Вы находитесь на странице: 1из 79

1 1 > Busbar Protection

Busbar Protection
Busbar Protection:
Including High Impedance,
Frame Leakage and
Directional Comparison
Principles
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
2 2 > Busbar Protection
Busbar Protection
There are fewer faults
on busbars than on
other parts of the
power system
F
2
F
1
Without Busbar Protection
No dislocation of system due to accidental operation of busbar
protection
Slow Fault Clearance
Busbar faults at F1 and F2 are cleared by remote time delayed
protection on circuits feeding the faults:
Time Delayed Overcurrent or
Time Delayed Distance Protection
3 3 > Busbar Protection
Busbar Protection
F
2
F
1
Busbar
Zone

With Busbar Protection
Fast clearance by Breakers at the Busbars
Where Busbars are sectionalised, protection can limit the amount of
system disruption for a Busbar fault
4 4 > Busbar Protection
Busbar protection must be
Reliable
Failure could cause widespread damage to the substation
Stable
False tripping can cause widespread interruption of
supplies to customers
Discriminating
Should trip the minimum number of breakers to clear the
fault
Fast
To limit damage and possible power system instability
5 5 > Busbar Protection
Busbar faults are usually permanent
CAUSES
Insulation failures
Circuit breaker failures
Falling debris
Isolators operated outside their ratings
Safety earths left connected
Current transformer failures
THEREFORE:
CIRCUIT BREAKERS SHOULD BE TRIPPED AND
LOCKED OUT BY BUSBAR PROTECTION
6 6 > Busbar Protection
Methods of providing Busbar protection
1. Remote Time Delayed Protection
2. Frame to Earth (Leakage) Protection
3. Directional Comparison Protection
4. Phase Comparison Protection
5. Differential Protection: High Impedance
Low Impedance
7 7 > Busbar Protection
Frame leakage protection
ADVANTAGES
1. Simple and economic form of protection
2. Ideal for the protection of phase segregated switchgear where
earth fault protection only is required

DISADVANTAGES
1. Insulation is required between switchgear sections
2. It is not possible to discriminate between faults on two sets of
busbars running through common switchgear frames
3. Care must be taken in construction of the substation in order to
ensure that the fixing bolts do not come in to contact with the
steel reinforcing of the concrete
8 8 > Busbar Protection
Frame earth protection scheme
Only an earth fault system
Involves measuring fault current from switchgear frame to
earth
Switchgear insulated by standing on concrete plinth
Only one earthing point allowed on switchgear
C.T. mounted on single earth conductor used to energise
instantaneous relay
All cable glands must be insulated
9 9 > Busbar Protection
Single Zone Frame - Earth Protection
64
G

Frame-earth
fault relay
H

J

K

+
Trip all circuit breakers
Switchgear frame
10 10 > Busbar Protection
Current Distribution for External Fault
Generator
Frame-leakage current
transformer
Switchgear frame
Switchgear frame
bonding bar
Outgoing feeder
System earthing resistor
Earth bar
Earthing electrode
resistance
Frame insulation
resistance to earth
I
1
+ I
2
I
2
I
1
I
1
I
F
=I
1
+ I
2
11 11 > Busbar Protection
Frame leakage Busbar protection
External Fault
I
1
I
1
>10
I
2
<1
I
1
+ I
2
I
F
=I
1
+I
2
I
1
= < 0.1I
F
64
12 12 > Busbar Protection
Frame leakage Busbar protection
INTERNAL FAULT
Suitable for phase segregated indoor metalclad
switchgear. Only E/F protection required.
I
1
I
2
Frame
Insulation
>10
I
2
I
1
+ I
2
I
F
=I
1
+I
2
Frame
System
Earthing
Resistance

Substation
Earthing
Electrode
<1
Earth Bar
64
Setting of
Instantaneous E/F
Relay (64)
= < 0.3 IF(Min)
= > 0.1 IF(Max)
Disadvantages:
Insulation of switchgear frame and between sections
Insulation of cable glands to prevent spurious currents
during through faults
13 13 > Busbar Protection
Frame leakage scheme
with double insulation barrier
64
Z1
Trip A

B

A

Insulation Barrier

Zone 1

Zone 2

C

Trip B

96
C
Trip C
Zone 3

96
A
96
B1
64
Z2
96
B2
14 14 > Busbar Protection
Frame leakage scheme
with single insulation barrier
64
Z1
Trip A
B

A

Insulation Barrier

Zone 1

Zone 2
C

A
Trip B
B1 B2
T
C Trip C
0.2 -1 SEC.

64
Z2
15 15 > Busbar Protection
Frame leakage scheme for duplicate Busbars
64
Z1
B

A

Insulation Barrier

Zone 1

Zone 2

c
Zone 3

+
64
Z3
R

M1

a

b

D

d

C

96
A
a

b

96
D1
96
D2
96
B1
96
B2
96
C
c

d

M1

M2

R

M2

-
16 16 > Busbar Protection
Frame leakage protection
Check feature
To differentiate between a genuine busbar fault and a fault
in the secondary winding of a c.t.
The check feature provides a second line of defence
The check relays pick up for both internal and external faults
Both check and discriminating relays must operate before
tripping can occur
The various methods of obtaining the check feature are:-
a) Neutral check provided by a relay energised from a single c.t.
in the power system neutral
b) Residual check provided by a relay energised from a residually
connected c.t. on the busbar incomers
c) Residual voltage check provided by a voltage relay energised
from a broken delta v.t. supply
Check relays are normally self-reset in order to avoid having
to reset the relay after each external fault
17 17 > Busbar Protection
Single Zone Frame Earth Protection
With Neutral Check
64
+

G H
64
CH
Neutral check relay
Trip all circuit
breakers
Frame-earth
fault relay
J K
Switchgear frame
18 18 > Busbar Protection
Typical Trip And Alarm Circuits For Frame Leakage
With Double Insulation Barrier And Check Feature
CSS-Z1

+
-
96
A
In

Out

64Z1-1

In

Out

CSS-Z2

64Z2-1

96
B1
96
B2
96
C
Trip Supply
Supervision

64CH-1
Alarm
Relay
74

64CH-2

64Z1-2

64Z2-2

74-1

74-2

Lamp
Lamp
Lamp
Lamp
Buzzer
In Out

In Out

CSS-Z1

CSS-Z2

Alarm
Supply
Supervision

Lamp
19 19 > Busbar Protection
Directional Comparison Scheme
R
+

(a)

Trip
R
R
+

(b)

Trip
R
BR
Load
current
Phase to earth external
fault, scheme (a)
20 20 > Busbar Protection
Directional Comparison Scheme
R
+

(a)
Trip
R
R
+

(b)

Trip
R
BR
Load
current
Phase to earth external
fault, scheme (b)
21 21 > Busbar Protection
Phase Comparison Scheme - External Fault
Positive Half Cycle Negative Half Cycle
A
B
A
B
B A B
Feeder X
A B A
Feeder Y
Relay Operation
Current Transformer
Secondary Current
+

Trip
+

Trip
X
Y X Y
22 22 > Busbar Protection
Phase Comparison Scheme - Internal Fault
A
+

B
A
B
Trip
Trip
A B A
Feeder X
A B A
Feeder Y
Relay Operation
Current Transformer
Secondary Current
X Y
X
Y
Positive Half Cycle Negative Half Cycle
+

23 23 > Busbar Protection
Basic Circulating Current Scheme
External Fault
R
R
Internal Fault
24 24 > Busbar Protection
Differential Protection
Uses Merz-Price circulating current principle. All currents
entering and leaving Busbar are compared
One set of CTs for each circuit associated with a particular
zone are all connected to a relay
A single element relay gives earth fault protection only
A three element relay gives phase and earth fault protection
25 25 > Busbar Protection
Basic Circulting Current Scheme
Earth Fault Protection Only
G

H

J

K

87

Differential
relay

26 26 > Busbar Protection
Phase And Earth Fault Circulating Current
Scheme Using Three-Element Relay
G

H

A

B

C

N

Differential
relay

87A

87B

87C

27 27 > Busbar Protection
High Impedance Protection
This is a versatile and reliable protection system applied to
many different Busbar configurations
If CT requirements are met, scheme performance may be
predicted by calculation without heavy current conjunctive
tests
28 28 > Busbar Protection
High Impedance Busbar Protection
Simple system to apply and extend
High Sensitivity for phase and earth faults
Extremely stable for external faults
29 29 > Busbar Protection
High Impedance Busbar Protection
R
ST
87

Metrosil

CT Requirements: Equal ratios
Class X
May require stabilising resistors, R
ST
May require non-linear resistors (Metrosils)

30 30 > Busbar Protection
High Impedance Differential Protection
Uses equal ratio CTs
Scheme assumes that with heaviest through fault, one CT
saturates, the other not
To ensure stability, voltage setting of relay circuit made
higher than voltage developed across relay circuit. To
achieve this an extra relay circuit resistance is required.
This is known as the stabilising resistance

31 31 > Busbar Protection
Equivalent Circuit
Y

Z
M
R
CT
R
LY
R
LX
R
CT
R
ST
R
R
R

Z
M
X

32 32 > Busbar Protection
High Impedance Theory
R
S

I
F
R
CT
Assume one CT saturates
Assume relay resistance is high
V = I
F
(2
RL
+ R
CT
)
V
S
> V
R
L
I
F
R
L
R
CT
R
L
R
L
V

33 33 > Busbar Protection
High Impedance Theory
Choose I
S
from min fault current ( 30%)
V
S
= I
S
R
S
+ I
S
R
R

I
S
R
S
= V
S
I
S
R
R

R
S
= - R
R

R
S
=
I
S
R
S
R
R
V
S
S
S
I
V
2
S S
S
I
VA
-
I
V
Thus we can choose a value of R
S
:-
Knowing 1) Max. & Min Fault Levels,
2) C.T. Circuit Impedances,
3) Relay Information,
4) C.T. Ratio,

34 34 > Busbar Protection


Primary Operating Current (P.O.C.)
The value of primary operating current should be around
30% of minimum fault current available. This ensures
sufficient relay current during internal fault conditions for
high speed operation

35 35 > Busbar Protection
Differential Relays
Relays used for high impedance protection are high
stability, unbiased and tuned to nominal frequency.
Two modular types are available:-
MCAG14/34
Current calibrated with external stabilising resistor
MFAC14/34
Voltage calibrated with internal high impedance

36 36 > Busbar Protection
Knee-Point Voltage Definition
For High Impedance Protection Choose V
K
such that:
V
K
> 2V
S
This ensures fast operation for all faults greater than the setting
current.
V
K
is thus dependent on setting voltage and hence on maximum
through fault current.
I
CK
E
x
c
i
t
i
n
g

V
o
l
t
a
g
e

(
V
S
)

V
K
Exciting Current (I
e
)
+10% V
K
+50% I
eK
37 37 > Busbar Protection
Internal fault on high impedance scheme
Z
m
R
ST
V
F
= I
F
.R
= I
F
.

Effective setting

I
S
= I
R
+ 2I
e
with 2 circuits
= I
R
+ nI
e
with n circuits

Primary effective setting

I
P
= T.(I
R
+nI
e
)
Or I
P
= T.(I
R
+ nI
e
+I
M
+I
SR
+I
V
)
R
CT
V
F
R
LY
R
LX
R
CT
R

Z
m
X

I
F
) R + (R
I
I
LX CT
R
Y
F

Y

38 38 > Busbar Protection
Use of fault setting resistor
I
0P
= I
R
+ I
SR
I
0P
I
SR
R
SR
I
R
R
ST
R
R
39 39 > Busbar Protection
Metrosil limitation of relay voltage
I
R
R
R
For heavy internal faults large voltages may develop across relay +
Stab. Resistor.

>3kV Voltages must use Metrosil

V
P
=
V
K
= Knee point voltage
V
F
= Max. RMS voltage if C.T. didnt saturate
= I
F
(R
CT
+ 2R
L
+ R
ST
+ R
R
)

For Metrosil:
V = CI

(D.C.)
= C (A.C.)
V
S
R
ST
I
m
V

I
OP
) V - (V 2V 2
K F K
|
(

52 . 0
I
RMS
V
M
S
V 2
40 40 > Busbar Protection
Use of Non Linear Resistors
Under in zone fault conditions it is possible for voltages above the
relay withstand of 3kV peak to be produced. Metrosil non linear
resistors may be necessary to limit the peak voltage below this
level
Approx peak volts =
Metrosil characteristic:- V = CI


where:- V and I are peak values
C = constant depending on metrosil
construction
= constant in range of 0.2 to 0.25

The values of C and are chosen to limit metrosil voltage to less
than 3kV peak at maximum fault current




) V - (V 2V 2
K F K
41 41 > Busbar Protection
Metrosil Limitation Of Relay Voltage
I
R
R
R
To ensure primary operating current not adversely affected,
metrosil constant C must be sufficiently high to restrict metrosil
current at relay setting voltage VS.

Typical currents:-
30mA for use with 1 amp CTs
100mA for use with 5 amp CTs
V
S
R
ST
I
NLR
I
OP
V
MLR
R

42 42 > Busbar Protection
CT Wiring Supervision
Open circuit connections between CTs and relay circuit result in
unbalance currents which may operate the protection.
Supervision is applied by a voltage relay across differential relay
circuit
Supervision relay is time delayed, gives alarm and also shorts out
bus wires to protect differential relay circuit
Typical effective setting is 25 primary amps or 10% of lowest
circuit rating, which ever is greater.




43 43 > Busbar Protection
Healthy Condition
Z
M4
CT
4
I
4
Z
M3
CT
3
Z
M2
CT
2
I
2
I
3
Super
Vision
Relay

R
R
R
ST
Z
M1
CT
1
I
1
I
1
= I
2
+ I
3
+ I
4
44 44 > Busbar Protection
Supervision Against Open Circuit C.T.s
I
4
Z
M2
I
1
Super
Vision
Relay

R
R
R
ST
CT1 open circuit, I1 flows through magnetising impedance and relay circuit
in parallel

Voltage measured by supervision relay
V = I1 (RZ
M2
Z
M3
Z
M4
)
If Supervision relay setting = V
SP
Out-of-balance current to operate the supervision relay

V

R

Z
M4
Z
M3
I
1
I
3
I
2
M4
SP
M3
SP
M2
SP SP
Z
V
+
Z
V
+
Z
V
+
R
V
= I
45 45 > Busbar Protection
Differential Relay Circuit
A

Metrosil
resistors

B

C

N

87

V

87

V

87

V

95X

95X

95X

Stabilising
resistors

95

Supervision
relay

Bus wire shorting contacts

Zone bus
wires

46 46 > Busbar Protection
Current Transformers
Current transformers must be of low reactance type (classx) and
have identical turns ratio (1 in 100)
They should be of similar design, or if not, of reasonably matched
magnetic characteristics
It is common practice to use CTs having 1 amp secondaries




47 47 > Busbar Protection
Current Transformer Wiring
Lead burdens between various sets of CTs must be kept low.
Usually buswires are run in closed ring between breaker control
panels.
Typical route:-
CTs to marshalling kiosk
Marshalling kiosk to isolator auxiliaries
Loop between marshalling kiosks
Conductor size:-
Normally 2.5mm
2





48 48 > Busbar Protection
Effect of C.T. Location
on Busbar Protection Performance
(a)Overlapping C.T.s


Circuit
Protection

F
1
Busbar
Protection

F
3
F
4
F
2
(b)All C.T.s on line side of
circuit breaker
F
1
Circuit
Protection

F
3
F
2
Busbar
Protection

Interlocked
Overcurrent
Relay

(c)All C.T.s on Busbar side of
circuit breaker
F
1
Interlocked
Overcurrent
Relay

F
3
F
2
Circuit
Protection

Busbar
Protection

49 49 > Busbar Protection
Zones of Protection for Double Bus Station
BC

Zone G

Typical feeder circuits

Zone H

BS

Zone J

BC

50 50 > Busbar Protection
Check Feature
Zone B

Usually provided by duplication of primary protection using second set of CTs on
all circuits other than bus section and coupler units. Check system forms one
zone only, covering whole of busbar systems and not discriminating between
faults on various sections.

87B

87
CK

Check Zone

87A

Zone A

51 51 > Busbar Protection
Isolator Auxiliary Switches
R

Auxiliary Switches Should:
1) Close before the isolator closes
2) Open after the isolator opens
in order to maintain stability on switching
A

Buswires

M

B

C

D

m

r

a
b

c
d

52 52 > Busbar Protection
Busbar Auxiliary Switches Requirements
Reserve Bar

Normal Operating Condition
R

R

Main Bar

53 53 > Busbar Protection
Busbar Auxiliary Switches Requirements
On-Load Transfer
R

R

Main & reserve zones
Ultimately paralleled by
reserve busbar selector
auxiliary switches

54 54 > Busbar Protection
Circuit Breaker Bypass
M

R

A.C.
Buswires

M

c1

b1

a1

c2

b2
a2

a
1

b
1

c
1

R

N

CH

N

a
2

b
2

c
2

a
1

b
1

55 55 > Busbar Protection
Circuit Breaker and CT Bypass
M

R

M

b1

a1

R

N

CH

N

Check
Zone
CTs
Normally
Shorted

AC
Buswires

a
1

b
1

56 56 > Busbar Protection
Tripping Circuits
One tripping relay (device 96) is required for each feeder
breaker and 2 for each bus section or bus coupler breakers
Both main and check relays must be energised before
tripping relays trip all breakers associated with zone



57 57 > Busbar Protection
Typical Trip Relay Arrangement
Double Busbar System
-

+

CSS M1

CSS M2

CSS - R

In

Out

87M1 - 1

87M2 - 1

87R - 1

96
D1

M1M2R

a1

c1

96
D2

96E

96
F1

96
F2

96G

b1

c2

96
H1

96
H2

87CH - 1

80T

D.C. Buswires

58 58 > Busbar Protection
Through Fault Stability
Busbar protection stability is based on maximum through fault
current
Generally this value is derived from the rating of the associated
switchgear irrespective of existing fault level, since it can be
expected that system will develop up to limit of rating




59 59 > Busbar Protection
Earth-fault protection for busbars and other primary plant
connections (one relay per zone)
T

A

A

A

D

G

H

K

Relay
Circuit

G

K

H

E
F

B

B

B

T

T

C

C

C

V
s
Rated stability limit phase
to earth external fault
V
s
> TxI
F
x(2H+2K+F+C)

OR: -
I
F
60 60 > Busbar Protection
Earth-fault protection for busbars and other primary plant
connections (one relay per zone)
T

A

A

A

D

G

H

K

Relay
Circuit

G

K

H

E
F

B

B

B

T

T

C

C

C

V
s
Rated stability limit phase
to earth external fault
V
s
> TxI
F
x(A+D+2G)

OR: -
I
F
61 61 > Busbar Protection
Earth-fault protection for busbars and other primary plant
connections (one relay per zone)
T

A

A

A

D

G

H

K

Relay
Circuit

G

K

H

E
F

B

B

B

T

T

C

C

C

V
s
Rated stability limit phase
to earth external fault
V
s
> TxI
F
x(B+E+2H)

whichever is the
greatest.
I
F
62 62 > Busbar Protection
Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
G

H

Relay
Circuit

G

H

E

F

T

T

A

A

A

D

K

K

B

B

B

T

C

C

C

K

K

G

G

H

H

Relay
Circuit
Relay
Circuit
I
F
Rated stability limit phase
to phase external fault
V
s
V
s
V
s
> TxI
F
x(H+K+C)

OR: -
63 63 > Busbar Protection
Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
G

H

Relay
Circuit

G

H

E

F

T

T

A

A

A

D

K

K

B

B

B

T

C

C

C

K

K

G

G

H

H

Relay
Circuit
Relay
Circuit
I
F
Rated stability limit phase
to phase external fault
V
s
> TxI
F
x(A+G)

OR: -
V
s
V
s
64 64 > Busbar Protection
Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
G

H

Relay
Circuit

G

H

E

F

T

T

A

A

A

D

K

K

B

B

B

T

C

C

C

K

K

G

G

H

H

Relay
Circuit
Relay
Circuit
Rated stability limit phase
to phase external fault
V
s
> TxI
F
x(B+H)

whichever is the
greatest
I
F
V
s
V
s
65 65 > Busbar Protection
Busbar Protection With Separate Relays Per Circuit
Breaker Basic Scheme
1

2

TR

+

+

1

+

+

2

+

2

D

CH

2

1

D

CH

TR

+
1

66 66 > Busbar Protection
Busbar Protection With Separate Relays Per Circuit
Breaker Basic Scheme With Additional Tripping Route
1

2

TR

+

+

2

+

+

1

+

2

D

CH

2

1

D

CH

TR

+

1

+

+

2

1

TR

+

+

TR

1

2

STN

+

67 67 > Busbar Protection
Busbar Protection With Separate Relays Per Circuit
Breaker Basic Scheme With Additional Relays Per Zone
And Back Tripping Facilities
1

2

TR

+

+

2

+

+

1

+

2

D

CH

2

1

D

CH

TR

+

1

STN

2

+

CH

BT

BT

+

1

D

+

68 68 > Busbar Protection
Busbar Protection With Separate Relays Per Circuit
Breaker Basic Scheme With Additional Relays Per Zone
And Back Tripping Facilities With Separate Trip Relays
1

2

TR

+

+

2

+

+

1

+

2

D

CH

D

CH

TR

+

1

+

STN

2

CH

BT

BT

D

+

+

2

1

+

+

1

2

TR

TR

+

1

69 69 > Busbar Protection
Double Busbar With Transfer Facilities
Main

By-Pass
Isolator
Reserve/ Transfer

By-Pass
Isolator
70 70 > Busbar Protection
Triple Busbar
Main

Transfer
CB.
Reserve

Transfer
Transfer
CB.
71 71 > Busbar Protection
1 Breaker Scheme
72 72 > Busbar Protection
1 Breaker Bus Protection
87
87
73 73 > Busbar Protection
Mesh Busbar
F4
T1
F1
T4
F3
T3
F2
T2
74 74 > Busbar Protection
Mesh Busbar Protection
F4
T1
F1
T4
F3
T3
F2
T2
87
R1
87
R3
87
R4
87
R2
75 75 > Busbar Protection
Busbar Protection and Breaker Fail
Where breaker fail protection is applied to a system, back
tripping of associated breakers is required in the event of a
breaker failure
Often, breaker fail protection is arranged in conjunction with
busbar protection tripping circuits to initiate tripping of
breakers on a busbar zone associated with the failed
breaker




76 76 > Busbar Protection
Midos Relays for High Impedance Protection
Differential Relay MCAG34 or MFAC34
Supervision Relay MVTP31
Tripping Relay (Hand Reset) MVAJ13
No Volt Relay MVAX12
Zone Indication Relay MVAA13




77 77 > Busbar Protection
Modern Low Impedance Busbar Protection
Fast
Modular scheme design allows relays to relate to each circuit and
function of the protection. This enables the user to easily
understand the principles of application
High sensitivity for phase and earth faults. Protection for each
phase can be relatively independent
Earlier schemes were less stable than high impedance schemes.
Modern schemes incorporate saturation detectors and are
extremely stable
Duplicate measuring circuits are included
Current transformers can be:
Of different ratio
Of relatively small output
Shared with other protections
Current transformer secondary circuits are not switched
Continuous supervision of CT circuits and constant monitoring of
vital circuits are included
78 78 > Busbar Protection
MBCZ 10 Single Bus Protection
F1
FM1
Z1
Z1
ZCK
Z1
FM2 BSM
BS
FM3
Z2
FM4
Z2
ZCK
Z2
F2 F3 F4
ZCK
79 79 > Busbar Protection
MBCZ 10 Double Bus Protection
Z1
Z1
FM1 BSM
BS
Z1
ZCK
Z3
ZCK
BC1
BCM
1
Z3
Z3
FM2
Z2
F2
F1
Z4
F3
FM3
Z2
Z4
FM4
F4
BC2
BCM
2
Z2
Z4
ZCK

Вам также может понравиться