SAFIE Commissioning

Operation

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

SAFIE EQUIPMENT REQUIRED


Appropriate installers manual

Copy of commissioning checklist/CCTV


Test apparatus

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CCTV INSTALLATION GUIDE

Using proper tools, fitting way of connector and complying with standard recommendation helps to reduce the signal loss

Image Graber Card


www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CCTV INSTALLATION GUIDE


Coax Cable Max Working Distance (meter) RG59 245 RG6U 365 RG11 500

Coax Cable Signal Loss (Attenuation) in dB per 100ft* (30m) Loss* 1MHz 10MHz RG-59 0.4dB 1.4dB RG-6 0.2dB 0.6dB RG-11 0.2dB 0.4dB

Since losses in cables need to be considered, obviously for longer cable runs a lower loss per metre cable should be used to keep overall losses within acceptable limits. A 6dB loss is generally considered acceptable
www.gst.uk.com

dB meter

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC HARDWARE INSTALLATION

Insert the Graphics Acquisition card(s) and relay output card into the PCI slot on the main board of the industrial PC one by one, and tight them with screws. Then, connect the relay output card and the terminal block with the accessory cable.
www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC SOFTWARE INSTALLATION

Install the SAFIE SETUP software


Note: Drivers for Graphic Acquisition card and Relay Output card are packed with SAFIE setup Make sure the dongle is fixed on the PC

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC SOFTWARE INSTALLATION


Hardware Update Wizard

Select a hardware to be updated, The right click select update Drivers

Window update to search for software, tick No

Tick Installed from a list..

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC SOFTWARE INSTALLATION


Hardware Update Wizard

6
Repeat the wizard until the hardware's were all update!!

Tick Search for the best driver in these location Tick Include this location , then select the path c:\WINDOWS\system 32
www.gst.uk.com

Finish

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC SOFTWARE INSTALLATION

SAFIE will enter to the detection mode automatically after the system starts

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
1. Password Configuration

2. Setting camera number and name


3. Configure the zones and sensitivity of each camera 4. Setting of Relay Output Cause and Effect

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

SAFIE MAIN WINDOW


Alarm Indicator

To enter into the programming menu

Operation Menu

Visual Confirmation

Channel Status
www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

PASSWORD CONFIGURATION

Factory default value Greenwell


www.gst.uk.com

Two levels of password 1. User Password 2. System Password


GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
GENERAL On the Setup

General to configure the basic system information

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
GENERAL

Video Channel
Valid ticked to register and allow particular camera in the system Text box- allowed 40 characters for camera location details

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
GENERAL Relay Output

Valid ticked to enable the function of relay out put


Text box- allowed 10 characters for relay details Read- to validate the changes in the relays details Ok to confirm
www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
Other Options

GENERAL

Video Switch Interval duration in second before the display switch to the next channel Auto Switch Waiting Time duration in second before allowed 40 characters for camera location details Log Save Path the location of local disk you wish to save the history Log Save Time Setting the time in month for saving a history Log Save Number- to validate the changes in the relays details

Ok to confirm
www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
PARAMETER

Under the Setup

PARAMETER for setting the parameters of each channel

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
PARAMETER

Current Channel selection of channels to be configured

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
PARAMETER

Parameter detailed parameters setting of each channel such as signal algorithm, fire algorithm, sensitivity and programs Warning: changing the parameter will inhibit the performance of the system

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
Grid Definition assigning to the numbers of grid particular channel (a grid= a zone) 4 x 3 = 12 zones 8 x 6 = 48 zones 12 x 9 = 108 zones 16 x 12 = 192 zones 20 x 15 = 300 zones

PARAMETER

A Grid each grid can set the sensitivity Note: To set sensitivity mouse left click To set the group mouse right click Grid Sensitivity for smoke or flame Sensitivity Levels: High, Normal, Low, Disabble
www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
PARAMETER Grid Group group of zones and the maximum groups can be set up is 24 Note: To set sensitivity mouse left click To set the group mouse right click

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
PARAMETER Relay Output Each group can be linked in one or more relays by ticking the box. Output Condition - is the cause and effect for each group
For example: the group A0 has 9 zones, and set the output condition into 1 of 9, it means any zones goes into an alarm in group A0 will activate the relay of DO.1

TEST to test the setting SAVE- To save the setting Ok to confirm


www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC OPERATION
1. System Silence 2. Disable the Alarm 3. Manual Operation of Relay Output 4. History Log

5. Basic Trouble Shooting

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

Alarm Indicator

BASIC OPERATION Operation Menu

Visual Confirmation

Fire

Normal

Disable Not Program

Fault

Channel Status
GST SMOKE AND FLAME INTELLIGENT EYE

www.gst.uk.com

SAFIE Commissioning

Operation

BASIC CONFIGURATION
MUTE

Mute Manual Start and Stop command of relay output. Note: by default, relay output 1 is set to sounder relay (latching), once the mute pressed it stop.

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
Pink

DISABLE THE ALARM

Disable to stop detecting fire even from the display video image

Enable To resume the channel into operating mode

Pink
www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
MANUAL OPERATION OF RELAY OUTPUT Manual Manual Start and Stop command of relay output. Note: by default, relay output 1 is set to sounder relay (Latching) and relay 16 is set to fault relay.

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

BASIC CONFIGURATION
HISTORY LOG Log two types of history log: Image or Text

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

BASIC TROUBLESHOOTING
SAFIE Commissioning
No. 1 Fault indication Access device failed

Operation
Possible Cause The address of the relay output card is incorrect.

Solution See , go into the System Setting dialog and press the Read button.

Relay Output Card Fault!

The driver of the relay output card is not Reinstall/update the driver. installed or incorrect.

Hardware key not found.

The dongle is not connected or the dongle driver is installed incorrect.

Check the parallel port connection of the PC or reinstall/update the dongle driver.

The number of the video channels is reduced. Not enough virtual memory for video card, please reset it!

The PCI slot is loose or the incorrect installation of the driver.

Make sure the connection is good or reinstall/update the driver.

The memory allocated for the card is too Go to the path: small. C:\windows\system32\, and execute file okdevman.exe, select the Buffer Allocator tag and input the size of the memory and restart the PC.

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE

SAFIE Commissioning

Operation

ANSWER AND QUESTION

www.gst.uk.com

GST SMOKE AND FLAME INTELLIGENT EYE