TESTING INSTRUMENT TRANSFORMERS

CT Testing Primary Insulation Resistance Dielectric Withstand Secondary Insulation Resistance Secondary Burden Saturation Ratio and Polarity Primary Ins. Resistance Test For Bar and Primary wound CTs DC voltage test at the rated crest voltage on the primary winding Secondary grounded 1 minute test

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


CT Insulation Resistance: Bar Type and Primary Wound

DC Voltage test
Isolate Primary Isolate & Gnd Secondary Connect HV lead to H1/H2 Connect LV to Gnd / 2ndary Test for 1 minute Record test value

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


CT Testing Primary Insulation Resistance Dielectric Withstand Secondary Insulation Resistance Secondary Burden Saturation Ratio and Polarity Dielectric Withstand Test For Bar and Primary wound CTs AC voltage test at the 75% factory test voltage Secondary grounded 1 minute test

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


CT Dielectric Withstand: Bar Type and Primary Wound

AC Voltage test
Isolate & Gnd Secondary Connect HV lead to H1/H2 Connect LV to Gnd / 2ndary Test for 1 minute Record test value

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


CT Testing Primary Insulation Resistance Dielectric Withstand Secondary Insulation Resistance Secondary Burden Saturation Ratio and Polarity 2ndary Ins. Resistance Test Test for secondary wiring Secondary wiring isolated and ungrounded 1000 VDC 1 minute test

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


CT Secondary Circuit Insulation Test

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


CT Testing Primary Insulation Resistance Dielectric Withstand Secondary Insulation Resistance Secondary Burden Saturation Ratio and Polarity 2ndary Burden Test Conducted in 2 parts Part 1, 1A current injection Measure circuit burden Part 2, four-wire resistance measurement Measure secondary winding resistance Burden = part 1 + part 2

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


Part 1: CT Secondary Circuit Burden Measurement

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


Part 2: CT Secondary Winding Resistance Measurement

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


Total burden calculation ZT = RCT + (RL + ZB) Where ZT

Total burden ()
DC Winding resistance () Lead resistance () Device impedance ()

RCT = RL = ZB =

3/31/2013

10

TESTING INSTRUMENT TRANSFORMERS


CT Testing Primary Insulation Resistance Dielectric Withstand Secondary Insulation Resistance Secondary Burden Saturation Ratio and Polarity Saturation Test Secondary winding excitation test Primary open circuited Step voltage increase, current proportional Test for knee-point voltage Rapid rise is I-excitation 10% V = 50% I

3/31/2013

11

TESTING INSTRUMENT TRANSFORMERS


CT Saturation test

3/31/2013

12

TESTING INSTRUMENT TRANSFORMERS


CT Testing Primary Insulation Resistance Dielectric Withstand Secondary Insulation Resistance Secondary Burden Saturation Ratio and Polarity Ratio and Polarity test Secondary winding excited at 1V per turn Primary open circuited H1-H2 compared to X1-X2 Phase measured, ratio calculated Phase difference 0 means polarity correct

3/31/2013

13

TESTING INSTRUMENT TRANSFORMERS


CT Ratio and Polarity Test

3/31/2013

14

TESTING INSTRUMENT TRANSFORMERS


CT Testing Primary Insulation Resistance Dielectric Withstand Secondary Insulation Resistance Secondary Burden Saturation Ratio and Polarity Ratio and Polarity test (ALT) Use individual meters, phase angle and voltmeter Secondary winding excited at 1V per turn Primary open circuited H1-H2 compared to X1-X2 Phase measured, ratio calculated Phase difference 0 means polarity correct
15

3/31/2013

TESTING INSTRUMENT TRANSFORMERS


CT Ratio and Polarity Test (alternate connections)

3/31/2013

16

TESTING INSTRUMENT TRANSFORMERS


VT Testing Insulation Resistance Dielectric Withstand Ratio and Polarity

3/31/2013

17

TESTING INSTRUMENT TRANSFORMERS


VT Testing Insulation Resistance Dielectric Withstand Ratio and Polarity Insulation Resistance Test DC voltage test at the rated crest voltage 3 tests HV to Gnd HV to LV LV to Gnd

3/31/2013

18

TESTING INSTRUMENT TRANSFORMERS


VT Insulation Resistance Tests

3/31/2013

19

TESTING INSTRUMENT TRANSFORMERS


VT Testing Insulation Resistance Dielectric Withstand Ratio and Polarity Dielectric Withstand Test AC voltage test at the 75% factory test voltage Secondary grounded 1 minute test

3/31/2013

20

TESTING INSTRUMENT TRANSFORMERS


VT Dielectric Withstand Tests

3/31/2013

21

TESTING INSTRUMENT TRANSFORMERS


VT Testing Insulation Resistance Dielectric Withstand Ratio and Polarity Ratio and Polarity test Primary winding excited at 1V per turns ratio Secondary open circuited X1-X2 compared to H1-H2 Phase measured, ratio calculated Phase difference 0 means polarity correct Compare ratio with nameplate
22

3/31/2013

NETA STANDARD
5. NETA Acceptance Testing Procedure
3/31/2013

5.1 Visual and Mechanical Inspection 5.2 Electrical Test 5.2.1 Current Transformer 5.2.2 Voltage Transformer 5.3 Test Value Analysis 5.3.1 Visual and Mechanical 5.3.2 CT Electrical Test 5.3.3 VT Electrical Test
23

TEST SET MANUAL


Module 3: CT Tester Module 2: 15 KV Insulation Resistance Test set AC High Potential Test set DC High Potential Test set Digital Low Resistance Test set

3/31/2013

24

TEST FORMS
Current Transformer Test Form Voltage Transformer Test Form

3/31/2013

25

3/31/2013

26

3/31/2013

27