Streamed Phasor Measurements (PMU) to IEEE C37.118.2005 Real time values sent to SCADA
Back to Index
Back to Index
Ethernet, serial communication and USB port available as standard - USB can be used to update device configuration, upgrade firmware or download data to a standard mass memory accessory (memory stick or portable hard drive).
Fast cross triggering over the network such that IDM+ devices on the same subnet can all record synchronised data to emulate a much larger recorder.
Clock synchronisation based on standard NTP protocol and separate 1pps. Slave units can be time locked to another IDM+ designated as master or an external source. IRIGB and IRIGJ can also be used if required.
Travelling Wave fault location - 2 circuits supported per 9 / 18 block of analogue inputs
Internal modem IP forwarding meaning one telephone line can support multiple devices Internal GPS receiver time synchronise the master device to 100ns. IEC61850 protocol to accept GOOSE DFR triggers, log digital status defined in the GOOSE message and send DFR comtrade files to third party software on recipt of the appropriate commands
Back to Index
Advantage Compact version with high ratio of digital to analogues Ideal for bay based distributed architecture or for small sub transmission sub stations DFR / slow scan monitoring for one or two curcuits
Back to Index
Two 6U Variations
Feature 6U high 19 wide Options of : 18 Analog and 64 digital channels, or 36 Analog and 128 digital channels Advantage Ideal for centralised architecture with higher channel counts
Analogue Inputs
Each input can be AC voltage, AC current or DC selected at
time of order
AC voltage range selected from 140V, 170V, 480V and 800V full scale deflection
AC current range selected from 10A, 20A, 50A and 100A full scale deflection (200A available on request) DC range selected from 12V, 120V, 240V, 480V, 4-20mA loop DC inputs can be used for monitoring circuit breaker trip coil current (to assist in condition based maintenance), s/s battery voltage or other transducer output
Back to Index
Digital Inputs
Wide ranging input from 48 to 250VDC. (24 to 250VDC optional). Selectable De-bounce Channels grouped in multiples of 8 with one common. Each group isolated from the other.
Calculated Channels
The FR engine calculates rms magnitude, phase angle, sequence components from each 3 phase group, single phase and three phase power from each circuit and system frequency.
Back to Index
Clock Synchronisation
Devices can be set up on a master slave basis Master can be synchronised from GPS, IRIGB, IRIGJ or NTP 100ns accuracy obtained with GPS necessary for TWS and PMU applications 1pps option required with IRIGB, IRIGJ and NTP for 1 micro second accuracy
Back to Index
Shows operation of overvoltage protection on CVT output. Too many occurrences indicate a potential problem
Back to Index
Back to Index
D1
D2
D3
D2
D3
Back to Index
DFR sample rate 128 samples/cycle shows high frequency transient when fault arc first struck, Helps to characterise the fault type
Back to Index
Back to Index
DSI logging
Back to Index
Back to Index
ReplayPlus
IQ+
Replaced by
Back to Index
deployment
Advantage
Software able to work for small monitoring systems as well as for big systems Data download workload can be split between different hardware servers
Benefit
Support for very big systems as well as small systems
Back to Index
Parts of iQ+
iQ+ Server
1 application The iQ+ Server is the core of iQ+.
It downloads data from devices It writes and reads into the SQL database iQ+ Client applications log into the Server
iQ+ Client
1 or more applications
Back to Index
Back to Index
1 3
Back to Index
iQ+ Client 2
TCP/IP
Server 1
Server 1 iQ+ Server with Communication Manager Server 2 SQL Server Database
Back to Index
iQ+ Client 2
Suitable for 50+ devices PC 1 & 2 iQ+ Client Server 1 iQ+ Server with Communication Manager SQL Database Server 2 iQ+ Communication Manager Desktop (High end PC) iQ+ Communication Manager
Back to Index
Server 2
Server 1
TCP/IP TCP/IP
Desktop
Benefit
Easy to use
Back to Index
IQ+ Architecture
Back to Index
Back to Index
Back to Index
IQ+ for FR
Back to Index
DFR Viewer
Back to Index
TWS FL Application
Back to Index
PQ Application
Back to Index
Advantage
Provides fast, customized information of entire power system in one single screen
Even for systems with hundreds of devices
Matrix with links to problem areas (color coded) of your entire power system. Particularly useful for PQ.
Compliance reports Sags/dips, swells, interruptions Steady state records
Benefit
Save time access new important data
Back to Index
Back to Index
Red filed: threshold exceeded or report incompliant Green field: parameter or report within limits Yellow field: no data available (i.e. not recorded or not downloaded)
Back to Index
Logs number of DTF results from each circuit over a given time period. Able to drill down from a red square to get more detail BENEFIT quickly see what circuits had fault activity and when.
Back to Index
Benefit Fix communication infrastructure problems before data is lost Conduct UPS maintenance when needed
Back to Index
Back to Index
Logs abnormal occurrences: Clock synch issues Comms issues Standing alarms Able to drill down from a red square to get more detail BENEFIT identify and fix defects before important information is lost
Back to Index
Back to Index
IDME Upgrade
IDME(evolution) is an upgrade path from an IDM to the next generation fault monitoring family from Qualitrol IDM T3 and T5 fault recorders can be upgraded to the IDME versions. Aim is to upgrade whilst maintaining existing field wiring
Upgrade
Back to Index
IDME Upgrade
Upgrade from IDM to IDME involves replacing the following boards
CPU board Analogue board Digital (event) board Front panel MMI
VT/CT Boards and PSU retained
The original IDM internal CT can be left in service but not used no need to touch the original CT cabling
Back to Index
This will provide improved CT performance without the need for external split core CTs BUT will require that the CT and VT wiring is disconnected from the rear of the IDM whilst the VT/CT board is modified or replaced. Some Utilities are OK with this arrangement as they can use test switches to short the CT wiring and can upgrade without the need for a line outage.
Back to Index