But first....
Design pressures... Its best to group equipment and give it all the same maximum op. pressure
What groups would you create? What would the max op. pressure be?
? hrs
? hrs
12 hrs
8 hrs
FE
PI
Controller
Manipulated Variable
FIC FV
Controllers
Initiating or First Measured Variable Letter Analysis A Burner, Combustion B Users Choice C Users Choice D Voltage E Flow Rate F Flow Quantity FQ Flow Ratio FF Users Choice G Hand H Current (Electrical) I Power J Time K Level L Users Choice M
Instrumentation Naming
ERC FRC FQRC FFRC EIC FIC FQIC FFIC HIC IIC JIC KIC LIC EC FC FCV FICV FFC HC ER FR FQR FFR HR IR JR KR LR EI FI FQI FFI HI II JI KI LI ESH FSH FQSH FFSH ESL FSL FQSL FFSL ESHL FSHL IRC JRC KRC LRC KC LC KCV LCV ISH JSH KSH LSH ISL JSL KSL LSL HS ISHL JSHL KSHL LSHL
Readout Devices Switches and Alarm Devices Self Actuated Control Valves Recording Indicating High Low Comb AR AI ASH ASL ASHL BR BI BSH BSL BSHL
Transmitters
ERT FRT
ET FT FQT
HT IT JT KT LT
Initiating or Measured Variable Analysis Burner, Combustion Users Choice Users Choice Voltage Flow Rate Flow Quantity Flow Ratio Users Choice Hand Current (Electrical) Power Time
First Letter A B C D E F FQ FF G H I J K
Safety Device
Final Element AV BV
EY FY FQY
EE FE FQE FE
FP
FG
EZ FV FQV FFV HV IZ JV KV
HY IY JY KY
IE JE KE
LT
Valve
LT
LIC
LV
LT
LIC
No Gas!
LV
LV
Note: - valve always on disch to prevent flashing on pump suction - pump may also require a minimum flow bypass
Fast to Measure Flow Changes usually require a control valve to change its position which can take seconds. Vapour systems have a capacitance that need to be overcome before the flow changes are experienced everywhere in the system
FE
FT FV
M I
FIC
FE
FT FV
FIC
SP
FRIC
SP
FE FT
Set one flow rate Other flow is proportionally controlled to first flow
Ensure correct mixture / recipes
FE
FV
PIC PV PT
Need to control vessel pressure Fast or slow?
PIC PT PV
Control pump discharge pressure - not very useful
PIC PT FT PV
Control pump discharge pressure - ensure constant feed pressure to FV
FIC
FE
FV
Q = U A Tln
C/w
C/w
FE
High Speed
FIC
SP
P
Low Speed
I
SIC
SP
Flow
FT
FE PT
FV
LT
LIC
FIC
FT FE
LV
LIC
LT
FIC
FT FE
LV
PIC PT
100 psig Compressed Air
PT PV
PV
User 1
User 2 User 3
User 1
User 2 User 3
PI
PI
HS HS
PI
LT
PI
LIC
LV
HS HS
Reflux Tanks
Set@ From Condenser
PI
From Pump
TI
LSLL
LIT
LAHL LIC
TO LV
LALL
Pump S/D
To Pump
Compressors - Centrifugal
For our purposes treat controls as a black box But... Provide an input control signal (cascade) Remember cooling water reqd (lube system...) CWS Control From ?
CWR
SIC
By Vendor By Owner
Columns
Composition control Pressure control
Put a control scheme to ensure Feed rate is constant or is slowly changing Level control
Level control
Composition control
Columns Bottoms
Put level control on bottoms outflow when outflow rate > 10 x boil up rate Put level control on Steam control boilup rate > 10 x outflow rate otherwise either scheme okay
FIC
HHLL
FT
5 bar Stm
LIT
TE
LAHL
LIC
TIC
TE
TIC
Columns - Overhead
PIC
CWS
PT
FV
CWR
FIC
FT
TI
Set@
PI
PV
RO
HLL = 4-6 NLL = 3-6 LLL = 2-0 LLLL = 2-0 LAHL LIC
LIT
PI PI
LSLL
LALL
Pump S/D
LV
HS HS
LSHH
LY
TI
LSHH
LI
LAHL
LSLL
LIT
LV
Workshop
Draw the level control that should go on a storage tank Provide a different control scheme for the reactor / condenser / flasher P&ID
draw it explain how your scheme works and responds to upsets explain the pros/cons of your scheme
using a BFD, including the syngas process, show how pressure control can be done
END
LT
LIC
LV
TV
TIC
CWS TAHL
TE