Ralph Mackiewicz, SISCO Inc. Marketing Committee Chair UCA International Users Group 1 September 2004
Objective
To provide a framework for substation engineers to identify the benefits of using IEC61850 technology for substation automation (SA) projects.
Justification
Cost
Traditional Approaches
IEC61850 Approaches
Payback Purchase
Time
IEC61850 is Unique
Not a recast serial RTU protocol Designed specifically for LANs to lower life cycle cost to use a device:
Cost to install, configure, and maintain
Ground Rules
Qualitative analysis based on comparison of legacy approaches versus IEC61850 approach
Simplified Examples Shown.
?
Tag Data Base
Driver 1 Driver 2 Driver 3
Gateway/RTU
IED
IED
IED
IED
IED
Protocols used have limited capabilities. Difficult or no access point for other apps. Comm. path must be reconfigured when new devices or applications are added.
Network Hub
IED
IED
IED IED
Gateway
IED
IED
Legacy Devices
SCADA
Manually entered. Manually verified. Applications tied to tag or free form alias. Any tag conventions are proprietary.
Data Objects
PhV
A
MMXU2
Logical Nodes
MMXU1
Physical Device
(network address)
Brand Y
Diff Relay
PIOC
ST DC
Measurements MMXU1
PDIF
ST DC
Measurements MMXU1
DC MX
PhV PhV
DC MX
PhV PhV
Mod
Mod
Mod
Mod
Point names can be retrieved from the device automatically without manual intervention.
All devices share a common naming convention.
Benefits
Reduced configuration costs from common naming and automatic point configuration and retrieval. Equipment migrations occur with minimal impact on applications. Application changes have minimal effect on devices, network or other applications.
Justification
Description
Equipment Purchase
Installation
Legacy
$ $ $$$ $$$ $$$
Network
$$ $ $ $ $
Impact
0 + + +
Configuration
Equipment Migration Application Additions
Legacy Architecture
Breaker
Relay 2 1
Breaker
2 5 6 Relay 3 3
Breaker
Relay 1 4
Relay 4
Hardwired signals for relay to relay links
Breaker
Legacy Architecture
Requires N*(N-1)/2 links for N relays.
Requires filtering on links to prevent false trips. Reprogramming can require rewiring.
Relay 1
Breaker
Relay 2
Breaker
Relay 3
Breaker
Relay 4
Breaker
GOOSE - Generic Object Oriented Substation Event (data sets) GSSE Generic Substation Status Event (status)
Benefits
Reduction of wiring costs More flexible programming is independent of wiring Reliability: Link status known before use. New capabilities not cost-effective with hardwired systems. Higher performance with more data.
Hardwired Performance
8-20ms
Signal
Contacts Close
Time
Input Threshold Reached
Network Performance
< 4 ms Using GSSE over Ethernet
Signal
Time
Improved Performance
Network access with collisions resolves very fast.
Data is transmitted multiple times to avoid missing data. Digital error checking instead of analog filtering.
Justification
Description
Equipment Purchase Installation Configuration Protection changes Flexibility
Network $$ $ $ $ $
Impact + 0 + +
Conclusion
IEC61850 substation architectures provide significant benefits to users.
Key intangible: flexibility to accomplish new objectives that are too costly (or not possible) with legacy technology. Justification is challenging but realistic.
IEC61850 Demonstration
The UCA International Users Group is sponsoring a demonstration of IEC61850 technology at Stand 48 in the exhibition hall.
IEC61850 Demonstration
IEC61850 Demonstration
Please come and visit us at Stand 48. Learn about the benefits of joining the UCA International Users Group. Learn about IEC61850.
Thank You