Generator Excitation System & AVR

20 July 2013 PMI Revision 00 1

Presentation outline
Understanding basic principle Types of excitation

Components of excitation system


Brief Description of most commonly used Excitation systems in power generating plants:

AVR

Static Excitation system


Brushless Excitation System

20 July 2013

Experience sharing
Conclusion
PMI Revision 00 2

What is Excitation system?


Creating and strengthening the magnetic field of the generator by passing DC through the filed winding.

20 July 2013

PMI Revision 00

Why Excitation system?


With large alternators in the power system, excitation plays a vital role in the management of voltage profile and reactive power in the grid thus ensuring Stability

20 July 2013

PMI Revision 00

EXCITATION PRINCIPLE

ROTOR

STATOR
20 July 2013 PMI Revision 00 5

EXCITATION PRINCIPLE

ROTOR

20 July 2013

STATOR

PMI Revision 00

EXCITATION PRINCIPLE
Stator induced Voltage

E = K. L. d/ dt K = constant L = length exposed to flux d/ dt = rate of change of flux Frequency of induced Voltage F = NP / 120 Magnitude of flux decides generated voltage and speed of rotation decides frequency of generated voltage
20 July 2013 PMI Revision 00 7

270 0 90 180

360

20 July 2013

PMI Revision 00

Flux in the generator rotor is produced by feeding DC supply in the field coils, thus forming a 2 pole magnet of rotor

The Equipment for supply, control and monitoring of this DC supply is called the Excitation system

20 July 2013

PMI Revision 00

TYPES OF EXCITATION
EXCITATION SYSTEM
ROTATING SYSTEM

STATIC SYSTEM

Conventional Rotating machines

High frequency excitation

Brushless Excitation System

20 July 2013

PMI Revision 00

10

EXCITATION SYSTEM REQUIREMENT


Reliability
Sensitivity and fast response Stability Ability to meet abnormal conditions Monitoring and annunciation of parameters User friendliness

20 July 2013

PMI Revision 00

11

COMPONENTS OF TYPICAL EXCITATION SYSTEM


Input and output interface , Aux. power supply, FB

AVR: At least two independent channels


Follow up control and changeover Excitation build up and Field Discharging system Cooling / heat dissipation components Limiters Protective relays Testing , Monitoring and alarm / trip initiation Specific requirements : Field Flashing, Stroboscope, PSS,
20 July 2013 PMI Revision 00 12

STATIC EXCITATION SYSTEM ( 200 MW)


575 v

AVR
AUTO

MAN

15.75 kV

FB
FF
FDR

415 v AC
20 July 2013 PMI Revision 00 13

Static excitation system


Excitation power from generator via excitation transformer. Protective relays for excitation transformer Field forcing provided through 415 v aux supply Converter divided in to no of parallel (typically4 ) paths. Each one having separate pulse output stage and air flow monitoring. Two channels : Auto & manual, provision for change over from Auto to Manual Limiters : Stator current limiter, Rotor current limiter, Load angle limiter etc. Alternate supply for testing

20 July 2013

PMI Revision 00

14

Static excitation system


GT

Field Breaker
FIELD THYRISOR BRIDGE

EXC TRFR 18KV/700V 1500KVA

voltage regulator

GENERATOR

Crow Bar

Non linear resistor

From TGMCC- C

Field discharge Resistor

Pre Excitation

415/40V,10KVA
20 July 2013 PMI Revision 00 15

Field flashing
For start up DC excitation is fed to the field from external source like station battery or rectified AC from station Ac supply . Filed flashing is used to build up voltage up to 30 %. From 30 to 70 % both flashing and regulation remains in circuit. 70 % above flashing gets cut-off

20 July 2013

PMI Revision 00

16

BRUSH GEAR

20 July 2013

PMI Revision 00

17

20 July 2013

PMI Revision 00

18

Brushless excitation
FIELD BREAKER
ARMATURE ROTATING DIODES

R Y B

FIELD (PM) PILOT EXCITER MAIN EXCITER GENERATOR

20 July 2013

PMI Revision 00

19

Components of Brush less Excitation System


Three Phase Main Exciter. Three Phase Pilot Exciter. Regulation cubicle Rectifier Wheels Exciter Coolers Metering and supervisory equipment.

20 July 2013

PMI Revision 00

20

BRUSHLESS EXCITATION SYSTEM (500 MW)

AVR

21 KV
20 July 2013 PMI Revision 00 21

Brushless Excitation System


Eliminates Slip Rings, Brushgear and all problems associated with transfer of current via sliding contacts Simple, Reliable and increasingly popular system the world over, Ideally suited for large sets Minimum operating and maintenance cost Self generating excitation unaffected by system fault/disturbances because of shaft mounted pilot exciter Multi contact electrical connections between exciter and generator field Stroboscope for fuse failure detection Rotor Earth fault monitoring system
20 July 2013 PMI Revision 00 22

Brushless Excitation system


Rotor E/F monitoring system alarm 80 K, Trip 5 K Stroboscope for thyristor fuse monitoring (one fuse for each pair of diodes, )

Auto channel thyristor current monitor For monitoring of thyristor bridge current , and initiating change over to manual.
Auto to Manual changeover in case of Auto channel power supply, thyristor set problem, or generator volts actual value problem
20 July 2013 PMI Revision 00 25

Excitation Power Requirement

Unit capacity MW

Excitation Current at Full Load

Excitation Voltage at full load

Ceiling Volts

200/ 210

2600

310

610

500

6300

600

1000

20 July 2013

PMI Revision 00

26

PMG

20 July 2013

PMI Revision 00

27

DIFFERENCES BETWEEN BRUSHLESS AND STATIC EXCITATION SYSTEMS


S.NO 1 Description Type of system. Brushless Excitation Brushless system gets activated with pilot exciter, main exciter and rotating diodes. Static Excitation Static excitation system uses thyristors & taking supply from output of the generator Field flashing supply required for excitation build up.

Dependency on external supply.

No external source requirement since pilot exciter has permanent magnet field.

Response of the excitation system.

Slower than static type since control is indirect (on the field of main exciter) and magnetic components involved.
One additional bearing and an increase in the shaft length are required. Less since slip rings and brushes are avoided.

Very fast response in the order of 40 ms. due to the direct control and solid state devices employed.
No additional bearing and increase in shaft length are required. More since slip rings and brushes are required. Also over hang vibrations are very high resulting in faster wear and tear.

Requirement of additional bearing and increase of turbo generator shaft length. Maintenance.

20 July 2013

PMI Revision 00

28

MAIN EXCITER

20 July 2013

PMI Revision 00

29

EXCITER ROTOR

20 July 2013

PMI Revision 00

30

EXCITER COOLING
VAPOUR EXHAUST

COOLER

20 July 2013

PMI Revision 00

31

GENERATOR
I XG EF = I . XG + VT

EF

VT

Equivalent circuit of Generator


20 July 2013 PMI Revision 00 32

GENERATOR
Phasor diagram of the Generator

Ef

IL.Xd
IL VT

20 July 2013

PMI Revision 00

33

GCB G

GT

GENERATOR

Xd

XT

Ef

VT

Vbus

Generator + Generator Transformer Eq. Ckt.


20 July 2013 PMI Revision 00 34

GENERATOR
Vector Diagram of Generator and GT connected to an infinite bus EF

IL.Xd
VT

IL.XT
Vbus

IL

20 July 2013

PMI Revision 00

35

GENERATOR
In the equivalent Circuit and Phasor diagram, the notations used have the following description:
Vbus VT EF : : : Infinite bus voltage Generator Terminal Voltage Induced Voltage (behind synchronous Impedance) of Generator, proportional to excitation. Direct axis sync. Reactance assumed same as quadrature axis sync. Reactance Transformer reactance Load Current Phase angle Torque Angle (rotor/load angle)
PMI Revision 00 36

Xd

XT IL
20 July 2013

: : : :

GENERATOR
POWER ANGLE EQUATION
Referring to the phasor diagram on slide no.14; Sin / IL.{Xd+XT} = Sin (90+ ) / EF

Putting Xd+XT =X, and multiplying both sides by VIL, V Sin /X = VIL Cos / EF

{Sin (90+ ) = Cos }


or, (EF . V / X) Sin Pmax
20 July 2013

= =

VIL Cos EF . V / X

Note that the Electrical Power Output varies as the Sin of Load angle
PMI Revision 00 37

Torque angle diagram


1.2 1
1.2 0.8 1 0.6 0.8 0.4 0.6 0.4 0.2 0.2 0 0

Torque angle diagram

Power in pu

Sin delta

30

60

90

12

15

Angle in degrees

Angle in degrees
20 July 2013 PMI Revision 00 38

18

30

60

90

120

150

180

Physical significance of load angle

red N ROTOR S

Stator mag. axis Rotor mag. axis yellow

S
blue
20 July 2013

STATOR

PMI Revision 00

39

Excitation constant; Steam flow increased Power output P1 to P2 EF1 EF2

P2
P1

2 1

2 I2 I1 Vbus

Locus of Constant Excitation

ACTIVE POWER CHANGE


20 July 2013 PMI Revision 00 40

Locus of P = const.
Steam Flow constant; Excitation increased Power output Constant EF1 EF2

2 I2 I1 Vbus

Locus of Constant Excitation

I Cos = Constant
20 July 2013 PMI Revision 00

EXCITATION CHANGE

41

Excitation Control
Power Angle Diagrams for Different Excitation Levels

1.4 1.2 1 0.8 0.6 0.4 0.2 0

Power in per unit

P1 P2 P3 0 30 60 90 120 150 180 Power Angle (delta), in degrees

20 July 2013

PMI Revision 00

42

AVR

20 July 2013

PMI Revision 00

43

TYPES OF AVR SYSTEMS


Single channel AVR system Dual channel AVR system Twin channel AVR system

20 July 2013

PMI Revision 00

44

Single channel AVR system


Here we have two controllers one is automatic and the other is manual and both the controllers are fed from the same supply The AVR senses the circuit parameters through current transformers and voltage transformers and initiates the control action by initiating control pulses , which are amplified and sent to the circuit components The gate controller is used to vary the firing angle in order to control the field current for excitation In case of any fault in the automatic voltage regulator the control can be switched on to the manual controller.
20 July 2013 PMI Revision 00 45

Dual channel AVR system


Here also we have two controllers in the same manner as the previous case i.e. one automatic voltage controller and one manual controller But here in contrary to the previous case we have different power supply, gate control and pulse amplifier units for each of the controllers Reliability is more in this case than previous one since a fault in either gate control unit or pulse amplifier or power supply in single channel AVR will cause failure of whole unit, but in dual channel AVR this can be avoided by switching to another channel.
20 July 2013 PMI Revision 00 46

Twin channel AVR system


This system almost resembles the dual channel AVR but the only difference is that here we have two automatic voltage regulators instead of one automatic voltage regulator and one manual Voltage regulator This system has an edge over the previous one in the fact that in case of failure in the AVR of the Dual voltage regulator the manual system is switched on and it should be adjusted manually for the required change in the system and if the fault in AVR is not rectified in reasonable time it will be tedious to adjust the manual voltage regulator

20 July 2013

PMI Revision 00

47

Twin channel AVR system


In Twin channel AVR both the AVRs sense the circuit parameters separately and switching to other regulator incase of fault is much easier and hence the system is more flexible than the other types. Generally switching to manual regulator is only exceptional cases like faulty operation of AVR or commissioning and maintenance work and hence we can easily manage with one AVR and one manual regulator than two AVRs. So Twin channel AVR is only used in very few cases and generally Dual channel AVR is preferred.

20 July 2013

PMI Revision 00

48

AVR
There are two independent control systems 1. Auto control 2. Manual control

The control is effected on the 3 phase output of the pilot exciter and provides a variable d.c. input to the main exciter

The feedback of voltage and current output of the generator is fed to avr where it is compared with the set point generator volts se from the control room
20 July 2013 PMI Revision 00 49

AVR

The main components of the voltage Regulator are two closed loop control systems each followed by separate gate control unit and thyristor set and de excitation equipment Control system 1 for automatic generator voltage control

(AUTO) comprises the following

20 July 2013

PMI Revision 00

50

AVR
Generator voltage control The output quantity of this control is the set point for a following.

Excitation current regulator, controlling the field current of the main exciter

Circuits for automatic excitation build-up during start up and field suppression during shut-down
20 July 2013 PMI Revision 00 51

AVR
This equipment acts on to the output of the generator voltage, control, limiting the set point for the above excitation current regulator. The stationary value of this limitation determines the maximum possible excitation current set-point (field forcing limitation);

Limiter for the under-excited range (under excitation limiter),


Delayed limiter for the overexcited range (over excitation limiter)

20 July 2013

PMI Revision 00

52

AVR
In the under excitation range, the under excitation ensures that the minimum excitation required for stable parallel operation of the generator with the system is available and that the under -excited reactive power is limited accordingly

20 July 2013

PMI Revision 00

53

AVR
The set-point adjuster of the excitation current regulator for manual is tracked automatically (followup control) so that, in the event of faults, change over to the manual control system is possible without delay Automatic change over is initiated by some special fault condition. Correct operation of the follow-up control circuit is monitored and can be observed on a matching instrument in the control room. This instrument can also be used for manual matching.
20 July 2013 PMI Revision 00 54

AVR
FAULT INDICATIONS The following alarms are issued from the voltage regulator to the control room. AVR fault

20 July 2013

AVR automatic change over to MANUAL


AVR loss of voltage alarm
PMI Revision 00 55

AVR
The current feedback is utilized for active and reactive power compensation and for limiters

There are 3 limiters


1.Under excitation limiter 2.Over excitation limiter 3. V/F limiter
20 July 2013 PMI Revision 00 56

Excitation Interlocks
Preconditions for Excitation ON
Excitation ON command N>90% Protection Off FCB Off feedback 5s delay Excitation ON

External trip
GCB is OFF

20 July 2013

PMI Revision 00

57

Excitation OFF Interlocks


Exc. OFF from Field flashing

Exc OFF command

GCB OFF
N>90% GCB OFF External trip Delay 1sec Exc OFF

20 July 2013

PMI Revision 00

58

Capability Curve
Capability Curve relates to the limits in which a generator can Operate safely. Boundaries of the Curve within with the machine will operate safely Lagging Power Factor/Overexcited region Top Section Relates to Field Heating in Rotor Winding Right Section Relates to Stator current Limit Straight line relates to Prime Mover Output Leading Power Factor/ Underexicted region

Lower Side relates to Stator end ring Limit Further down relates to Pole slipping
20 July 2013 PMI Revision 00 59

20 July 2013

PMI Revision 00

60

LIMITERS
Over excitation limiter Under excitation limiter Rotor angle limiter Stator current limiter V/F limiter

20 July 2013

PMI Revision 00

61

Over excitation limiter


Line voltage drops due to more reactive power requirement , switching operations or faults AVR increases generator excitation to hold the voltage constant Line voltage drops , thermal over loading of generator can result OEL is automatic limitation of generator excitation by lowering the generator voltage (otherwise the set point of generator voltage is reduced in time or the transformation ratio of the GT is to be adjusted ) OEL permits excitation values above the normal excitation and extended to max excitation (for field forcing) for a limited time, so as to permit the generator to perform the grid stabilization in response to short drops in line voltage When IF >110% of Ifn , the OEL and Field forcing limiter are active
20 July 2013 PMI Revision 00 62

Under Excitation limiter


Function is to correct the reactive power when the excitation current falls below minimum excitation current value required for stable operation of generator Activation of UEL takes over the control from the closed loop voltage control, acting via a max selection The limit characteristic is adjustable (shifted parallel) I reactive ref is compared with the measured I reactive , the error is fed to P- amplifier. When the value drops below the characteristic the amplified diff signal causes the field current to increase For commissioning purpose provision is made to mirror the characteristic in the inductive range, this allowing both the direction in which the control signal acts and the blocking of the set point generators is to be changed
20 July 2013 PMI Revision 00 63

Rotor Angle Limiter


Stable operation rotor angle <900, for higher degree of stability a further margin of 10-12% is normally provided RAL gives the o/p as permissible I reactive =F ( I active) Characteristic is shifted linearly as a function of generator voltage Permissible I reactive is compared with the measured value and is fed to the limit controller when the I reactive achieved value drops below the permissible value then the limiter comes in action and I reactive

20 July 2013

PMI Revision 00

64

Stator current limiter


During operation at high active power P and / low voltage the stator current of the generator tends to rise beyond its rated value and can cause the thermal overloading of stator, in spite of the action of the UEL An additional stator current limiting controller acting on the generator excitation is provided as a safe guard against such states of operation SCL always monitors the stator current measured value for crossing the rated stator current SCL permits small time over load but comes in action thereafter and influences the effective generator voltage set point- to reduce the Q till the stator current is brought down below the rated value Change in generator voltage set point is not blocked when SCL active SCL does not operate near the unity PF because near this value any limiter would cause oscillations
20 July 2013 PMI Revision 00 65

V/F limiter
Also known as over fluxing limiter It is the protection function for the GT V/F ratio , eddy current , the local eddy current causes thermal over loading of GT In DVR mode V/F ratio is continuously monitors the limit violation In case V/F ratio crosses the limit characteristic, the upper limit as the effective AVR set point is reduced as a function of V/F ratio This limiter is used when it is required to keep the unit operating even in case of substantial frequency drops , for instance in order to prevent complete breakdown of the system, a V/F limiter is used to lower the voltage proportional with frequency drop 20 July 2013 PMI Revision 00 66

PRIORITY STRUCTURE OF AVR


1st priority Rotor current limiter UN1024 Stator current li miter inductive UN0027

2 nd priority

Load angle limiter UN1043

Stator current limiter Capacitive UN0027

3 rd priority

Voltage regulator UN-2010

20 July 2013

PMI Revision 00

67

Field failure protection


Loss of generator field excitation under normal running conditions may arise due to any of the following condition. 1. Failure of brush gear. 2.unintentional opening of the field circuit breaker. 3. Failure of AVR. When generator on load loses its excitation , it starts to operate as an induction generator, running above synchronous speed.cylindrical rotor generators are not suited to such operation , because they don't have damper windings able to carry the induced currents, consequently this type of rotor will overheat rather quickly.
20 July 2013 PMI Revision 00 68

THANK YOU