREA Sq m Sq. Mt Wt/sq m
TOTAL wt IN Kg ACCOUS TIC LINING Sq. Mt 115 Recommended Metal Gauges for Duct: Greatest Inches Dimension Gauge Thickness mm Nom Kg/sq.m <30 <76.2 24 0.6mm 5.64 31- 60 79 - 152 22 0.7mm 6.86 61 90 155 - 228 20 0.9mm 8.08 91 > 231> 18 1.2mm 10.52 117
Area = 2x(w+H) x L Straight Duct w L H L D c A B Taper Area=(A+B+C+D) x Length
c Shoe Piece Area = [(A+B+C+D) x Length] Elbow:- Area=2(b + a)(L + L) (or) Area = {(A + B) x length + (0.5 x A)} 3.14 + angle/90 + 2(A + B) x [E x t1 + Ex t2] B A D Area= 2(w + H )L +2(W + H ) L + 2(w + H ) L 1 2 3 1 1 2 2 3 3 89 FIRE FIGHTING CLASS OF FIRE: A: SOLID MATTERS FORMING GLOWING RESIDUES (Wood, Rubber, Car Tire, Paper, Textiles.) B: LIQUID COMBUSTIBLE MATTER (Petrol, Oil, Grease, Ether, Alcohol.) C: Burning gases emerging under pressure (Propane, Butane, Methane, Acetylene, Town gas.) D: FIRES ON ELECTRICAL PLANTS. NFPA :- Natural Fire Protection Association. 90 Sprinklers Types 1. Pendant Type Each sprinkler 20gmp 2. Up-right type 3. Side Type Each fire hose cabinet =50gpm
Pipe size No. of Sprinklers O1 2 O1.25 3 O1.5 5 O2 10 O2.5 30 O3 50 O4 80 O5 160 O6 275 FHU FHU 30M 30M 60M Maximum distance between two fire hose cabinets. 6M 6M 91 SPRINKLER :- A sprinkler installation comprises of inter- connected pipes into which sprinkler heads are fitted on a definite basis of distribution i.e.. 8-10 feet apart according to nature of risk. The heads are so constructed that the heat arising from fire will cause them to rupture thus permitting the water to discharge in the form of spray. The main function of the sprinkler installation are:- 1) To detect the fire 2) To sound an Alarm 3) To attack the fire 4) To restrict the spread of fire Types of sprinkler system:- a) Wet system:- it is installed where there is no danger of the water in the pipes freezing & the pipes are always filled with water. b) Dry system:- it is employed where temp. is liable to fall below freezing point, the pipes are always kept charged with air under pressure. Some times found in cold stores. c) Alternate wet and dry system:- it is used where the risk of freezing is present at certain period of year at which times the water is drained from the pipes and the system is charged with air under pressure. 93
FOAM:- Fire fighting foam =foaming agent + water aerated used for oil fires. Powders Burning metals, chemicals fire, form sticky residue over the fire. Class A organic material (wood, paper, cloth, plastic etc.) Class B flammable liquid (petrol, paints, solvents). Class C Flammable gas (LPG, Acetylene). Class D combustible metals (Mg, Na, k). Class E Electrical fires, motors, switch gear. 99
Water supply for 30 min before the pump starts. sprinkler Deluge System Total flooding System which comes in operation with the help of a single heat sensing sprinkle used to protect electrical transformer, Main Deluge Valve is located out side the risk area.
Over Head Tank 22,500L 92 WATER EXTINGUISHERS:- These are filled with regular tap water & pressurized with air. DRY CHEMICAL EXTINGUISHERS:- These are filled either with foam or powder, usually soda or potassium bi carbonate & releases carbon di oxide. Dry chemical extinguishers interrupt the chemical reaction by forming a thin layer of powder or foam, separating the fuel from the surrounding air. CARBON DI OXIDE (CO2) EXTINGUISHERS:- These contain CO2 a non-flammable gas, these extinguishers work by displacing away oxygen from the surrounding air. 101 In high rise building (15-16 stored & above) Static becomes high so divide
the building into vertical hydraulic zones & use pressure reducing valves. Min pressure provided in a wet Riser = 3.5kg/sq cm. 63mm 12mm Nozzle.
Water=500l/m
Automatic Sprinkler System:- Spacing is determined by Hazard classification, Exposure & height at which it is & installed. ` Air vessel pump Tank 103 Hydrant stations are provided to serve an area. Place the Hydrant station near staircase or Lobby.
Hydrant station contains:- * First Aid Hose reel with dia.20mm, Rubber hose 30- 36m long with dia.6mm nozzle. * dia.63mm Single ordouble headed landing valve. 15m x dia.63mm reinforced Rubber lined hose, & a brand pipe with 12mm Nozzle.
105 CO2 & Halon system:- Electrical switch room, control room, computer room, storage area, in libraries, archives, museums. co2 if concentration is more than 9-10% can cause severe in consciousness. Halons less toxic but environmentally hazards. CO2 is used for dosing electrical fires or other fires which cannot be put out with water. Halogenated Agents ( Halons ) Hydrocarbons in which one or more H atom is replaced with Fl, Cl, Br or I
70 Fire Alarm System Analog low profile high performance optical smoke sensor Minimum distance between each smoke detector cost=400/-SR (or) Heat detector Installed in kitchen cost=370/-SR
5m allowed but 3.75m recommended by civil defense. 7.5m S S 7.5m H S S 5M S 5M 5M 74 Auto Dialer system to automatically dial the three programmed number in case of fire. Fire Alarm control panel for Analogue addressable fire alarm system, 4 loop with maintenance free Rechargeable batteries (3hrs duration) 12,000/-SR Emergency light with Rechargeable batteries. {COST: 50SR ~ 1500SR+100SR (Labour+ wiring) +25%profit+10%over heads} = 345/-SR 16 STAIRWELL PRESSURIZATION * Wood, paper, cotton cellulose: products of combustion:- CO, CO2, H2O. * PVC HCL appears as chlorinated material. Application of large amount of nitrogen in plastics, nylon appearance of HCN. According to ASHRAE, design of smoke management system fire protection is defined in two basic approaches. 1) Prevent fire ignition. 2) Manage fire impact. Example of fire impact management: a) compartmentation. b) fire suppression. c) control of construction material. d) smoke management. SMOKE MANAGEMENT SHAFT PROTECTOR PROTECTOR FLOOR STAIR CASE PRESSURIZATION SYSTEM ELEVATION HOISTWAY SYSTEM 2/2 Q) A Staircase serves 6 floors. There is a double door to outside at ground level & single doors into the accommodation on each floor calculation the requirements for the supply fans fo4r pressurization system. Q=0.83Ae P Q=The volume of air required (m qu/sec) Ae=Leakage area from the space (m sq) P=Pressure differential (Pa) 50 Pa n=Leakage factor for large leakage areas-doors etc n=2 for small leakage areas-window cracks n=1.6 Ae=1xdouble door at0.03=m sq to hold smoke behind doors the formula become 6xSingle door at 0.01=0.06msq Q=0.83Ae P Ae=0.09msq Q = 0.83 x 0.09 x 50 = 0.53mqu/sec Increase by 50% +0.26mq u/sec 0.79mqu/sec 0.8mqu/sec(1)
A=Area of single leaf door= 2.0mx0.8m= 1.6sqm v=velocity through door ------------------ 0.75m/sec Q= V x A = 0.75 x 1.6 -------------------- 1.20mqu/sec Add(1)-------------------- 0.80mqu/sec 2.0m qu/sec a) To calculate Pressure required in stair well to exhoust 1.2mqu/sec to atmosphere via fire floor. Are of single leaf door = 2.0x0.8=1.6msq area of exhoust vent=1.2/2.5=0.48msq Ae=[1/A + 1/A ] = [1/1.6 + 1/0.48 ] = 0.46msq P1= [Q/ 0.83XAe] = [1.2/0.83X0.46] = 10.01Pa b) To calculate Area of pressure relief. Quantity of Air to be wasted =(2.0 - 0.8) = 1.2m qu/sec Area of pressure Relief = Q/0.83 x P = 1.2/(0.83) x (50) = 0.204m sq` 1m qu/sec=2118CFM 1M/Sec=196FPM 1 2 2 2 1/2 1/n 1/2 1/2 2 2 2 -1/2 6 Flore Exhoust vent Double doors stairs p p 1 V=0.75m/sec Exit vent A=Q/2.5 125 Maintenance of A/C System
1. Stop the machine/open the cabinet. Clean the condensing tray/evaporator's coil/condensing pipe on drain pipe. 2. Lubricate the fan motor. 3. Tighten the nuts & bolts of M/cs isolators. 4. Balance the duct by adjusting SD( splitter damper) /VLD. 5. In AHUs tension the fan belt. 6. Charge/clean the filter. 7. Balance the flow of CHW by adjusting gate valve. 8. Check the thermostat & cut out [O/P] over load protector. 9. Check the electrical controls like fuse, switches, relay regulation, capacitor.
Periodic/ Regular Maintenance Brake down Shutdown maintenance. 127 <REGULAR MAINTANANCE @ PIPING> If PH is 7water is natural no remedy. If < 7water is basic. /Fungus formation started reduces efficiency / bad smell. Remedy:- prepare chlorine (HCL) of suitable concentration sol = remix into dosing pot (D.P) to remove the scale. If > 7 water is acidic erosion / occur impact reduce life of pipe / increase friction rate. Remedy:- prepare hydroxide (NaOH) of suitable concentration. 129 < REGULAR MAINTAINANCE @ PUMPS>
1. Close the pump fittings. 2. Lubricate the motor. 3. Tighten the nuts and bolts of coupling and isolator fittings and flanges. 4. Take out the filter from the strainer and clean. 5. Check the electrical controls, switches, fuse, relay, temp. gauge, pressure gauge. 6. Collect the water sample, send it to lab for water Ph value, to water treatment department. 7. Cut off the power supply and start the stand by.
131 FILTER:- Permanent Nylon for residential Temporary Paper for commercial to replaced for every 6 months. [regular maintenance @ chillers] 1. Clean the condensing unit by recommended cleaning agent. 2. Lubricate the fan motor of condensing unit. 3. Check the gas into the chiller via sight glass. 4. Check the oil via oil level or gauge. 5. Check the flow of CHW. 6. Rea & the temp & pressure of gas & CHW-@Inlet & outlet. 7. Tighten the nuts & bolts of chillers, chaser & cabinet & isolator.
After the expansion valve From condenser liquid To evaporator 30 Heat balance calculation for COOLING TOWER TO CALCULATE THE REQUIRED HEAT REJECTION FOR THE SCREW CHILLER 1. Cooling capacity of the screw chiller=300TR=300x3.516 KW=1055KW 2. Compressor = 205KW 3. Total heat rejection required=(1055+205)kw = 1260kw Capacity of the selected cooling tower 1. Water flow rate selected = 330CMH 2. Water inlet temp. to cooling tower = 38 C 3. Water outlet temp. from cooling tower=33C 4. Capacity of cooling tower= MC p ^T. where ^T=(water inlet temp. water outlet temp.) C M: MASS FLOE RATE THROUGH COOLING TOWER = (selected flow rate x Density of water Kg/s) / 3600 Cp: specific heat of water = 40186 K3/Kg.deg c CAPACITY OF COOLING TOWER = {330X1000X4.186X(38-33) } /3600 = 1918.58kw
35 Air delivery system Single zone system: 1AHU Required for one large Hall/zone- Adjustments are done to AHU Itself supply air: 4000cfm peak Load (partial Load) Temp=57F Typical supply Air temperature for commercial air conditioning.
VAV System:- The temperature of supply Air remain constant but the volume of the air supplied varies VAV Terminal = VAV Box with dampers, diffusers & control units.
Temperature recorded by the thermostat is noted by control unit of VAV terminal & the damper position is accordingly maintained to supply the air which will meet the requiremend of load. High load system supplies more air at constant CAV System:- The volume of air supplied is constant. But the Temp. of supply Air varies as per load. Two AHUs with ducting one producing cool air & other hot air.
Heating mode; 4000cfm; T=120 F
cooling mode; 4000cfm; T=57 F
Intermediate mode; 4000cfm; T=65 F Hot air Cool air Hot air Cool air Cool air Hot air CU T =25 C 36
S.NO SYSTEM PUPOSE FORMULA FROM 1. CHILLER FLOWRATE TRx2.4=us GPM Mcquay chillerdata 2. Chiller Power Consumption TRx1kw/tr=kw Asper chiller 1kw/tr=0.65 3. Cooling tower Flow rate Trx3=us GPM Mcquay chiller data 4. Cooling tower Power Consumption Trx0.0275=kw Assumption 5. Pump Power consumption Us GPMx0.054=kw Assumption 6. Ventilation car parking kitchen toilet ex. Power consumption Cfmx2.5/6356x0.7x 1.1=kw ISHRAE 7. Stair case lift, smoke Air volume Volume(quft)xno.airc/ hr/60=cfm ISHRAE (cooler) chiller 7 c 12 c condenser condenser T=12-7=5 c WBT+4 c=Ambient Temp. of the air. T=35-30=5 c 30 c 35 c T=37-32=5 c 32 c 37 c CT 83
Chiller Selection is based on : GPM System Capacity Entering Water Temp 55 F Chilled water Temperature Rise Chiller Tube surface Area =__Heat gain in BTU/hr_____ Loading Rate in BTU/hr/sq ft Loading Rate (LR) = Tons/ftsq It is the load in heat unit per surface are of chiller refrigerant tube for a given METD.
t = Entering water Temperature = 55 f t = Leaving water Temperature = 45 f tr = Chiller Refrigerant Temp (35 f 38 f) Chilled Water Hot Water Entering Temperature 55 F 160 F Leaving Temperature 12 F 180 F T 10 F 20 F METD= ___(t1 -t2 )______ 2.3 log (t1 - t2 ) (t2 - t1 ) Mean Effective Temperature Difference (METD) 85 Example:- If LR (Loading Rate)=2.16 Toms/ft find the METD & the chiller tube surface area for a 50 Tr System. METD=55-45/2.3LOG(55-36)/(45-36) =10/2.3LOG19/9 METD=13.39 Loading Rate (LR) = 2.16 Toons/ft 2.16x12000=25920Btu/hr/ft Chiller tube surface Area = 50x12,000 btu/hr
Cooling coil selection:- is based on. Entering DBT, Entering WBT Air temp, refrigerant coil no. of rows, fins facing, coil face velocity (velocity of air over face of the coil, it should not exceed 7000fpm) Chilled water coil selection is based on Entering Water temp, water Temp. Rise, Entering DBT & WBT, coil face Area. 2 2 2 25920 Btu/hr/ft 2 1/4 2/4 FPS = 10 x 24 x 30 = 7200 hrs/yr FPS = 8 Straight pipe:- Sec GPM FPS pipe dia. eq. length Fric Fric eq.lg. AB 200 8 3 12 _ _ CD 200 8 3 17 _ _ Valve:- Condenser:- Gate 200 8 3 4.0 7 0.28 Gate 200 8 3 100 7 7 7.28 Cooling Tower:- Gate 200 8 3 4.0 7 0.28 Gate 200 8 3 100 7 7 7.28 4/4 Condenser ft = 2.31 x P si = 2.31 x 13 = 30.03 ft Total ft. loss = 1.68 + 7.28 + 9.73 + 5.25 + 30.03 + 13.86 = 75.11 ft. Pump HP = GPM x total pressure loss 3960 x pump efficiency = 200 x 75.11 3960 x 0.8 = 4.74 HP = 5HP 3/4 PUMP:- Gate 200 8 3 4.0 7 0.28 Gate 200 8 3 100 7 7 Gate 200 8 3 35 7 2.45 9.45
ELBOWS:- 1 200 8 15 7 1.05 2 200 8 15 7 1.05 3 200 8 15 7 1.05 4 200 8 15 7 1.05 5 200 8 15 7 1.05 5.25 Note:- For cooling tower assume Fr. loss as 6 P si For condenser assume Fr. loss as 13 P si Cooling Tower ft = 2.31 x P si = 2.31 x 6 = 13.86ft