Академический Документы
Профессиональный Документы
Культура Документы
BEFORE GOVERNOR
BLOCKED GOVERNOR
GOVERNOR
CHARACTERISTICS
DEAD BAND
TIME DELAY
DROOP RESPONSE IN SR
PTI TAPE
ORDERS
IEGC 1.6 IEGC 6.2 (e) & 6.2(f) IEGC 6.2 (g)
FREE GOVERNOR OPERATION
PRIMARY CONTROLS
Load dependent on frequency
NERC
2003
2002
2003 2002
Frequency Variation based on data integrated over ONE minute interval 49.0 & 49.5 & 50.5 & <49.0 Max Min Avg FVI <49.5 <50.5 Above 1.6 19.7 78.1 0.6 50.85 48.56 49.65 1.86 98.1 0.3 1.2 0.4 50.62 47.76 48.02 40.25
TG
SYSTEM
GOVERNOR
GOVERNOR
SPEED GOVERNOR IS THE CONTROLLING MECHANISM WHICH
CONTROLS THE INPUT TO THE PRIME MOVER AUTOMATICALLY WHEN THERE IS A CHANGE IN SYSTEM SPEED (FREQUENCY)
MISCONCEPTION
Governors attempt to restore frequency to normal.
In reality, Governors attempt to restore load generation balance, using frequency change as a signal.
CHARACTERISTICS
1. 2. Respond promptly to a small change in speed. Adjust the throttle valve with a minimum of overshoot. Have sufficient power to overcome friction losses and unbalance forces in the throttle valve. Permit very little speed fluctuation under constant load and steam conditions.
3. 4.
TYPES OF GOVERNORS
Mechanical
shaft Direct acting orifice Oil relay Precision oil relay Electronic governor
DEAD BAND
DEAD BAND OF THE SPEED GOVERNORING SYSTEM IS THE TOTAL AMOUNT OF CHANGE IN STEADY STATE SPEED WITHIN WHICH THERE IS NO ACTION BY GOVERNOR.
IN 50HZ BASE
0.075HZ
5 to 30mw
0.10
0.050HZ
> 30mw
0.06
0.030HZ
IEC - 45
DROOP CHARACTERISTICS
THE AMOUNT OF SPEED (OR FREQUENCY) CHANGE THAT IS NECESSARY TO CAUSE THE MAIN PRIME MOVER CONTROL MECHANISM TO MOVE FROM FULLY CLOSED TO FULLY OPEN.
NORMAL RANGE
3 TO 5%
THE MINIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE LESS THAN 0.4 TIMES OF ITS DROOP. THE MAXIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE MORE THAN 3 TIMES OF ITS DROOP.
160
GENERATION IN MW --->
120
80
40
FREQ IN HZ --->
500
GENERATION IN MW --->
400
300
100MW for 0.5HZ Frequency
200
100
40MW for 0.5HZ Frequency
500
500
GENERATION IN MW ---->
400
300
300
200
200
100
210 200
GENERATION IN MW ---->
150 125
100 85
50
350 300
MW ->
300
4 % DROOP
250
5 % DROOP
200
125
100
50
50.5
51
51.5
Steam flow
4 seconds
During transient state Governor is of little help. Effect is felt during steady state
BLOCKED GOVERNOR
BYPASSING THE GOVERNING FEEDBACK MECHANISM TO MAINTAIN FIXED GENERATOR OUTPUT.
DISADVANTAGES: SYSTEM INSTABILITY RESTORATION OF SYSTEM FREQUENCY TO NORMAL TAKES MORE TIME AFTER A DISTURBANCE.
Example:2200MW
200MW Generation Lost
0.5 Hz /second
220 50.4
FREQUENCY
210 50.2
200
50
MW->
GENERATION
170
49.4
49.2
160 11:00
11:15
11:30
11:45
12:15
12:30
12:45
49 13:00
HZ->
49.8
205
200
195
190
185
180
175
FREQ CHANGE 49.7 - > 50.4 0.7Hz GEN CHANGE 205 -> 177 35MW CHANGE IN GEN 28 MW FOR 0.7 Hz CHANGE IN FREQ FOR 200 MW CHANGE IN GEN FREQ CHANGE REQD = (200*0.7)/28 = 5 Hz i.e 5*100 /50 = 10% Droop
170 49.6
49.7
49.8
49.9
50
50.1
50.2
50.3
50.4
50.5
50.4
MW -->
GENERATION
49.8
49.6
FREQUENCY
49.4
49.2
11:45
12:00 TIME-->
12:15
49 12:30
HZ -->
190
185
180
175
170
165
FREQ CHANGE 49.9 - > 50.5 0.6Hz GEN CHANGE 191 -> 168 23MW CHANGE IN GEN 24 MW FOR 0.6 Hz CHANGE IN FREQ FOR 200 MW CHANGE IN GEN FREQ CHANGE REQD = (200*0.6)/24 = 5 Hz i.e 5*100 /50 = 10% Droop
160 49.8
49.9
50
50.1
50.2
50.3
50.4
50.5
50.6
50.7
51
350
FREQUENCY
50.5
300
250
50
200
150
49.5
100
GENERATION
50
49
0 0 2 4 6 8 10 12 14 16 18 20 22 0
48.5
FREQ ->
MW
350
300
250
200
150
100
50
0 49.3
49.4
49.5
49.6
49.7
49.8
49.9
50
50.1
49.1
49.2
49.3
49.4 POINT C
49.5
49.6
49.7
49.8
49.9
POINT D
POINT B
POINT A
BACKLASH
The distance through which one part of connected machinery, as a
wheel, piston, or screw, can be moved without moving the connected parts.
BOILER CONTROLS
BOILER FOLLOWING SYSTEM
50
ADVANTAGES
1. Reduce the random change of frequency 2. Mitigate effect of load generation mismatch 3. Prevents wastage of fuel during low load condition 4. Faster restoration from grid disturbance
PROBLEMS
1. 2.
3.
4. 5.
Steam deposits on the valve stem . Lubrication deposits (i.e., soaps, dirt, detergents, etc.) in the top works of the valve exposed to the elements. Mechanical failures of the valve resulting from bent stems, either in the valve proper or the upper works, damaged split couplings, etc., all within about a 6" area near the center of the valve mechanism. Galling of the piston in the hydraulic latch cylinder. Jamming of the screw spindle in the larger cylinder-type valve design due to forcing by operations personnel
Most equitable
Reduces risk of collapse
200
360
GENERATION IN MW --->
190
300
180
240
170
180
AT 50 HZ GEN= 190MW
120
150
60
140 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
0 50.5
FREQ IN HZ --->
UI PRICE -->
OVER GENERATED BY 5%
210
GENERATION INCREASED BY 10 MW
360
GENERATION IN MW --->
190
300
180
240
170
180
160
120
150
60
140 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
0 50.5
FREQ IN HZ --->
UI PRICE -->
OVER GENERATED BY 5%
210
200
360
GENERATION IN MW --->
190
300
180
240
170
180
160
120
150
60
140 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
0 50.5
FREQ IN HZ --->
UI PRICE -->
200
360
GENERATION IN MW --->
190
300
180
240
170
180
AT 50 HZ GEN= 190MW
120
150
60
140 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
0 50.5
FREQ IN HZ --->
UI PRICE -->
INITIAL
420
360
GENERATION IN MW --->
190
300
180
240
170
180
160
120
150
UI PRICE = 84 Ps
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
60
140
0 50.5
FREQ IN HZ --->
UI PRICE -->
INITIAL
420
360
GENERATION IN MW --->
190
300
180
240
170
180
160
120
150
UI PRICE = 84 Ps
60
140 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
0 50.5
FREQ IN HZ --->
UI PRICE -->
FINAL
420
GENERATION IN MW --->
190
300
180
240
170
180
160
120
150
60
140 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
0 50.5
FREQ IN HZ --->
UI PRICE -->
5% DROOP OF 210MW UNIT OF STATION A SINCE VARIABLE COST OF VARIABLE COST = 140 Ps
STATION A > UI PRICE
210
FINAL
420
200
360
GENERATION IN MW --->
190
300
180
240
170
180
160
120
150
60
140 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4
0 50.5
FREQ IN HZ --->
UI PRICE -->
PROPORTIONAL CONTROL
A simple form of control, where the controller response is proportional to the control error.
Kc
FB
Provides immediate controller response to setpoint change, but speed may not settle exactly on SP using proportional control alone
INTEGRAL CONTROL
Control action is control error integrated over time.
Kc
1/Tc
fdt
FB
Integrates the error over time to overcome the offset from Proportional alone such that speed = SP. However, Integral action may cause overshoot, oscillation and/or instability problems
DIFFERENTIAL CONTROL
In differential control, control action is based on the change (derivative) of the control error.
Kc
Td
df/dt
FB
Used to put the reigns on PI control to prevent overshoot and oscillation and to add stability
PID CONTROL
A form of control based on the three basic types of control: proportional, integral and differential control. PID Controllers are created by combining P, I and D elements to get the desired control characteristic.
OPEN
QUOTE
1.6
Free-Governor Action: The dates from which the stipulations under sections 4.8(c), 4.8(d), 6.2(e), 6.2(f), 6.2(g) and 6.2(h) would come into effect shall be as under : (i) All thermal generating units of installed capacity 200 MW and above and reservoir based hydro units of installed capacity 50 MW and above : } } Eastern Region } } Northern Region } The date for the } implementation of the Western Region } Commercial mechanism } mentioned in Section 7.1(d) (ii) All thermal and reservoir based hydro } for the respective region. generating units of installed capacity } 10 MW and above in North Eastern Region } (iii) All other generating units - three months after the above dates for the respective regions except in the case of Nuclear Power Stations which shall be exempted till the next review of the IEGC. Any exemption from the above may be granted only by CERC for which the concerned constituent shall file a petition in advance.
UNQUOTE
Southern Region
QUOTE
6.2(e)
All generating units, which are synchronised with the grid, irrespective of
their ownership, type and size, shall have their governors in normal operation at all times. If any generating unit of over fifty (50) MW size (10 MW for North Eastern Region) is required to be operated without its governor in normal operation, the RLDC shall be immediately advised about the reason and duration of such operation. All governors shall have a droop of between 3% and 6%. 6.2(f) Facilities available with/in load limiters, Automatic Turbine Run up System
(ATRS), Turbine supervisory control, coordinated control system, etc. shall not be
used to suppress the normal governor action in any manner. No dead bands and/or
time delays shall be deliberately introduced.
UNQUOTE
QUOTE
6.2(g) All Generating Units, operating at/up to 100% of their Maximum Continuous
Rating (MCR) shall normally be capable of (and shall not in any way be prevented from) instantaneously picking up five per cent (5%) extra load for at least five (5) minutes or within technical limits prescribed by the manufacturer when frequency falls due to a system contingency. The generating units operating at above 100% of their MCR shall be capable of (and shall not be prevented from) going at least up to 105% of their MCR when frequency falls suddenly. Any generating unit of over fifty (50) MW size (10 MW for NER) not complying with the above requirement, shall be kept in operation
(synchronised with the Regional grid) only after obtaining the permission of RLDC.
However, the constituent can make up the corresponding short fall in spinning reserve by maintaining an extra spinning reserve on the other generating units of the constituent.
UNQUOTE
QUOTE
6.2(h) The recommended rate for changing the governor setting, i.e. supplementary
control for increasing or decreasing the output (generation level) for all generating .units, irrespective of their type and size, would be one (1.0) per cent per minute or as per manufacturer's limits. However, if frequency falls below 49.5 Hz, all partly loaded generating units shall pick up additional load at a faster rate, according to their capability.
UNQUOTE
FREE GOVERNOR MODE OF OPERATION The matter discussed in 368 OCC meeting
th
All SR constituents/ISGS agreed to convey their readiness by 21.01.2003 SRLDC again requested all constituents vide letter dt.21.01.03 to intimate unit/station wise status/ programme Matter discussed in 109th TCC/131st SREB meeting.
ISGS/SR constituents agreed for FGM by 1st May 2003. Discussed in 369th, 370th, 371st & 372nd OCC meetings.
KSEB & TNEB furnished unit wise/ station wise program/ constraint/ preparedness APTRANSCO conveyed readiness for FGM of all generators except thermal units of APGENCO Freq response characteristics calculation details covering 3 events furnished for examination & necessary feedback by the constituents. Constituents
AP KAR KER TN
Actual response
(AVG)
Shortfall
(AVG)
2% 17 % 29 % 13 %
98 % 83 % 71 % 87 %
210 50.2
200
50
49.8 190 49.6 180 REDUCTION OF 21 MW IN 5 MTS NYL U-4 GENERATION 170 49.2 49.4
49 13:00
Thank you